Communications and Information Technology  Government Departments Closing in 0 days TDR #36712483

Tender For Construction Of It Office Buildings Civil Construction, Hvac, Electrical Ht And Lt, Dg Sets, Ibms, Fire Protection, Plumbing, Structural Facade, Landscaping, Stp, Wtp, And External Works At Salem District.

Issued by Government Departments · omalur, Tamil Nadu
Tender Value
Ref. Documents
Estimated cost
Bid Submission
10 Apr 2023
0 days left
EMD
22.50 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
omalur → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Construction Of It Office Buildings Civil Construction, Hvac, Electrical Ht And Lt, Dg Sets, Ibms, Fire Protection, Plumbing, Structural Facade, Landscaping, Stp, Wtp, And External Works At Salem District.

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 20-Mar-2023 Pre-Bid meeting Postponed Date 10-Apr-2023

BOQ

Name of Work: Construction of IT Office Buildings Ground floor + 3 floors + Terrace including Civil Construction, HVAC, Electrical HT/LT, DG Sets, IBMS, Fire Protection, Plumbing, Structural Façade, Landscaping, STP, WTP, & External Works at Salem District.
Sl. No. Item Description
1EXCAVATION
2Earth work excavating and depositing on bank with initial lead of 10 m & initial lift of 2m in Hard stiff clay, stiff black cotton, hard red earth, shales, murram, gravel, stoney earth and earth mixed with small size boulders.
3All Kind of Soil - (Upto 2.00m depth from NGL)
4All Kind of Soil - (Upto 2.00m to 3m depth)
5All Kind of Soil - (Upto 3.00m to 4m depth)
6All Kind of Soil - (Upto 4.00m to 5m depth)
7FILLING
8Refilling with excavated earth other than sand with an initial head load of 100 mts. and depositing the earth as shown by the departmental officersin layers of not more than 15 cm thick well rammed, watered and consolidated etc. complete complying with standard specification
9Supplying and filling conveyed gravel other than sand with an initial head load of 100 mts. and depositing the earth as shown by the departmental officersin layers of not more than 15 cm thick well rammed, watered and consolidated etc. complete complyin
10Supplying and filling in foundation and basement with filling Excavated earth in layers of not more than 15 cm thick well rammed watered and consolidated complying with std spec.
11Supplying and filling in foundation and basement with filling Quarry dust in layers of not more than 15 cm thick well rammed watered and consolidated complying with std spec.
12PCC
13Cement Concrete 1:5:10 (One Cement, Five Crushed stone sand and ten hard broken stone jelly) using 40 mm gauge hard broken granite stone jelly for foundationincluding dewatering wherever necessary and laid in layers of not more than 15 cm thick well rammed, consolidated and curing etc. complete (The crushed stone sand to be used on concrete work shall confirm to gradation as per IS 383-1970)
14Flooring
15FORM WORK
16Centering and shuttering with 12mm thick shuttering ply wood confirming to IS 4990-2011 andremoval of form at all heights, ply wood will be supported on lock bars.suspended floors, roofs, landings, balconies and aceess platform,
17Footing
18Grade Beam
19Plinth Beam
20Pedestal Concrete
21Column upto Plinth Level
22Shear Wall upto Plinth Level
23Lintel at all Levels
24Sill Concrete at all Levels
25Sunshade at all Levels
26Staircase at all Levels
27Column above Plinth Levels
28Shear Wall above Plinth Levels
29Roof Beam at all Levels
30Roof Slab at all Levels
31Coping concrete at all levels
32CONCRETE
33Providing of placing RMC Reinforced Cement concrete of the following grades using Slag Cement, machine crushed coarse agrregates 20 mm and 12.5 mm, M sand, Water and admixtureetc complete allfor casting concrete elements of all shape and size and at all heights. (M35Grade - 425 Kg/Cum)
34M25 Grade Concrete
35Footing Concrete
36M35 Grade Concrete
37Grade Beam
38Plinth Beam
39Cover Slab
40RCC Wall
41Foundation below the plinth level
42Column
43Pedestal Concrete
44Foundation Column below the plinth level
45Providing of placing RMC Reinforced Cement concrete of the following grades using OPC 53 grade cement, machine crushed coarse agrregates 20 mm and 12.5 mm, M sand, Water and admixtureetc complete allfor casting concrete elements of all shape and size and at all heights. (M35 Grade - 425 Kg / Cum)
46M - 35 Grade of concrete
47Floor Slab / cover slab
48RCC Wall
49Ground Floor
50First Floor
51Second Floor
52Third Floor
53Headroom
54Lintel
55Ground Floor
56First Floor
57Second Floor
58Third Floor
59Headroom
60Sill Concrete
61Ground Floor
62First Floor
63Second Floor
64Third Floor
65Headroom
66Sunshade
67Ground Floor
68First Floor
69Second Floor
70Third Floor
71Headroom
72Staircase Waist Slab
73Ground to First Floor
74First to Second Floor
75Second to Third Floor
76Fourth to Headroom
77Roof Beam
78Ground Floor
79First Floor
80Second Floor
81Third Floor
82Headroom
83Roof Slab
84Ground Floor
85Coping concrete - compound wall - GF
86First Floor
87Second Floor
88Third Floor
89Headroom
90M35 Grade Concrete
91Column
92Ground Floor
93First Floor
94Second Floor
95Third Floor
96Terrace & Headroom
97STEEL REINFORCEMENT
98Supplying, fabricating and placing in position Mild Steel / Ribbed Tor Steel grills for all RCC works as per design given including cost of steel and G.I. binding wire in all floors etc. complete complying with standard specification, Grade of Steel ( Fy )- Fe - 550 Confirm to IS : 1786: 1985.
99MASONARY WORK
100Brick work in following Cement Mortar using best quality II class table moulded chamber burnt bricks of size 9\" x 4-1/2\" x 3\" for foundation and basement including curing, etc., complete complying with standard specifiction. In Cement Mortar 1:5
101For Foundation and Basement.
102For Superstructure in Ground Floor
103Brick partition walls of 11.50cm thickness using best quality II class table moulded chamber burnt bricks of size 9\" x 4-1/2\" x 3\" in Cement Mortar 1:3 (One Cement and Three M.Sand) using hoop iron reinforcement if found necessary including curing etc. complete and as directed by the departmental officers. (Hoop iron reinforcement will be measured and paid for separately)
104For Foundation and Basement.
105Masonry work using Autoclaved Aerated cement blocks of size 600 x200 200 mm in cement mortar 1:6 (one oc cement six of sand) for super structure in all floors including fixing frames of door and windows, proper setting curing etc., complete complying with standard specification as directed by the departmental officers.
106For Foundation and Basement.
107For Superstructure in Ground Floor
108For Superstructure in First Floor
109For Superstructure in Second Floor
110For Superstructure in Third Floor
111For Superstructure in Terrace Floor
112Masonry work using Autoclaved Aerated cement blocks of size 600 x200 x100 mm in cement mortar 1:5 (one of cement five of sand) for super structure in all floors including fixing frames of door and windows, proper setting curing etc., complete complying with standard specification as directed by the departmental officers.
113For Superstructure in Ground Floor
114For Superstructure in First Floor
115For Superstructure in Second Floor
116For Superstructure in Third Floor
117For Superstructure in Terrace Floor
118Supply and erection of Double Leaves Fire Rated Door with Frame having the dimension of 1800mm x 1400mm with following specification:a. Door Frame 1.6mm: Galvanized 120 GSM branded make JSWb. Door Leaf 1mm: Galvanized 120 GSM branded make JSWc. Shutter Thickness: 46mmd. Honeycomb: In-fille. Glue Macroplast UR-7221f. Door Hinges: 4\" x 3\" x 3mm, Double Ball: Make Assa Abloy Yale Ball bearing Butt Hinges Grade SS 304 - Finish SSg. Door Closer with Standard Arm Finish: Silverh. Lock Set: Dead Lock with both side keyi. Door Orientation: To be confirmed by clientj. Mounting of door: Brick wall mountedk. Powder Coating: Powder coated in standard RAL paintcolour of PO Red (60 to 90) Micronsl. Single Point Panic Bar (2 Horizontal): Make Assa Abloy Yale or Equivalentm. Dead Lock with both side key: Make Assa Abloy Yale or Equivalentn. Vision Panel 200 x 300mm 2 Hrs. Fire Glass Schott Pyran with Frameo. Rated Glass Schott Pyran with Framep. Anchor Bolt with EndcapsThe above assembly mounted on concrete or brick wallincluding the cost of cutting, chipping, concrete packing,pastering, scaffolding all other conveyence as per standard methods and as directed by the Departmental Officers.
119Staircase
120AHU and Electrical Room
121Shaft door
122Supply & Fixing of ALTERRA ALT 50 Frameless Glass Door (Single / Double Leaf) with toughened glass and door accessiories Frameless door Rebate Profile all around the door. Rebated Door Frame size 50x54mmdesign. Hardware - Dormakaba junior Office Hinges(3 nos) ,Studio Gala Locks (1no) in aluminium silver (EV1) finish and Dormakaba TS 89 Slide Channel Door closer with (as per EN 1154) and saddle plate for fixing on the Glass door. Glass Mounted Sweep seal or Door Bottom Seal. In case of Glass overpanel OHP100-SG Over Panel Door profile to be used.The hardware should be suitable for Glass thickness of 10/12mm.The Profile finish shall be as per Approved Architects specifications. Profile Manufacturer to supply all the necessary clips, seals and fixing accessories for the system.All Profiles to be with 1.5 mm Gauge thickness Excluding 20 Micron of Anodizing. Max Door Height - 2700mm Max Door Weight - 80 Kgs
123Double Leaf Door - (1400 x 2400mm)
124Providing and fixingAutomatic Sliding door operator, Make: DORMAKABA ES 200 (EASY) 6250, compliant with future European standards and produced according to the guidelines for power-operated windows, doors and gates,BGR 232, the UVV and the VDE regulations. TÜV design tested for Durability of 1,000,000 Cycles, Manufactured according ISO 9001, tested according to the low voltage guidelines, CE Compliant, fulfils DIN 18650 standards for Padestrian Safety, for framed glass door application with DORMA ST-Flex Profiles Systems,modular design including internal cover and with 12.52 mm Laminated glass for1 Nos sliding door panels and 1 Nos fixed panels, both sliding & fixed panels with DORMAKABA ST-Flex framed profile system with Interlocking Seals.Operator & Frame Finish should be Silver Anodised, with operator dimensions (H x D) : 100 x 180 mm and of length as required to suit the opening sizes as given below. DORMAKABA ES200 Operators are of very sturdy design with Self balancing Panel suspension system and with Anti-Jump fitting.The track profile should be separate from the main profile for enabling reduction in vibration insulation. Microprocessor-controlled control unit, Self-learning, with adjustable parameters for opening and closing speed, hold-open time and opening and closing force, reversing when obstruction is encountered, Class of protection IP 20 with SMPS for Power regulation. Activators- DORMAKABA Nemo Motion + Nemo Dual ( Safety & Motion ) Pack, EM Lock - Fail Safe with CableProgram Switch with Key. Max Panel Weight Carrying Capacity of 1 X 200 Kgs. The system shall have constant power supply230V+ 5%, 50Hz, AC . The requirement in total is as mentioned below:
125Providing and fixing of 25 mm thick Flush shutter, with 6 mm ply finished with 1 mm thk laminate on both sides of the shutterand finishing with 3 horizontal grooves of 6 mm x 6 mm andbeech wood door frames of size 90mm x 50mm.using hinges, locks and door closure.Cost is inclusive of providing beech wood door frame duco painted / polished to desired color.
126UPVC Ventilator : Supplying and fixing UPVC (Un-Plasticized Polyvinyl Chloride) Louvered Ventilators of from the profile the size of outer frame 60mm x 58mm and shutter profile size of 60 x 78mm both profiles are reinforced with GI/1mm 125GSM and 100% corrosion free, the profile are multi chambered sections with wall thick of 2mm. The EPDM rubber (black colour) covered with all over the edges of frame and shutter. The corners and joints should be welded and cleaned. Radiations pin headed glass 4mm thick should be provided in the louvers. The window should be fixed to the wall with 100% packing with screws and silicon packing all round the frames. The ventilator should be got approved from the Executive Engineer before use on work
127UPVC Glazed Windows in Elevation : Supplying and fixing UPVC (Un-Plasticized Polyvinyl Chloride) Windows of from the profile the size of outer frame 60mm x 58mm and shutter profile size of 60 x 78mm both profiles are reinforced with GI/1mm 125GSM and100% corrosion free, the profile are multi chambered sections with wall thick of 2mm. The EPDM rubber (black colour) covered with all over the edges of frame and shutter.The corners and joints should be welded and cleaned. Radiations pin headed glass 4mm thick should be provided in the louvers. The window should be fixed to the wall with 100% packing with screws and silicon packing all round the frames. The ventilator should be got approved from the Executive Engineer before use on work
128MS GRILL
129Supplying and fixing mild steel grills for windows, ventilators, etc., including priming coat etc., complete.
130Providing and fixing M.S.Steel angle with Rolled double stand barbed wire
131SS HANDRAIL
132Manufacturing, Supplying and Fixing of Stainless Steel Hand rails for staircase near wet riser using 50mm dia 304L Grade Stainless Steel pipe of 1.60mm thick will be provided with tubular supports made of 304L Grade Stainless Steel pipe of 25mm dia of 1.60mm thick welded to the railing. The supports will be grouted into the wall and providedwith93.00mm thick Stainless Steel circular base plate of 304 Grade. The rate shall included for grouting into concrete with necessary supporting arrangements the hand rail in floorpolishing buffing, bonding, cutting, grinding, conveyance, welding charges, electrical charges, etc. complete
133PLASTERING
134Plastering in Inner walls with Cement Mortar 1:5 (One cement andM.sand), 12mm thick in all floors including curing etc. complete complying with standard specification and as directed by the Engineer-incharge.
135Ground Floor
136GF - Sump,STP
137First Floor
138Second Floor
139Third Floor
140Headroom
141Special ceiling plastering and finishing the exposed surface of all RCC items of work such as slabs, beams, sunshades, facia, canopy slab, staircase waist slab, landing slab etc., with Cement Mortar 1:3 (One Cement and Three M.Sand) 10mm thick including hacking the surfaces, providing cement mortar nosing, beading for sunshades, staircases, steps, landing slabs and curing, etc., in all floors complying with standard specification and as directed by the Engineer-in charge.
142Prepare surfaces and plaster with CM 1:5 (1 cement: 5 fine sand) 17mm thick(12mm+5mm) to all exteriorfaces of walls including hackingas required on RCC surfaces continuous to masonry in super structure and 12mm will be rough plastering includes water proofing chemical compound and 5mm will be sand paper finishing & double layer chicken mesh .The ratesincluding curing, providing and removal of scaffolding, cost of materials, labour, equipments and machinery, all leads and lifts, loading and unloading, transportation and all other incidential charges etc, all as complete and directed by Engineer in charge at all levels.
143Prepare surfaces and plaster with CM 1:5 (1 cement: 5 fine sand) 17mm thick(12mm+5mm) to all exteriorfaces of walls including hackingas required on RCC surfaces continuous to masonry in super structure and 12mm will be rough plastering includes water proofing chemical compound and 5mm will be sand paper finishing & double layer chicken mesh .The ratesincluding curing, providing and removal of scaffolding, cost of materials, labour, equipments and machinery, all leads and lifts, loading and unloading, transportation and all other incidential charges etc, all as complete and directed by Engineer in charge at all levels.- BASEMENT HEIGHT
144PAINTING
145White washing three coats with best shell lime in all floors complete complying with standard specification and as directed , including gum, conjee,water, etc., complete.
146Painting two coats of newly plastered wall surface with ready mixed plastic emulsion paint of first class quality and of approved colour over a priming coat including thorough scrapping, clean removal of dirt, and including necessary plaster of paris putty, wherever required etc., complete complying with standard specification.
147Painting two coats of newly plastered wall surface with Weather Proof Exterior emulsion paint of first class quality and of approved colour over a priming coat including thorough scrapping, clean removal of dirt, and including necessary plaster of paris putty, wherever required etc., complete complying with standard specification.
148Painting new wood/iron work with two finishing coats of synthetic enamel ready mixed paint of approved quality and colour over one coat priming coat in all floors including the cost of primer etc., complete complying with standard specification. (The make, quality and colour of paint should be got approved by the Executive Engineer before use on works.)
149Providing and applying Texture Finish Paint (for External painting)and approved shade including preparation of surface for painting, applying primer and two or more coats of paint as per manufacturer’s specifications, scaffolding curing etc. complete as directed at all levels.
150FLOORING
151Supplying and fixing superfine polished Ruby red or equivalent colour Granite slab 20 mm thick for Lift facia with bullnose edges are set in CM 1:3 10mm thick for base and pointed with the same colour cement etc complete.The rate inclusive of labour charges for laying & pointing curing etc. complete
152Supplying and fixing pre polished Ruby red or equivalent colour Granite slab 20 mm thick for Pantry and wash basin counter with bullnose edges are set in CM 1:3 10mm thick for base and pointed with the same colour cement etc complete.The rate inclusive of labour charges for laying & pointing curing etc. complete
153Supplying and fixing pre polished Ruby red or equivalent colour Granite slab18mm to 20mm thick for stair case riser set in CM 1:3 20mm thick for base and pointed with the same colour cement etc complete.The rate inclusive of labour charges for laying
154Providing the floor with 20 mm thick Granite slabs of approved colour and sizein all floors over a base layer of 20 mm thick CM 1:3, the granite slab be laid over the cement mortor by applying white cement slurry in between base mortor and granite slab. The granite slabs are to beso laid that there should not beany gap inbetween the adjacent slabs and the joints shall be in line with another joint and uniform by using cutting machine without any damage to the sides of corners of the granite slab. The entire area of the flooring so laid shall be neatly pointed with coloured cement of 1.80 kg/m2. The granite slabs proposed for the work shall be shown to the departmental officers and got approved by them before use in the work etc., complete.
155Dadoing walls with following best approved quality, white / colour Glazed tiles of approved sizes set in Cement Mortar 1:2 (One Cement and Two M.sand) 10mm thick and pointing the joints with white cement mixed with colouring pigments at the rate of 0.40 Kg. / sq.m. neatly in all floors, curing, etc., complying with standard specification and as directed by the departmental officers.
156Paving the floor with best quality Virtified Tiles of size 600 x 600 x 8mmof approved colour, shade and quality laid in cement mortar 1:3 (one cement and three M.sand) 20mm thick in all floors and the top pointed with the white cement mixed same colour pigments etc., complete complying with standard specification.(The make and brand of the tiles should be got approved by Executive Engineer before use on works)
157Providing Granolithic floor finish 40mm thick with Plain Cement Concrete 1:2:4 using 3 to 10mm ISS HBG metal, river sand and including rubbingthe top surface smoothly thread lining if found necessary and curing etc. complete complying with standard specification and as directed by SIPCOT Officersincluding cost and conveyance of all material and labour, incidental charges, etc. complete.
158Supplying & laying of sun reflective index tiles 305 x 305 x 7 mm of 30 mm thick in cement mortar 1:3, 30 mm thick using white cement and hard crate mixed same colour pigments etc., complete complying with standard specification.(The make and brand of the tiles should be got approved by Executive Engineer before use on works) - IN TERRACE FLOOR AREA
159WATERPROOFING
160TERRACE WATER PROOFING
161Surface Treatment: Providing and laying water proofing treatmentof podium including cleaning the surface with wire brush, treating all surface cracks, construction joints and honeycombs by grouting with specialised non shrink grout and preparation of surface in all aspects to receive the waterproofing.
162Bore Packing / Core Cut Treatment: Providing and sealing the gaps in the core cuts around PVC pipes treated with ReArm Bond SBR 45 bonding agent & sprinkled sand; using a non shrink grout ArmGrout M 50 or equivalent offollowed by sealing of the same joint by using Joint Tape SealArm Joint Tape 2000 or equivalent with Epoxy adhesive.
163Coving: Providing and Applying at the junction of slab and vertical offsets with Cement Mortar 1:4 and admixed with ReArm Bond SBR 45at dosage of 1Ltr per 50kg cement.
164Application of Primer: ApplyWater based Epoxybased primer FloArm Primer EPW 44 of MYK Arment or equivalent over well prepared surface at 200-400 gm per Sq.Mtr.
165Application of Polyurethanewaterproof coating: Providing and applying Two coats ofliquid applied single component polyurethane based waterproofing system AquaArm WPU-1KEof MYK Arment or equivalent . It has to beapplied 2.6 @kg/sqmtr to achieve a thickness of1.2 mmin two coats.The membrane will have the following technical parameters: Tensile Strength : 1.4 N/mm2 ,. Elongation at break : 450% , Adhesion To concrete: >1.5 N/mm2,
166Protection Screed:Horizontal Areas: Providing and Laying M25 grade screed concrete in 1:100to a average thickness of 100 mm mixed withIntegral Waterproofing admixture AquaArm Proof WP 10 at the dosage of 125 ml/bag of cement over waterproofing layer to a minimum thickness of 75 mm as per site requirement(Civil Contractor Scope) including control joints of 4M X 4M size and filling the panels with polyurethane sealant.
167LIFT & OHT W.P
168Surface Preparation:Providing and laying water proofing treatment to horizontal and vertical surfaces ofpodium slabs, including cleaning the surface with wire brush, treating all surface cracks, construction joints and honeycombs by grouting with specialised non shrink grout,coving preparation at wall - slab joint and preparation of surface in all aspects to receive the waterproofing.
169Bore Packing / Core Cut Treatment: Providing and sealing the gaps in the core cuts around PVC pipes treatedwith SBR bonding agent & sprinkled sand; using a non shrink grout ArmGrout M 50 or equivalent offollowed by sealing of the same joint by using Joint Tape SealArm Joint Tape 2000 or equivalent with Epoxy adhesive.
170Coving: Providing and Applying at the junction of slab and vertical offsets with Cement Mortar 1:4 and admixed with SBRat dosage of 5 litre per 50kg cement. (cement and sand shall be supplied by the main contractor)
171Waterproofing Coating-Providing and applyingtwo compoent acrylic cementitious coating AquaArm TG of MYK Arment or equivalent witha coverage of 2.0 kg /m2 .The coating shall be taken upto 300mm from finished floor level on the vertical walls.The coating shall have an elonagtion of 40%,Shore A hardness of 90,Tensile strength of 0.86 N/mm2.
172TOILET
173Surface Preparation:Providing and laying water proofing treatment to horizontal and vertical surfaces ofpodium slabs, including cleaning the surface with wire brush, treating all surface cracks, construction joints and honeycombs by grouting with specialised non shrink grout,coving preparation at wall - slab joint and preparation of surface in all aspects to receive the waterproofing.
174Bore Packing / Core Cut Treatment: Providing and sealing the gaps in the core cuts around PVC pipes treatedwith SBR bonding agent & sprinkled sand; using a non shrink grout ArmGrout M 50 or equivalent offollowed by sealing of the same joint by using Joint Tape SealArm Joint Tape 2000 or equivalent with Epoxy adhesive.
175Coving: Providing and Applying at the junction of slab and vertical offsets with Cement Mortar 1:4 and admixed with SBRat dosage of 5 litre per 50kg cement. (cement and sand shall be supplied by the main contractor)
176Waterproofing Coating-Providing and applyingtwo compoent acrylic cementitious coating AquaArm TG of MYK Arment or equivalent witha coverage of 2.0 kg /m2 .The coating shall be taken upto 300mm from finished floor level on the vertical walls.The coating shall have an elonagtion of 40%,Shore A hardness of 90,Tensile strength of 0.86 N/mm2.
177Water Stops for Joints :Supply and applyof WPM SWa swellable waterbar based on polymer technology and designed for use in construction joints.
178FALSE CEILING
179GYBOARD FALSE CEILING
180Providing and fixingin position M / Fsuspended false ceiling to detail as per drawing with GI frame work and 12.5mm tapered type gyp board panels to form grids of 457 x 1220mm as per manufacturers specification including provision for stepped shaped ceiling for light troughcomprising.
181Frame work of intermediate channels (M.F.T.) at 1220mm centres along one direction M/F ceiling section MF5 at 457mm centres along other direction.Perimeter channels (MF 6A)along walls alround perimeter side of the ceiling, all to detail as per drawing.
182The intermediate channels suspended from ceiling, through strap hangers 25 x 0.5mm (MF 8) at 1220mm centres connected to soffit cleats P534 (27 x 37 x 25 x 1.6mm) the cleats connected to ceiling through metal expansion rawl plugs 12mm dia and 17/16\" long with necessary bolts and nuts etc. all connected with additional perimeter channels (MF 6A) for openings for light fixtures, AC ducts, vertical drops, offsets etc. wherever necessary all to detail and as per direction.
18312.5mm thick gyp board with tapered edges fixed to underside of suspended gridwith 25 mm screws to form grids of 457mm x 1220mm varied along wall ends etc. including Architectural boxing,design and painting the underside of gyp board with 2 coats of plastic emulsion paint of approved colour over a priming coat etc., complete.
184ARMSTRONG GRID FALSE CEILING
185Providing & Fixing of Armstrong Mineral Fibre Acoustical Suspended Ceiling System with Classic Max Beveled Tegular Edge Tiles with Armstrong Suprafine 15mm Exposed grid.The tiles should have Humidity Resistance (RH) of 99%, NRC 0.7, Light Reflectance =85%, Thermal Conductivity k = 0.052 - 0.057 w/m K, Colour White, Fire Performance UK Class 0 / Class 1 (BS 476 pt - 6 &7) with pin-hole visual in module size of 600x600x17mm, suitable for Green Building application, with Recycled content of 65%. The tile shall be laid on Armstrong Suprafine 32 with 15 mm wide T - section flanges colour white having rotary stitching on all T sections i.e. the Main Runner, 1200 mm & 600 mm Cross Tees with a web height of 32 mm and a load carrying capacity of 8.8 Kgs/M (as per standard installation layout mentioned below) & pull out strength of minimum 100 Kgs. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system of Armstrong make.The Tile & Grid system used together should carry a 30 year warranty.
186INSTALLATION: To comprise main runner spaced at 1200mm securely fixed to the structural soffit using Armstrong suspension system (specifications below) at 1200mm maximum. The First/Last Armstrong suspension system at the end of each main runner should not be greater than 450mm from the adjacent wall.Flush fitting 1200mm long cross tees to be interlocked between main runners at 600mm to form 1200 x 600 mm module.Cut cross tees longer than 600mm require independent support. 600 x 600mm module to be formed by fitting 600mm long flush fitting cross tees centrally between the 1200 mm cross tees. Perimeter trim to be Armstrong wall angles of size 3000x19x19mm, secured to walls at 450 mm maximum. Installation to be carried out by Armstrong Trained Installation team & Installation should be carried out as per Armstrong recommended procedure.
187ARMSTRONG SUSPENSION SYSTEM accessories manufactured and supplied by Armstrong World Industries consisting of M6 Anchor Fasteners with hanger hole, pre Straightened Hanger wire of dia – 2.5 mm of 1.80 m length having a tensile strength of 344-413 MPa and a minimum pull strength of 110 kgs. (Adjustable hook clips of 0.7mm thick, galvanized spring steel can also be used for installation purpose as an additional accessory. The adjustable clip also consists of a 4 mm aquiline wire to be used with the main runner).Tentative Pricing for Supply and Installation of Classic Max Microlook Tile with 15mm Suprafine 32H Grid
188Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main \"T\" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross \"T\" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main \"T\" at 600 mm center to center to form a grid of 1200x600 mm andecondary cross \"T\" of length 600 mm and size 24x25 mm made of0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle ofsize 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main \"T\" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mmcenter to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.
189Supply and installation of of FAMELINE GI Plain Lay-in ceiling system using FAMELINE GI grid work with Main Runners of size 15mm X 32mm X 3600mm X0.3mm and Cross Runners of Size 15mm X 32mm X 1200mm X0.3mm and 15mm X 32mm X 600mm X0.3mm which snap locked in with each other forming a 600 X 600mm grid work. The suspension system comprises a Rawl plug fixed to the true ceiling and mend to 3mm GI rod knit to a ‘J’ bolt which holds the Main runners at every 1.2m intervals. Finally FAMELINE GI Plain Lay-in Tiles of Size 595mm X 595mm X 0.5mm (T) are laid upon the formed grid. The price should include the cost of making any cuts and openings for lights and other fittings. The hold down clips should be fixed with wall angles to hold down the end tiles -
190Providing and fixing Toilet cubicles made of 12mm solid compact laminate panels including doors & intermediate panels finished with textured melamine of \"\"nuvo series \"\" ofStylammakes conforming to ISO 2046 as per the detail drawings. This also includes providing and fixing in position necessary nylon& aluminium hardwareas per manufacturers specifications & project design consultants instructions like handles, hinges, latches, indicators, top rail, connectors, hooks, knobs, brackets, U channels, thumbturn, locks etc. Provision to made in the cubical for fixing Toilet paper holder, Health Faucet etc., as directed by the project design consultants and as per the detailed drawings.
191cubicle size 1000 to 1100mm widh x 1550 depth x 2003mm ( include bottom gap
192MISCELLANEOUS
193Providing Anti-termite treatment to soil adjecent and under building foundation, plinth periphery of the building by application of chemicals of IS 63613 part I to IV in stages to suit the progress of work consist as per the detailed specification as below.Including breaking of termite mounds, making holes with crow bar, closing the holes after the treatment and including cost of chemicals, labour charges, transport and storing etc., complete and as directed by the departmental officers.
194Providing and fixing in position Heavy duty precast SFRC. manhole cover and frame.Square shape 600mm internal dimensions
195Providing and fixing PVC coated MS rungs as per drawing and instruction of Engineer in-charge complete.
196Supply and Installation of Chain Link Fencingat all levels as per drawing of PVC coated chain link of 50mm x 50mm size mesh with a GI metal frame work (above tie beam height 300mm to 1500mm ) and GI pipe supports etc., inclusive of all welding, supporting, scaffolding and required insert plate, painting etc., to complete.
197Providing and fixing of \"\" - TIDEL \"\" Signage Board With Backlighting
198ELEVATION
199STRUCTURAL GLAZING - UNITIZED GLAZING SYSTEM
200Design, supply and install unitized four sided structural glazing system curtain wallcustom designed to withstand the design wind pressure confirming to IS -875 part III.The system must pass the proof test at 1.5times design wind pressure without any failure, with silicon gaskets in exposed grooves and microwavecured EPDM gaskets in unexposed area, structural and weather sealants of Dow Corning or approvedmake, Norton spacer tape,backer rod, Bracketing system with MS /aluminium alloy of 6005 T6bracketsdesigned to accommodate three dimensional movements with serrated plate and serrated washers, SS316 grade fasteners and anchor bolts of approved make, nylon separators to prevent bi-metalliccorrosion,1.2 mm thk GI trims and flashings to seal the gaps between curtain wall and the buildingstructure allcomplete required to perform as per specification and drawing in conjunction with BOQ.
201The system shall be designed of floor height unitswith wind resistance subcill gutter at floor level andwindload & Dead load bracket at topwith provision to accommodate movement at all floor levels and at everygrid panels horizontally.The system shall be designed to accommodate 24 mm thk.DGU in vision area and 6mm SGU in Spandrel area.System shall accomodate openable panel asper architectural requirment in the unitised system as per the design drg. All fix vision glass and openableshall look similar in the elevation.
202The design of drain gutter profile container shall be deep enough to contain and drain water entering 2ndbarrier. The design shall also provide slope in gutter profile with drain slots of sufficient size.
203All in between mid transome shall be flush with mullion.
204The complete system shalldemonstrate performance for air seal / water seal / structural /seismicrequirement .Onsite testfor workmanship verification shall be carried out in stages for water penetration hose test as per AAMA501.2 at minimum 6 locations.
205The extruded aluminium sections of Alloy 6063 T5 / T6 & tolerances confirming to DIN / EN standard fromapproved extruder. The structural profiles shall have minimum 2mm wall thickness. All the profilesshall have minimum 60 -80 microns powder coating finish as per AAMA 2604 specification. The non visiblealuminium surfaces shall have minimum chromatizing treatment.
206All shade approval shall be as per Architect\"s Approval.
207The quote rate shall include all design, engineering & shop drawing approval from architect & consultant.The quote rate shall include all Taxes, duties, statutory obligations and safety code compliance as per PMC.
208Unitisedglazing systemcost
209Glass : 24mm thick DGU of 6mm thick SKN Reflective HS glass + 12mm airgap + 6mm thick clear toughened glass
210Extra over for Openable
211:Extra over for Top hung openable aluminium window systems integrated with Unitized curtain wall system are to be fully prefabricated assembled units completed withfactory glazed panels with accessories,limit restricted stay arm, Handles, SS friction stay arm, excludes glass. All aluminium extrusion shall be Powder coating finish 50 Microns Color to architect\"s selection. Additional framing system to accommodate openable window integrated with Unitized system- Glass Qty covered in item 1b and system price in 1a.Windows all fittings such as accessories, Multi point locking, hardwares etc as per specification and to Architect selection.
212SEMI UNITIZEDSTRUCTURAL GLAZING SYSTEM
213Providing and fixingof Semi Unitized Structural glazing system using suitable extruded aluminium sections for frames Powder coating approved colour of 50 microns.Extruded section to be of aluminium alloy6063 (T5 or T6temper) confirming to BS4174 or approved equivalent standard.The framework should have water tight joints and designed for Pressure Equalized system with provision for rainwater drainage. MS brackets (hot dip Galvanized for 60 - 80 microns thickness ) oraluminiumbrackets of required size as perthe structural requirementto be fixed to building structure with required size ofanchor fasteners.The main aluminium frame to be fixed to bracket with suitablebolt/nut washer.The complete framework to be aligned and leveled as required.
214SEALANT - The reflective glass units are to be glued to separate glass panel frames (made out of suitable aluminium section) with specified / approved structural silicone sealant ofDC 795 &weather sealant DC 789 or of approved equilvalant .The sealant to be applied as per design and system approved by the manufactures in writing for this project.After proper curing and testing by Sealant Manufactures,Each panel to be fixed to main frame individually with anchor fasteners.After aligning the panels to correct line / level the gaps between glass to be sealed with weather sealant of approved make.
215SYSTEM – The system to be designed to take horizontal and vertical movement upto 10mm for every floor and capable of withstanding wind pressure as per IS 875.The system design should be generic to accommodate double or single glass as may be required and gasket based, designed with chamber for pressure equalization.Shop drawings to be submitted for approval. The rate include detailed design calculations taking into consideration the wind load, seismic forces adequate factor of safety and the relevant I.Scode and the international code and approved by qualified structural consultant. The Verticalsand Horizontalofsuitable for floor height as per drawing . Main frame to be assembled as per design required and fixed to prefixed clamps with bolt/nut and washer.The frame work thus fixed to be properly aligned and leveled to required grid work.The glass frames suitably glazed as described above with glass specified is then fixed to main frame with EPDM gaskets .
216The gaps between panels are properly sealed with weather sealant .(DC 789)to ensure no leakage and work completed as per design and specification
217Semiunitized system cost
218Glass : 24mm thick DGU of 6mm thick SKN Reflective HS glass + 12mm airgap + 6mm thick clear toughened glass
219Extra over for Openable
220:Extra over for Top hung / side hung openable aluminium window systems integrated with Unitized curtain wall system are to be fully prefabricated assembled units completed withfactory glazed panels with accessories,limit restricted stay arm, Handles, SS friction stay arm, excludes glass. All aluminium extrusion shall be Powder coating finish 50 Microns Color to architect\"s selection. Additional framing system to accommodate openable window integrated with Unitized system- Glass Qty covered in item 2b and system price in 2a.Windows all fittings such as accessories, Multi point locking, hardwares etc as per specification and to Architect selection.
221Z type Louver
222Providing and fixing of 50Microns colour Powder coating finishaluminium louvers using Bhoruka section63 x 38 x 1.5mm thick box section for outer frame,100 mmZ Blade Bhoruka make sectionand aluminium plate 50 x 5mm thickwith silicone sealant and other necessary hardwares etc. all complete
223ALUMINIUM COMPOSITE PANEL CLADDING (Wooden Finish)
224Supplying and fixing aluminum composite panels cladding The systemto detail as per drawing and job for external cladding in combination of approved color ofEurobond wooden finishACP/ Equivalentincluding all necessary framework and using aluminum frame L angle section , HDGI MS brackets , GI bolt /nut washeres , SS screws & aluminium pop rivets . Wherever shown in the drawing and wherever it is necessary as wind bracing fixed at the rear side of the cladding panel using tray type method fixing or approved equivalent frames fixed to the RC columns / walls using necessary aluminum cleat with required size of GI anchor fasteners and complete weather sealing.The composite panel of weather resistant 4mm thick consist of 3mm LDPE resin core, sand witched between 2 skins of 0.5mm thick, Aluminum sheet (alloy designation 3000 series ) making a total panel thickness of 4mm approved make and color for the cladding bent to shape at grooves width of grooves angles firmly and grooves to be closed with weather sealant of approval make for 12 to 16mm.
225The surface will be finished with fluorocarbon -, coating in topsides and service coating on reverse side coating confirms to the mechanical properties of panel as per detailed drawing shall include all fixing accessories,screws, washers, bolts, nuts, cleats, other required fasteners, sealant brackets, etc., complete.
226Providing, fabricating and fixing in position M.S. Structure made out of M.S. rolled/hollow (rounds/rectangular/ square etc.) sections as per architect’s details including shearing /cutting, riveting, welding, grinding to smooth surface of all works, MS fixing holdfasts / anchor bolts to be grouted in concrete1:2:4 , providing and fixing nuts bots fasteners as required as per architect’s details, including painting with two or more coats of first quality synthetic enamel paint of approved quality and make over a coat of primer etc. complete as directed. ( MS standard section shall be measured and paid under relevant Item. Nuts, bolts, washersshall be deemed to have been included in the unit rates and nothing extra shall be paid for)
227LANDSCAPE WORKS
228Lawn: Supply and Planting of Bermuda grass by Dibbling method in the developed area for lawn
229Small shrubs- 1,6\" ht
230Tall shrubs - 1, - 2, ht
231Ground covers: Towards cost and supply of Ground covers, inclusive of pitting and planting
232Hedges: Towards cost and supply of Hedges, inclusive of pitting and planting
233Accent Trees: Towards cost and supply of Accent trees, inclusive of pitting and planting
234Plumeria alba
235Terminalya mantaly
236Accent palms: Towards cost and supply of Accent palms, inclusive of pitting and planting
237Foxtail palm
238Specimen Plants: Towards cost and supply of Specimen Plants, inclusive of pitting and planting
239Ficus benjamina: Towards cost and supply of Ficus benjamina-dome shape of 5 ft. ht., inclusive of pitting and planting
240Cycas: Towards cost and supply of Cycas of 1.5 inch dia., inclusive of pitting and planting
241Trees: Towards cost and supply of Trees, inclusive of pitting and planting
242Soil Work:
243Towards cost of soil mix (i.e Garden Soil and Manure)
244Irrigation work
245LAND DEVELOPMENT
246Supplying and filling in the area wherever specified with good gravel earth filling in plint, area development, etc, wherever specified in layers of not exceeding 150mm thick, including breaking clods, storing, transportation, double handling watering, compacting each layer with vibrator compactor and at unaccessible places with wooden / steel rammers to achieve 95% proctor density at optimum moisture content, all leads and lifts bailing/pumping out of water to keep site dry while back filling, cost shall include conveyance of all materials , labours , machineries etc complete as directed,the rates to include loading , unloading , hire and fuel charges for tools and plants, and other incidental charges etc. as complete with all respect compiling with relevent standard specificatioons.as directed by engineer in charge ( Payment will be Based on Actual Initial and Final Level based quantity)
247PARKING PAVER
248Providing and laying of 80mm thick factory made cement concrete interlocking paver block of M-25 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 75mm thick compacted bed of coarse sand / M-Sand, filling with machine compaction, joints filling with fine sand / M- Sand etc., all complete as per the direction of Engineer-in-charge. PARKING
249LIFT
250Supply, erection , testing and Commissioning of Machine Room Less Liftof 20 Person capacity having 5 Stops for G + 4 Floor of 4 M travel distance between floorsin LIFT Well size of 2200 X 2850 mm including Floor level indicators in each floor, False ceiling with Light, Mirror and wall finish ofSS Grade 304Brushed finish, Brushed SS Handrail for rear wall , Door having SS Brush finish , Car Floor , call indicators in each floorsetc ;.
251Supply, erection , testing and Commissioning of Machine Room Less Liftof 16 Person capacity having 5 Stops for G + 4 Floor of 4 M travel distance between floorsin LIFT Well size of 2200 X 2500 mm including Floor level indicators in each floor, False ceiling with Light, Mirror and wall finish ofSS Grade 304Brushed finish, Brushed SS Handrail for rear wall , Door having SS Brush finish etc ;.
252SANITARY INSTALLATIONS
253Supplying and fixing in position White / Colour Special Delux Model Glazed Cascade Type Parryware / Hindware / Equivalent Wall Mounted European Water Closet of best quality and approved make with 100mm or trap connecting with CI pipe of 100mm dia / PVC pipe of 110mm dia, double flapped rigid PVC black seat and seat cover with CP brass hinges including cost of white cement, cement for packing, spun yarn, teak wood plugs, brass screws, etc., including supplying and fixing 10 litres capacity PVC / 12.5 litres capacity porcelin low level flushing tank with a pair of CI brackets, etc., complete with all fittings, such as, 15mm brass ball valve with polythene float with brass handle, union coupling connected by means of 40mm white PVC flush hand using indian adopter joint including all internal fittings, such as, 15mm bras connections, 15mm GM wheel valve, 15mm brass nipple (2 Nos.), 15mm nylon connection, TW plugs, screws and also giving necessary connection to the PVC pipe and painting the CI brackets with 2 coats of approved paint over one coat of red oxide primer, dismantling the masonry and re-doing the dismantled masonry to original condition, etc., complete complying with standard specifications. (The WC and flushing tank with all accessories should be got approved by the Executive Engineer before use on works) with 10 litres capacity flushing tank with all internal dual flush fittings with normal seat coverWall Fitting
254Supplying and fixing in position White / Colour Glazed Model Floor Mounted European Water Closet of best quality and approved make with 100mm “P” or “S” trap connecting with CI pipe of 100mm dia / PVC pipe of 110mm dia, double flapped rigid PVC black seat and seat cover with CP brass hinges including cost of white cement, cement for packing, spun yarn, teak wood plugs, brass screws, etc., including supplying and fixing 10 litres capacity PVC / 12.5 litres capacity porcelin low level flushing tank with a pair of CI brackets, etc., complete with all fittings, such as, 15mmbrass ball valve with polythene float with brass handle, union coupling connected by means of 40mm white PVC flush hand using indian adopter joint including all internal fittings, such as, 15mm bras connections, 15mm GM wheel valve, 15mm brass nipple (2 Nos.), 15mm nylon connection, TW plugs, screws and also giving necessary connection to the PVC pipe and painting the CI brackets with 2 coats of approved paint over one coat of red oxide primer, dismantling the masonry and re-doing the dismantled masonry to original condition, etc., complete complying with standard specifications. (The EWC and flushing tank with all accessories should be got approved by the Executive Engineer before use on works) Floor FittingFloorFitting for Handicapped Toilet
255Supplying and fixing of Oval Shape Wash Hand Basin of size 560 x 450mm with all accessories such as 32mm dia CP Waste Coupling, Rubber Plug and Chain, 32mm dia \"B\" Class GI Waste Pipe, 15mm dia GM Wheel Valve, 15mm dia Nylon Connection, 15mm dia Brass Nipples, 15mm CP Pillar Tap etc
256Supplying and fixing of Wash Hand Basin of size 550mm x 400mm with all accessories such as Cast Iron Brackets, 32mm dia CP Waste Coupling, Rubber Plug and Chain, 32mm dia \"B\" Class GI Waste Pipe, 15mm dia GM Wheel Valve, 15mm dia Nylon Connection, 15mm dia Brass Nipples, 15mm CP Pillar Tap etc - Wash Basin without Pedestal for Handicapped Toilet
257Supplying and fixing of Lipped Mouth Porcelain Flat Back Urinal with all accessories such as 32mm dia Bell Mouth PVC Connection, 15mm dia GM Wheel Value, 15mm dia \"B\" Class GI Waste Water Pipe, 15mm dia Nylon Connection, 15mm dia Brass Nipple etc.
258Supplying and fixing Stainless Steel Sink of size 600mm x 600mm x 200mm with 32mm dia \"B\" Class GI Waste Water Pipe and 32mm dia CP Waste Coupling
259Supplying and fixing SS Swan Neck Tap for sink
260Supplying and fixing of CP Two Way Bib Cock with Health Faucet with one no. of CP angle cock etc., complete.
261Supplying andfixing stainless steel paper holder with necessary fixing material paper roll etc.complete.
262Supplying andfixingC.P. Robe hook with C.P. screws etc., complete. Fixed on the toilet door
263Supplying and fixingC.P. towel ring with necessary fixing materials
264Supplying and fixingBrass Chromium Plated Towel Rail 60cm long and 20mm dia with Brackets, fixing materials
265Supplying and fixing liquid soap dispenser fixed with necessary fittings etc. complete as directed.
266Supplying andfixingpaper dispenser with necessary fixing materials etc.
267Supplying andfixingelectrically operated automatic hand drier with necessary fixing materials etc.
268Supplying and fixing Grab bar 450mm Long with necessary fixing materials . .
269Supplying andfixingPVC Nahini / Floor Trap with PVC Grating100mm x 75mm & required concrete encasing all around, complete.
270DRAINAGE WORKS
271Supplying and fixing in position best quality PVC soil / waste pipes of various dia having 6 kg / sq.cm. pressure BIS mark and providing leak proof joints using PVC adhesives including fixing to the wall with special PVC / MS clamp, teak wood plugs, brass screws, etc., and making connection to all sanitary fittings, dismantling masonry / RCC works wherever found necessary and making the good dismantled portion to the original condition, including testing for any leakages, etc., complete complying with standard specifications.(The PVC pipes should be got approved by the Executive Engineer before use on works). Internal & Vertical
27240mm dia
27350mm dia
27475mm dia
275110mm dia
276Supplying and fixing in position best approved of BIS quality PVC rain water down fall pipes having a pressure of 4 kg. / sq.cm including cost of necessry PVC shoe, PVC bend, cast iron gratings of required diameter and special clamps, brass screws, nails, etc., and fixing of cast iron gratings at junction of parapet and the RCC roof slab including finishing neatly etc., complete. The rate shall be inclusive of cast of removable cast iron grating. The PVC pipe shall be fixed in wall with special type of \"U\" clamp at the centre of the pipe line in addition to those for more than 3.0 metre pipe length, etc., complete complying with standard specification.
277110mm dia - 4kg/Sqcm
278200mm dia - 4kg/Sqcm
279Supply, installation, testing and commissioning of CI Khurra with CI Grating - L type with necessary accessories to complete the work including threading, cutting and fixing in/on walls under ceiling, on terrace, etc.,. The quoted rate shall include for making necessary chasing, making bores in foundation, walls, slabs, etc., and making good the chased surfaces and bores in cement mortar.
280110mm dia
281200 mm dia
282Supplying and fixing in position best quality PVC soil / waste pipes of various dia having 6 kg / sq.cm. pressure BIS mark with solvent cement joints confirming to IS 4985 for Under ground drainage works. The quoted rate shall include necessary earth work, fittings,pipe to be laid below ground level in trenches upto required depth, dewatering, jointing of pipes, water testing and setting/encasing the pipes if required in cement concrete M-15 as per specifications 150mm thk. all around, refilling, and making good the same complete as required. (The PVC pipes should be got approved by the Executive Engineer before use on works). The rate for earth work excavation will be measured and paid separately in the cases where the pipe lines are proposed to laid below ground level . (External)
283110mm dia
284160mm dia
285200mm dia
286Supplying andfixingPVC cowl to vertical Soil/Waste pipes above terrace level
28775mm dia
288110mm dia
289Construction of gully chamber ofsize 0.23 x0.23x0.3m with (150 mm X 100mm S.W.gully trap) 100 mm dia outlet set inPCC 1:4:8 bed, 120mm thick masonry chamber in CM 1:5, internal and external plastering 12mm thick in CM 1:3, necessary earthwork, C.I. cover (medium duty) etc., complete.
290Providing and constructing Inspection Chambers/ Manhole Chamber/ any other Chamber size 600 x600 mm x450mm to 1000mm deep including necessary excavation in soil/murrum/rock as per required invert level and working space all around, 150mm thick bed of cement concrete in proportion of CC 1:5:10 with 150mm offsets at all around the outer faces of walls, providing and constructing of minimum 230mm thick brick/cement concrete block masonry walls in CM 1:4 , providing and applying 15mm thick water proof plaster in CM 1:3 added with integral waterproofing compound as per manufacturers specifications and finished with a floating coat of neat cement @ 2.2 Kg/SqM at the internal & external faces all around the masonry walls, necessary floor benching and channels in cement concrete 1:1.5:3 of minimum 150mm thick rendered smooth with waterproof plaster followed by neat cement, providing CI circular/square Manhole cover with frame of minimum 600mmX600mm weighing minimum 40 kg (double seal) of approved make and confirming to IS and fixing with reinforced cement concrete 1:1:2 of minimum 150mm thick slab including shuttering, finishing the concrete surface and faces with waterproof plaster/IPS in mild slopes with float of neat cement etc complete as directed.
291600 x600 mm x450mm to 1000mm deep
292900 x 900 mm x 1000mm to 1500mm deep
293Supplying and construction of Rain water recharge pit with filter media, recharge bore, top slab complete as approved recharge pit drawing
294a. 600mm wide x 1500mm long x 1000mm Deep ( Bore well depth 3.5 Meter)
295Construction of oil and grease trap for canteen building 1200 x900 x 800mm deep mm with230mm thick walls in well burnt table molded bricks in CM 1:6 over a bed of 150mm thick PCC 1:4:8 internal walls shall be plastered smooth in CM 1:3 and external walls plastered CM 1:3 with sponge finish. Fixing CI frame and grating conforming to IS 5967 /1970 The top surface of the catch basin grating shall beflushed to the landscape level and making suitable outlet arrangement to lateral drain with necessary excavation, back filling with the selected earth.with allleads and lifts etc., complete. including SS bucket arrangement.
296WATER SUPPLY WORKS
297Supplying, laying and jointing CPVC pipes SDR 11(having working pressure 10 kg. / sq.cm) of approved quality and best variety conforming to BIS of the following dia including cutting, threading and fixing CPVC specials using CPVC adhesives (but excluding cost of such specials) and fixing into wall with teak wood plugs, CPVC clamps and screws making holes on the wall (or) drilling holes in the roof and making good the dismantled portion to original condition with necessary brick work / cement concrete and plastering neatly wherever necessary with necessary scaffolding charges upto 4 metre height above ground level, etc., complete complying with standard specifications.The CPVC pipes shall be got approved by Executive Engineer before use on works.Internal & Vertical
29840mm dia
29950mm dia
30065mm dia
301Supplying, laying, jointing, testing & commissioning approved make class \"B\" G.I. pipes and fittings confirming to IS 1239 PI & II, malleable fittings viz., tees, elbows, flanges, unions etc.,including cutting threading, etc., as per drawings. The quoted rate shall include necessary making bores in walls,etc., a coat of including Painting. (Pumproom)
30250mm dia
30365mm dia
30480mm dia
305100mm dia
306Providing and fixing gun metal gate valve with C.I. wheel of approved quality
30720mm dia
30825mm dia
30932mm dia
31040mm dia
31150mm dia
31265mm dia
313Providing and fixing CI D/F Sluice valve with cap / wheel as perIS 14846/2000 PN 1.0 with ISI Marking
31465mm dia
31580mm dia
316100mm dia
317Providing and fixingGM Non return valve as per IS BS 5154 and related IS Specifications
31850mm dia
31965mm dia
320Providing and fixing of of approved make automatic air release valve 20mm dia to release air lock in pipes as directed by EC/Client.
321Providing and fixing of approved make 50mm dia, Brass float valve, complete brass body contruction, PN6 rating, with SS ball. The scope of work includes terminating the OHT inlet pipe and positioning for smooth operation.
322Supplying, installing, testing and commissioning approved make electrically operated 50mm dia solenoid valve with level controllersto be fixed in the OHT. The cost of valve shall also include necessary level switches, wiring upto control panel at terrace level, control panel, etc.,complete
323Providing and fixing GI. puddle flanges (IS 1239) fabricated out of 6 mmthick M.S. plate of size 300 x 300mm plusdia of pipe of 750mm long pipe pieces fixed to RCC wall of water tanks. Including painting with two coats of primer complete as required. The entire fitting shall be hot dipped galvanized.
32425mm dia
32540mm dia
32650mm dia
32765mm dia
32880mm dia
329100mm dia
330150mm dia
331200mm dia
332Supplying, installing, testing and commissioning approved make Brass pressure reducing station including pressure reducing valve ,3 Nos Isolation valves, 2 Nos Pressure Gauges with union, flanges etc., complete.
33365mm Dia
334Earth work excavation and depositing on bank with initial lead of 10 m and lift of 2 M in narrow trenches having bed width 1.25m & below for laying of pipes for water supply and sewerage works in the following type of soils as directed by Departmental officers
335Sand, silt or other loose soil, wet sand or silt not under water light black cotton soil, sandy loam and ordinary soil.SS20B
336PUMPS & WATER TREATMENT PLANT
337Supply and delivery of Electric Monoset centrifugal pump conforming to IS 9079:2002 as amended from time to time, with CI FG 200 Casing , hydraulically and dynamically balanced Bronze grade LTB-2 impeller, impeller ring and casing ring, stainless steel shaft capable of discharging requiredquantity of water against a total head noted below due to all causes. Pumpshall of BEE 3 Star Rated and capable of discharging the specified quantityat the head noted at the minimum NPSHA at site conditions. The shut offhead shall be atleast 25% over and above the head at duty point. The pumpshall be suitable for operation in AC three phase , 415 V+/- 10% , 50 Hz +/-5%. Squirrel cage induction motor for continuous operation. The speed ofthe Pump and Motor shall be not less than 2700 to 2900 RPM respectively.
338Treated Water Pump (From Domestic Water Sump to O.H.T) Duty of Pump :1 LPS x35m head(1 No. Working+ 1 No. Stand By)
339Supply and delivery of clear water submersible pump conforming to IS 8034/2002 and as amended thereafter and BEE 3 Star Rated capable of discharging noted LPM against head of water column due to all causes. The pump shall be with stainless steel shaft and dynamically balanced bronze or Cast SS impeller, brass screws and CI FG 200 grade pump bowl/diffuser with ISI mark. The pump shall be directly coupled to a continuos rated two pole suitable wet type vertical squirrel cage induction motor suitable for operation in AC single phase 230 V+/- 10 %,50 HZ +/-5 %
340Pumproom drain pump Duty of Pump :0.5Lps x 35m head (1 No. Working )
341Supply and delivery of clear water vertical wet type submersible pump conforming to IS 8034/2002 and as amended thereafter and BEE 3 Star Rated capable of discharging noted LPM against head of water column due to all causes. The pump shall be with stainless steel shaft and dynamically balanced bronze or Cast SS impeller, brass screws and CI FG 200 grade pump bowl/diffuser with ISI mark. The pump shall be directly coupled to a continuos rated two pole suitable wet type vertical squirrel cage induction motor suitable for operation in AC single phase 230 V+/- 10 %,50 HZ +/-5 %
342Pumproom drain pump Duty of Pump :0.5Lps x 40m head (1 No. Working )
343Supplying, Installing, testing & commissioning approved make variable Hydropneumatic system comprising of Vertical Centrifugal pumps mounted on a common skid with automatic control panel including overload relays, on-off push button switches, phase indicator lamps, dry run protection relays, pressure switches & guages, 1no. FRP pressure vessel of 425Lts. mounted on the pump complete with cabling between the Pumps, control paneletc., complete. The pumps shall run on 440V, 3ph, 50Hz electric supply. (For flushing & landscaping watersupply system)
344Supplying, Installing, testing & commissioning approved make water treatment plant2000 LPH comprising of below units
345supplying, fitting, fixing Installation of Water cooler Aqua guard Storage Cooler-cum-Purifier Model- AG Green Pure Chill 120SS, with storage capacity 120 Ltrs., with - in built purifier (UV based) etc. complete and all as per direction of Engineer-in-charge.
346STP (Capacity 20 KLD - MBBR TYPE)
347Design, Supply,Installation,Testing & Commissioning of10 KLD MBBR technology package type including all tanks MS FRP coated equipment\"s such as Air Blowers for complete Aeration and Treatment Plant consists of Activated Carbon Filter(ACF),pressure Sand Filter(PSF),Softener etc complete with required pumps components & accessories as required to achieve the TNPCB parameters. (Excluding Civil works for Raw sewage and treated water tanks). Equipment Foundations and shelter for panel shall be considered in the scope.
348HVAC WORKS
349VARIABLE REFRIGERANT FLOW OUTDOOR UNITS (VRF ODU):Supply Installation,Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating,having all hermetically sealed inverter type Scroll Compressor(s),minimum two compressors for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc. complete as required.The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V+/10%, 3Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required.The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 .
35038hp
35124HP
352CEILING MOUNTED HORIZANTOL VRF AIR HANDLING UNITS:Design, Supply, Installation, Testing and commissioning of factory made, Ceiling mounted Double Skin, (25-mm thick CFC free PUF panels with 0.6-mm thick inner & 0.6-mm outer skin) horizontal air-handling units, Pre-filter section with Pre-filters (90% down to 10 micron - MERV 8) with filter frame, Box filter (98% down to 3 micron - MERV 13) , minimum 6 rows deep Dx Cooling coil section, 1.2-mm thick Stainless steel (SS 304) Insulated condensate drain pan with 9-mm thick closed cell Nitrile rubber bottom Insulation, plug fan with EC motor (Efficiency class IE3), necessary mounting frame, Vibration isolators,2mm thick GI base frame, Aluminium structural frame work, Fire retardant flexible connection, Access door, View port for fan section and accessories. The quoted priceinclude the cost of supply, installation, testing and commissioning of suitably rated electrical starter panel, fabricated of 16G sheet metal enclosure powder coated using seven tank process, color Siemens gray, wall mounted type, knockout for cables will be factory cut, selector switch and indication lamps for Auto/Manual/OFF status, The price include control cabling for limit switch and marine light operation, all MCCB\"s, controls and transformers cabling will be of approved make.
35310 TR, 6800 CMH (Office Area)
354CEILING MOUNTING TYPE CASSETTE UNITS(REGULAR): Supply, installation, testing and commissioning of the following capacity, ceiling mounting type, Variable Refrigerant Flow cassette Unit consisting of Thermo plastic Cabinet, Dynamically balanced centrifugal blowers, fan motors, fresh air port, Direct Expansion type cooling coil, Insulated drain tray, Prefilters, Electronic Refrigerant Flow Control valve, connection / branching kit, additional refrigerant charging, Room temperature sensor & Cordless remote controller, Infra red sensor, Control module self-diagnostic features, Inbuilt condensate drain pump, necessary supports as per the specification and drawings. The VRF System shall use R410A as refrigerant.NOTE: Indicated Cooling & airflow Capacities of IDUs are the minimum requirement to meet the Designed indoor Conditions for the out door peak Weather Conditions as noted on the drawings and specification. The HVAC Vendor is responsible to make the selection of suitable indoor units from their available product range to meet both TR & airflow rate and considering capacity loss due to pipe length and level difference between VRF IDUs & VRF ODUs and Indoor/Outdoor design conditions etc.
3554.0 TR, 1669 CMH ( Lift Lobby)
3563.2 TR, 1442 CMH ( Gym)
357CEILING MOUNTING TYPE DUCTABLE UNITS: Supply, installation, testing and commissioning of the following capacity, ceiling mounting type, Variable Refrigerant Flow Low/Mid static Ductable units consisting of GI Cabinet, Dynamically balanced centrifugal blowers, fan motors, Direct Expansion type cooling coil, Insulated drain tray, Prefilters, Electronic Refrigerant Flow Control valve, connection / branching kit, additional refrigerant charging, Room temperature sensor & Cordless remote controller, necessary supports . The VRF System shall use R410A as refrigerant.NOTE: Indicated Cooling & airflow Capacities of IDUs are the minimum requirement to meet the Designed indoor Conditions for the out door peak Weather Conditions as noted on the drawings and specification. The HVAC Vendor is responsible to make the selection of suitable indoor units from their available product range to meet both TR & airflow rate and considering capacity loss due to pipe length and level difference between VRF IDUs & VRF ODUs and Indoor/Outdoor design conditions etc.
3588.0 TR, 4262 CMH (Caffeteria)
3594.0 TR, 2380 CMH ( Double Height Lobby)
360VRF HI-WALL UNITS : Supply, installation, testing and commissioning wall mounting type, Hi-wall Unit consisting ofThermo plastic Cabinet, Dynamically balanced centrifugal blowers, fan motors, Direct Expansion type cooling coil, Insulated drain tray, Prefilters, Electronic Refrigerant Flow Control valve, connection / branching kit, additional refrigerant charging, Room temperature sensor & Cordless remote controller, Infra red sensor, Control module self-diagnostic features, necessary supports as per the specification and drawings. The VRF System shall use R410A as refrigerant.NOTE: Indicated Cooling & airflow Capacities of IDUs are the minimum requirement to meet the Designed indoor Conditions for the out door peak Weather Conditions as noted on the drawings and specification. The HVAC Vendor is responsible to make the selection of suitable indoor units from their available product range to meet both TR & airflow rate and considering capacity loss due to pipe length and level difference between VRF IDUs & VRF ODUs and Indoor/Outdoor design conditions etc.
361Wall-Mounted Panel with Cordless Remote Controller
3621.6TR 1150 CMH
363DX SPLIT UNITSUPPLY & INSTALLATION OF AIR-CONDITIONER WITH COPPER COIL
3642.0 TR, 1037 CMH (Server Room & UPS Room)
365Supply and installation of 5 KVA capacity Automatic Voltage Stabilizer with time delay relay
366Supply and fixing of MS stand for fixing outdoor unit
367REFRIGERANT PIPING & ELECTRICAL POWER/CONTROL CABLING: Design, Supply, Installation, Testing, and Commissioning of1.2mm thick hard drawn (below 6HP soft drawn) copper refrigerant pipes for VRF Indoors and Outdoors with necessary copper fittings, closed cell nitrile tubular insulation (Class-O) with Glass cloth and polyshield coating and silver-soldered joints to withstand minimum 3000 kPa pressure. The exposed piping shall be with powder coated perforated cable tray and covered with powder coated sheet cover on it. The pipe sizes will be selected according to the equipments capacities. The price include connection kit, additional refrigerant charges, power cabling for outdoor units, communication cabling between IDU\"s and ODu\"s and wired remote cabling for IDU\"s in MS conduits.
36841.3 mm Dia Copper Pipe with 19mm thick insulation
36934.9 mm Dia Copper Pipe with 19mm thick insulation
37028.6mm Dia Copper Pipe with 19mm thick insulation
37122.2mm Dia Copper Pipe with 19mm thick insulation
37219.1mm Dia Copper Pipe with 19mm thick insulation
37315.9mm Dia Copper Pipe with 19mm thick insulation
37412.52 mm Dia Copper Pipe with 13mm thick insulation
3759.5mm Dia Copper Pipe with 13mm thick insulation
3766.4mm Dia Copper Pipe with 13mm thick insulation
377REFNET
378Supply,installation,testing and commissioing of Refnet joint (Y-Branch kit) for suction and liquid line as per OEM recommendation
379PVC CONDENSATE PIPING:Supply,installation,Testing & Commissioning of Heavy duty PVC pipes of following sizes; with 9mm thick Aluminium Foil faced Nitrile Rubber Insulation
38025 mm
38132 mm
38240 mm
383FACTORY MADE RECTANGULAR GI DUCTING : Supply, installation, testing and commissioning of factory made lock-forming quality rectangular GI ducting, complying with IS: 277 and having 120 GSM coating classification. The price include the cost of necessory accessories & supports (like TDF flanges, ms angle flanges, neoprene gaskets, threaded rod, corner saddles, guide vanes as per SMACNA standards, joints, labelling etc..
38424 Gauge ( 0.63 mm Thick )
38522 Gauge ( 0.8 mm Thick)
38620 Gauge ( 1.0 mm Thick)
387FACTORY MADE FLAT OVAL GI DUCTING : Supply, installation, testing and commissioning of factory made lock-forming quality Flat OvalGI ducting with Inner Thermal Insulation, complying with IS: 277 and having 120 GSM coating classification. The price include the cost of necessory accessories & supports (like TDF flanges, ms angle flanges, neoprene gaskets, threaded rod, corner saddles, guide vanes as per SMACNA standards, joints, labelling etc..
38822 Gauge ( 0.8 mm Thick) Ground floor
389SEMI RIGID DUCT:Supply, installation, testing and balancing of Semi Rigid duct as per above specification.
390150 mm Dia
391300 mm Dia
392GRILLES:Supply and fixing of extruded aluminum powder coated, Supply and fixing of return Air Grilles / Diffusers with Volume Control Damper
393LOUVER :Supply, installation, testing and commissioning ofextruded Aluminium powder coated Fresh air & Exhaust air louver. The color & pattern shall be pre-approved by Architects/Client.
394DOOR TRANSFER AIR GRILLES:Supply and fixing of extruded aluminum powder coated, Supply and fixing of return Air Grilles / Diffusers with Volume Control Damper
395ROUND DISC VALVE: Supply, fixing and testing of Al. powder coated Round disc Valve of 150 mm dia for Toilet Exhaust with damper.
396COLLAR DAMPERS: Supply, installation, testing and commissioning of aluminium collar damper to be mounted for grilles & diffusers.
397FIRE-RETARDANT CANVASS:Supply, installation, testing and commissioning of fire-retardant canvss, with GI matching flanges, with a provision of operable zip. The entire assembly shall be fabricated at factory.
398SPICOT DAMPER: Supply and installation of GI Spicot Damper
399VOLUME CONTROL DAMPERS: Supply, installation, testing and commissioning of Factory fabricated Rectangular shape Aero foil type Aluminium volume control dampers, 1.2-mm Al Frame, 1.0-mm, 150-mm width, with required hardware and accessories.Stiffen damper blades for stability.Include locking device to hold single-blade dampers in a fixed position without vibration & engraved marking on position of damper, as per specifications. The shafts shall be suitable to mount electric actuators, where-ever required. Dampers\" flanges shall be suitable to TDF. Please refer technical specifications for complete details and scope & quote accordingly.
400BACK DRAFT DAMPERS: Supply, installation, testing and commissioning of Factory fabricated Rectangular shape Aero foil type Aluminium volume control dampers, 1.2-mm Al Frame, 1.0-mm, 150-mm width, with required hardware and accessories.Stiffen damper blades for stability.Include locking device to hold single-blade dampers in a fixed position without vibration & engraved marking on position of damper, as per specifications. The shafts shall be suitable to mount electric actuators, where-ever required. Dampers\" flanges shall be suitable to TDF. Please refer technical specifications for complete details and scope & quote accordingly.
401FIRE DAMPERS: Supply, installation, testing and commissioning of Fire dampers with fusible link, 1.5-hours fire rating, for supply ducts and return air duct where-ever crossing the space separating walls or as shown in the drawings. The damper shall be made out off 1-mm thick gal vanished Sheet metal blades, with 1.4-mm thick Galvanized sheet frame, Fusible link Fire dampers, 1-mm thick gal vanished Sheet metal blades, with 1.6-mm thick Galvanized sheet frame.
402MS SUPPORT WORK:Supply, fabrication and installation of mild steel support work for support works as per the drawing , other than for duct, pipe and equipment supporting. The supports should be duly painted using two coats of primer and two coats of black enamel paint.
403DUCT THERMAL INSULATION :Supply and providing thermal insulation of 9mm thick vidoflex with Aluminum Foil
4049mm thick
405DUCT ACOUSTIC INSULATION :Supply and providing acoustic for initial portion of ducting with 12mm thick Fibre Glass Rigid Board covered with Tissue Paper and Aluminum Perforated Sheet
40612 mm Thick
407UNDERDECK INSULATION :Supply, installation, testing and commissioning 13mm thickness of closed cell nitrile preformed sheet insulation without Aluminium foil for underdeck insulation with support like round insulation disc and cross steel wire. Adhesive shall be used as recommended by insulation manufacturer for applying over concrete structures.
408CABINET FRESH FAN: Supply, installation, testing and commissioning of Ventilation fan cabinet type units. The unit shall be 0.6mm GIS construction, belt driven centrifugal fan, High efficiency motor, spring vibration isolator for fan and motor, Fire retardant canvass connections, with acoustic enclosure for fan & noise level not exceed 65 dBA at 1.5m distance,weatherproof type, internal power and control wiring, GI base frame complete as per specifications as required. Fan motor shall be suitable for 415±10% volts, 50Hz, 3 phase AC supply & & 230V, 1 phase, 50Hz AC supply.
409Air Qty: 2300 CMH, ESP:15mmWC ( Canteen,Gym & Cafeteria)
410INLINE EXHAUST FANS:Supply, Installation, testing and commissioning of factory-fabricated, assembled,tested, and finished, direct-driven circular / Rectangular fansconsisting of internally lined housing, wheel, fan shaft, bearings, motor, drive assembly, with joints between sections sealed. Themounting frame will be Galvanized Steel frames of minimum 3-mm Thick with factory fabricated corner pieces.
411Air Qty: 2210 CMH, ESP:15mmWC ( Toilet )
412Air Qty: 1700 CMH, ESP:15mmWC ( Electrical Room )
413Air Qty: 1870 CMH, ESP:15mmWC ( Low Voltage Room)
414AXIAL FAN :Design, Supply, installation and commissioning of the following capacity Axial Flow Fans with silencer length is equal to fan dia. The fan motor shall be suitable for operating on 415±10% V, 3 phase, 50Hz AC supply. The cost shall inclusive of required length and adequate power wiring from the nearest isolator to the fans, weatherproof, wall housing, Fire retardant canvass connections, vermin net on both sides, louvers on one end, steel supports required for mounting the fan and bird screen, wire mess and storm proof louvers as required
415Air Qty: 19550 CMH, ESP: 25mmWC (Lift Well Pressurization), Motor Rating: 11KW
416Air Qty: 24650 CMH, ESP: 25mmWC (Staircase Pressurization), Motor Rating: 11KW
417Air Qty: 30090 CMH, ESP: 25mmWC (Lift Lobby Pressurization), Motor Rating: 11KW
418Supply, installation, testing and commissioning of Pressure Sensorlocated at Pressurized Room to maintain the pressure.The sensor shall be microprocessor based and shall incorporate suitable measurement techniques to be capable of generating an output signal proportionalto the pressure achived the signal need to transmit to close the damper & maintain the fan Speed.
419FIRE FIGHTING
420Supply, erection, testing and commissioning of Fire Fighting Application Horizontal Centrifugal Type Pump rated for 2280 LPM at 70 metres head with Electrical Motor of 60HP of 415 volt, 3 phase connection complete with base plate and accessories. (Make Kirloskar or Equivalent). The rate inclusive of neessary vibration, bed mounting, etc., as per standard specifications and as directed by the Departmental Officers(Sprinkler & Hydrant Pump )
421Supply, installation, testing and commissioning of Diesel Engine Driven Main Fire Pump suitable for automatic operation and consisting of followings complete in all respects as required. 1 No. horizontal split casing centrifugal type fire pump capable of delivering 2280LPM against a total head of 70 metres, so as to ensure a minimum pressure of 3.5 kg. per sq.cm at the farthest top most hydrant /utlet with pump casing of cast iron to grade FG 200, IS 210-1978 and parts like impeller, shaft sleeve, bearing ring, etc., of non-corrosive metal either like bronze, brass or gun metal and shaft of stainless steel. 68 BHP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant BS & IS standard complete. Auto starting mechanism, 12 volts / 24 volts electric starting equipment like self motor, dynamo, solenoid switches etc.110 litres capacity diesel tank mounted over stand fabricated using 25mm x 25mm x 6mm size MS angle providing with level indicator, inlet port, outlet port, drain port and diesel return line port and fuel pre filter, after filter etc..Exhaust system having flexible metallic mufler, 100mm dia MS heavy pipe extended upto 1m outside pump house duly insulated with 50mm thick glass wool with 1mm thick aluminium sheet cladding, residential silencer with necessary MS support arrangements from wall or ceiling as per site condition.
422Dash board consisting of the instruments like Temperature Gauge, Galvano Type DC Ammeter, Lubricant Oil Pressure Gauge, Ignition Switch, Emergency Stop and all other protection equipments as per specification, stop soleneid for auto stop in the event of fault with audio indications, painted with Post Office Red Colour etc., as required.12 V / 24 V, storage battery, maintenance free tape, 180AH rating. MS fabricated common base plate, coupling guard, foundation bolts, etc., as required. Positioning the Diesel Engine Driven Fire Pump over cement concrete foundation using suitable size anti vibration mounting arrangements. All works including conveying, fixing and incidental charges, etc., completed as per standard specification and as directed by the Departmental Officers. (Make: KIRLOSKAR / EQUIVALENT).Supply, installation, testing and commissioning of Diesel Engine Driven Main Fire Pump suitable for automatic operation and consisting of followings complete in all respects as required.
423Supply, erection, testing and commissioning of 180 LPM, 70 metres Head Pressurization Pump with 10HP electrical motor of Kirloskar make with suitable base frame including necessary vibration bad mounting etc., including conveying, fixing and incidental charges, etc., complete as per standard specification and as directed by the Departmental Officers. Make: KIRLOSKAR / EQUIVALENT. Jockey Pump
424Supplying and fixing air vessel made of 250 mm dia, 8mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
425Supplying, installation, testing and commissioning of Fire Fighting Electrical Control Panel of cubical construction, floor mounted type fabricated using CRCA sheet, compartmentalised with hinged lockable door dustand vermin proof, cable alley, inter connection having switch gears and accessories mounting and internal wiring, earth terminals, numberings, necessary metering protections and indications complete in all respect suitable for operation on 415volt, 3 phase, 50 Hz AC supply with enclosure protection class IP 54 and mounted with the followings. A. Common Panel in Fire Pump House(i). Incomera. 1 No. 600A TP & N SDFU with HRC fusesb. 1 set of 600A, 4 bar aluminium bus bar, 415 V, 50 HZ AC supplyc. 1 No. (0-500A) digital ammeter with selector switch & CTsd. 1 No. (0-500V) digital voltmeter with selector switch and control fusese. 3 Nos. phase indication lamp LED type with toggle switches with control fuses
426(ii). Outgoinga. Main Fire Pump400 A TPN SDFU with HRC fuses with sutable HP fully automatic starter / delta starter with over load protection, digital ammeter with built-in selector switch and suitable CTs, current sensing type single phasing preventer complete with all accessories and internal wiring required for automatic operation, selector switch for auto / manual / OFF operationb. Jockey Pump125 A TPN SDFU with HRC fuses with suitable HP fullyautomatic starter / delta starter with over load protection,current sensing type single phasing preventer complete withall accessories and internal wiring required for automaticoperation, selector switch for auto / manual operation - 1 No.c. Diesel Engine Control comprising of:1. Auto / manual selector switch and 3 attempt starting device, timers and relays as required, push buttons, start /stop in manual mode.2. Indication lamp for high / low lubricant oil pressure, high water temperature and engine ON indication.3. Battery charger suitable for 12V /24V DC with boost and tickle selector switch, 0-15V / 0-30V DC volt meter, 0-20A DC ammeter.
4274. All standard relays and accessories for automatic operation of diesel engine.5. The above combined panel mounted over MS channel fabricated frame with cement concrete platform, all other connection works carried out as per standard methods and including conveying, fixing and incidental charges, etc.,complete as per standard specification and as directed by the Departmental Officers. Note: Cables, Earthpit Quantity for Pumproom considered in electrical BOQ
428Supply, erection, testing and commissioning of Pressure Gauge with 0 to 14 kg. range of reputed make with necessary valve, milling thread MS coupling fixed at delivery pipe line in pump house to read the developing pressure including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: H-GURU / ISI MAKE / EQUIVALENT.
429Supply, erection, testing and commissioning of suitable Pressure Switch of reputed make line Indfoss or Donfoss including necessary valves, couplings, etc., connected with electrical main control panel and setup at proper differential so as to auto start and auto stop the electrical motor, jockey motor including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., completed as per standard specification and as directed by the Departmental Officers. Make: DONFOSS / INDFOSS / ISI MAKE / EQUIVALENT.
430250mm dia
431200mm dia
432150mm dia
433100mm dia
43480mm dia
43565mm dia
43650mm dia
43740mm dia
43825mm dia
439Wrapping and coating anti-corrosive treatment for the following under ground MS pipe having one coat of anticorrosive metal primer, one layer of asphalt tar tape wound over the MS Pipe as per standard methods as per standard specifications and as directed by the Departmental Officers.
440150mm dia
441100mm dia
44280mm dia
443Supply, erection, testing and commissioning of cast iron body and bronze internal non-rising spindle sluice valve of sizes at required places to control the flow of water including necessary MS flange of table gaskets, bolts & nuts including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: NORMEX / KARTAR / EQUIVALENT
444250mm dia
445200mm dia
446150mm dia
447100mm dia
44880mm dia
44965mm dia
450Supply, erection, testing and commissioning of Gun Metal Gate Valve of size 50mm dia size including necessary MS flange of table gaskets, bolts & nuts etc., installed at pump house delivery line for the purpose of priming water to suction line including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: LEADER / EQUIVALENT.
45150mm dia
452Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :
45325mm dia
454Supply, erection, testing and commissioning of Cast iron body and Gun metal or stainless steel internal Non-return valve of following sizes to control one way flow of water to be installed pump room at delivery line and near overhead tank at terrace level near to jockey pump and motor including necessary MS flange of table gaskets, bolts & nuts, etc. as per IS 5312 including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
455200mm dia
456150mm dia
45765mm dia
458Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
459250mm dia
460Supply, erection, testing and commissioning of AirRelease Valve of 20mm dia, so as to release airlock in 100mm dia MS pipe at top most wet riser, including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: KARTAR /EQUIVALENT.
46120mm dia
462Providing, fixing pipe supports from columns / wall or suspenders from roof slab to suit various dia of pipes made out of GI / MS adjustable rods threaded for a sufficient length to adjust the height of support along with clamping arrangement for holding pipes of anchor fastening, arrangement design of hanger and should confirm with specification.
463100mm dia
46480mm dia
46550mm dia
46640mm dia
467Supply and fixing of Fire fighting application oblique type stainless steel Hydrant Valve of size 63mm dia with oblique type instantaneous coupling with rotating wheel to open and close the valve including MS flange of table bolts & nuts with washer as per IS 5290 at ring main around the building and wet riser inside the building including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFE GUARD /EQUIVALENT.
468Supply, installation of Fire Fighting Application 180 degree swinging type, hose reel drum with 20mm dia braided thermoplastic hose of 30 metres long, so as to extend to necessary distance by self rolling spindle wheel including necessary 20mm dia ball valve and open and close spray nozzle, warm clip, etc., as per the standard pattern of any reputed make at every floor nearer to hydrant valve, including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary., etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFEGUARD / SAFE GUARD / EQUIVALENT.
469Supply, and fixing in position of Fire Fighting Application Hose of 63mm dia of 15 metres length binded by copper wire with 63mm dia stainless steel male and female instantaneous fire fighting special coupling as per IS 901 as directed by the Departmental Officers. Near every hydrant points including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR/ LIFE GUARD / SAFE GUARD / EQUIVALENT.
470Supply, and fixing in position of Fire Fighting Application 63mm dia stainless steel short length Branch Pipe with hexagonaltype spray nozzle of 15mm (or) 20mm jet bore. Near every hydrant points including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFEGUARD / EQUIVALENT.
471Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
472Supply of Fire Fighting Application MS Hose Box to keep two number of hoses and 1 No. of branch pipe with nozzle having proper glass window type double door with universe open key, painted inside white and outside Post Office Red. Near every hydrant point including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFE GUARD / EQUIVALENT.
473Supply and fixing in position of Fire Fighting Duct Window having proper glass window type double door with universe open key, painted inside white and outsid post office red for the sizes of 1300 x 900 x 500mm (L x B x D) fabricated using 25 x 3mm MS \"L\" Angle and all sides covered with 2mm thick MS sheets, suitable arrangements to kept 2 Nos. of Fire Fighting Hoses and 1 No. Branch Pipe, mounted in fire duct using anchor fasteners, etc., as per standard specifications and as per directed by the Departmental Officers.
474Supplying, installing, testing and commissioning flow switch on sprinkler distribution header and shall be connected to fire alarm panel through cable. Cable shall be measured separately. (150mm dia/100mm dia)as per IS standards
475Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, testcontrol box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of 150mm dia.
476Sprinkler Annunciator Panel shall consist of 12 windows.The panel shall be capable of working on 230 V AC, single phase supply and also provided with battery back up of 24 V.The panel shall have battery charger in built so that it charges the batteries when it works on AC supply.The charger shall be two rate type i.e Trickle and boost.The panel shall be fabricated powder coated sheet metal of at least 16 Gauge thickness.The panel also shall have selector switches, Indication lamp, ON, OFF and trip switches etc.Adequate cable entry point shall be provided in the panel for accommodating the cables.Whenever any annunciation signal is received panel shall give both audible / visual indication.Accept button shall be provided so that whenever signal is accepted, only audio sinal will get silenced.Each window shall be connected to the relay contacts with RS 485 for connecting the same to the building automation system. The Annunciation Panel shall have annunciation for all pumps “ON” and “TRIP” conditions and “Fire water Tanks High / Low level / Overflow conditions and “Operations of Control valves”.It shall have test, acknowledge and reset push buttons.The panel shall operate on DC supply. Make for Parts: Honeywell / Siemens / OEM Panel Board Builders.
477Supply and fixing nominal bore quartized bulb type sprinkler bulb 68 Deg CK80, fast response pendent type including GI collar for each sprinkler bulb, mounted in MS pipe line using suitable size MS threaded coupling, thread, shellac etc., as per standard methods and including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFEGUARD / EQUIVALENT.
478Supply, Installing, testing and commissioning of Stainless Steel Corrugated Flexible Braided Pipe (Hose) for dropping sprinklers below false ceiling. Pipe shall be 16 bar pressure rating and 1500mm long, 25mm dia with union / reducer, collar, clamps, etc. It shall have UL listed and FM approved.
479Supplying and installing of approved type Rosette Plates (Recessed Type in Two Pieces) for sprinklers below false ceiling area. The Rosette shall be fabricated by MS plate of 2mm thick and the finish shall be powder coated and colour, as directed by the Departmental Officers.
480Supply, erection, testing and commissioning of Fire Fighting 4 Way Fire Brigade Inlet with necessary gun metal 63mm dia non return spring shutter arrangements, so that to control one way flow at the time of emergency water supply by fire and rescue service fire engine entry including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: KIARTAR / OMEX / EQUIVALENT.
481Supply, erection, testing and commissioning of Fire Fighting 2 Way Fire Brigade Inlet with necessary gun metal 63mm dia non-return spring shutterarrangements so that to control one way flow at the time of emergency water supply by fire and rescue service fire engine entry including conveyance, allincidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary., etc., complete as per standard specification and as directed by the Departmental Officers. (Make: KIARTAR / OMEX / EQUIVALENT)
482FIRE EXTINGUISHER
483Supply and fixing of stored pressure ABC (Mono Ammonium Phospate) Powder Type Fire Extinguisher of 6 kg. capacity as per IS:15683 with pressure gauge, discharge hose & control nozzle, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc, complete as per standard specification and as directed by the Departmental Officers. Make: EXCELLENT / SAFETY FIRST / EQUIVALENT
484Supply and fixing of DCP (Dry Chemical Powder ) Type Fire Extinguisher of 6 kg. capacity as per IS:15683 with pressure gauge, discharge hose & control nozzle, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc, complete as per standard specification and as directed by the Departmental Officers.
485Supply and fixing of Carbon-di-Oxide Gas Type 4.5 kg. capacity Fire Extinguisher as per New IS15683, complete with control valve, discharge hose with horn, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc., complete as per standard specification and as directed by the Departmental Officers.
486Supply and fixing of Carbon-di-Oxide Gas Type 2 kg. capacity Fire Extinguisher as per New IS15683, complete with control valve, discharge hose with horn, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc., complete as per standard specification and as directed by the Departmental Officers. Make: EXCELLENT / SAFETY FIRST / EQUIVALENT
487Supply and fixing of Aqueous film forming foam 9lts. capacity Fire Extinguisher as per New IS15683, complete with control valve, discharge hose with horn, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc., complete as per standard specification and as directed by the Departmental Officers.
488Supply and kept in position of Trolley Mounted Type 22.5 kg. Carbon-di-Oxide Fire Extinguisher as per IS15683, complete with control valve, gun metal cap, pressure gauge, operation sticker, discharge hose, mounting trolley with moving wheel, safety clip, etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standardspecification and as directed by the Departmental Officers. Make: EXCELLENT / SAFETY FIRST /EQUIVALENT
489Supply and kept in position of 9 litres capacity Fire Buckets of 4 Nos. with Bucket Stand as per standard specifications and as directed by the Departmental Officers
490SIGNAGES
491Providing and installing in position the following type of sign boards made out of 3mm thick \"Opaque\" PVC foam board with computer cut, PVC non-reflective self adhesive vinyle painted foam board, complete with mirror fasteners.
492Signage with printed\"IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE\" of 1.5cm height letters in red with white back ground.The size of the board shall be 25cm x 30 cm and shall be fixed at the height of 2 mts. from finished floor near Manual call points.
493Floor indentification signage ( ie, GROUND FLOOR …etc.) at each stair enclosure on every floor, indicating the floor number in words, lettering size shall be 7.5 cm with contrasting colour from back ground.Size shall be 15cm x 60cm.
494Providing and fixing in position the signages \" FIRE ORDER\" it should contain the following matter on 3mm thick \"Opaque\" PVC foam board of computerised cut, PVC non-reflective self adhesive vinyle painted foam board of 3\" x 4\".ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL POINT LOCATED AT STRATEGIC LOCATION . EVACUATE THE OCCUPANTS BY USING THE FIRE EXITS & EMERGENCY EXITS ONLY. ASSEMBLE AT VARIOUS ASSEMBLY POINTS. IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY USING THE NEAREST/SUITABLE PORTABLE EXTINGUISHER OR WATER FROM NEAREST WET RISER BE CALM, DO NOT GIVE ANY ROOM FOR PANIC, WALK, DO NOT RUN IF YOU ENCOUNTER SERIOUS DIFFICULTY IN EVACUATION, STAY IN YOUR PLAN AND TRY TO ATTRACT ATTENTION OF RESCUE TEAM
495Providing and installing in position the following type of sign boards made out of 3mm thick \"Opaque\" PVC foam board with computer cut, PVC non-reflective self adhesive vinyle painted foam board, complete with mirror fastenersACTION BY SECURITY/RECEPTION UPON RECEIPT OF INFORMATION THROUGH FIRE ALARM OR FIRE DETECTORS OR BY USING PUBLIC ADDRESS SYSTEM. A) ALERT THE OCCUPANTS BY USING PUBLIC ADDRESS SYSTEM. B) INFORM FIRE CONTROL THROUGH ANY ONE OF THE FOLLOWING PHONE NUMBERS:C) IN CASE OF THE CASUALTIES, CALL AMBULANCE BY DIALLING NUMBER…….. FIRE FIGHTING AGNECY-------------------------------PHONE : ----------------------- FAX : ----------------------------
496Fire and emergency signage Boards( Fire escape directions, First aid charts, First aid box indications, safe material handling procedures, Fire assembly area indications etc,)
497Providing and installing of Fire Evacuation Plan with route inrectangular Acrylic sheet with ss bolt of size 600 x 450mm& 2 to 3mm thick
498FIRE ALARM & PA SYSTEM
499Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.Two Loop Panel.
500Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector (smoke detector) complete with mounting base complete as required.
501Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
502Supplying, installation, testing & commissioning of fault isolator complete with base as required.
503Supplying, installation, testing & commissioning of intelligent addressable thermal detector (Heat detector) with rate of rise cum fixed tempreature thermistor complete with base as required.
504Supplying, installation, testing & commissioning of addressable fire control module complete as required.
505Supply, installation, testing and commissioning of Manual Call Point (MCP) providing on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods and as directed by the Departmental Officers. (Make: Ravel / Equivalent)
506Supply, installation, testing and commissioning of Electronic Hooter / Sounder providing on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods and as directed by the Departmental Officers (Make: Ravel / Equivalent)
507Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
508Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
509Supply and laying of FRLS PVC insulated 2 core 1.5 sq.mm. Armoured Copper Cable on ceiling / wall using fixing accessories like screws, plug, clamps, etc., as per standard methods and as directed by the Departmental Officers.
510Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
511Supplying, installing, testing & commissioning of 15 W Wall Mount Speaker
512Supplying, installation, testing & commissioning of PA Mixer Amplifier 240 Watts
513Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.
514Supply and laying of 2 core 1.5 sq.mm.Armoured Speaker Cable on ceiling / wall using fixing accessories like screws, plug, clamps, etc., as per standard methods and as directed by the Departmental Officers.
515Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
516Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.
517Supplying, installing, testing & commissioning of 6 W Ceiling Mount Speaker (False Ceiling)
518ELECTRICAL WORKS
519HT INSTALLATION AND ALLIED WORKS
520Unloading, handling, safe keeping, Installation, testing and commissioning of Outdoor Weather & Dust proofType,floor mounting, free standing 11kV RMG 3 PANEL unit made out of M.S sheet steel clad dust and vermin proof with Copper Busbars, Interconnections, necessary protections(CDG 31 with 2 nos Over currrent and 1 nos earth fault relay with high speed tripping relay including power pack, ammeter and voltmeter, Fixed Type PTs 11kV/110/v3V-110/v3V 100VA 0.2s CL, CTs with 40/5A with required Class of accuracy as per norms), Indicating Instruments,with necessary control fuses/MCBs, Termination arrangements for Incoming and Outgoing Cable of 11 kV 3Core XLPE Alu.Armoured earthed cable, Terminal Blocks, Earthing, Powder coated painting, Sign writing and Base channels etc., with completeall accessories as required for satisfactory operations and asper the detailed Technical Specifications enclosed and as per EB Requirements comprising of the following.
52111kV, 630A, 500MVAVCB with necessary required accessories -3 Nos
52211kV, 630A, 500MVATrolley Mounted EACH VACCUM Circuit Breaker withM2 Trolley Mechanism for VCB and necessary required accessories like Tripping relay : 1No with EB (TVM) Meter provision -
523ThePanelshould have required power pack for control wiring and shall be manufactured as required by the electrical authorities. The cost is inclusive of suitable rating of builtin power pack for all control wiring.& panel colourshall be with RAL 7035 IS 5 to suit EB norms.
524Note : Including All civil work like excavation concreting and back filling etc,
525FENCING & GATE
526Fencing : Fencingwith 75 x 75mm 10SWG chain link mesh to a height of 1.8Mtrs. above ground level and a retaining wall with brick all around to a height of 330mm above ground with vertical members of 50 x 50 x 6mm M.S. angles at 1.5mtr. Interval and tie angle at top with 25 x 25 x 6 M.S. angle.
527Gates : 1.8mtr. Height and 1.5mtr. Width gate made out of 50 x 50 x 6mm M.S. angle cross supports fixed on 100 x 50 x 6mm M.S. channels andcovered with 50 x 50 mm weld mesh with pad locking arrangements.
528Leveling the Yard: Leveling the yard and spreading 40mm blue metal to a height of 75mm.
52911KV HT singleVCB PANEL
530The HT singleVCB Switchgear panels will be of metal clad, free standing construction, suitable for operation on 11KV 3 Ph, 50 Hz, AC earthed system and fabricatedfromsheet steel, with powder coat finish painting of shade RAL 7032 . The panel shall contain components as mentioned below, complete with bus bar inter connections control wiring designation labels, caution labels, sealing and pad locking facilities and wherever necessary space provision for entry of HT cables from the bottom through detachable gland plates
531Supply, Installation, Testing and commissioning of 11KV 800A, 350MVA, 26.3kA HT outdoor THREEPanel VCB Board unit made out of M.S sheet steel clad dust and vermin proof with 800A COPPER Bus bars, Interconnections, necessary protections, Measuring Instruments, Indicating Instruments, Protection Relays, CTs, PT with necessary control fuses/MCBs, Termination arrangements for Incoming of 11 kV 3Core 185 Sq mm and Outgoing Cable of 11 kV 3Core 185 Sq mm cable, Terminal Blocks, Earthing,Powder coated painting, Sign writing and Base channels etc., with complete all accessories as required for satisfactory operations-Outdoor type
532Description
533Circuit Breaker(11KV,800A, 31.5KA for 1 sec VCB, Close / Trip Coil 110V DC, Spring charge Motor - 110 V DC-1 no I/C-1 no, 3 nos O/G-1 no) Current Transformer(Dual core, dual ratio :300/100/50/25/1A, CLASS:0.2 / 5P20 ,BURDEN:15VA, STC:26.2KA/1.0SEC.I/C-3 nos)(Dual core,dual ratio 300/100/50/25/1A, CLASS:0.5 / 5P20 /,BURDEN:15VA, STC:26.2KA/1.0SEC.-O/G-3 nosVoltage Transformer(3xPh,11000 V/ Root 3 / 110 V/ Root 3,CL :0.2s, 100VA with fuse protection on Primary and secondary sides)(3xPh,11000 V / Root 3 / 110 V/ Root 3,CL :0.2s, 100VA with fuse protection on Primary and secondary sides-I/C-3 nos, bus PT-3 nos)Numeric type Multi function relay for 50,51,50N , 51N,49,&95, CONTROL RELAY PANEL(with Communication Port-I/C-1 no, O/G-1 no)Master trip relay-I/C-1 no, O/G-1 nMulti function Digital Meter (TOD)(\"PM5510 or Equivalent with Cl:1.0 with RS 485 Com. Port or equivalent make-I/C-1 No)Multi function Digital Meter (MFM)(\" PM3360or Equivalent with Cl:1.0 with RS 485 Com. Port or equivalent make- O/G-1 no)CB ON / OFF Indication Lamp(Red, Green 110V DC-I/C -2 no, O/G-2 nos)Phase Indication Lamps(Red, yellow, Blue 110V AC-I/C-3 nos, O/G-3 nos)CB Spring Charge Indication Lamp(blue-I/C-1 no, O/G-1 no)Trip Circuit Healthy IndicatingLamp(white-I/C-1 no, O/G-1 no)12 way Alarm Annunciator with built in Push buttons for Accept,Test and Reset(O/C,E/F, WTA,BUA, WTT, BUT, -O/G-1 no)
534Control Switch(Trip_Neutral_Close ,Spring return to Neutral ,30 A DC-I/C-1 no, O/G-1 no)Space Heater with switch and Thermostat(60 W,strip type,230 V,AC- I/C- 1no, O/G-1 no &bus pt-1 no)Panel Illumination Lamp with door switch(11W CFL, 230 V AC-I/C-1 no, O/G-1 no &bus pt-1 no)Control Terminal Blocks, ANNUNCIATION PANEL 8 DISPLAY(Stud type 30 amps,1100 V grade(I/c&O/G-lot bus pt-1 no)Earth Bus bar(Electrolytic Copper 50 x 6 mm-i/C & O/G-Lot bus pt-1 no)Main Bus bar(630 A ,Electrolytic Copper of size 50 x 10 mm,Color sleeved-I/C & O/G- Lot bus pt-1 no)Test terminal blocks for CTs with CT shorting Links(I/C-1 no , O/G-1 no)Removable Power cable gland plate(I/C-1 no , O/G-1 no)Removable Control cable gland plate(I/C-1 no , O/G-1 no)Earth Switch on HT Cable side(I/C-1 no , O/G-1 no)Electrical interlock in VCB Closing circuit by providing micro switch (1 NO+1 NC) at earthing switch .(I/C-1 no , O/G-1 no)Plug and Socket(I/C-1 no , O/G-1 n, bus pt-1 no)Common Power Pack suitable for All Incoming and outgoing panels(Input; 230/110V AC Output:110V DC with Stored energy 60W sec. Continuous energy 40W for spring charging motor also- I/C- 1 no)Provision for receiving 230V A.C External Source(10A DP MCB - 3 Nos.-I/C-1 no & O/G- 1 noPotential free contacts for BMS monitoring (I/C-1 no , O/G-1 no)
5351000KVA 11KV / 433V TRANSFORMER (OIL TYPE)OUTDOOR WITH OLTC
536Design,Manufacture,Transport,Erection, Testing and Commissioning of 11KV / 433V 3 phase 50 Hz, DYn11, 1000 KVA OIL type Transformer with OLTC,of tapping +5% to -15% of steps 1.25% (16 Steps)level 2 losses and with terminal arrangement ofHT side cable box and LT sideWITH CABLES erected in platform, flat channels to place the wheels and stoppers as required.OLTC MAKE OLG OR CTR
537HT CABLE & END TERMINATION
538Supply and Laying of 11KV 3 Core (E) 185 Sq.mm.XLPEcable.The cable shall be laid in the cable tray which is fixed inside the cable trench as required as per the site condition
539Supply and Terminating of 11KV heat shrinkable indoor type termination kit suitable for terminating 3core 185 Sq.mm. XLPE cable with necessary cable jointing accessories.
540Supply and Terminating of 11KV heat shrinkable Outdoor type termination kit suitable for terminating 3core 185 Sq.mm. XLPE cable with necessary cable jointing accessories.
541CONTROL CABLES & TERMINATIONS
542Supply and laying of the following 1.1KV grade PVC copper control cables laid on cable trays / cable trench / wall / clamped inside the enclosure complete with necessary clamps and hardwares as required.
5433C x 2.5 Sqmmcablefrom Transformer-1,2 to Main MV Panel
54412C x 1.5 Sqmmcu.from Tr-1 fault to VCB
54512C x 1.5 Sqmmcu.from CP-1to Engine set-1,2
5464Cx 2.5 sq. mm cable from Main MV Panel to DG CP-1
5473C x 4 Sqmmcable
548Supply and providing end termination for the following cables by using suitable single compression gland and copper sockets as required. The cost of earthing glad with copper strips/wires shall also be included.
54912C 1.5sq.mm cu.cable
5504C x 2.5 Sqmm cu .cable
5513C x 2.5 Sqmmcable
5523C x 4 Sqmmcable
5532C x 4 Sqmmcable
554Excavation and backfilling of cable trench for HT Cable comprising of : - a) Excavation of cable trench of 1200mm D x 600mm W, b) Providing sand for 250 mm depth, c) Concrete truffs, d) Bricks and Back filling
555Cutting, Excavation of existing groundfor laying the above referred cable in 300 mm diaRCC Hume pipe protection of class \"NP2\". The excavated trench should be of 1000mm depth 600mm width. After laying it is vendor responsibility to make the original surface and hand over to the client.(For Road Crossing)
556EARTHING
557Supply, Installation, testing and commissioning of earth plate of size 600 x 600 x 3mmcopper plate earth electrode at a depth 3000 mm in an earth pit of 450 x 450 x 350mm filled with salt and charcoal mixed with sand in alternate layers of 150mm each up to a height of 3000mm from bottom. Two copper flats of size 25 x 3 mm shall be braced to this copper plate throughout the overlapping length with the copper plate and brought to the surface of the earth pit. This plate shall have provision for connecting wires or flats as the case may be. A suitable size of 25/ 38mm dia GI pipe shall be provided up to bottom of the earth pit. This GI pipe shall have provision for watering through a funnel. A masonrystructure of wall thickness of not less than 230mm shall be constructed to a depth of 450mm and heavy duty SFRC cover shall be used to cover the pit.
55825 x 3mm copper flats for Transformer and Generator body, structure and LT Panel body earthing
55925 x 6mm copper flats for 1000 KVA Transformer , DG neutral earthing
5608 SWG bare Copper conductor for fencing earthing
56110 SWG copper wire
562Jumbering with O SWG copper
563cable route marker with cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required
564SAFETY EQUIPMENTS
565Supply and Installation of Danger Boards 11000 V (Stove enameled) as per EB standards.
566Supply and Installation of Danger Boards 415 V (Stove enameled) as per EB standards.
567Supply and fixing of GIfire buckets with round bottom, each set comprising 4Nos.fire buckets of 9Kg capacity including supply of M.S pedestal stand with hooks suitable for holding of 4Nos of fire buckets, painted with Post Office Red oil paint and letter FIRE on each bucket and filling with sand complete as required. .
568Supply and laying of 12mm thick 1000mm wide chequered rubber mat with ISI mark suitable for 440V installation .
569First Aid Box with stand.
570Shock Treatment Chart in 2 Language (Local Language and English)
57111kv highly insulated fiber glass FRP EARTH / DISCHARGE ROD KUSAM MECO MAKE Or eqvt-03x5feet-assembled height 15 feet-30mm diadie cast alum earthinginstrument to grip , 7/20 cu wire -7m,rubber hand grip 2 set, with canvas cover for carrying, Die cast alu. Grounding “C” Clamp as spare
572L.T. SWITCHGEAR
573A) Incomer - 1For Transformer 1,1600 AMPS EDOACB, WITH NC 50 KA (Ics) AC Motor operated with \"Draw Out ( EDO )Type Four Pole Microprocessor based release with communication port RS485 \"having Over current, 2no /nc cotacts,2a control fuse with base neutral link\" short circuit with time setting and \"6NO + 6 NC,indication for test,service,isolated ON \"/OFF trip indications, on delay timer \"MFMMANAGER (A+V+HZ,KW,KVA,PF,KWH), CTR: =/5A, PORTFOR TR I/C .-EMIFIXVI FPE(\"EMIFIX VIFPE) \"Shutter Assembly,Racking interlock Manual /Electrical \"closing& tripping , REVERSE POWER RELAY, ANNUNCIATION PANEL as specified in the technical Specifications.Annunciation panels-2 nos A) Incomer - 1 and 2No. FROM DG :EACHwith\"ACB, 1600A, 50 KA,4 POLE ,EDO WITH NC (ELECTRICALLY OPERATED DRAWOUT) WITH MICROPROCESSOR BASEDRELEASE FOR O/L, S/C & E/F PROTECTION AUX CONTACT ON DELAY TIMER(\"E-MAX ( WITH PR-121 RELEASE) \"ACEESORIES FOR DG I/C ACBs :\"UNDER VOLTAGE, CLOSING COIL , SPRING CHARGING MOTOR- 240V AC & SHUNT TRIP COIL-24V DC \"METERING FOR D.G. I/C \"KWH METER WTH SEALING ARRANGEMENT CTM(\"CTM) \"MFMMANAGER (A+V+HZ,KW,KVA,PF,KWH), CTR: =/5A, PORTFOR DG I/C .-EMIFIXVI FPE(\"EMIFIX VIFPE) \"PROTECTION RELAYS :TNC SWITCH AM SWITCH, REVERESE POWER RELAY \"EARTH FAULT RELAYCDG11,64R,MRA 4 RELAYDIFFERENTIAL RELAY,AUTO SYN RELAY,UNDRER OVER VOLTAGE RELAY(\"CDG1/MC12) \"CURRENT TRANSFORMER \"CURRENT TRANSFORMER,1600/5A, CL-1, 5VA FOR METERING ( 3 Nos. FOR ECAH PANEL)(\"BPL (TAPE WOUND )) \"CURRENT TRANSFORMER, 1600/5A, CL-5P10, 7.5VA CL-5P10 FOR E/F RELAY REVERRSE POWER REALY LVM(\"BPL (TAPE WOUND )) \"EF RELAY,DIFFERENTIAL RELAY,AUTO SYN RELAY UNDER OVER VOLTAGE RELAY \"FUNCTION SPD WITH 160A FUSE \"
5744Sets of 50 KVAR Capacitor(2 x 25 KVAR) with suitable 200A TP MCCB with all other required necessary accessories, Cap.Duty Contactors,, control fuses, On,Off & Trip Indicating Lampsetc.,Including interconnection busbars, control wiringwith all other required necessary accessories.(One set spare) as per schematic, 4Set of 25 KVAR Capacitor(1 x 25 KVAR) with suitable 100A TP 36KA MCCB with all other required necessary accessories, Cap.Duty Contactors, control fuses, On,Off & Trip Indicating Lampsetc.,Including interconnection busbars, control wiringwith all other required necessary accessories. as per schematic.2Set of 10 KVAR Capacitor(1 x 10 KVAR) with suitable 40A TP 36 KA MCCB with all other required necessary accessories, Cap.Duty Contactors, control fuses, On,Off & Trip Indicating Lamps etc.,Including interconnection busbars, control wiringwith all other required necessary accessories as per schematic.4Set of 5 KVAR Capacitor(1 x 5 KVAR) with suitable 40A TP 36 KA MCCB with all other required necessary accessories, Cap.Duty Contactors, control fuses, On,Off & Trip Indicating Lamps etc.,Including interconnection busbars, control wiringwith all other required necessary accessories as per schematic.(One set spare) as per schematic,Each capacitor bank in a separate compartment with necessary ventilation arrangements as required by the Electrical Authorities .COPPER BUSBARS
575DG ISOLATIONPanel -OUTDOOR WITH ENCLOSURE Incoming WITH CT PROVISION 630 A 4P ACB Not less than 50 KA with necessary accessories CT, control wiring etc.- 1 No. as incomer.
576SSB-GFDesign, supply, erection, testing and commissioning of cubicle type floor mounting panel board made out of MS sheet enclosure with Copper busbars, single busbar system, cable chamber, protection relays, interconnection, painting, earthing etc. comprising of the following.IncomingWITH250A, TPN, 35kA, MCCB - 1No.The incomer shall have,1 set –Digital Comibined meter having the parameters of Ammeter,Voltmeter and Energy meter1 set –200/5A CT CL 1, 10VA“ON/OFF & TRIP,\"RYB\" indicating lamp and also refer the schematic drawing.240Amps TPN cu. busbars: Current density consider 1.2Amp/1Sq.mm.Earthing : 50 x 6mm GI flatOutgoing100A, TPN, 16kA, MCCB - 2Nos.63A, TPN, 16kA, MCCB - 8Nos.All outgoing feeders shall be having \"ON,OFF&TRIP and \"RYB\" indication lamps.Note:With necessaryCOPPER. busbars, interconnection providing multifunction meter ,phase indication lamp, fuse and switch control etc. in theincomer. All switch boards shall be fabricated as per the detailed specification enclosed.Cable Entry: Top/BOTTOMCable Gland Plate: 3mm thick MS sheets.Note: Incomer/Outgoing MCCB shall have rotary handle mechanism and spreader wherever necessary.
577UTILITY Design, supply, erection, testing and commissioning of cubicle type floor mounting panel board made out of MS sheet enclosure with Copper busbars, single busbar system, cable chamber, protection relays, interconnection, painting, earthing etc. comprising of the following.Incoming 250A, 4P, 35kA, MCCB - 1No.The incomer shall have,1 set –Digital Comibined meter having the parameters of Ammeter,Voltmeter and Energy meter1 set –200/5A CT CL 1, 10VA“ON/OFF & TRIP,\"RYB\" indicating lamp and also refer the schematic drawing.250Amps TPN copper. busbars: Current density consider 1.2Amp/1Sq.mm.Earthing : 50 x 6mm GI flatOutgoing160A, TPN, 16kA, MCCB - 4Nos.100A, TPN, 16kA, MCCB - 2No.63A, TPN, 16kA, MCCB - 4Nos.All outgoing feeders shall be having \"ON,OFF&TRIP and \"RYB\" indication lamps.Note:With necessary cu. busbars, interconnection providing multifunction meter ,phase indication lamp, fuse and switch control etc. in theincomer. All switch boards shall be fabricated as per the detailed specification enclosed.Cable Entry: Top/BOTTOMCable Gland Plate: 3mm thick MS sheets.Note: Incomer/Outgoing MCCB shall have rotary handle mechanism and spreader wherever necessary.
578HVACPANEL-1 OUTDOOR -supply, installation, Testing and Commissioning ofPANEL floor mounting type, dust and vermin proof by construction of 14 SG CRCA sheets with bolted construction, cable entry & exit provision for bottom/top, powder coated panel, surge arrester (1No) as per tender technical specification and the details mentioned below.INCOMER:- 1 No –400A 4PMCCB TPN 36 KA OL ,SC RELEASES with FD KIT1 Set –400/5A CT CL 2, 15VA for metering,1 No. –Digital type Ammeter (0-400A) with selector switch,1 No. –Digital typeVoltmeter (0-500V) with selector switch,1 Set –LED type RYB indication lamp with control MCBs,1 Set –LED type ON/OFF indication lamp with control MCBs.OUTGOING:-10 nos 63A TPN MCCB,-,BUS BAR RATING: One set:400A TPN 36KA for 1 sec. cu. bus bars with colour coated heat shrinkable PVC sleeves with DMC/SMC bus bar supports and suitable earth bus.PH:1R40x10mmAL.Flat,N: 1R 25 x 10mm AL.Flat,E: 1R 25x3mm Cu.Flat,Cable gland plates- Al 3mmthick,CABLE ENTRY & EXIT : TOP/BOTTOM
579HVACPANEL-2 OUTDOOR -supply, installation, Testing and Commissioning ofPANEL floor mounting type, dust and vermin proof by construction of 14 SG CRCA sheets with bolted construction, cable entry & exit provision for bottom/top, powder coated panel, surge arrester (1No) as per tender technical specification and the details mentioned below.INCOMER:- 1 No –630A 4PMCCB TPN 36 KA OL ,SC RELEASES with FD KIT1 Set –630/5A CT CL 2, 15VA for metering,1 No. –Digital type Ammeter (0-630A) with selector switch,1 No. –Digital typeVoltmeter (0-500V) with selector switch,1 Set –LED type RYB indication lamp with control MCBs,1 Set –LED type ON/OFF indication lamp with control MCBs.OUTGOING:-10 nos 63A TPN MCCB,-,BUS BAR RATING: One set:630A TPN 36KA for 1 sec. CU. bus bars with colour coated heat shrinkable PVC sleeves with DMC/SMC bus bar supports and suitable earth bus. 630A CU BUSBARS,E: 1R 25x3mm Cu.Flat,Cable gland plates- Al 3mmthick,CABLE ENTRY & EXIT : TOP/BOTTOM
580LIFTPANEL OUTDOOR -supply, instCulation, Testing and Commissioning ofPANEL floor mounting type, dust and vermin proof by construction of 14 SG CRCA sheets with bolted construction, cable entry & exit provision for bottom/top, powder coated panel, surge arrester (1No) as per tender technicCu specification and the details mentioned below.INCOMER:- 1 No –160A TPN MCCB 36 KA OL ,SC RELEASES with FD KIT1 Set –160/5A CT CL 2, 15VA for metering,1 No. –DigitCu type Ammeter (0-160A) with selector switch,1 No. –DigitCu typeVoltmeter (0-500V) with selector switch,1 Set –LED type RYB indication lamp with control MCBs,1 Set –LED type ON/OFF indication lamp with control MCBs.OUTGOING:3SETS EACH CONSISTS OF 1no63A TPN MCCB,1NO 20A DP RCCB-WITH 3 NOS6A SP MCB AND 6/16A SOCKET 1NOWITH SWITCH,BUS BAR RATING: One set:160A TPN 36KA for 1 sec. Cu. bus bars with colour coated heat shrinkable PVC sleeves with DMC/SMC bus bar supports and suitable earth bus.PH:1R20 x 10mm Cu.Flat,N: 1R 25 x 10mm Cu.Flat,E: 1R 25x3mm Cu.Flat,Cable gland plates- Cu 3mmthick,CABLE ENTRY & EXIT : TOP/BOTTOM
581LIFT isolation panel-INCOMER:- 1 No - 63A TP+N 35KA MCCBLED type RYB indication lamp with control 25a dp MCBs,enclosure.RCBO 4p 63a,busbar and busbar chambers,fabricted box
582PUMP PANEL -supply, instCulation, Testing and Commissioning ofPANEL floor mounting type, dust and vermin proof by construction of 14 SG CRCA sheets with bolted construction, cable entry & exit provision for bottom/top, powder coated panel, surge arrester (1No) as per tender technicCu specification and the details mentioned below.INCOMER:- 1 No –160A 4PMCCB TPN 36 KA OL ,SC RELEASES with FD KIT1 Set 160/5A CT CL 2, 15VA for metering,1 No. –DigitCu type Ammeter (0-160A) with selector switch,1 No. –DigitCu typeVoltmeter (0-500V) with selector switch,1 Set –LED type RYB indication lamp with control MCBs,1 Set –LED type ON/OFF indication lamp with control MCBs.OUTGOING:-6 nos 32A TPN MPCB with DOL starter, 4 nos 32A TPN MCCB with ,-,BUS BAR RATING: One set:200A TPN 36KA for 1 sec. Cu. bus bars with colour coated heat shrinkable PVC sleeves with DMC/SMC bus bar supports and suitable earth bus.PH:1R25 x 10mm Cu.Flat,N: 1R 25 x 10mm Cu.Flat,E: 1R 25x3mm Cu.Flat,Cable gland plates- Cu 3mmthick,CABLE ENTRY & EXIT : TOP/BOTTOM
583STP PANEL -supply, instCulation, Testing and Commissioning ofPANEL floor mounting type, dust and vermin proof by construction of 14 SG CRCA sheets with bolted construction, cable entry & exit provision for bottom/top, powder coated panel, surge arrester (1No) as per tender technicCu specification and the details mentioned below.INCOMER:- 1 No –100A 4PMCCB TPN 36 KA OL ,SC RELEASES with FD KIT1 Set 100/5A CT CL 2, 15VA for metering,1 No. –DigitCu type Ammeter (0-100A) with selector switch,1 No. –DigitCu typeVoltmeter (0-500V) with selector switch,1 Set –LED type RYB indication lamp with control MCBs,1 Set –LED type ON/OFF indication lamp with control MCBs.OUTGOING:-4 no32A TPN MCCB,1 NO 63A TPN MPCB WITH DOL STARTER,-,BUS BAR RATING: One set:120A TPN 36KA for 1 sec. Cu. bus bars with colour coated heat shrinkable PVC sleeves with DMC/SMC bus bar supports and suitable earth bus.PH:1R25 x 10mm Cu.Flat,N: 1R 25 x 10mm Cu.Flat,E: 1R 25x3mm Cu.Flat,Cable gland plates- Cu 3mmthick,CABLE ENTRY & EXIT : TOP/BOTTOM
584SSB-:(SSB-typical for GF AND 1TO 3)Design, supply, fixing, testing and commissioning of cubicle type floor mounting switch board comprising of the following, the board shall be fabricated as per the detailed specification enclosed A) Incomer 1& 2 :1Nos 160 Amps Fourpole Type Motorized MCCB with Autimatic Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L andfixed Magnetic S/C Protection.There shall be one set of Metering Compartment incorporated with the following:-1No - Class 2.0,Digital Dual source MultifunctionMeter with Inbuilt Selector Switch,communication port RS 485 having MODBUS Protocol with control fusese etc.3Nos. - 160/5A CL-0.2,15VA current transformer with CT short link terminal block for Multi function Meter1Set. - 3Nos.ofR,Y,Bphase indicating lamps, On, Off, Trip Indication lamp with protection fuse for potential circuit.1Set of ELR 100mA with CBCT to be provided for incomer feeder.
585Continue aboveB) Outgoing :4 Nos 160 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L andfixed Magnetic S/C Protection with Suitable Class 0.2,Digital Dual source MultifunctionMeter with Inbuilt Selector Switch,suitable rating of CTs and communication port RS 485 having MODBUS Protocol with control fusese etc.1 Nos 125 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating withadjustable Thermal O/L andfixed Magnetic S/C Protection.Digital Dual source MultifunctionMeter with Inbuilt Selector Switch,suitable rating of CTs and communication port RS 485 having MODBUS Protocol with control fuses etc.2 Nos 63 Amps TP&N MCCB with Manual Closing Mechanism of 35 kA Short Circuit Rating with adjustable Thermal O/L andfixed Magnetic S/C Protection.Digital Dual source MultifunctionMeter with Inbuilt Selector Switch,suitable rating of CTs and communication port RS 485 having MODBUS Protocol with control fusese etc.C) Busbar :160A TPN 35KA Copper Busbar with heat shrinkable colour insulated PVC sleeves and provide 1NO+1NC contact in the incomer feeder for BMS status.Current density - 1.2Amps/Sqmm.
586FLOOR AHU PANEL-Design,Manufacture,supply, installation,Testing, Commissioning and earthing of thepanel-with necessary metal base frames, free standing dust and vermin proof byConstruction of 14 / 16 SWG CRCA sheets with bolted construction powder coated panel incoming and outgoing breaker details as per the technical specification, SLD & as mentioned below1 NO -40 A TPN MCB,O/G 40A TPN MCB 3 NOS- RYBIndication Lamp and Power& control terminal Terminal block
587Treated fresh airunits panel-TERRACEINCOMER:-1 No - 100A TP+N 25KA MCCB 2 No - 32A TP+N 25KA MPCBas outgoing feeders WITH 7.5 kw motor SD starters 3 No - 32A TP+N 25KA MPCBas outgoing feeders WITH 5.5 /3.7kw motor DOL starters LED type RYB indication lamp with control MCBs.
588Cable adopter box(to be provided near the chiller with suitable bus bar extension for the incoming and outgoing feeders with 6 runs of 3.5cx300sqmm XLPE Al.Ar. ) and connected to chiller
589MCB, ISOLATORS, MCCB
590Supply,installation,testing andcommissioningofthe followingMCCBs / MCBs / ISOLATORs / STARTERs of type-II coordination etc.in manufacturer\"s sheet steel enclosures, IP 20 Protection, fixed on the concealed wall including all interconnections and accessories. Supply, Installation, testing and commissioning of of cubicle type floor mounting/wall mounting isolator panel. The rate shall be inclusive of suitable MS angle ion standand suitable size enclosure with adopter boxes for cable termiantion,spread bar,etc.
59125A DP MCB along with moulded front plate in GI anodized box
592100A TPN Isolator(MCCB type)with enclosure for ups/VRF
59363A TPN Isolator(MCCB type)with enclosure for ups /VRF
59440A TPN(MCB type)
59563A TPN RCCB 300MA IP66with metal power coated steel enclosureforVRF
596DISTRIBUTION BOARDS
597VTPN 6 WAY (Vertical TPN) MCCB INCOMER DB: Supply, fixing, testing and commissioning of the double door type VTPN 8 way MCCB DB comprising of the following :INCIMER: 100A TPN MCCB 16 KA – 1No. as incomer with ELMOUTGOING:40A TP MCB 10kA (C-Curve) – 6 Nos..as outgoings.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases.The board shall be powder coated type fixed with concealed system in wall/ fixed in column.The rate shall include necessary connected civil works like chipping, rough plastering etc.
598LDB - 4 WAY (7 segment) MCB INCOMER DB: Supply, fixing, testing and commissioning of the double door type compartmental Phase segregated 8way MCB DB comprising of the following :INCIMER: 40A 4P MCB 10kA with all necessary connected accessories – 1No.25A DPMCB WITH 25A DPRCBO 30 mA – 3 Nos. as individual phase incomersOUTGOING:Each 25A DP RCBO outgoing consist of 4nos.6\16\20 A 10KASP MCB (C-Curve) in a separate compartment with necessary phase segregation as required by the Electrical Inspectorate.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases.The board shall be powder coated type fixed with concealed system in wall/ fixed in column.The rate shall include necessary connected civil works like chipping, rough plastering etc.
599PDB - 4 WAY (7 segment) MCB INCOMER DB: Supply, fixing, testing and commissioning of the double door type compartmental Phase segregated 8way MCB DB comprising of the following :INCIMER: 63A TPN MCB 10kA with all necessary connected accessories – 1No.32A DP RCBO 100 mA – 3 Nos. as individual phase incomersOUTGOING:Each 40A DP ELCB 100MAWITH 40A DP MCB outgoing consist of 4nos.6\16\20 A 10KASP MCB (C-Curve) in a separate compartment with necessary phase segregation as required by the Electrical Inspectorate.With necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases.The board shall be powder coated type fixed with concealed system in wall/ fixed in column.The rate shall include necessary connected civil works like chipping, rough plastering etc.
600UPSSPN DB : Supply, fixing, testing and commissioning of the Singledoor type compartmental8 way MCB DB comprising of the following :INCIMER: 1no - 16/40A DP RCBO, 1 No. OUTGOING: 6 Nos 6\16\20a 10 KA MCB
601SPN DB : Supply, fixing, testing and commissioning of the Singledoor type compartmental8 way MCB DB comprising of the following :INCIMER: 1no - 16/40A DPMCB, 1 No. OUTGOING: 6 Nos 6\16\20a 10 KA MCB
602LDB-STREET LIGHT/ SECURITY ROOM: Supply, fixing, testing and commissioning of the double door type compartmental Phase segregated 4 way MCB DB comprising of the following :INCIMER: 1no - 63A TPN MCB, 1 No. 0-24 Hrs. timer with contactor OUTGOING: 2nos - 16/63A TP EL+MCB, 6nos - 6/10A DP EL+MCBWith necessary tinned copper busbars, interconnections, separate earth bus, separate neutral bus for each phases.The board shall be powder coated type fixed with concealed system in wall/ fixed in column.The rate shall include necessary connected civil works like chipping, rough plastering etc.
603CABLES AND TERMINATION
604For all items in section-D, the rate includes necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the sameSupply and Laying of following size PVC/XLPE (FR-LS) insulated outer sheathed (1100 V grade) copper/aluminium armored & un armored conductor cable partly laid incable tray and partly laid in wall/ ceiling with suitable individual clamps at every 1 mtr interval . Cable tray will be measured and paid separately. Cable Tags to be provided at every 50mtr interval and at either side of the bends.Only for Lighting cables cable tie will be permitted other cables clamps to be provided
6053.5 Core 300 Sq.mm XLPE Aluminium armoured Cable
6063.5 Core 185 Sq.mm XLPE Aluminium armoured Cable
6073.5 Core 120 Sq.mm XLPE Aluminium armoured Cable
6083.5 Core 95 Sq.mm XLPE Aluminium armoured Cable
6094 Core 25 Sq.mm XLPE Aluminium armoured Cable
6104 Core 16 Sq.mm XLPE Aluminium armoured Cable
6114 Core 10 Sq.mm XLPE Copper armoured Cable
6124 Core 6 Sq.mm XLPE Copper armoured Cable
6134 Core 4 Sq.mm XLPE Copper armoured Cable
6143 Core 4 Sq.mm PVC Copper armoured Cable
615Supply, Fixing of Termination kit(Glands & lugs) of the following size cables with suitable double compression glands with suitable crimping socket. The rate shall be inclusive of Gland Earthing Plate Prefabricated as per Gland Size with provision for connecting Cu.SWG and Cable Tags should be engraved type for all I/C,O.G& lighting Circuits (copper sockets for copper cables and Alu. Sockets for alum. Cable)
6163.5 Core 300 Sq.mm XLPE Aluminium armoured Cable
6173.5 Core 185 Sq.mm XLPE Aluminium armoured Cable
6183.5 Core 120 Sq.mm XLPE Aluminium armoured Cable
6193.5 Core 35 Sq.mm XLPE Aluminium armoured Cable
6204 Core 25 Sq.mm XLPE Aluminium armoured Cable
6214 Core 16 Sq.mm XLPE Aluminium armoured Cable
6224 Core 10 Sq.mm XLPE Copper armoured Cable
6234 Core 6 Sq.mm XLPE Copper armoured Cable
6244 Core 4 Sq.mm XLPE Copper armoured Cable
6253 Core 4 Sq.mm PVC Copper armoured Cable
626TRENCHING AND EXCAVATION
627Excavating the ground for a Depth of 0.75 Mtrs for LT cables with required widthfor laying the LT Cables. After filling the excavated trench with sand of 150mm before and after laying cable Including supply,erecting brick laying over thecables This excavation will be measured for each route only- not for each cables
628Excavation of hard Rock, Removal of Soil,Back filling and restoring to normal state. the following size cable trench in soft soil including excavation, river sand cushioning (150mm thick both at top and bottom of the cable), back filling, ramming and compacting the soil,etc., as required.(600mm depth,300mm width for street light)
629Supply, laying of 100mm dia HDPE Pipe flexiblelayed /clamped in the existing wall/ground with suitable supportsfor street light cable
630Supplying, fixing, HT/ LTcable route markers with 10 cm x 10 cm x 5mm. thick CI plate with inscription thereon,bolted / welded to 35mm x 35 mm x 6 mm. angle iron , 60 cm. long andfixing the same in ground as required.The cable route marker shall be fixed at both the ends of cable at joints and at 100 Mts. spacing for straight runs.
631WIRING - CIRCUIT CUM POINT WIRING The rates for all point wiring items shall also includesupplying and fixing of the Conduits,conduitspecials, bushes and other fittings,Approved GI saddles and grouting thesame for exposed conduit work,2 mm thick Outlet boxes and junction box,All fixing accessories such as clips, brass screws etc,Allwork & materials necessary for wiring a point circuit of anylengthfromtheFinal DistributionBoardto connectorviaswitch and shall include thecircuitwiring also except where identified.
632Primary Light / Fan Point Wiring: Supply, wiring, connecting& commissioning of 3Runs1.5 Sq.mm. (Ph, Neutral & Earth) PVC insulated multistrandedHR-FRLSH-LFcopper wires in 1.8mm thick MS conduits fixed on ceiling partly and1.8 mm thick PVC conduit concealed in the wall partly with necessary clamps, screws, etc., as required as per the site condition including supplying and fixing of modular 6A One way switch along with moulded front plate in GI anodised manufacturer\"s mounting box-Flat switches with indication fixed flush with the wall complete with all accessories including 3 plate ceiling rose.NOTE: Above false ceiling when it is open wiring it should be of MS conduit
633Secondary Light Points: The secondary light points will have to be wired from the primary light point as mentioned above.
634Lighting Circuit Mains: Supply and laying of 3 Runs2.5 Sq.mm. (Ph, Neutral & Earth) PVC insulated multistrandedHR-FRLSH-LFcopper wires in 1.8mm thick MS conduits fixed on ceiling partly and1.8 mm thick PVC conduit concealed in the wall partly with necessary clamps, screws, etc., as required as per the site condition., from LDB to Lighting Switch Boards and MCB to First Light Point.
635TWO-WAY POINTSSITC of Concealed Point wiring (from Switch board) including Concealed Circuit Wiring (from DB to switch board) for two way like staircase points after cutting grooves on wall/ RCC, neatly filling the grooves with cement mortar,making good thereof, etc. using 3 x 1.5 Sq. mm.heavy duty PVC insulated copper conductor stranded cable (1 for earthing),2 Nos. Modular 2-way switch complete with non metallic inner & outer plates, suitable metal boxes, etc,IS marked(IS 9537 Part-3) suitably sized heavy duty rigid concealedMS conduits (20mm min), Saddles, junction boxes, bends, other accessories, ceiling roses, etc.
636Ceiling Fan Points: Supply,installation,testingand commissioning of ceiling fan points same asPrimary Light Point Wiringbut for ceiling fan points including supplying and fixing concealed type fan hook box and supply and fixing of electronic type 300W fan step regulator with moulded front plate in GI anodised manufacturer\"s mounting box fixed flush with the wall complete with all accessories as required as per the site conditions.
637Ex Fan Points: Supply,installation,testingand commissioning of Ex-fan points same as Primary Light Point Wiringbut for exhaust fan points including supplying and fixing one no 6A switch with indicator in switch board and one no 6A socket near Exfan location in wallwith moulded front plate in GI anodised manufacturer\"s mounting box fixed flush with the wall complete with all accessories as required as per the site conditions. in MS conduits
638Emergency Lighting Circuits: Supply and laying of 3 Runs1.5 Sq.mm. (Ph, Neutral & Earth) PVC insulated multistranded FRLS copper wires in 1.8mm thick MSconduits fixed on ceiling partly and1.8 mm thick PVC conduit concealed in the wall partly with necessary clamps, screws, etc., as required as per the site condition.,from ELDB to Emergency Light fittings.
639Wiring for Lift Well Light Point and socket oulet with 2 x 1.5 sqmm FRLS PVC insulated Stranded Copper Conductor Cable along with 1 x 1.5 sqmm FRLS PVC insulated Stranded copper conductor cable as earth wire in surface MSconduit including providing and fixing Galvanised / Cadmium plated MS switch box, 2 no 6ASingle Way Modular Switch for (controlling light point and socket Outlet) , 1 No 6 A 5 Pin shuttered modular socket outlet with modular switch plate and making necessary connections etc., as per specification (5 Meters shall be considered for Wires & conduit per point.)
640Primary Light / Fan Point Wiring: Supply, wiring, connecting& commissioning of 3Runs1.5 Sq.mm. (Ph, Neutral & Earth) PVC insulated multistranded FRLS copper wires in1.8 mm thick PVC conduitwith necessary clamps, screws, etc., as required as per the site condition including supplying and fixing of modular 6A One way switch along with moulded front plate in GI anodised manufacturer\"s mounting box fixed flush with the wall complete with all accessories including 3 plate ceiling rose.
641Secondary Light Points: The secondary light points will have to be wired from the primary light point as mentioned above.
642Providing and fixing/ laying of conduit and wires for Light point wiring with 1.5 sq. mm PVC insulated, FRLS, copper conductor (stranded) 1100V grade wires alongwith earthing in 25mm dia. medium duty PVC concealed conduit system including providing and fixing one no. 10 Amp single pole modularswitch grid plate mounted with moulded cover plate in zinc chromate passivated GI box suitable for modular switch, complete in all respect (wiring & conduiting up to switchboard not included in item cost), for controlled by 2 nos. 2 way switch. Including making zaries in the wall and finishing the same
643Lighting Circuit Mains: Supply and laying of 3 Runs2.5 Sq.mm. (Ph, Neutral & Earth) PVC insulated multistrandedHR-FRLSH-LFcopper wires in1.8 mm thick PVC conduit concealed in the wall partly with necessary clamps, screws, etc., as required as per the site condition., from LDB to Lighting Switch Boards and MCB to First Light Point.
644Providing and fixing/ laying of conduit and wires for Ceiling fan point wiring with 1.5 sq. mm PVC insulated, FRLS, Cu. conductor (stranded) 1100V grade wiresalongwith earthing in 25 mm dia. Medium duty PVC surface/ concealed conduitsystem including providing and fixing one no. modular 10A single way switch, grid plate mounted with moulded cover plate, two module electronic stepped fan regulator in zinc chromate passivated GI box suitable for modular switches, with GI box for fan suspension, complete in all respect. Including making zaries in the wall and finishing the same
645Providing and fixing/ laying of conduit and wires for Exhaust / Brackat fan pointwiring with 1.5 sq. mm PVC insulated, FRLS, Cu. conductor (stranded) 1100Vgrade wires alongwith earthing in 25 mm dia. Medium duty PVC surface/ concealed conduit system including providing and fixing one no. modular 10A single way switch, grid plate mounted with moulded cover plate in zinc chromate passivated GI box suitable for modular switches complete in all respect.Including making zaries in the wall and finishing the same
646Emergency Lighting Circuits: Supply and laying of 3 Runs1.5 Sq.mm. (Ph, Neutral & Earth) PVC insulated multistranded FRLS copper wires in 1.8 mm thick PVC conduit concealed in the wallwith necessary clamps, screws, etc., as required as per the site condition.,from ELDB to Emergency Light fittings.
647SOCKETS
648Supply, Installation, testing and commissioning of 1 no 6A Universal switched socketand withmoulded frontplate, GIanodised enclosure, and mounting box in the wall(concealed/open)andother associated accessories including chasing embeddingrough plastering as required as per the site conditions forpower points.
649Supply, Installation, testing and commissioning of 1 no 6/16A universal switched socket and withmoulded frontplate GIanodised enclosure in the wall/floor(concealed/open andother associated accessories including chasing embeddingrough plastering as required as per the site conditionsforpower points.
65016 A SOCKET: Supply, Erection,Testing and commissioning of 16 A Socket.Make : WIPRO
651Supply, Erection,Testing and commissioning of 32A 3Phase Metal clad plug and socket with 32 A TP MCB as control with enclosure,Plug top cover and connected accessories . Legrand cat no 056614
652Supply and installation of Power supply cables for various instruments, data converters, data logger,control room equipment etc connected to Energy management system.
653Supply & Laying of 2R 4 sq.mm and 1R 2.5 Sq.mm. PVC insulated FRLS multistranded cu wires 20mm dia 2 mm thick MS conduit with all accessories as reqd. (From DB to 6/16A Power Sockets / 20A Metal clad plug & sockets.).
654Supply & Laying of 2R 4 sq.mm and 1R 2.5 Sq.mm. PVC insulated FRLS multistranded cu wires 20mm dia 2 mm thick PVC conduit with all accessories as reqd. (From DB to 6/16A Power Sockets / 20A Metal clad plug & sockets.).
655Supply & Laying of 2R 2.5sqmm and 1R 2.5 Sq.mm. PVC insulated FRLS multistranded cu wires in the 20mm dia 2mm thickMS conduits with all accessories as reqd. (From DB to 6A Switch & Sockets)
656Supply & Laying of 2R 2.5sqmm and 1R 2.5 Sq.mm. PVC insulated FRLS multistranded cu wires in the 20mm dia 2mm thick PVC conduits with all accessories as reqd. (From DB to 6A Switch & Sockets)
657LIGHT FITTING
658Supply, Erection, testing and commissioning of2X2 36W LED lightfittings with all accessories along with lamp, driverand fixing the same in theceiling with wooden blocks, screws ,hardwares as required as per the site condition-recess mounted -(Ref cat no - (Crompton -CCR-127-36-57-SL-NWH) or eqvt
659supply erection and testing and commissioning of Recess mounted type - CROMPTONSQUARE -18WATTS -(CDR-206-18-30-SL-NWH) or eqvt
66020W TUBE
661Supply, Erection, testing and commissioning ofSurface mountedlight fitting with 12w LED Lampsand fixing the same in ceiling with all accessories like clamps, supporting brackets, hardwares as required as per site condition. (CAT Ref. No. Crompton LSCSM12W CDL NW/WW
662Supply of surface LED downlighter system wattage not more than 36W and luminaire lumens not less than 1200 lumens. The system efficacy shall be > 100 lm/W, cut out dia shall not greater than 85mm. The housing shall be die-cast aluminium with deep recessed optics with low glare and reflecter shall be matt black in color. Luminaire shall be compatible to access/replace the LED moudle without removing the trim from the ceilng. LED make: that satisfies IEC62471 Photobiological/RoHS Standards with and LED Efficacy of > 130lm/W,Colour Temperature-4000K or Higher with LED binning as per ANSI Bin C78.377A, 120Deg LED Beam Angle, CRI > 90, Life of LED as per L70 > 50000burning hours, Ambient temp-0 to 50DegC, Driver efficiency>85%, THD<10%, Power factor>0.95, Inbuilt Surge protection in CM = 2.5KV, LED Driver with Voltage range 150-270V AC andSafety Extra Low Voltage Safe level<60V DC as per IEC standard, Electrical Safety with Class 1 Insulation. Luminaire shall be BIS compliance.Driver shall be compatible for auto cut off and restart with deviation to operating voltage also the ripple shall be less 5% CAT REF.NO :LCTLSNE-36-FO-WW OREQVT
663Supply, Installation, including assembling, testing and commissioning of Wall mounted down light fitting with 9W or 10W LED lamps and sutable drivers for Mirror light fitting.
664Supply, Erection, testing and commissioning of Cove/Strip light with 1 x 20WEACH 5M LED COOL white with driver and with all accessories and interconnecting with 3 core 1.5 sqmm PVC insulated multistrand wires and accessories as required.Crompton cat no LST20CDL/BL/WW
665Orient Electric 10W LED Inverter Emergency Batten (White, Square)
666Low glare, height efficiency SURFACE mounted LED down light - CIRCULAR profile-LCRP-10-CDL( Royal Rimless)
667Supply, Installation, testing and commissioning ofCrompton Energion HS 1200 mm (48 inch) Energy Efficient 5 Star Rated High Speed BLDC Ceiling Fan sweep Ceiling fanand fixing the samewith extended rod from roof, required clamps,bolts,fan hook , screws ,hardwares as required as per the site condition -BEE 5 Star rated white colour doubl
668Supply and installation of 3WEXIT/ toilet double sided signageLIGHT 180 min back uppolite auto glo ip 44or eqvt with CABLE and 5a pin incl hanging arrangement cat no LED EM(S)
669Supply erection of Integral decorative LED bollard with opal acrylic with IP65 Protection-Bajaj cat no BGBOM 650 9W LED ww - or eqvt incl concrete foundation as per item no 176, incljunction box WIPRO LB14-880-XXX-65-05
67015W LED TRACK LIGHT FOR RECEPTION-WIPRO LD 57-251-036-40-XX OR EQVT with aluminium support accessories
67128/36W LED Suspended type linear in sleek designCROMPTON LCLP54-72-CDLN OR EQVT
672Hyper FREQUENCY MOTION SENSORS-HAGER EE883 OR EQVT
673CABLE TRAYSSupply and erection of following size 2mm thickLadder type,Pregalvanized, cable trays and cable tray of rolledGI Sheet, supports out sections, pipes, plates, etc. including welding, anchor bolts, threaded down rods(for 300 mm trays only), supply of necessary anchor bolts and grouting etc. including breaking walls, floors, etc. for structures as required including supply of all GI hardware materials, all labour and materials complete as per approved drawings, specifications of this tender and directions of Engineer-in-charge.The rate shall include supply & fixing of MS Grip bolts in columns/beams/walls/ceiling etc.as required & including drilling also. Rod supports shall be of galvanized full threaded rods of sizes 8,10 & 12mm dia for fixing to anchor fastener, anchor bolts.The length of the full threaded rods for the purposes of quoting shall be 1200 mm & includes nuts & washers and supports shall be at a min.distance of 1Mtr.The rate will include all required bends, tees, vertical up & downs, radius bends and other applicable accessories shall be factory fabricated, complete & as required. The rate shall inclusive of necessary theaded rods,nuts & bolts, making clamp in the Z perlin/Truss, cable tray clamps etc,(8 mm threaded rod shall be providedat every alternative purlin appx. 2 mtr length)
674600 x 70mm x2mmLadder type cable trays
675300 x 50mm x2mm Ladder type cable trays
676150 x 50mm x2mmLadder type cable trays
677Supply and fixing of Perforated Cable tray WITH COVER AND with horizontal & vertical bends, reducers, Tee\"s, cross over , suitable supports and brackets and other accessories as required confirming to IEC-61537. The Tray shall be galvanized for corrosion protection confirming to DIN EN 10346 / ISO 1461 .The trays should be tested for a safe working load of 150 Kgs with a span distance of 1.5 meters and the deflection should be within the limits as per standard. The safety factor shall be 1.7 times of the safe working load. The perforated tray shall be supplied with the standard length of 3 Mtr . incl cover for vertical areas The rate shall inclusive of necessary theaded rods,nuts & bolts, making clamp in the Z perlin/Truss, cable tray clamps etc,(8 mm threaded rod shall be providedat every alternative purlin appx. 2 mtr length)
678450 mm width X 62.5 mm depth X 2.0 mm thickness
679300 x 50mm x1.6mm
680100 x 50mm x1.6mm
681110 mm X 50 mm
682210 mm X 50 mm
683310 mm X 50 mm
684EARTHING
685EARTHING : Supply, Installation, testing and commissioning of earth plate of size 1200x1200x12mm CI Plate earth electrode at a depth 3000 mm in an earth pitfilled with salt and charcoal mixed with sand in alternate layers of 150mm each up to a height of 3000mm from bottom. including supply and fixing of 38mm dia perforated GI pipe funneling for watering purposeincluding constructionmasonry. Heavy duty SFRC cover shall be used to cover the pit, Manhole cover size 450X450 mm as per IS 3043.
686Supply, Installation, testing and commissioning of earth plate of size 600 x 600 x 3mmcopper plate earth electrode at a depth 3000 mm in an earth pit of 450 x 450 x 350mm filled with salt and charcoal mixed with sand in alternate layers of 150mm each up to a height of 3000mm from bottom. Two copper flats of size 25 x 3 mm shall be braced to this copper plate throughout the overlapping length with the copper plate and brought to the surface of the earth pit. This plate shall have provision for connecting wires or flats as the case may be. A suitable size of 25/ 38mm dia GI pipe shall be provided up to bottom of the earth pit. This GI pipe shall have provision for watering through a funnel. A masonrystructure of wall thickness of not less than 230mm shall be constructed to a depth of 450mm and heavy duty SFRC cover shall be used to cover the pit.
68750X10 mm GI . Flat for panel cable tray Body earthing
68825X6mm GI . Flat for panel cable tray Body earthing
689Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required
6908 SWG Cu. Wire for DBs earthing
69125X6mm Cu Flat forearthing
692STREET LIGHTING
693STREET LIGHTING -- MAIN ROADSThe rate includes excavation and foundation for erecting thereferred street light pole as required at site and inclusive of necessary connected minor civil works if required and necessary supports as required at site. No extra payment will be made for the same. each arm with light- The pole shall be grouted inside ground pit (cross section 600 x 600 mm)with cement concrete 1:2:4 with necessary GI ‘A’ class pipes (not less than 38 mm dia, NB) to facilitate pulling of cables. Separate pipes shall be provided for incoming and outgoing cables. The cement concrete shall be protected from premature drying by curing for at least seven days after pouring. All concrete surfaces from 150 mm below ground level to top shall be finished smooth with cement mortar 1:4.-pole height above ground 6-m-top 70mm,bottom 130mm,thickness 3mm,with base plate size220x220x16mm-4nos foundation bolts,700 mm length 24mm dia.
694Supply, erection, testingand commissioning ofstreet light fitting with 1x120W LED lamp, driver,fixed on 7m(above ground)MSOCTAGONAL polesconfirming to IS1161,- and 1.5 m angle arm - Single armconventional bracket for mounting fitting ,bracket assembly on to the pole top by means of angular rings , foundation base plate,ribs,4 fixing bolts (600mm anchoring bolt with 90 degree bend, including red oxide paint 24mm rod with 2nos PL Washers and 3nos nuts) anchoring bolt,cable entry pipe, poles treated for corrosion protection, earthing arrangement, excavation and back filling, supplying and laying cables through Hensel make weather proofjunction box withDP 3 ampsMCB ,wiring with 3x2.5 Sq.mm PVC insulated 1100 volts grade copper conductor wires from junction box to lighting fixture complete as required. finish to be of approved colour.Entire application shall confirm to IS2713 for Tubular Steel Poles for Overhead Power lines including numbering of poles. 4 way 30 A rated terminal block for loop in & loop out cable arrangements coil earthing etc.The pole shall be painted with one coat of primer and two coats of enamel paint,with 1Mtr long 25mm dia \"B\" class G.I. Pipe as earth electrode with charcoal ,Salt with 10SWG copper wire interconnected with street light pole. cable entry G.I pipe of 2.5\" dia. as per Drg and Technical Specification.CROMPTON TRP-411-120-57-SL-GL-NSGor equivalent approved make
695Supply, erection, testingand commissioning ofstreet light fitting with 1x120W LED lamp same as above item but with Double Arm with7meter galvanised Hexogonal pole with necessary fixing accessories.
696Bajaj BGAV 302 LED Aviation Light Luminaires
697SAFETY EQUIPMENTS:
698MISC ITEMS:
699Supply and providing of 6mm thick MS Chequered Plates as floor separators for covering the shafts with angle iron supports at floor level to form a complete fire barrier protection between two floors and to cover thegaps around the cable trench etc., in the duct.
700WALL/POLEmounted cable junction boxes
701Supply and laying of 25mm dia 2mm thick MS Conduit with all connected accessories.
702Supply and laying of 32mm dia 2mm thick MS Conduit with all connected accessories.
703Supply and laying of 20mm dia Heavy duty PVC Conduit with all connected accessories.
704Supply and laying of 25mm dia Heavy duty PVC Conduit with all connected accessories.
705Supply and laying of 32mm dia Heavy duty PVC Conduit with all connected accessories.
706Supply and laying of 50mm dia Heavy duty PVC Conduit with all connected accessories.
707Supply and laying of 25mm dia 2mm thick GI Conduit with all connected accessories. FOR flame proof lighting class A
708Supply & Erection of Cable Tags as per the Cable Schedule.
709Liaison with the Chief Electrical Inspector to Govt., /CEA for preparation ofWorking drawings etc., obtaining approval for drawing.Preparation of completion Report, Arranging for Inspection and attending to defects report and preparation of as fitteddrawings and obtaining Safety Certificate fromCEIG /CEA for commissioning. Liaison with the Chief Electrical Inspector to Govt., for issue of Safety certificate approval for energisation. clearance from SUPPLIER includingfor installation and running DG set.The works executed as built drawings need to be submitted in the blue print of A1 sizein 4 Sets of hard copy and two set sets of soft copy in CD.The necessary statutory fees/charges will be paid by the client against demand advice.
710Supplying and Installation Testing and commissioning of 990Lts Fuel Tank fabricated by 2mm Sheet, suitable stiffners, Man Hole (400x400) , Breath went, Drain,Delivery, Fuel level indicator,Float valve arrangement, Level switch,Lifting Hook,etc as required.( One Intermediate tank one overflow tank)
711Supply and laying of 50mm dia C class MS pipe in the exposed surface the pipe line shall be painted with one coat of primer and two coats of synthetic enamel paint i/c. with necessary supports complete as required. (FROM DAY TANK TO DG SET AND RETURN TO DAY TANK and FROM INTERMEDIATE TANK TODAY TANK).
71225 mm dia float valve for day tank
71350 mm dia ball valve
714Supply of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No.RD 8/ALU I (5450 08 6)
715Supply of Roof conductor holderfor parapet- Polyamide Conductor holder:With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distanceOBO Type No.177 30 M8(5207 46 0 )
716Polyamide roof cable holder for flat roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black@ 1 meter distance. OBO Type No.165 MBG 8-10 ( 5218 70 0)
717Providing of cross universal connector: For T and cross connection,to route vertical down conductor /mesh formation made of hot dipped galvanisediron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts . OBO Type No.251 8-10 ( 5312 03 5 )
718Providing of expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU. OBO Type No. 172 AR ( 5218 92 6 )
719Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Conforms to the requirements according to DIN VDE 0185-305 (IS-IEC 62305)(2nos/expansion piece ). OBO Type No. 249 8-10 ST ( 5311 50 0 )
720Vertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 16mm rod tapered to 10 mm aluminium rod :Meets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202).Meets the requirement of VDE0185/305(IS/IEC 62305) 4Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. OBO Type No. 101 VL 4000 ( 5401 995 ).
721Accessories : System consist of Fang Fix with base and clamp, on the top air terminal is erected. OBO Type No. F-FIX 16 ( 5403 20 0 ).
722Fang fix clamp made of SS, lightning tested for 100 KA 10/350 micro sec waveform.16 KG stone of 365 mm diameter, high level of stability.Quick and easy mounting of interception rod using anchors.Concrete, frost-resistant, can be stacked.OBO Type No. F-FIX S16 I ( 5450 08 0 )
723Supply of 8 mm Aluminum Round Conductor complete as specified in drawing & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305) , OBO Type No.RD 8/ALU I (5450 08 6)
724Supply ofConductor holderfor Sidewall- Polyamide Conductor holder:With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distanceOBO Type No.177 30 M8(5207 46 0 )
725Supply of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by 30x3 mm GI strip as specified in drawing and directed by EngineerOBO Type No. 271 8-10 ( 5317 40 1 )
726Enclosure for Test joint: RoHS Complied, IP66, 6mm², 500V, IK08, UV resistant, Halogen free Thermoplastic junction box ,installation of cables either directly through the 7 x M25 seals, polypropylene,Light grey.Overall Dimensions: 114mm X 114mm X57mm, Internal Dimensions: 100mm X 100mm X 48mmOBO TYPE : T 60 (2007 061)
727Lightning counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6.OBO Type No. LSC I+II ( 5091 72 2 )
728Supply of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor shall be of Hot Dipped & Cross sectional area of 90mm squareAccording to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of VDE0185/305(IS-IEC 62305) Zinc coating: 500 g/m square (Approx:70 micron coating) Should be tested and used exclusively for lightning protection earthing system and ring equipotential bonding.OBO Type No. 5052 DIN 30X3 ( 5019 34 4 )
729Providing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. OBO Type No. 255 FL30 FT (5314 53 4 )
730Providing of flat conductor holder suitable for FL 30. Installed with 2 hexagonal bolts.OBO Type No. 166 LS 70 (5226570)
731Providing of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. OBO Type No.356 50 ( 2360 05 5 )
732Supply of CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250micron tested as per IEC 62561-2 ( OBO Type No. 17 3000 CCER)& is provided with universal clamp made of SS to connect rod with flat conductor ( OBO Type No. 17 25 RTC) . Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested(OBO Type No.OEC 2 25) . The above arrangements shall be provided withHeavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system(OBO Type No.UFE) .
733Supply of CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250micron tested as per IEC 62561-2 ( OBO Type No. 17 3000 CCER)& is provided with universal clamp made of SS to connect rod with flat conductor ( OBO Type No. 17 25 RTC) . Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested(OBO Type No.OEC 2 25) . The above arrangements shall be provided withHeavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system(OBO Type No.UFE) .
734Supply of CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250micron tested as per IEC 62561-2 ( OBO Type No. 17 3000 CCER)& is provided with universal clamp made of SS to connect rod with flat conductor ( OBO Type No. 17 25 RTC) . Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested(OBO Type No.OEC 2 25) . The above arrangements shall be provided withHeavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system(OBO Type No.UFE) .
735Supply of CPRI tested maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250micron tested as per IEC 62561-2 ( OBO Type No. 17 3000 CCER)& is provided with universal clamp made of SS to connect rod with flat conductor ( OBO Type No. 17 25 RTC) . Earth conductivity enhancing compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested(OBO Type No.OEC 2 25) . The above arrangements shall be provided withHeavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system(OBO Type No.UFE) .
736DIESEL GENARATOR
737S.I.T.C of1 No. of 380 KVA DG sets PRIME DUTYwith Acoustic Enclosure, AMF Control Panels & connected works such as Exhaust Pipe & Exhaust stack with supporting arrangements,Earthing and other associated works etc,.Design, manufacture, Supply and Transportation, Installation, Testing and Commissioning of the380KVAcontinuous Prime Duty DG set inside the Acoustic Enclosure, 1500 rpm, four stroke, designed for operating on HSD, 415V,3Phase,50Hz,0.8pf,4wire AC complete with all accessories, like base frame,vibration bellow and includes the following transport, insurance, handling, safe keeping at site etc., erection, installation, testingand commissioning, excluding civil foundations and trenches inside the Acoustic enclosure andaccess ladderfor DG set\"s radiator watering. The DG set shall be as per the detailed specification enclosed.
738Note: The Acoustic enclosure shall be meeting the noise level requirements as specifiedviz. less than 70 dBA during night time at 6 meters distance from DG sets and less than 75 dBA during daytime at 6 mtr distance from the DG sets with all DG sets operating at full load All necessary civil works for Acoustic Enclosure required to be implemented by other agency shall be listed separately. Noise levels shall be guaranteed by the Bidder. The acoustic treatment shall be as per the detailed specification enclosed.
739SITC of 24Volts, 40Amps, SCR controlled battery charger made up of 16SWG MS sheet enclosure with all accessories having automatic boost and trickle charging arrangements with volt and current limiting circuits, voltmeter for AC/DC supply, ammeter for charging circuit (DC), automatic cut off facility when the Engine alternator is in working condition when the battery is fully charged. MCB for protection, suitable for 230V,50Hz, AC supply, interconnections, body earthing etc. complete as required.
740Design, manufacture, supply, installation,testing and commissioning of 10\" (inch) dia MS exhaust pipe class B suitable for 380KVAengine exhaust line (Vertical) including with all accessories such as bends,.flanges, gaskets, condensation removal plug, fixing of flexible coupling, residential silencer supplied along with the engine. Providing necessary MS angle iron supports for the pipe line and the silencer, welding arrangements/ flanged joints with bolts/nuts as perthe site conditions. Terminating the pipe line in duct /shaft including the complete insulation with 50mm thick glass wool, polythene covering, chicken mesh and aluminium claddingcomplete as per the specifications etc. as required.
741Design, Manufacture,Supply, Installation, Testingand Commissioning of the Exhaust Stack suitable for 2 x 380 KVADG set with exhaust gas flow with wind pressure suitable for LOCAL condition and exhaust gas velocity, necessary stiffner rings & flanges, sampling ports, foundation bolts, lightning arrestor, earth strip of 25 x 6mm GI for Earthing stack and LA, insulators, foundation bolts etc. Detail design for civil foundation should be furnished by the supplier well in advance to make the foundation ready by other agency. Design data should be furnished for wind pressure, base diameter and thickness of plate at cone and shaft areas. The rate shall include Lightning Protection, aviation warning lamp( LED type) with photo cell including cabling, termination, control MCB etc. The rate shall include necessary steel structure including necessary supports, Scaffolding charges,necessary bellows etc.,. Exhaust Pipe including necessary painting. The Exhaust stack height will be 30 Mtrs. DG sets to be provided for 2 x 380 kVAEnd of the Exhaust stack shall be design shaped to protect & to avoid rain water entry inside pipe and bended towards wind flow direction at LOCAL condition etc,.
742Supply, fixing, testing and commissioning of theResidential silencer for the 380KVA Prime Duty DG set with complete insulation covering with 50mm thick glass wool, polythene covering, chicken mesh and aluminium claddingcomplete as per the specifications etc. as required.
743Supply and erection of 25 mm dia, Class \"B\" MSpipe for the interconnection of the Day fuel tank with the engines, with necessarywelding, jointing and painting etc.,
744Design, supply, erection of 600 x 600 x 12 mm CI plate burried in ground in a depth of 3.0 M from ground level with alternate layer of charcoal and slat including supply and fixing of 40 mm dia perforated GI pipe funneling for watering purpose including construction of masonry chamber with RCCtop cover.The thickness of top cover should be suitable for heavy duty vehicle movements. This item covers all earth work, shifting of removed soil
745Supply, erection of3 mtrs long 13mm thick and 100mm dia Cast Iron Pipe electrode earth station. burried in ground in a depth of 3.0 M from ground level with alternate layer of charcoal and slat.The identification number shall be provided both inside and outside.
746Supply and laying of 40 x 6 mm copper flat for 380KVA generator neutral earthing joint connections brazing.
747Supply and laying of 8 Gauge bare copper wire for Gland earthing.
748Supply and laying of 25 x 3 mm Cu flat for generator body earthing joint connections brazing.
74916 C x 2.5 sq.mm PVC insulated Copper cable
7504C x 2.5 sq.mm PVC insulated Copper cable
7514C x 1.5 sq.mm PVC insulated Copper cable
7521.5 sqmm PVC insulated Copper cable Screened communciation cable
753supplying and laying of rubber mat of 2 mm thick with ISI : 15652-2006 marked suitable for the 3.3 KV grade etc. as required.(size 1m wide x 2m length)
754Fuel unloading hand pump.
755PVC Hose
756ELV WORKS
757READERS AND CONTROLLERS
758Supply, installation, testing & commissioning of Smart card readers as per specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories
759Supply, installation, testing and commissioning of Biometric - cum -Pinpad cum Proximity Reader with 3000 Users (Templates on Reader) - 2 Templates each User with Membrane Sensor for Live Finger Verification.
760Supply, installation, testing and commissioning of electromagnetic Lock (fail safe type) of 600lb holding force, with built-in Door Feedback & door ajar alarm buzzer for the following type doors :
761Single leaf Door- 600LB
762SITC of Recessed Magnetic Door Contactfor Doors with mounting accessories to complete the installation in all respects.
763Supply installation, testing, commissioning of Green ABS plastic Emergency Break Glass Units.
764Supply installation, testing, commissioning of Weather Proof Green ABS plastic Emergency Break Glass Units.
765Supply, installation, testing and commissioning ofTwo Reader Control panel housed in MS Powder Coated Cabinet with Tamper Switch, complete with On-board IP / LAN port, and Built-in Web Server for Remote Log in to every controller.Also the Controller should have spare potential free contact to trip any third part system if required.
766Complete with power supply unitfor Controllers & Magnetic Locks
767Supply, installation, testing and commissioning ofFour Reader Control panel housed in MS Powder Coated Cabinet with Tamper Switch, complete with On-board IP / LAN port, and Built-in Web Server for Remote Log in to every controller.Also the Controller should have spare potential free contact to trip any third part system if required.
768Supply, installation, testing and commissioning of Blank Unprinted Smart cards as per specification.
769Anti-Tailgate Detector at Mantrap Locations
770Server Hardware / Client Hardware
771- Windows 2008 or higher Server Standard OS with License.
772- Microsoft SQL Server 2005 or Higher, standard edition License
773SITC of Client PC for Access Management :
774AccessServer shall comprise of the following minimum hardware:Xeon Octa Core IntelSeries Processor at mim 3 GHz 20M Cache,4GB or more of RAM, 1 Tb hard drive,DVD player- Read and write with video card and video recording application with 15 min UPS Redundant power supply unit ,Standard video display adapter Microsoft® Windowslatest 64 bit OS with AntiVirus,MS Windows Server Software and operating license; and MS SQL Server License etc
775Access ControlSoftware
776Client Version Application Software for Access Control :- (Location :BMS Room). Shall be Capable of Generating Multiple Reports in Excel format , such as Department wise / Door Wise/ Card Wise / Day wise / Weekly, monthly reports etc.
777Pedestrian & Vehicle Traffic Management
778Supply, Installation, Testing and Commissioning of 3 Set Speedflap barrierin SS Finish, with SS long housing, Servo position Drive with tooth holding break technology, 1800 mm Glass , sensor should be hidden not visible and shall be in specific pattern , detection shall be in algorithm based and with all mounting accessories. Capable of Free Egress in case of Fire Alarm / Emergency Event and Automatic Reset after resuming of Normal signal or Power. Mean Cycle Between Failure shall be minimum 12 Million Shall have Access reader on both sides for Bi-directional Access.
779Supply,Installation,Testing & commissioning of Handicapped Swing Gate Barrier, SS Finish with Toughen Glass/ Polycarbonate showing Universal Handicap Insignia.Capable of Free Egress in case of Fire Alarm / Emergency Event and Automatic Reset after resuming of Normal signal or Power.Mean Cycle Between Failure shall be minimum 12.0 MillionShall have Access reader on both sides for Bi-directional Access.
780Articulated Boom Barrier - 4.5 mtr long Electromechanical type maintenance free Boom Barrier ,Boom made of 2mm zinc coated sheet Steel Powder coated & base of SS with reflective tape strips, with opening time less than 3 sec`s,complete with fixed support post,IP 65 Protection.It shall also include Control Panel and remotely placed manual override switch. Complete with 2 pairs ofPhotocell safe beam with Mounting Frames & SS Stand posts as required to complete the installation.
781FRLS AB Copper Armoured Cable,PVC insulated, shielded PVC Sheathed layed with fittings & G.I Supports at 0.3mtr
7828 c x 0.75 Sq.mm
7834c x 0.75 Sq.mm
7842c x 1.0 Sq.mm
785Supply, Installation,Testing Commissioning of IP Based CCTV System comprising of following: - Matrix, Sparsh, lilin, Bosch
786IP Cameras :Indoor/Outdoor surface mount enclosure, Mounted on True Ceiling / False ceilingas per site requirement (including required accessories), UL Listed as per detailed specifications.
787Indoor Dome Camera, Wide AngleIP dome, POE ,1/3\" CMOS, Min. 5 MP Resolution, Dual H.264 / H.265 Streaming, 25 fps, fixed lens 2.6/2.8/3/3.6mm, 0.5 lux for colour, Tamper detection, 3D Noise reduction, Auto Gain / Auto White Balance. PoEWith LATEST ONVIF ComplianceIEEE802.1X Security Protocol is must in all models IP cameras. Camera Shall also have Listing of (UL60960-1,IEC 600068-2-1,EN 55022 Class B , EN 61000-6-1, EN 61000-6-2 )
788Outdoor IP Bullet Type Camera ( Periphery walls / Building external walls)IP Bullet Camera, POE, Outdoor Weatherproof, Min 5MP , 1/3 CMOS, IR Cut lens , IR for 25 meters, POE ,Vandal / Tamper proof, Optical WDR > 100 Db ,Auto Gain / Auto White Balance. IP 66 & Vandal proof enclosure , 3D Noise reduction, PoE & standard 12VDC/24VAC power input . IEEE802.1X Security Protocol is must in all models IP cameras.Camera Shall also have Listing of (UL60960-1,IEC 600068-2-1,EN 55022 Class B , EN 61000-6-1, EN 61000-6-2 )
789SITC of Outdoor Application Low Light IP Hi speed Dome type PTZ camera with 2 MP Resolution, mim 32X optical zoom, Low Light ,Day/Night, Wide dynamic range > 100 dB, Dual H.264 streaming, 0.05 lux, vandal resistant, 360° continuous pan, -0° to +90° tilt, 256 preset, IP66 rated with built in heater and blower, Mounted on Wall/Pole as per site requirement (including required accessories), UL listed as per detailed specifications. IEEE802.1X Security Protocol is must in all models IP cameras.Camera Shall also have Listing of (UL60960-1,IEC 600068-2-1,EN 55022 Class B , EN 61000-6-1, EN 61000-6-2 )
790SITC of 16 channel High resolution (720x576) Video and Audio encoder with Dual streaming with 25FPS & highest resolution, Dual H.264 streaming support, PoE, RS232/485 connection as per detailed specifications.
791SITC of 8 channel High resolution (720x576) Video and Audio encoder with Dual streaming with 25FPS & highest resolution, Dual H.264 streaming support, PoE, RS232/485 connection as per detailed specifications. (For lift & PTZ cameras)
792SITC of GI Pole, 100mm dia, 5m high with 2 coats of reoxide primer and 3 coats of external weatherresistant colour as per Architects recommendation, complete with mounting accessories as required for the pole as well as the cameras, suitable to mount the outdoorcameras to the directions of the consultant.
79310 Tb hard diskindustry tye
794Servers , Networking Hardware & Softwares : -
795SITC of Client PC Hardware with a minimum specification of Intel i7 Quad Core Processor 7th Generation at mim 3.6 GHz ,12M, Intel HD Graphic 630, 6.4GT/s, 4x4 GB or more of RAM,500GB SATA,10K RPM 3.0Gb/s Hard Drive for OS and VMS ApplicationsNetwork Interface Card - 10/100/1000 MBNetwork Fiber Interface Card - 4 x 1Gbps in fault tolerance configurationVideo Card – nVidia 2 x NVS295 Quad Monitor Graphics card to support 4 multiplexed MonitorsMotherboard should support Intel as well nVidia GPU in active-active mode and both devices should be enabled.DVD-R/WMicrosoft® Windows® 8.1 / 10 Pro or Higher 64 bit
79621\" colour ,Flat Screen type Professional CCTV Surveillance HD monitor for above client workstation
79755\" colour , Flat Screen Type Professional CCTV Surveillance HD monitor for above client workstation
798SITC of Video Analytics Processing Software & Hardware :- - 20 NosTO Support Minimum 1 cameras, programmed with any 1 or more, of the following of the following Video Analytics features :a) Object left behind, b) Directional Motion ( Adaptive Motion),c) Object Removal d) Camera Sabotagee) Loiteringe) Crowd Detectionf) Trip Wireg) Object Countingh) Vibration Removal(The System shall allowimplementation of Video Analytics on any user defined cameras during commissioning). Independent servers, if required to be used for video analytics shall be included in this item as required.
799Independent LAN for IP CCTV Camera System :-
800SITC of Edge Switch : 24 port layer 2 switch with 10/100/1000 POE Managed Switches withIP multicast snooping and data-driven IGMP support and with Two 1000baseT single mode FO uplink ports (with Fibre Module ) and all related termination accessories as per site specific System requirement. Dual Powered .Compliance to Tender specs to be Provided
801SITC of Edge Switch : 16 port layer 2 switch with 10/100/1000 POE Managed Switches withIP multicast snooping and data-driven IGMP support and with two 1000baseT single mode FO uplink ports (with Fibre Module ) and all related termination accessories as per site specific System requirement. Dual Powered .Compliance to Tender specs To be provided
802SITC of Core / Aggregator Switch : Modular 24 port Layer 3 managed switch withFibre ports; required number of 10/100 ports etc. as per project requirement. Dual Powered . Compliance to Tender specs To be provided
803Cables
804Cable/Conduits shall be laid on surface with GI saddle & spacers every 0.3 meters. Complete with GI Junction Box, LIUs/ Pigtails , Patch cord /Patch Panels etc ,Splicing , lugs, cable compression glands, cable tags and Ferruling.The Structure cabling Scan test shall be Done and inspected by OEM and report for the same shall be provided by OEM
805SITC of Supply & Laying of Armoured FRLS Cat-6(LHZH) cable laid in Conduits / cable Trays. Shall be complete with IO Module Boxes at the Camera End, Patch Cords, GI Gang Boxes, Termination lugs, Labelling and tagging, ferruling etc
806Single mode 2 core Fibre optic cable, Zero Halogen Low Smoke outer Sheath. laid in Conduits / cable Trays. Shall be complete with IO Module Boxes at the Camera End, Patch Cords, GI Gang Boxes, LIUs, Pigtails, Termination lugs, Labelling and tagging, ferruling etc ( switch to switch and wherever 120 mts exceeds)
807Media converter for OFC- Rj45
808Any other accessories required to complete the system configuration as per vendor specific requirements i.e. Power supplies, fiber converters, LIUs, Specific System cables etc. to complete the installation.Contractor to mention the quantity of the below items with costapart from the below item if any other accessoriesare required , controator to add the same Patch Panels,1mtrs Cat6 Patch Cords,LIU’s,Pigtail cables,1mtr LC to LC Single Mode Patch Cords,Labels,any Other componentto complete the design intent

AI Tender Summary

OUR REF NO 36712483
AUTHORITY Government Departments
TENDER VALUE Ref. Documents
LAST DATE 10-04-2023
Authority
Authority Name Tidel Park Ltd
Work Description Construction Of It Office Buildings Civil Construction, Hvac, Electrical Ht And Lt, Dg Sets, Ibms, Fire Protection, Plumbing, Structural Facade, Landscaping, Stp, Wtp, And External Works At Salem District.
Basic Detail
Tender No TIDEL/2022-23/13
Bidding Type Tender
Location
City omalur
State Tamil Nadu
Key Dates
Publish Date 20 Mar 2023
Submission Date 10 Apr 2023
Open Date 11 Apr 2023
Finance
Tender Value Ref. Documents
Tender Fee Ref. Documents
EMD 22.50 Lakhs
Exemption Not Available
Document List
51645abb-a317-4dc6-b954-4cde43037c1a.html
BOQ_349586.xls
VolumeI.pdf
VolumeII.pdf
Drawings_Architectural.pdf
Drawings_Electrical_ELV.pdf
Drawings_FPS_HVAC_PHE.pdf
Tendernotice_1.pdf
VolumeIII.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Mar 20, 2023
11:30 IST

Tender Published

Tender notice published.

Completed
Apr 10, 2023
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Apr 10, 2023
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Apr 11, 2023

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

51645abb-a317-4dc6-b954-4cde43037c1a.html

xls

BOQ_349586.xls

pdf

VolumeI.pdf

pdf

VolumeII.pdf

pdf

Drawings_Architectural.pdf

pdf

Drawings_Electrical_ELV.pdf

pdf

Drawings_FPS_HVAC_PHE.pdf

pdf

Tendernotice_1.pdf

pdf

VolumeIII.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders