| 1 | Disconnecting and taking out old defective LT cables with aluminium conductor of any size/type from trenches/poles/walls/from pipes etc complete all as directed. |
| 2 | Disconnecting and taking out old rusted control panels/bus bar chambers /MCCB/Timer switch /High mast panel etc of any type/any sizecomplete. |
| 3 | Excavation in trenches in hard/dense soil n. exc. 1.5 M wide and n. exc. 1.5 Mts in depthfor laying of cables poles stay, and getting out complete all as specified and directed. |
| 4 | All as per the description of Srl item No 1 herein above but depth exceeding 1.50 metre but not exceeding 3.00 metre |
| 5 | Returning filling in including spreading, wateringand well ramming in layers n.exc. 25 cm thick after the cable are laid. |
| 6 | Removal of surplus soil to a distance n. exc. 50 Mtrs and depositing where directed at a lavel n.exc. 1.5 Mtr above the starting point. |
| 7 | Supplying laying, jointing and testing LT underground electric cable XLPE insulated, PVC sheathed, armoured heavy duty 1100 volts grade heavy duty aluminium conductor laid in trenches/ducts or passing through pipes under road or fixed to poles complete all as specified and as directed, with and including taking up or down old damaged electric cable and removing from site of work, complete allas directed for following size :- |
| 8 | (a) Cross sectional area 35 Sqmm 3.50 Core. |
| 9 | (b) Cross section area 25Sqmm 4.00 Core |
| 10 | (c) Cross section area 16 Sqmm 4.00 Core |
| 11 | (d) Cross section area 10 Sqmm 4.00 Core |
| 12 | Supplyingingand laying double walled corrugated HDPE duct pipe of 50mmouter dia confirming to IS 14930 Pt II with antirodent and non flame propergating propertiesof approved colour complete with fitting for cable protection complete all as specified and as directed |
| 13 | Supplying installation, testing and commissioningin replacement of out door typeCCMS Panel 20KW 3 phase in replacement with Group Control management system using GPRS/GSM technology suitable for incoming of 63 Amps , including sensor for anti-tampering of panel, fibre glass in front for display of connection indicator & display MF meter, external locking arrangement sheet enclosure to be used should be CPRI approved CCMS Panel IP55 as per IS/IEC 61439, Die electric property as per IS/IEC 61439 and clearance & creepage distance, CCMS Panel drawing must be approved by CPRI with angle iron frame 50 x 50 x 6 mm size legs , 04 nos legs 600 mm long, PCC 1:2:4 type B-1 for grouting of base,suitable for 3 phase 415 volts 50 Hz 4 wire AC Supplying and earthing. Following sub componentSupplyingingand fixingeatures (Ser No 30.1 to 30.10)must be included within panel:-i) Supplying only MCCB TPN 63 Amps capacity 16 KA 415 Volts - 01 No (Incoming) with separate SPD of 40 kV capacity.(ii) Supplying only Resing cast CT\"s 100/5A - Set of 3, (iii) Supplying only Multi-function digital meter class 1 accuracy ,feeding information to GPRS controller. |
| 14 | Supplyinging only GPRS controller module for dual communication with additional power back up upto 48 hrs. The CCMS should have inbuilt capabiity to directly measure three phase & its prameters & have 1.0 class accuracy using Multifunction meter, should have LCD display to show all events & manually setting the parameters. the IOT GPRS/RFHybrid device must be communicable with GPRS & RF Both (future ready) & device should be password access via cloud platform so that only authorised person can access the CCMS panel & can alter settings using dashboard. The device should have led indication forpower net work and data and also parameters should be manually set on GPRS unit is as low voltage, high voltge, high temp, overload, set fault enable, disable, sunrise-sunset, CT ratio, password enable disable & change password. Web site specifications : When user login to website it should have dashboard for easy understanding of total light installed and no of on light and off light based on total power consumption only , actual load, enery saving & map vie of panel installation, all parameters should be remotely set by website and for remote setting there should be 2nd level password protection, theparameter which can be remotely shoud be as remote on-off, schedule write, set CT ratio, set RTC as per server if device\"s RTC misbehave & control twilight time, all units shoud be set simultaneously as well individual as user required, there should failure report generation program as well network off devices report to easy find fault sites. |
| 15 | The GUI Unit : The GUI shall able to measure Voltage, Current, Power Factor, Active power, Apparent power, metering cumulative active energy, metering cumulative aparent energy. Time scheduling which could be defined from the GUI running locally in smart device. GPRS communication between panel and cloud server and an option in panel for RF communication between panel and individual street lights for futuristic expansion. Wireless local control for field staff to on/off panel incase of GSM failure. The panel should be capable of sending following alerts:- (a) Phase wise over current / short circuit (b) Phase wise over voltage (c) Group failure of lights (d) No output Supplying (e) Tampering of door (f) Over voltage and under voltage protection for contactors and smart device (g) Low power factor detection (h) Under load and over load detecion. (j) GSM network down alert (k) RTC and NVM failure. (l) In built astronomical timer. (m) MCB tripping to be monitored on web application. The GUI should also support Google Maps overlay for live status monitoring of panel.Support for COAT (Configuration over the air) and FOTA (firmware over the air), Live instaneous load update, Total monthly /weekly/daily power consumption, on time and saving info, Configuration for user hierarchy from the GUI, Configuration for SMS and email for alert and reporting complete all as specified and directed. Note: Quoted rate shall be deemed to be inclusive of 2G/3G SIM charges & one year charges of the SIM for data, the complete information to be displayed with provision of userid through an SSL encrypted web applicaton and SMS alerts to selected mobile numbers complete all as specified and directed. Note: Quoted rate shall be deemed to be inclusive of 2G/3G SIM charges & one year charges of the SIMfor data, the complete information to be displayed with provision of userid through an SSL encrypted web applicaton and SMS alerts to selected mobile numbers complete all as specified and directed. |
| 16 | Supplying only inbuilt astronomical timer within IOT Device or external on the basis of latitude and longitude of the instllation for place controller itself decides switch on-off timings, sun rise/ sun set on-off, set time on - off incluiding 6 years battery reserve or equivalent power backup. |
| 17 | Supplying only Switch 6 Amps capacity with operation between ,Automatic mode/Manual mode/Timer mode/Off mode |
| 18 | Supplying only Line contactor, AC 3 duty, 3 phase, 415 Volts, 50 Hz, 32 Amps-02 No. |
| 19 | Supplying only MCB TPN 32 Amps capacity - 02 (Outgoings). |
| 20 | Supplying only Terminal block suitable for 100A rating with brass contacts for INPUT/OUTPUT termination. |
| 21 | Supplying only inbuilt with CCMS Panel Anti tampering micro switch for automation mode, timer mode, on mode, phase indicators, By pass mode. |
| 22 | Material & labour for Control wiring & control MCB of 6 Amps and power wiring of toggle switch, indicators/ protection circuits contactors, gateway/relay with 1.5 Sqmm multi strand copper cable(for control wiring), and of apropriate size for power wiring, incl lugs and ferrules- 01 Job as per circuit design complete all as specified and directed |
| 23 | Providing recharge for GPRS SIM as specified for street light automation panels including subscription for cloud data usage for 12 months complete all as specified and directed. |
| 24 | Disconnection of electric connection ,repair, replace, refixand servicing the following (ser No 15 to 27 as required ) alongwith painting and foundation work with PCC 1:2:4 ofstreetlight panel with Group Control management system using GPRS/GSM technology suitable for incoming of 63 Amps , including sensor for anti-tampering of panel, fibre glass in front for display of connection indicator & display MF meter, external locking arrangement , dressing of cable including replacement ofburnt out aluminium lugs and fixing with lugs, nuts bolts etc complete including necessary wiring of feeder pillar box with copper conductor cable excavation and earth work all as directed by Engr-in- Charge.Note :Supplying and fixin replacement of unserviceable parts shall be measured and paid seperately under items No. 15 to 27 |
| 25 | Supplyingin replacement MCCB TPN 63 Amps capacity 16 KA 415 Volts(complete for serial No 14 above complete all as specified and as directed). |
| 26 | Supplyingin replacement SPD of 40 kV capacity (complete for serial No 14 above complete all as specified and as directed). |
| 27 | Supplyingin replacement Resing cast CT\"s 100/5A - Set of 3 (complete for serial No 14 above complete all as specified and as directed). |
| 28 | Supplyingin replacement Multi-function digital meter class 1 accuracy feeding information to GPRS controller. (complete for serial No 14 above complete all as specified and as directed). |
| 29 | Supplyingin replacement IoT Device (Hybrid GSM & RF). (complete for serial No 14 above complete all as specified and as directed). |
| 30 | Supplyingin replacement astronomical timer switch (67DDT0)on the basis of latitude and longitude of the instllation for place controller itself decides switch on-off timings, sun rise/ sun set on-off, set time on - off incluiding 6 years battery reserve or equivalent power backup.(complete for serial No 14 above complete all as specified and as directed). |
| 31 | Supplyingin replacementSwitch 6 Amps capacity with operation between Automatic mode/Manual mode/Timer mode/Off mode.(complete for serial No 14 above complete all as specified and as directed). |
| 32 | Supplyingin replacementLine contactor, AC 3 duty, 3 phase, 415 Volts, 50 Hz, 32 Amps(complete for serial No 14 above complete all as specified and as directed). |
| 33 | Supplyingin replacementMCB TPN 32 Amps capacity (complete for serial No 14 above complete all as specified and as directed). |
| 34 | Supplying only Netural link 32 Amps (complete for serial No 14 above complete all as specified and as directed). |
| 35 | Supplyingin replacement rotary Switch, 3P, 3W.(complete for serial No 14 above complete all as specified and as directed). |
| 36 | Supplyingin replacement Indicators for automation mode, timer mode, on mode, phase indicators, By pass mode to be provided such that they are visible from outside. (complete for serial No 14 above complete all as specified and as directed). |
| 37 | Supplyingin replacementMCB of 6 Amps and power wiring of toggle switch, indicators/ protection circuits contactors, gateway/relay with 1.5 Sqmm multi strand copper cable(for control wiring), and of appropriate size for power wiring, incl lugs and ferrules- 01 Job as per circuit design complete all as specified and directed.(complete for serial No 14above complete all as specified and as directed). |
| 38 | Earthing complete with galvanized steel plate electrode 600mm x 600mmx6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level), with top edge of the plate not less than 1.50m below ground level, connected with and including GI /Steel 32 mm x 6mm earth lead strip by means of bolts, nuts, check nuts & washers of galvanized iron / steel complete all as shown in electrical plate No 5 of MES Schedule Part-I and connected to earthing test point all as specified or indicated and testing on completion as directed by Engineer-in-Charge including excavation and earth work in any type of soil, funnel, plain cement concrete (1 :3:6) type C-1 Chamber, precast reinforced cement concrete (1:2:4) type B-1 pit cover of appropriate size with and including steel reinforcement, of thickness 50mm, charcoal, common salt including protection of earthing strip by and including 40mm bore galvanized steel tubing, medium grade and 20mm bore galvanized steel tubing, medium grade pipe for watering complete all as specified as shown on drg /plates as indicated and as directed including dismantling existing earthing and removing demolished materials outside the MoD land as directed. Notes :-(a)RCC pit cover shall be precast with cement concrete 1:2:4 type B1 reinforced with 8mm dia TMT steel bars @ 100mm c/c bothways. (b) Earth lead 32mm x 6m of galvanised iron / steel protected with 40mm bore GI pipe shall be provided upto a length of 7.50 metre. |
| 39 | Disconnection of electric connection ,repair, replace, refix and servicing the following (ser No 30 to 32 as required ) of old 63 amp automatic street light switch using Infrared Sensorbased NATURE SWITCH for automatic switching of street lights based on LUX level of Natural light. Sensor alongwith suitable power contactors and incoming - outgoing MCB and supported terminal should be enclosed in pole /wall mountable enclosure , dressing of cable including replacement ofburnt out aluminium lugs and fixing with lugs, nuts bolts etc complete including necessary wiring of feeder pillar box with copper conductor cable excavation and earth work all as directed by Engr-in- Charge.Note :Supplying and fixin replacement of unserviceable parts shall be measured and paid seperately under items No. 30 to 32 . |
| 40 | Supplyingin replacement MCB TPN 63 Amps capacity 10 KA 415 Volts(complete for serial No 29 above complete all as specified and as directed). |
| 41 | Supplyingin replacement MCB SP 6-32 Amps capacity 10 KA 415 Volts(complete for serial No 29 above complete all as specified and as directed). |
| 42 | Supplyingin replacement 3 phase contactorsupto 20 Ampor as suitable capacity for nature switch 63 Apms. (complete for serial No 29 above complete all as specified and as directed). |
| 43 | Supplying installation, testing and commissioningin replacement out door type of Street Light Panel for Three Phase Load of 5KW, The Enclosure Pole / Wall CPRI approved OEM shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE with latest IEC - IS: 61439 (PART-1AND PART-2) of 2011. The gasket should be internally embedded made of polyurethane. The panel should pass glow wire test 960ºC in accordance with IEC 60695-2-11 & also Impact Protection Tested as per EN50298-98 for IK 09. (Flame Retardant And Self Extinguishing). Assembled Panel in Polycarbonate should be tested from CPRI as per latest IEC 61439-1.Make of Panel - Hanson / Universal / Hensel / Tricolite.Make of Switchgear & Controlgear – L&T / Schneider / Siemens / Havells / C&SThe Panel shall be comprising of following:1. INCOMING : SP MCBs CURVE ‘C’ 16-20A -3Nos.2. CONTACTOR : AC3 18A -3Nos3. OUTGOING : SP MCBs CURVE ‘C’ 16-20A -3Nos.4. NATURE SWITCH: A Sensor for Automatic Switching of Street Light Based on LUX Level of Natural Light with bypass and time adjustment arrangement -1No.5. Earthing Terminals -2Nos.6. Circuit wiring of Copper wire min. 10Sqmm. |
| 44 | Supplying , installation, testing and commissioningin replacement of Polycarbonate CPRI approved OEM LT FEEDER PILLAR shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE with latest IEC - IS: 61439 (PART-1AND PART-2) of 2011. The gasket should be internally embedded made of polyurethane. The panel should pass glow wire test 960ºC in accordance with IEC 60695-2-11 & also Impact Protection Tested as per EN50298-98 for IK 09. (flame retardant and self-extinguishing). Assembled Panel in Polycarbonate should be tested from CPRI as per latest IEC 61439-1.LT Panel as per IE rules , 415 volts for outdoor use, including aluminium bus bar with provision of hole on bus bar fixing of cable mounted on PVC / epoxy insulators, with MC 75 for base frame & angle iron legs 600mm of size 50x50x5mm, legs duly spray painted internally and externally with powder coated including provision of opening for incoming/outgoing cables and testing complete all as directed. |
| 45 | Make of Panel - Hanson / Universal / Hensel / Tricolite.Make of Switchgear & Controlgear – L&T / Schneider / Siemens / Havells / C&SThe Panel shall be comprising of following:1. INCOMING: MCCB 125A 4P 415 Volts, 50 HZ, , breaking capacity 25 KA with adjustablethermal and adjustable magnetic release -01 No.2. BUS BAR: 200A Aluminium TPN heat shrink insulated including all connection with aluminumstrip-1Set.3. METERING: Multifunction Meter (VAF+PF) with Ct’s & Set of R Y B Led Indicating Lamps -1Set.4. OUTGOING:MCCB 63A 3P 415 Volts, 50 HZ, , breaking capacity 16 KA with adjustable thermal and adjustable magnetic release -03 Nos.5. Earthing Terminals -2Nos.6. Danger Notice Plate dully riveted / Pasted on front door -1No |
| 46 | Disconnection of electric connection ,repair, replace, refix and servicingthe following (ser No 36 to 43 as required ) alongwith painting and foundation work with PCC 1:2:4 of Polycarbonate CPRI approved OEM LT FEEDER PILLAR , made of modular POLYCARBONATE THERMOPLASTIC for street light & high mast pole , dressing of cable including replacement ofburnt out aluminium lugs and fixing with lugs, nuts bolts etc complete including necessary wiring of feeder pillar box with copper conductor cable excavation and earth work all as directed by Engr-in- Charge.Note :Supplying and fixin replacement of unserviceable parts shall be measured and paid seperately under items No. 36 to 43 . |
| 47 | Supplyingin replacement of MCCB 125A 4P 415 Volts, 50 HZ, , breaking capacity 25 KA with adjustablethermal and adjustable magnetic release (complete for serial No 35 above complete all as specified and as directed). |
| 48 | Supplyingin replacement ofBUS BAR: 200A Aluminium TPN heat shrink insulated including all connection with aluminum strip Set of 1. (complete for serial No 35 above complete all as specified and as directed). |
| 49 | Supplyingin replacement ofBUS BAR: 100A Aluminium TPN heat shrink insulated including all connection with aluminum strip Set of 1. (complete for serial No 35 above complete all as specified and as directed). |
| 50 | Supplyingin replacement of METERING: Multifunction Meter (VAF+PF) with Ct’s & Set of R Y B Led Indicating Lamps -1 Set.(complete for serial No 35 above complete all as specified and as directed). |
| 51 | Supplyingin replacement ofMCCB 63A 3P 415 Volts, 50 HZ, , breaking capacity 16 KA with adjustable thermal and adjustable magnetic release -(complete for serial No 35 above complete all as specified and as directed). |
| 52 | Supplyingin replacement of Danger Notice Plate dully riveted / Pasted on front door .(complete for serial No 35 above complete all as specified and as directed). |
| 53 | Supplyingin replacement of Digital Type Time Switch 240V Single Phase, Make: L&T, Siemens , Indo asian(complete for serial No 35 above complete all as specified and as directed). |
| 54 | Supplyingin replacement ofModular din rail mounted Three Pole, 415Volt Power Contactor nominal 63A with standard coil Voltage 240/220 Volt complete with din rail of suitable size complete for serial No 35 above complete all as specified and as directed). |
| 55 | Supplying, installation, testing and commissioningin replacement of Polycarbonate CPRI approved OEM made LT FEEDER PILLAR shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE OF DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE with latest IEC - IS: 61439 (PART-1AND PART-2) of 2011. The gasket should be internally embedded made of polyurethane. The panel should pass glow wire test 960ºC in accordance with IEC 60695-2-11 & also Impact Protection Tested as per EN50298-98 for IK 09. (flame retardant and self-extinguishing). Assembled Panel in Polycarbonate should be tested from CPRI as per latest IEC 61439-1.LT Panel as per IE rules with dimension 900x900x500 mm ,415 volts for outdoor use, including aluminium bus bar with provision of hole on bus bar fixing of cable mounted on PVC / epoxy insulators, with MC 75 for base frame & angle iron legs 600mm of size 50x50x5mm, legs duly spray painted internally and externally with powder coated including provision of opening for incomming/outgoing cables and testing complete all as directed. Make of Panel - Hanson / Universal / Hensel / Tricolite.Make of Switchgear & Controlgear – L&T / Schneider / Siemens / Havells / C&SThe Panel shall be comprising of following: |
| 56 | 1. INCOMING: MCCB 63A 4P 415 Volts, 50 HZ, , breaking capacity 16 KA with adjustable thermal and adjustable magnetic release ICS=100%ICU -01 No. |
| 57 | 2. BUS BAR: 100A Aluminium TPN heat shrink insulated including all connection with aluminum strip-1Set. |
| 58 | 3. METERING: Multifunction Meter (VAF+PF) with Ct’s & Set of R Y B Led Indicating Lamps -1Set. |
| 59 | 4. OUTGOING:a) Digital Type Time Switch 240V Single Phase -1No. Make: L&T, Siemens, Schneider.b) Modular din rail mounted Three Pole, 415Volt Power Contactor nominal 63A with standard coil Voltage 240/220 Volt complete with din rail of suitable size -01Nos.c) MCB TP 415Volt breaking capacity 10KA of rating 32A with Aluminium Bus Bar strips of suitable current ratings -02Nos. and MCB SP 6A -01No.d) Earthing Terminals -2Nos. |
| 60 | 5. Danger Notice Plate dully riveted / Pasted on front door -1No. |