Tender For Sub Station Work For Medical College And Upgradation Of Hospital At Sikar (Phase-Ii), sikar-Rajasthan

Rajasthan State Road Development And Construction Corporation Limited has published Tender For Sub Station Work For Medical College And Upgradation Of Hospital At Sikar (Phase-Ii). Submission Date for this Tender is 04-04-2023. Substation Tenders in sikar Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

36893491
Corrigendum : Tender For Sub Station Work For Medical College And Upgradation Of Hospital At Sikar (Phase-Ii)
Open Tender
Indian
Rajasthan
sikar
04-04-2023

Tender Details

Sub Station Work For Medical College And Upgradation Of Hospital At Sikar (Phase-Ii)

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Apr-2023 Engineers cost 01042023 Other 04-04-2023

Key Value

Document Fees
INR 5900 /-
EMD
INR 1666260.0 /-
Tender Value
INR 8.33 Crore /-

BOQ Items

Name of Work : -Sub Station work for Medical College and Upgradation of Hospital at Sikar (Phase-II)
Sl. No. Item Description
1Supply , Installation, Testing and Comissioning of 11KV, 630 A, 25 kA / 1 Sec,SF6 / VCB Indoor type panel HT board, free standing motor operated & withdrawal type fabricated from 2 mm thick CRCA sheet steel , With Ammeter, Voltmeter, PF Meter, KWH Meter, MDI Meter, Selector Switches as required, CRT-CT of required ratio ( 15VA ; Cl-1.0 / 0.5 ) PT (11 KV /110V/v3) , Fuses , IP42 Protection, 4 / 8 /10 / 12-window Annunciation Panel , AC/ DC Control voltage 24/48/ 110/230V , LED Indication lamps , S/C, O/C & E/F Protection (IDMT) Relays Alarm & trip contacts for Transformer protection ( High oil temperature , Buchholz protection ,high winding temperature), power pack 2 x 12 V,etc complete in all respect Ready To Use(RTU),OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDA lab type test reportsbefore execution complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
2Supply , Installation, Testing and Comissioning of 11 KV, 630 A, 20kA / 3 sec, Out door,Extensible type Ring main unit (RMU) in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, earthing switch, mechanical ON / OFF /Earth indication, Voltage presence indicator, Ring core protection CT 2.5 VA, 10P10 as per transformer rating, Shunt trip coil, Anti reflex operating handle, right angle boots etc. OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDAlab typetest reportsbefore execution as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
3Supply , Installation, Testing and Comissioning of factory made11 KV, 630 A, 20kA / 3 sec, Out door Extensible type IP54 for panel & IP67 for main circuits Ring main unit (RMU) IEC 62271-200in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuitbreaker with over load, Earth fault, short circuit relay, copper bus bar, bus support and insulation marerial epoxy resin,ring core protection & metering CT, Auxiliary relay for WTI, OTI ,Bucholz alarm & trip along with annuciator panel, master trip relay, mechanical ON / OFF /Earth indication, Voltage presence indicator, Shunt trip coil, 24 V DC power pack, Digital multi function meter, with Bus PT panelwith 3 Nos single phase voltage transformers of the ratio 11kV/v3 / 110 V/v3, 25 VA, Class 1.0 with HT fuses in the primary and MCB on the secondary side, Voltmeter with selector switch, R Y B phase indication, Anti reflex operating handle, right angle boots etc. OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDAlab tpye test reportsbefore execution as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
4Supply , Installation, Testing and Comissioning of following capacity IK10Sandwich TypeRising Mains / Bus Bar trunking Confirming to IEC 61439 part 1 & part 6 standard & IS 8623 P-II for use on 3 phase 4 wire, 50% internal earth , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 4 as per IS1892,with IP-54 enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminium bus bars, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDA /ASTAlab typetest reportsbefore execution as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
5630 amps 40 KA SC for 1 sec
6800 amps 50 KA SC for 1 sec
7Supply , Installation, Testing and Comissioning offollowing capacity End Feed Unit Confirming to ANSI C37.23 standard & IS 8623 P-II suitable for Sandwich typy for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDAlab typetest reportsbefore execution as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
8For 630 Amp. (Without MCCB)
9For 800 Amp. (Without ACB)
10Supply , Installation, Testing and Comissioning offollowing capacity Plug in / Tap off Box suitable forSandwich type bus bar trunking Confirming to ANSI C37.23 standard & IS 8623 P-II & IEC-60947-2-2000 for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with provision of MCB/MCCB / ACB (but without MCB/MCCB/ACB) complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1163 amps(Suitable for MCCB) without MCCB
12100/125 amps (Suitable for MCCB) without MCCB
13160/200/250 amps (Suitable for MCCB) without MCCB
14400 amps (Suitable for MCCB) without MCCB
15630 amps (Suitable for MCCB) without MCCB
16Supply , Installation, Testing and Comissioning of Silent DG Set (As per latest CPCB emissionnorms) havingspecifications as per A, B, C, D, E, F,G,H
17A. 1500 RPM Diesel Engine conform to BS:649/5514 of suitable BHP Engine shall have residential silencer (isolated from main DG chamber), up to 3 M exhaust piping (with insulation & cladding ) as required .
18B.AC Brush less SPDP Alternator conform to BS 5000 (part 99) or IS 4722.-2001 . Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown).Engine & Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled
19C. Standard canopy with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mm CRCA sheet steel (structure) with side wall fabricated from 1.6 mm CRCA sheet & filled withglass wool (96Kg/m3)/ Foam. as per IS 8183 the doors of 28/40/50/85 mm thick as per rating and fabricated from 1.6mm CRCA sheet packed with accoustic material,All doors/ opening are sealed with neoprene/EPDN gaskets. The enclosure has built in fuel tank, with protection and tripping of DG set against temperature of more than 50 degree centigrade
20D. Electronic / Mechanical governor, Manual & electric Start ,Batteries with battry charger,Engine instruments panel,AVM pads All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring & control system, MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter,digital fuel display meter,Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dB at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity :
21E. (A)Accoustic glass wool wall thickness should not be less then 40mm and not less then 20mm PU foam upto rating 100 KVA. (B).Accoustic glass wool wall thickness should not be less then 65mm and not less then 50mm PU foam upto rating 250 KVA.(C)Accoustic glass wool wall thickness should not be less then 100mm forrating above 250 KVA.
22F. First filling of the fuel tank shall be done by contractor and the prevailing fuel cost at that time shall be reimbursed to the contactor by department.
23G. Servicing of the DG set (as per OEM guidelines) during the DLP period shall be done by contractor including all consumables,actual charges shall be reimbursed to the contractor by department/client complete in all respect.
24H.OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDA/ CPCB standards approved lab typetest reportsbefore execution as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
25Radiator Cooled & Turbo Charged /AC
26320 KVA at 0.8 pf 415V 50Hz 3-?
27500 KVA at 0.8 pf 415V 50Hz 3-?
28Supply , Installation, Testing and Comissioning ofAuto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stopcommands, control Relays , Ammeter & Voltmeterwith selector switches, Control & 2 nos 4 pole Power Contactors with 2 no. of required size 4 pole MCCB, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets. OEM Must have BIS certificate and&shall have submitNABL / CPRI / ERDAlab typetest reportsbefore execution as required complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
29PLC Based:
30250 TO 320 KVA
31500 KVA
32Supply, Installation, Testing & Commissioning of HT metering cubical panel as approved By DISCOMs fabricated out of 14 SWG CRCA sheet steel in two compartment & MS angle of size 60mmX6mm having provision for Following: (i)Provision for fixing Trivector Meter (To be supplied by DISCOMs) (ii)Provision for fixing of combined CT PT Set (To be supplied by DISCOMs), (iii)TT Block, (iv) 6mm Bakelite sheet on all sides, (V) 3/6 core copper cable for interconnections etc. as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
33Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
343.3 KV,2 mm thick with proof voltage 10 KV / 3 min. and Break Down Voltage 30 KV
3511 KV,2.5 mm thick with proof voltage 22 KV / 3 min. and Break Down Voltage45 KV
36SITC of IP 40quick make and quick break4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings as per PWD specification for electrical Works, conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 800 V, provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connections with lugs & spreaders,etc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
37With Thermal Magnetic release
38up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
39125 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
40160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
41200 Amp ,35kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
42250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
43400 Amp ,50 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu
44630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu
45SITC ofDraw out type 3/4 pole IP53, IK 08 door interlock Air Circuit Breaker (ACB) as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 in existingLT panel suitable for LT installation 440 V, 50 Hz and havingadjustable over load short-circuit, earth fault and withseparate LED indication for each type of fault ,Password protected relase (trip mechanisum) shall confirm to EMI/ EMC test , LCD/LEDdisplay , Thermal memory , pollution degree 4, trip free mechanisum , suitable for ambient 50 degree and utilization catagary B.In built electrical & mechanical anti pumping fearute , 100% rated neutral . ACB shall have separate indication for service, test, isolation & maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , U imp - 12 KV, break time not more then 25 ms. Provision for electrical & mechanical interlock between ACBs, Min.electricaloperation 10,000 upto 2000 A rating and 5,000 for2500 A. including making connectionsetc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution & All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
46Microprocessor based release Draw out type (Manual spring charged) 4Pole
47800 A Rating, 50kA
48Supply and fixing of following accessories for Air circuit breaker (ACB)compatible with MAin ACB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution . All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
49Shunt Trip Release
50Under Voltage Release
51Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Un-armoured / Armouredaluminiumcable of 1.1 KV grade as per PWD specification for electrical Worksin existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench, on existing cable trays or on surface etc.including making necessary connection, testing etc. as required of size andas per points (a), (b), (c), mentioned below:-
52(a) Material :- H4- Gradealuminium conductor of purity >99.6 %& as perIS:1554 P-I / IS :7098 P - I
53(b) conductor shall have electrolytic aluminium confirming to IS 8130, IS 3975-1999for armouring of cables in armoured cable items , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures .
54(c)OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities forcables . Appropriate type test certificate / OEM test report shall be submitted .All above as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
55Un-armoured
564.0 Sq. mm
572 core
586.0 Sq. mm
592 core
60Armoured Cable
616.0 Sq. mm
624 core
6310.0 Sq. mm
644 core
6516.0 Sq. mm
664 core
6735.0 Sq. mm
683.5 core
6950.0 Sq. mm
703.5 core
7195.0 Sq. mm
723.5 core
73185.0 Sq. mm
743.5 core
75240.0 Sq. mm
763.5 core
77300.0 Sq. mm
783.5 core
79400.0 Sq. mm
803.5 Core
81Labour charges for Excavation of 30cmx120cm size trench in tar road including refilling of excavatedearth,compaction of earth, making good the same complete as required .
82Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.
83Laying Charges for cable through Vermeer machine by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required.
84Providing & Laying P.V.C./ XLPE insulated & P.V.C. sheathed Un-armoured / Armoured copper cable of 1.1 KV grade as per PWD specification for electrical Worksin existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench, on existing cable trays or on surface etc.including making necessary connection, testing etc. as required of size andas per points (a), (b), (c),mentioned below:-
85(a) Copper conductor of electrlytic grade copper,purity >99.97 % ISI marked as perIS:1554 P-I / IS :7098 P - I
86(b) conductor shall made of copper rodsconfirming to IS 613-1964,IS 3975-1999for armouring of cables in armoured cable items , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures
87(c) OEM Must have ISO 9001 & 14001 certifications & its own in house NABL lab setup for all testing facilities forcables . Appropriate type test certificate / OEM test report shall be submitted . All above as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
882.5 Sq. mm
897 core
90Supplying and making one end termination with heavy duty brass compression gland (as per IS 12943- 1990) SIBG type, heavy duty aluminium lugs (as per IS 8309 -1993 & IS 8337-1976 ) duly crimped with crimping tool, PVC tapeas per PWD specification for electrical Works etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required of size. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
912 x 4.0 sq.mm
922 x 6.0 sq.mm
933.5 x 35.0 sq.mm
943.5 x 50.0 sq.mm
953.5 x 95.0 sq.mm
963.5 x 150.0 sq.mm
973.5 x 185.0 sq.mm
983.5 x 240.0 sq.mm
993.5 x 300.0 sq.mm
1003.5 x400.0 sq.mm
1014 x 6.0 sq.mm
1024 x 10.0 sq.mm
1034 x 16.0 sq.mm
104Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
105150mm x 50mm x 1.6mm
106300mm x 50mm x 1.6mm
107450mm x 50mm x 2.0mm
108600mm x 50 mm x 2.0mm
109600mm x 62.5mm x 2.0mm
110600mm x 75mm x 2.0mm
111supply & fixing of cable route markeras per PWD specification for electrical Works with 10cm x 10cm x 5mm thick and 10cm dia. G.I.plate with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron,60cm long and fixing the same in ground in C C ( 1:3:6 ) as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
112Providing & laying of Double wall corrugated pipe confirming to IS : 14930 P - 1 & 2with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required( Excavation of Earth to be paid Extra as required. )of following Outer Dia. / Inner dia as per IS:4984:1995. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
11355/50 mm
114110 / 95 mm
115160 / 136 mm
116300 / 260 mm
117Providing and laying Non Pressure NP-3 class (Medium duty) R.C.C. pipes including collars/spigot jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) etc. as required. ( Excavation of Earth to be paid Extra as required. ) All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
118200 mm Dia.
119300 mm dia
120450 mm dia.
121Plate Earthing as per PWD specification for electrical Works as per IS:3043 withcopper Earth plate of size 600mm x 600mm x 3.0mm by embodying3 to 4 mtr. below the ground level with 20mm dia. G.I. "B" class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, and Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm. and embodying the pipecomplete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
122SITC ofchemical Gel earthing system ofDual Pipe Technology made of with "B" ClassG I Pipeas per IS 1239 ( part-1):2004of Medium duty of following sizesas per points mentioned (a), (b), [c), (d), (e) below :-
123(a) filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 35- 40 KA for withstanding 1 second .
124(b) To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts
125©Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm.
126(d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.
127(e) Self certificate for confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
128GI pipe 3000 mm long, 80 / 50 mm, Terminal 50 mm x 6 mm GI Strip
129GI pipe 2000 mm long, 80 / 50 mm, Terminal 50mm x 6 mm GI Strip
130Supply & Laying following size earth stripin horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, Jointing shall be done by overlapping and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
13120mm x 3mm copper strip
13250mm x 6mm copper strip
13325mm x 3mm G.I. ( Hot Dipped) Strip
13425mm x 6mm G.I. ( Hot Dipped) Strip
13532mm x6mm G.I. ( Hot Dipped) Strip
13650mm x 6mm G.I. ( Hot Dipped) Strip
137Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cuthimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1388 SWG copper Wire
1398 SWG G.I. ( Hot Dipped) Wire
140Supply & Laying following size" B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc.for laying earth conductor/ strip / cable in ground/ surface/ recess as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
14140 mm dia.
14265 mm dia.
143Supply and fixing of 1.6 mm thick MS 11 kV Danger plates as per IS :2551-1982 & specification of Discom on the existing poles complete in all respectas per PWD / DISCOM specification. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
144Providing & Laying XLPE insulated as per IS:7098/II/85H.T.cable as per PWD specification for electrical Works for working voltage 11 K.V.(E) in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench with filling of excavated earth in trench, on existing cable trays or on surface etc.including making necessary connection, testing etc. as required of size as per points (a), (b), (c) mentioned below:-
145(a) Material :- H4- Gradealuminium conductor of purity >99.6 %& as perIS:1554 P-I / IS :7098 P - I
146(b) conductor shall have electrolytic aluminium confirming to IS 8130, IS 3975-1999for armouring of cables , IS 5831 for sheath, IS 10810 (Part 0 to 64 ) for testing procedures
147(c)OEM Must have ISO 9001 & 14001 certifications for quality assuarance & its own in house NABL lab setup for all testing facilities forcables .All above as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1483 core 185.0 Sq.mm
1493 core 300.0 Sq.mm
150Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit as per PWD specification for electrical Works suitable for11 KV / 33 KV cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 which covered all sequence for table 2 for termination kit and table 3 for streightthrough joint inclusive thermal & dynamic short circuit test, humidity test, soil fog test. Crosslinking shall be done out side factory with E- beam/ peroxide technology. Extrusion process shall be in house OEM within same vicinity. OEM test lab should be as per ISO 9001:2015 & 14001 : 2015 & reports submitted to engineer in charge includingtesting etc. as required of following sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
15111 KV End Termination Kit Indoor type
1523 core 120/150/185 Sq.mm
1533 core 240/300 Sq.mm
15411 KV End Termination Kit Outdoor type
1553 core 240/300Sq.mm
15611 KV Straight Through JointKit
1573 core 120/150/185 Sq.mm
1583 core 240/300 Sq.mm
159Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as requiredcomplete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
160Providing & Fixing of ISO certified company made IK10IP65 protected Top/Bottom mounted LED Post top Light system. Fixture made of powder coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy =90 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N)and efficiency > 85%, PF>0.9, THD<20% and input Voltage range of 90-270V AC at 50Hz. System life of 30000 Burning hours with 70% of Initial Lumens maintainedLight output in Cool white or Warm White Colour as per engineers choice. driver current <1000mA shown in LM79 report.Fixture must be in compliance with BIS Standards and T.C . Certificate complete in all respect.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
16145 W LED Post Top Fixture
162Supply and erection of M.S. Galvanized Octagonal pole ( as per BSEN 40-3-3:2003 /BSEN 10025/IS 2062 IS:875 Part-1 – 2015/ for MS plate for baseflange )of following length and dimension as per table P-01 with base plate on the cement concrete foundation of M-20 grade (1:1.5:3) as perIS 456/IS 2911. with the help of anchor bolts of grade 6.8 (IS: 1367 P III ).The pole shall have a weatherproof flush door and locking arrangements. complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
163Octagonal MS Polesmade of S-355JO grade steel sheet , folded lengthwise to obtained Octagonal shape, having single longitudinal seam weld and hot dipped galvanised internally & externally in accordance with IS 2629. (See Table P -01 for specs.)
1647 Mtr.
1654 Mtr.
166Supply, Erection and Fixing of hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
167Single arm overhang
168Providing & Fixing of IK07 IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum LM6/ ADC12 material with heat dissipation fins on housing with UV stabilized PC/Toughened Glass cover (UV stablzation report submitted for UV cover ) and secondary lens on each LED & should be SMD type . The System level Luminaire efficacy >=120 lm/ wtwith High Power LEDs is to be usedand potted driver must be potted & has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety ,Input Frequency 50Hz±3% Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <1000mA shown in LM79 report. The luminaireshall be BIS certified and T.C. certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened ,color Rendering Index >70 and CCT 5700K +355K. Surge protection shall be min = 4 KV internal and min 10 KV external. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.
169OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
170LED Street Light fixture 70 Watt
171Providing and fixing of IP 65 protected Polycarbonate / Polysterene fuse box moulded with inside knock outs of following size with hinged cover, transparent window,PU gasket, locking arrangement, duly holded with 2 nos. pole clamps of 20 mm x 3 mm flat with nut and bolts, The box shall be provided with Din rail, 4 / 8 way 10.0 / 16.0sq.mm heavy duty connector, earth terminal,complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
172125 mm X 200 mm X 122 mm
173Providing & Fixing of Street light bracket made out from following size of " B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
17440 mm Dia.
175Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
17650 mm dia per running inch length
177100 mm dia per running inch length
178150 mm dia per running inch length
179200 mm dia per running inch length
180Providing and making wall openings in existing stone masonary wall complete with all requited T & P , Scafolding and providing lintel of required size andstrength, repairing ,plastering and cleaning the sitedebrises as required.
181Providing and making wall openings in existing Bricks masonary wall complete with all requited T & P ,Scafolding andproviding lintel of required size and strength, repairing ,plastering and cleaning the sitedebrises as required.
182Supplying and Laying ISI marked P.V.C. insulated submersible cable as per PWD specification for electrical Worksconfirming to IS:694 and as per IS 8130 : 2013 of 1.1 kV grade .Wire should be made from99.99% purity copper, class 5 stranding in acc. to IEC 60228 forlower watt loss , oxygen free ( <10 ppm) for less chances of oxidization and higher silver content for gives better conductivity , insulation PVC type A ,flame retardant as per IS 10810-53, better amperage rating as per VDE 0298 part 4 including making connection etc. as required.OEM Must have its own in house NABL lab setup for all testing facilities for wires. All as per pre approved by Engineer in charge, making connections.For additional technical parameters of products/ work, referAnnexure "A" attached with this BSR .
1832.5 Sq.mm 3 core flat / Round
184Providing & Fixing of 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C tripping characteristic as per type of load andsite requirement) 4KV impulse withstand voltage,as per PWD specification for electrical Works with ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductorline load reversibility, label holding facility , IP 20 contact protection and fitted withexisting distribution board/sheets, min. operation 20,000 upto 32 A rating and 10,000 upto 63 A, 5000 for 80 A ratingincluding making connections, testing etc. as required.. OEM shall have submitNABL / CPRI / ERDA accrediated lab test reportsbefore execution & All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
185Triple pole MCB
1866 A to 32 A rating
18740 A rating
18850-63 A rating
189Providing & Fixing of IK 09 rating recessed/surface mounting heavy duty Vertical type sheet steel 1.6 mm thick Distribution board as per PWD specificationfor electrical Works ISI marked conforming to IS-13032 & IS-8623 / conforming to IEC 61439-3 with provision of incomer suitable for MCCB and SP / TP MCB as outgoing ,phosphatised ,powder painted complete with insulated suitable ratingcopper bus bar , neutral link, earth link and din bar, masking sheet,including making internal DB terminations with copper lugs and with detachable gland plate, testing etc. as required complete in all respect.OEM shall have submitNABL / CPRI / ERDA accrediated lab test reportsbefore execution & All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
190IP 43- Double door with Provision of Incomer MCCB 100 / 125/160 A Rating
1914 Way
19212 Way
193Providing & Fixing ofrecessed/surface mounting heavy duty sheet steel 1.6 mm thick End Box as per PWD specificationfor electrical Works for distribution board duly phophatised powder coatedcomplete asrequired. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
194For all VTPN DB
195Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.99% purity copper, class 5 stranding in acc. to IEC 60228 forlower watt loss , oxygen free ( <10 ppm) for less chances of oxidization and higher silver content for gives better conductivity , insulation PVC type A ,flame retardant as per IS 10810-53, better amperage rating as per VDE 0298 part 4,, in existingsurface or recessed PVC/ MS conduit/casing capping includingall as per pre approved by Engineer in charge,making connections, etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of products/ work, referAnnexure "A" attached with this BSR .
1962 x 6.0 sq. mm. + 1 x 4.0 sq. mm.
1974 x 6.0 sq.mm
1982 x 4.0 sq.mm
199NON BSR
200Supply installation testing & Commissioning of Copper wound distribution Transformerof following ratingand % Impedance, 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooledlosses as per IS 1180 part I 2014 (Fourth Revision) Level-1, with boltless core designincluding standardaccessories like conservator with prismaticoillevelgauge , silica gel breather,Bucholz relay,pressed steel radiator fins, Radiator Valve(above 800 Kva) Suitable size HT cable box,LT cable box with Busbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ),temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device,Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800 Kva rollers with locking arrangement etc. as required. The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including Temperature rise test inOEM"s own lab shall be witnessed by Department engineer Physically.
201Transformer shall be tested from CTLof discombefore charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor)Following tests shall be carried out on each transformer at site by OEM enginer in presence of department authorised representative:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per pre approved by Engineer in charge.Make : Uttam bharat/ Danish/ Verdhman/ Voltamp /United
2021000 KVA with % Impedance 5.0
2032000 KVA with % Impedance 6.25
204SITC of Marshalling box fabricated out of 2.0 mm thick sheet steel, provided with water tight hinged doors with padlock arrangement, neoprene gasket all around door to make enclosure water and dust proof (IP-55). Space Heater, Illumination lamp, 5A switch & Socket, MCB, Viewing window, detachable gland plate completely wired, ready for external connections at the terminal blocks. All wirings shall be carried out with 1100 V grade PVC insulated stranded conductors. Power circuits if any shall be wired with stranded copper conductors of adequate sizes to suit the rated current. The minimum size shall be 2.5 sq.mm. Control, alarm and indication circuits, shall be wired with stranded copper conductor of sizes not smaller than 1.5 sq. mm. CT circuits shall be wired with stranded copper conductor of size not smaller than 4 sq.mm. including 150 mm dia. Winding temperature indicator with A&T contacts, 150 mm dia. Oil temperature indicator with A&T contacts , 150 mm dia. Magnetic Oil level Gauge ( MOG) with alarm contact, double float type Buchholz relay with isolating valves on both sides and as per IS: 3637 with A&T Contacts etc. as required.
205All as per pre approved by Engineer in charge.
206SITC ofBus Rising Main OEM manufacturedTinned copper flexible joint with enclosure of following capacity with Transformer / DG / Panelas required complete in all respect. All as per pre approved by Engineer in charge.Make : L&T, Schneider, C&S, GE, Legrand, Siemens, ABB
2073200 Amp.
208SITC of following capacity IK10Sandwich TypeRising Mains / Bus Duct Confirming to IEC 61439 part 1 & part 6standard & IS 8623 P-IIand Manufactured in India for use on 3 phase 4 wire, 50% internal earth , 415 volts, 50Hz A.C. supply , class F insulation, rated insulation voltage 1000V, impulse withstand voltage 12 KV, min. seismic zone 4 as per IS1892,with IP-54 / IP-66 (With Canopy) enclosure made of 1.6mm thick sheet steel duly powder coated in convenient sections complete with 4 Nos aluminium (with 6101 or 63401 grade) bus bars, necessary joints & expansion joints, fire barrier at each floor, provision of tapping at every metre, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system including making opening in RCC / Brick Masonary and repairing the same etc. as required. Type Tests reports like(i) Short Circuit Test (ii) Degree of Protection (iii) Temperature rise test of Rising main in CPRI / UL / ASTA accrediated lab will be submitted by OEM.
209Routine test as per OEM"s QAP in It"s own Manufacturing facility in Indiashall be witnessed by department Engineer virtually / Physically.Complete Installation of Rising Mains shall be Vetted by Manufacturer before Comissioning. All as per pre approved by Engineer in charge.Make : L&T, Schneider, C&S, GE, Legrand, Siemens, ABB
210Out Door Bus Duct IP66 with Canopy
2113200Amps 120kA SC for 1 sec
212Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810. Make :Havell"s, KEI, Gems Cab, Ishwar Cab,Unistar,Polycab,RR Kable,Grandlay
213800.0 Sq. mm
2141 core
215Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge.
2161 x 800.0 sq.mm
217Supply of cubicle type totally enclosed free standing type dust & vermin proof Main Panel made out of 2.0 mm thick and partition made out of 1.6 mm MS sheet steel, suitable for 3 phase , 4 wire , 415 V , 50 Hz , AC supply complete with incoming ACB / MCCB / SFU & outgoing MCB / MCCB / SFU , All the MCCB should be with Rotary handle, Four Pole Electrolytic grade Al busbar of required capacity, indication lamp etc complete as per drawing, enclosed specifications as per approved makes.makes-E&E, Ankit, Mile Stone, Expert, Pyrotech.
218NOTE:
219All MCCBs shall have Ics=Icu=100%
220MCB Should be connected throught terminal Strip of suitable rating
221All the Main panel incomer shall have 3 pole + neutral type 1 + 2 SPD & all the sub main panel incomer shall have 3 pole + neutral type 2 SPD with suitable rating 4 pole MCB.
222same as above description ( Light Floor Panel)
223Incomer
2241 Nos 100 A FPManual Change over Switch
2251 No. 100 A FP MCCB (25 KA)
2261 Set phase indication lights (R, Y, B)
2271 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
228BUS BARS:-
229150 Amps. TP&N aluminium bus bars
230OUT GOINGS:-
2316 Nos 40/63 Amp. FP MCB (10 KA)
232same as above description ( Light Floor Panel)
233Incomer
2341 No.160 A FP Manual Change over Switch
2351 No. 160 A FP MCCB (36 KA)
2361 Set phase indication lights (R, Y, B)
2371 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
238BUS BARS:-
239250 Amps. TP&N aluminium bus bars
240OUT GOINGS:-
24110 Nos 40/63 Amp. FP MCB (10 KA)
242same as above description ( Power Floor Panel)
243Incomer
2441 No.250 A FP Manual Change over Switch
2451 No. 250 A FP MCCB (36 KA)
2461 Set phase indication lights (R, Y, B)
2471 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
248BUS BARS:-
249400 Amps. TP&N aluminium bus bars
250OUT GOINGS:-
25110 Nos 63 Amp. FP MCB (10 KA)
252same as above description ( Power Floor Panel)
253Incomer
2541 No.160 A FP Manual Change over Switch
2551 No. 160 A FP MCCB (36 KA)
2561 Set phase indication lights (R, Y, B)
2571 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
258BUS BARS:-
259250 Amps. TP&N aluminium bus bars
260OUT GOINGS:-
2616 Nos 40/63 Amp. FP MCB (10 KA)
262same as above description ( ACFloor Panel)
263Incomer
2641 No. 250 A FP MCCB (36 KA)
2651 Set phase indication lights (R, Y, B)
2661 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
267BUS BARS:-
268400 Amps. TP&N aluminium bus bars (36 KA)
269OUT GOINGS:-
2704 Nos 40/63 Amp. FP RCBO ( 300Ma)
271same as above description ( ACFloor Panel)
272Incomer
2731 No. 400 A FP MCCB (50 KA)
2741 Set phase indication lights (R, Y, B)
2751 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
276BUS BARS:-
277600 Amps. TP&N aluminium bus bars (50 KA)
278OUT GOINGS:-
27912 Nos 40/63 Amp. FP RCBO ( 300Ma)
280same as above description (AC Panel )
281Incomer
2821 No. 250 A FP MCCB (36 KA)
2831 Set phase indication lights (R, Y, B)
2841 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
285BUS BARS:-
286400 Amps. TP&N aluminium bus bars
287OUT GOINGS:-
2886 Nos 40/63 Amp. FP RCBO ( 300Ma)
289same as above description ( ACFloor Panel)
290Incomer
2911 No. 400 A FP MCCB (50 KA)
2921 Set phase indication lights (R, Y, B)
2931 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
294BUS BARS:-
295600 Amps. TP&N aluminium bus bars (36 KA)
296OUT GOINGS:-
29716 Nos 40/63 Amp. FP RCBO ( 300Ma)
298same as above description ( ACFloor Panel)
299Incomer
3001 No. 250 A FP MCCB (36 KA)
3011 Set phase indication lights (R, Y, B)
3021 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
303BUS BARS:-
304400 Amps. TP&N aluminium bus bars (36 KA)
305OUT GOINGS:-
30612 Nos 40/63 Amp. FP RCBO ( 300Ma)
307same as above description (UPS normal)
308INCOMER
3092 Nos. 250 Amps. FP MCCB (36KA)
3102 Set phase indication lights (R, Y, B)
3112 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
312BUS BARS:-
313400 Amps. TP & N aluminium bas bar
314OUT GOINGS:-
3152 Nos. 160 Amps FP MCCB (25KA)
3166 Nos. 100 Amps FP MCCB (25KA)
317same as above description (Equipment Panel)
318Incomer
3191 No.400 A FP MCCB (50 KA)
3201 Set phase indication lights (R, Y, B)
3211 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
322BUS BARS:-
323600 Amps. TP&N aluminium bus bars
324OUT GOINGS:-
3256 Nos. 100 Amps. FP MCCB (25KA)
3262 Nos. 160 Amps. FP MCCB (25KA)
3271 Nos. 200 Amps. FP MCCB (36 KA)
328same as above description (Equipment Panel)
329Incomer
3301 No.630 A FP MCCB (50 KA)
3311 Set phase indication lights (R, Y, B)
3321 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
333BUS BARS:-
334900 Amps. TP&N aluminium bus bars
335OUT GOINGS:-
33610 Nos. 100 Amps. FP MCCB (25KA)
3372 Nos. 160 Amps. FP MCCB (25KA)
3382 Nos. 200 Amps. FP MCCB (36 KA)
339same as above description (UPS OT)
340INCOMER
3412 Nos. 160 Amps. FP MCCB (36KA)
3422 Set phase indication lights (R, Y, B)
3431 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
344BUS BARS:-
345250 Amps. TP & N aluminium bas bar
346OUT GOINGS:-
34710 Nos. 100 Amps FP MCCB (25KA)
348same as above description (Light bus panel)
349Incomer
3501 No.800 A FP MDO TYPE ACB (50 KA)
3511 Set phase indication lights (R, Y, B)
3521 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
353BUS BARS:-
3541200 Amps. TP&N aluminium bus bars
355OUT GOINGS:-
3563 Nos. 63 Amps FP MCB (10 KA)
3572 Nos. 630 Amps. FP MCCB (50 KA)
3582 No. 400 A FP MCCB (50 KA)
3592 No. 250 A FP MCCB (36 KA)
3602 Nos. 160 Amps. FP MCCB (25 KA)
361same as above description (Power bus panel)
362Incomer
3631 No.2000 A FP MDO TYPE ACB (50 KA)
3641 Set phase indication lights (R, Y, B)
3651 No. Multi function meter (digital type) with inbuilt VSS, ASS & control MCB with RS 485 port with 3nos CT
366BUS BARS:-
3673000 Amps. TP&N aluminium bus bars
368OUT GOINGS:-
3692 Nos. 63 Amps FP MCB (10KA)
3702 No. 400 A FP MCCB (50 KA)
3714 Nos. 800 Amps. FP MCCB (50 KA)
3722 Nos. 250 Amps. FP MCCB (36 KA)
3732 Nos. 160 Amps. FP MCCB (25 KA)
374MAIN LT Panel (SK Hospital Campus)
375Supply of cubicle type totally enclosed free standing type dust & vermin proof Main Panel made out of 2.0 mm thick and partition made out of 1.6 mm MS sheet steel, suitable for 3 phase , 4 wire , 415 V , 50 Hz , AC supply complete with incoming ACB / MCCB / SFU & outgoing MCB / MCCB / SFU , All the MCCB should be with Rotary handle, Four Pole Electrolytic grade Al busbar of required capacity, indication lamp etc complete as per drawing, enclosed specifications as per approved makes-E&E, Ankit, Mile Stone, Expert, Pyrotech.
376All the Main panel incomer shall have 3 pole + neutral type 1 + 2 SPD & all the sub main panel incomer shall have 3 pole + neutral type 2 SPD with suitable rating 4 pole MCB.
377PROVISION OF BUSDUCT/CABLE MUST BE AS PER SLD.
378Note:
379The incoming of Transformer feeders as shown on drawing shall be connected through bus duct. The suitable adopter box shall be provided on top only and DG feeders & Solar Incommer through cable from top.
380All Intelligent ACB shall have Micro processor based O/C, S/C & E/F. All ACB"s shall have Ics=Icu=Icw as per BOQ for 1Sec & should be supplied with Adopter Terminal Connections whose orientation can be changed on site.
381All Intelligent MCCB shall have Micro processor based release. All CTs and PTs shall be cast resin type. All MCCB shall have Ics = 100% Icu & should have Isolation Feature & Class II Front Face as standard.
382The LT Panel manufacturer shall provide necessary,CT"s Aux. contacts; multiply those contacts in the respective panels etc. to hook up in to PLC system
383INCOMING
384TRANSFORMER INCOMER (1 Nos. 1000 KVA) one set for each incomer
3851 No. 1600 A, 65KAFP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor basedO/C, S/C& E/F releases
3861 No. 230 volt A.C.Shunt release
3871 No. 230 volt A.C.closing coil
3881 No. 415 volt A.C. under voltage release.
3891 Set of CTs 1600 / 5A class-1 for metering
3901 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB.
3911 No. multi ratio CT 1600/800 / 5A Class-1 for Capacitor panel.
3921 Set of O/C, S/C, and E/F relay
3931 No Breaker control switch
3941 Set of phase indication lights R,Y,B.
3951 set ofON-OFF-TRIP ckt. Healthy. indication lights
3961 No Spring charged indication.
397D.G. PANEL INCOMERS (320 KVA DG set)one set for each incomer
3981 No. 630 A, 50KAFP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor basedO/C, S/C& E/F releases.
3991 No. 230 volt A.C.Shunt release
4001 No. 230 volt A.C.closing coil
4011 No. 415 volt A.C. under voltage release.
4021 Set of CTs 630/ 5A class-1 for metering
4031 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB.
404Battery charger 230 V/ 24 V DC, 20 A with DC ammeter and DC voltmeter. Charger should have all basic protections like over load, over Voltage reverse polarity etc.
4051 Set of O/C, S/C, and E/F relay
4061 No Reverse power relay
4071 No Breaker control switch
4081 Set of phase indication lights R,Y,B.
4091 set ofON-OFF-TRIP ckt. Healthy. indication lights
4101 No Spring charged indication.
411BUS BARS:-
4122500 Amps. 4P aluminium bus bars
413BUS COUPLER:-
4141 No. 1600 A ,65KA ,4POLE ,EDO ACB with 230 V A.C. spring charged motor.
4151 sets Breaker Control switch
4161Sets of phase indication lights R,Y,B.
4171sets ofON-OFF-TRIP ckt. Healthy. indication lights
418Interlocking: Transformer incomers , DG Panel Incommers, and bus couplers shall be electrically andinterlocked so that no different source can be paralled at any point of time.
419OUTGOINGS:-
4202 Nos. 800 Amps, 50 KA FP MDO type ACB with M.R. releases for O/C, & S/C.
4211 Nos. 800 Amps, 50 KA TP MDO type ACB with M.R. releases for O/C, & S/C. FOR APFC INCOMER
4221 Nos. 630 AFP MCCB , 50KA,with M.R. releases for O/C, & S/C.
4231 Nos. 400 AFP MCCB , 50KA,withM.R. releases for O/C, & S/C.
4242 Nos. 250 AFP MCCB , 36KA,with M.R. releases for O/C, & S/C.
4252 Nos. 200 AFP MCCB , 36KA,with M.R. releases for O/C, & S/C.
4264 Nos. 160 AFP MCCB , 36KA,with M.R. releases for O/C, & S/C.
4272 Nos. 100 AFP MCCB , 25KA,with M.R. releases for O/C, & S/C.
428APFC SECTION1nos 400 Kvar
4291 No.16 step APFC Relay (intelligent micro-processor based with current sensitivity less than 1%)
4303 Nos. CTs- 800/5 Amps. Cl-1
4311 Set phase indication lights (R, Y, B)
4321000 Amps. TP&N aluminium bus bars (50 KA)
4332 No.250Amps. TPN MCCB (25 KA) with thermal magnetic release
4342 No.125 Amps. TPN MCCB (16 KA) with thermal magnetic release
4352 nos 63 Amp TP MCB (10KA) D curve
4362 nos 25 Amp TP MCB (10KA) D curve
4376 nos 16 Amp TP MCB (10KA) D curve
4382 No. 100 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 7% D-tuned Harmonic Al reactor filter
4392 No. 50 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 7% D-tunedHarmonic Al reactor filter
4402 No. 25 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 7% D-tunedHarmonic Al reactor filter
4412 No. 10 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 7% D-tunedHarmonic Al reactor filter
4426 No. 5 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 7% D-tunedHarmonic Al reactor filter
4432 No.100 KVar TP capacitor duty contactors.
4442 No. 50 KVar. TP capacitor duty contactors.
4452 No. 25 KVar. TP capacitor duty contactors.
4462 No. 10 KVar. TP capacitor duty contactors.
4476 No. 5 KVar. TP capacitor duty contactors.
44814 No. Auto-Off-Manual selector switch.
44914 Sets self illuminated Red-Green ON-OFF push buttons.
4502 Sets of Axial flow fans with thermostate.
451Auto AMF:-The AutoAMF panel SECTION
452Suitable PLC forAMF operation of One DG sets - 1 nos
453Suitable slot I/O rack with power supply
454Hooter for various status annunciation
455All the software required for proper operation
4561 KVA online UPS with half an hour battery (SMF) back up for start operation
457SPARE SPACE
458The panel should have sufficient space for expansion modules & required hardware for future expansion as per SLD.
459LT Panel described above & as per specification.
460MAIN LT Panel (College Campus)
461Supply of cubicle type totally enclosed free standing type dust & vermin proof Main Panel made out of 2.0 mm thick and partition made out of 1.6 mm MS sheet steel, suitable for 3 phase , 4 wire , 415 V , 50 Hz , AC supply complete with incoming ACB / MCCB / SFU & outgoing MCB / MCCB / SFU , All the MCCB should be with Rotary handle, Four Pole Electrolytic grade Al busbar of required capacity, indication lamp etc complete as per drawing, enclosed specifications and as per approved make-E&E, Ankit, Mile Stone, Expert, Pyrotech.
462All the Main panel incomer shall have 3 pole + neutral type 1 + 2 SPD & all the sub main panel incomer shall have 3 pole + neutral type 2 SPD with suitable rating 4 pole MCB.
463PROVISION OF BUSDUCT/CABLE MUST BE AS PER SLD.
464Note:
465The incoming of Transformer feeders as shown on drawing shall be connected through bus duct. The suitable adopter box shall be provided on top only and DG feeders & Solar Incommer through cable from top.
466All Intelligent ACB shall have Micro processor based O/C, S/C & E/F. All ACB"s shall have Ics=Icu=Icw as per BOQ for 1Sec & should be supplied with Adopter Terminal Connections whose orientation can be changed on site.
467All Intelligent MCCB shall have Micro processor based release. All CTs and PTs shall be cast resin type. All MCCB shall have Ics = 100% Icu & should have Isolation Feature & Class II Front Face as standard.
468The LT Panel manufacturer shall provide necessary,CT"s Aux. contacts; multiply those contacts in the respective panels etc. to hook up in to PLC system
469INCOMING
470TRANSFORMER INCOMER (2 Nos. 2000 KVA) one set for each incomer
4712 No. 3200 A, 65KAFP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor basedO/C, S/C& E/F releases
4722 No. 230 volt D.C.Shunt release
4732 No. 230 volt A.C.closing coil
4742 No. 415 volt A.C. under voltage release.
4752 Set of CTs 3200 A/ 5A class-1 for metering
4762 No.Multi function Meter (digital type) with inbuilt VSS ASS & control MCB.
4772 No. muti ration CT 3200/1600/800 / 5A Class-1 for Capacitor panel.
4782 Set of O/C, S/C, and E/F relay
4792 No Breaker control switch
4802 Set of phase indication lights R,Y,B.
4812 set ofON-OFF-TRIP ckt. Healthy. indication lights
4822 No Spring charged indication.
483D.G. PANEL INCOMERS (500 KVA DG set)one set for each incomer
4842 No. 800 A, 50KAFP, EDO air circuit breaker with 230 V A.C. spring charged motor and micro processor basedO/C, S/C& E/F releases.
4852No. 230 volt D.C.Shunt release
4862 No. 230 volt A.C.closing coil
4872 No. 415 volt A.C. under voltage release.
4882 Set of CTs 800 A/ 5A class-1 for metering
4892 .Multi function Meter (digital type) with inbuilt VSS ASS & control MCB.
490Battery charger 230 V/ 24 V DC, 20 A with DC ammeter and DC voltmeter. Charger should have all basic protections like over load, over Voltage reverse polarity etc.
4912 Set of O/C, S/C, and E/F relay
4922 No Reverse power relay
4932 No Breaker control switch
4942 Set of phase indication lights R,Y,B.
4952 set ofON-OFF-TRIP ckt. Healthy. indication lights
4962 No Spring charged indication.
497BUS BARS:-
4984500 Amps. 4P aluminium bus bars
499BUS COUPLER:-
5001 No. 3200A ,4POLE ,EDO ACB with 230 V A.C. spring charged motor.
5011Sets of phase indication lights R,Y,B.
5021 sets Breaker Control switch
5031 sets ofON-OFF-TRIP ckt. Healthy. indication lights
5041 No. 1600 A ,4POLE ,EDO ACB with 230 V A.C. spring charged motor.
5051Sets of phase indication lights R,Y,B.
5061 sets Breaker Control switch
5071 sets ofON-OFF-TRIP ckt. Healthy. indication lights
508Interlocking: Transformer incomers , DG Panel Incommers, and bus couplers shall be electrically andinterlocked so that no different source can be paralled at any point of time.
509OUTGOINGS:-
5103 Nos. 800 Amps, 50 KA FP MDO type ACB with M.R. releases for O/C, & S/C.
5112Nos. 1600 Amps, 50 KA TP MDO type ACB with M.R. releases for O/C, & S/C. for apfc
5121 Nos. 1000 Amps, 50 KA FP MDO type ACB with M.R. releases for O/C, & S/C.
5132 Nos. 400 AFP MCCB , 50KA,withM.R. releases for O/C, & S/C.
5144 Nos. 250 AFP MCCB , 36KA,with M.R. releases for O/C, & S/C.
5153 Nos. 200 AFP MCCB , 36KA,with M.R. releases for O/C, & S/C.
5164 Nos. 160 AFP MCCB , 25KA,with M.R. releases for O/C, & S/C.
5174 Nos. 125 AFP MCCB , 25KA,with M.R. releases for O/C, & S/C.
5184 Nos. 100 AFP MCCB , 25KA,with M.R. releases for O/C, & S/C.
519APFC SECTION2nos 700 Kvar
5202 No.20 step APFC Relay (intelligent micro-processor based with current sensitivity less than 1%)
5216 Nos. CTs- 1250/5 Amps. Cl-1
5222 Set phase indication lights (R, Y, B)
5231800 Amps. TP&N aluminium bus bars (50 KA)
5244 No.250Amps. TPN MCCB (25 KA) with thermal magnetic release
52516 No.125 Amps. TPN MCCB (16 KA) with thermal magnetic release
5264 nos 63 Amp TP MCB (10KA) D curve
5276 nos 25 Amp TP MCB (10KA) D curve
5288 nos 16 Amp TP MCB (10KA) D curve
5294 No. 100 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tuned Harmonic Al reactor filter
53016 No. 50 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tunedHarmonic Al reactor filter
5314 No. 25 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tunedHarmonic Al reactor filter
5326 No. 10 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tunedHarmonic Al reactor filter
5338 No. 5 KVAR TP Shunt capacitor Heavy duty MPP type at 525 volt with discharge resistor and 14% D-tunedHarmonic Al reactor filter
5344 No.100 KVar TP capacitor duty contactors.
53516 No. 50 KVar. TP capacitor duty contactors.
5364 No. 25 KVar. TP capacitor duty contactors.
5376 No. 10 KVar. TP capacitor duty contactors.
5388 No. 5 KVar. TP capacitor duty contactors.
53938 No. Auto-Off-Manual selector switch.
54038 Sets self illuminated Red-Green ON-OFF push buttons.
5414 Sets of Axial flow fans with thermostate.
542Auto synchronisation :-The Auto LOAD Management cum AMF panel should be capable for two no external source and two nos DG sets.
543Suitable PLC for synchronisation & AMF operation of four DG sets - 1 nos
544Digital I/P module
545Digital O/P module
546Suitable slot I/O rack with power supply
547Analouge I/P module
548KW tranducer
549EEPROM memory module
550Phase angle tranducer
551Operator interface 3" diagonal with key pad
552Communication cable from Operator interface to PLC
553Hooter for various status annunciation
554All the software required for proper operation
5551 KVA online UPS with half an hour battery (SMF) back up for start operation
556SPARE SPACE
557The panel should have sufficient space for expansion modules & required hardware for future expansion as per SLD.
558LT Panel described above & as per specification.
559Supply of cubicle type totally enclosed free standing type dust & vermin proof Main Panel made out of 2.0 mm thick and partition made out of 1.6 mm MS sheet steel, suitable for 3 phase , 4 wire , 415 V , 50 Hz , AC supply complete with incoming ACB / MCCB / SFU & outgoing MCB / MCCB / SFU , All the MCCB should be with Rotary handle, Four Pole Electrolytic grade Al busbar of required capacity, indication lamp etc complete as per drawing, enclosed specifications and as per approved make-E&E, Ankit, Mile Stone, Expert, Pyrotech.
560INCOMER:-
5611 Nos.200 Amps. TPN MCCB(25 KA)
5621 Set phase indication lights (R, Y, B)
5631 No. Volt Meter (digital type) with inbuilt VSS & control fuses.
5641 No. 0-200 Amp. Ammeter (digital type) with inbuilt ASS
565BUS BARS:-
566300 Amps. TP&N Aluminium bus bars (25 KA)
567OUT GOINGS:-
5686 Nos. 63A TPN, MCB (10KA).
5696 Nos. 24 Hr Timer Switch
5706 Nos. 63A TPN contactor
571P & F of Early streamer Emission type lightning arrester on GI mast with air terminal configured as spheroid which is comprised ofseparate electrically isolated 4 panels surrounding an earthed central finial, the terminal shall be tested by CPRI for impulse current of 45 kA ( 8 / 20 Sec ) with 5 positive & 5 negative impulse, the arrester having following protection radius at level 1, Make : LPI (Australia ), LPSFR (France ), Sudafix ( UK ), EF ( Switzerland )
57260 - 79 Mtr.
573S & Laying of down conductor of 70 Sq.mm single core insulated flexible copper cable with accessories as required.
574Supply, installation, testing & commissioning of the following: IGBT based 100 KVA parallel True Online Double Conversion UPS suitable for unbalanced, 3 Phase input and 3 phase 415 V output UPS system with isolation transformer (i.e., K-13 type), suitable for operating in parallel and each comprising as per technical specification complete as required. Make : Numeric /ETON/Emerson/APC
575VRLA sealed maintenance free batteries for 100 KVA UPS system, for providing 30 minutes back upto each 100 KVA UPS. Each bank of batteries shall comprise required Nos. ofSMF batteries etc as per specifications as required.(cost Included in above)
576Matching cabinet to house SMF batteries for 100 KVA UPS system along with interconnecting links andI/c S/F MCCB as required.(Cost Included in above)
577labour charges for Excavating trenches of required width for pipes dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr.:
578All kind of Soils
579HT PANEL BOARD (5 Cubical panel)
580Supply, installation, testing and commissioning of INDOOR type, 5 no.11 KV switch panel board ( Two Incoming, one Buscoupler, Two Outgoing ) fabricated out of minimum 2 mm thick sheet steelas per specifications. The panel shall be complete with cable termination arrangementfor incoming and outgoing with 1x 3C x 300 Sqmm XLPE 11 KV cable and required rating copper bus bar arrangement .The panel shall comprise of the following:Make : ABB/SCHNEIDER/SIEMENS/L&T
581Incoming
58211 KV, 25 kA for 3 sec (2 I/C)630 A, horizontal drawout type VCB/SF6 breaker with motorised spring charge closing mechanism with antipumpingprotection and trip free features , motor voltage 240V AC and tripping / closing coil voltage , 24V DC and VCB /SF6 breaker complete with 3 NO + 3 NC auxillarycontact as sparecomplete with following.
5831 no. 240V AC spring charge motor.
5841 no. 24V DC shunt trip coil.
5851sets 11KV Epoxy Cast Resin, Single Phase, Withdrawable Type, with HT Fuses, PT of ratio 11kV/sqrt3 / 110V/sqrt3, 50VA , Class. 0.5per phase with control MCB.
5861set of 400/1-1A, core 1, class 0.5 accuracy, 15VA current transformer (cast resin) for metering, core 2 class 5P10, 5VA accuracy current transformer (cast resin) for protection.
5871set Digital Multi function meter of suitable range.
5881 no Numerical non directional IDMT 3 O/C + 1 E/F protection relay for each breaker.
5891 no. master trip relay for each breaker.
5901 no. Trip circuit supervision relay for each breaker.
5911 no. Antipumping relay for each breaker.
5921 no. breaker control switch : (TNC) for each breaker.
5931 set of phase indication lamp (LED type) for each breaker.
5941 no. threepin socket + switch (240 V) for each breaker.
5951 set of circuit breaker ON / OFF / Auto trip / Spring charged / Trip circuit healthy indicating / SF6 gas pressure indication lamp (LED type) for each breaker.
5961 no. 60W 230 V anti condensation space heater with thermostat with heater ON/Off switch for each breaker in breaker comprment & cable compartment.
5971 set of 800A, 11kV rectangular electrolytic grade colour coded and sleeved copper busbars for each breaker.
598Motor On / Off togle switch for each breaker.
599Yellow/white Puh Button for Alarm Accept/Reset for each breaker.
600Black Push Button for Trip Circuit Check for each breaker.
601Suitable rating MCB for AC / DC supply control for each breaker.
602Door Lamp with Switch for each breaker.
603Outgoing & Bus Coupler
6043 Nos. 11 KV, 25 kA for 3 sec, 630 A, horizontal drawout type VCB/SF6 breaker with motorised spring charge closing mechanism with antipumpingprotection and trip free features ,motor voltage 230V AC and tripping / closing coil voltage , 24V DC and VCB /SF6 breaker complete with 3 NO + 3 NC auxillarycontact as sparecomplete with following:
6051 no. 240V AC spring charge motor.
6061 no. 24V DC shunt trip coil.
6073 set of 400-150/1-1A, core 1, class 0.5 accuracy, 15VA current transformer (cast resin) for metering, core 2 class 5P10, 5VA accuracy current transformer (cast resin) for protection.
6081 no. Numerical non directional IDMT 3 O/C + 1 E/F protection relay for each breaker.
6091 no. master trip relay for each breaker.
6101 no. Trip circuit supervision relay for each breaker.
6111 set of auxillary relay for each breaker.
6121 no.Antipumping relay for each breaker.
6131 no. breaker control switch : (TNC) for each breaker.
6141 set of phase indication lamp (LED type) for each breaker.
6151 no. threepin socket + switch (230 V) for each breaker.
6161 set of circuit breaker ON/OFF/Auto trip / Spring charged/Trip circuit healthy indicating/ SF6 gas pressure indication lamp (LED type) for each breaker.
6171 no. 60W 230 V anti condensation space heater with thermostat with heater ON/Off switch for each breaker in breaker comprment & cable compartment.
6181 set of 800A, 11kV rectangular electrolytic grade colour coded and sleeved copper busbars for each breaker.
619Motor On / Off togle switch for each breaker.
620Yellow/white Push Button for Alarm Accept/Reset for each breaker.
621Black Push Button for Trip Circuit Check for each breaker.
622Suitable rating MCB for AC / DC supply control for each breaker.
623Door Lamp with Switch for each breaker.
624Surge arrester to be provided in all outgoing panels
625OTI, WTI and Bucholz alarm and trip relays with necessary Anunnciator panel
626Note:-
627Potential free contact to be provided for HT trouble in breaker to be used for annunciation in the control room.
628The potential free contacts for transformer troubles annunciation & trips for WTI should be provided for remote annunciation in the control room. Required contactors / control relays with sufficient NO/NC contacts shall be provided.
629Each Breaker to be provided with 8 window annunciator with hooter.
630Each Breaker to be provided with suitable rating Power pack (240VAC to 24VDC) with 7Ah Battery
631HT Panel described above & as per specification.Makes : Siemens/L&T/ABB/Schneider
632Miscellaneous Item
633Supplying and fixing of shock restoration chart written in English and Hindi duly framed in as required.
634Supplying and fixing of first aid box as approved complete with standard kit as prescribed by Indian Red Cross.
635P & F of IP65 IK10 protected LED Bollard fixture with extrusion aluminium housing, LED 8W - 12W, 220V-240V, 50Hz LEDs with available in quick connectingcable coupled with various mounting accessories. Driver shall be high efficiency having efficiency > 85% and in compliance to IEC standards (Integral with light fixture). system life of 25000 Burning Hours with 70% of initial Lumens maintained.Light output in Cool white or Warm White Colour as per engineers choice. Fixtures shall be CE compliance.(0.8 mtr high bollard) Make : Wipro/Philips/Crompton Greaves/Panasonic /Jacquar /Surya/Bajaj
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail