Tender For Development Of Taluk Hospital, Chirayinkeezhu, Thiruvananthapuram Package Ii And Iii (Sh Miscellaneous Civil Works, Electrical Works, Elv, Hvac, Fire Protection, Sitc Of Lifts, Medical Gas Pipeline System), chirayinkeezhu-Kerala

INKEL Limited has published Tender For Development Of Taluk Hospital, Chirayinkeezhu, Thiruvananthapuram Package Ii And Iii (Sh Miscellaneous Civil Works, Electrical Works, Elv, Hvac, Fire Protection, Sitc Of Lifts, Medical Gas Pipeline System). Submission Date for this Tender is 25-03-2023. Passenger Lift Tenders in chirayinkeezhu Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

36703583
Corrigendum : Tender For Development Of Taluk Hospital, Chirayinkeezhu, Thiruvananthapuram Package Ii And Iii (Sh Miscellaneous Civil Works, Electrical Works, Elv, Hvac, Fire Protection, Sitc Of Lifts, Medical Gas Pipeline System)
Open Tender
Indian
Kerala
chirayinkeezhu
25-03-2023

Tender Details

Development Of Taluk Hospital, Chirayinkeezhu, Thiruvananthapuram Package Ii And Iii ( Sh Miscellaneous Civil Works, Electrical Works, Elv, Hvac, Fire Protection, Sitc Of Lifts, Medical Gas Pipeline System ) Miscellaneous Civil Works, Electrical Works, Elv, Hvac, Fire Protection, Sitc Of Lifts, Medical Gas Pipeline System

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 24-Mar-2023 CORRIGENDUM No. 1 Date 25-03-2023

Key Value

Document Fees
INR 17700 /-
EMD
INR 500000.0 /-
Tender Value
INR 22.38 Crore /-

BOQ Items

Work Name : Development of Taluk Hospital, Chirayinkeezhu, Thiruvananthapuram - Package II & III (SH: Miscellaneous Civil Works, Electrical Works, ELV, HVAC, Fire Protection, SITC of Lifts, Medical Gas Pipeline System )
Sl. No. Item Description
1SH 1 - CIVIL WORKS JOINERY
221.1.1.2 : Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron)
321.1.2.2 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron)
4Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With toughned glass of 6mm thickness
5Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade II Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
621.3.1 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness
721.3.2 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness
821.4.1 : Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors including cost of cutting floors, embeding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer -in- Charge.With stainless steel cover plate minimum 1.25 mm thickness
99.84 : Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
109.121 : Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness.The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat.Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs.The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
119.122.1 : Providing and fixing to existing door frames.30 mm thick Glas Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS : 14856, including fixing to frames.
129.97.1 : Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:300x10 mm
139.97.2 : Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:250x10 mm
149.100.1 : Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm
159.100.2 : Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:100 mm
1621.15.2 : Providing and fixing aluminium casement windows fastener of required length for aluminium windows with necessary necessary screws etc.complete.Powder coated minimum thickness 50 micron aluminium
179.101.1 : Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Single rubber stopper
189.101.2 : Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper
1921.11.2 : Providing and fixing stainless steel (SS 304 grade) adjustable friction window stays of approved quality with necessary stainless steel screws etc.to the side hung windows as per direction of Engineer - in-Charge complete.255 x 19 mm
20Providing and fixing Powder coated aluminium (minimum thickness of powder coating 50 micron) locking arrangement for sliding windows including necessary screws and fittings of approved make as directed by Engineer-in-charge.
21Providing and fixing roller for shutters of sliding aluminium windows with necessary screws etc.complete.As approved by Engineer-in-charge
2221.13 : Providing and fixing 100 mm brass locks ( best make of approved quality ) for aluminium doors including necessary cutting and making good etc. complete
2321.18 : Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately)
24Providing and fixing Stainless Steel Corner Patch Lock with Strike Plate of SSS finish for toughened glass door including all necessary fittings Or equivalent.
25Providing and fixing Stainless steel D type glass door handle with SSS polished finish of 25mmx450mm size.
269.106.2 : Providing and fixing PTMT handles with necessary screws etc. complete.150x34x24 mm weighing not less than 26 gms
279.108.2 : Providing and fixing PTMT Tower Bolts with 12 mm one piece rod inside and necessary screws etc., complete.202x42x18 mm weighing not less than 78 gms
2850.9.15.2 : Supplying and fixing 300 mm Aluminium aldrop
299.88 : Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete.
30Frosted film - Supply and installation of 3M make frosted film pattern throughout all the internal glass panels wherever required of approx. 1.5 m height as per the approved pattern.
31Providing and fixing of hollow metal door at all levels fromISO 9001-2015 certified manufacturer. All hollow metal general doors with or without vision panel. Pressed galvanised steel Single /Double leafto required sizes of approved makewhich consists of frame, shutter, infill and finish as detailed below and conforming to IS 277. Door frame shall be double rebate profile of size 143 x 57mm made out of 2.0mm (14gauge) thick galvanized steel sheet. Frames shall be butted and field assembled with bolts. The inside face of the frame face trim to rebate heightshould be protected with 2.0 mm thick lead line. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Rubber door silencers should be provided on the strike jamb. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Once frame installed should be grouted with cement & sand slurry necessary for doors on the clear masonry opening.Door leaf shall be 48mm thick fully flush double skin door. Door leaf shall be manufactured from 1.2mm (18guage) thick galvanised steel sheet. The internal construction of the door should be rigid with lead line of 2.0mm thick all across the inside of the exposed surface. In addition the door should have a basic infill steel stiffened special core with necessary reinforcement both on top and bottom. All doors should be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers as per ANSI Standard. The edges should be interlocked with lock seam.For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Approved hardware make : Lawrence / Gallery / Zero.All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate should include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule.1500mmX2400mm
32Providing and fixing of hollow metal door at all levels from ISO 9001-2015 certified manufacturer. All hollow metal general doors with or without vision panel. Pressed galvanised steel Single /Double leaf to required sizes of approved make which consists of frame, shutter, infill and finish as detailed below and conforming to IS 277. Door frame shall be double rebate profile of size 143 x 57mm made out of 2.0mm (14gauge) thick galvanized steel sheet. Frames shall be butted and field assembled with bolts. The inside face of the frame face trim to rebate height should be protected with 2.0 mm thick lead line. All provision should be mortised, drilled and tapped for receiving appropriate hardware. Rubber door silencers should be provided on the strike jamb. Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Once frame installed should be grouted with cement & sand slurry necessary for doors on the clear masonry opening.Door leaf shall be 48mm thick fully flush double skin door. Door leaf shall be manufactured from 1.2mm (18guage) thick galvanised steel sheet. The internal construction of the door should be rigid with lead line of 2.0mm thick all across the inside of the exposed surface. In addition the door should have a basic infill steel stiffened special core with necessary reinforcement both on top and bottom. All doors should be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers as per ANSI Standard. The edges should be interlocked with lock seam. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Approved hardware make : Lawrence / Gallery / Zero.All doors and frames shall be finished Pure Polyster Powder;coated and shall have passed minimum 500 hours of salt sprey test. Rate should include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule.1200mmX2400mm
33Providing and fixing of Hollow metal doorsmade of pressed galvanized steel confirming to IS 277 with the following specification. Doors shall be with vision glass and louver as a part of complete assembly.Door frame shall be single rebate profile of size100 x 57mm made out of minimum 1.20mm (18gauge) thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system and shall be site fitted with PVC seal as standard. All provision should be mortised, drilled and tapped for receiving appropriate hardware.Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with puff.Door leaf shall be 46mm thick fully flush double skin door, with or without vision lite. Door leaf shall be manufactured from minimum 0.8mm (22guage) thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be resin bonded honeycomb core. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable should be provided as per manufacturers recommendation with a clipon arrangement. The glass should be 5mm clear toughned glass of relavant rating of the door.All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule.Once frame installed should be filled with PUF as recomended by the manufacturer or engineer.1200mmX2400mm
34Providing and fixing of Hollow metal doorsmade of pressed galvanized steel confirming to IS 277 with the following specification. Doors shall be with vision glass and louver as a part of complete assembly.Door frame shall be single rebate profile of size100 x 57mm made out of minimum 1.20mm (18gauge) thick galvanized steel sheet. Frames shall be mitered and field assembled with self tabs. Frames to have inbuild grooved sealing system and shall be site fitted with PVC seal as standard. All provision should be mortised, drilled and tapped for receiving appropriate hardware.Frames should be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Frames shall be filled with puff.Door leaf shall be 46mm thick fully flush double skin door, with or without vision lite. Door leaf shall be manufactured from minimum 0.8mm (22guage) thick galvanised steel sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be resin bonded honeycomb core. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of doors integrated astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable should be provided as per manufacturers recommendation with a clipon arrangement. The glass should be 5mm clear toughned glass of relavant rating of the door.All doors and frames shall be finished Pure Polyster Powder coated and shall have passed minimum 500 hours of salt sprey test. Rate shall include supply and installation of door and hardware as a complete assembly as mentioned in the door and hardware schedule.Once frame installed should be filled with PUF as recomended by the manufacturer or engineer.2000mmX2400mm
3513.52.1 : Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer"s specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work
3610.25.1 : Item Shifted to head 14 as item 14.74Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In stringers, treads,landings etc. of stair cases, including use of chequered plate wherever required, all complete
3710.25.2 : Item Shifted to head 14 as item 14.74Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
3825.1 : Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account).
3925.2 : Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cumsmoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineerin-Charge (detailed specification as per part C)
40Providing and supplying Single glazing comprising of 6 mm thick heat strengthened monolithic float glass of approved colour and shade with transmission 31% min,external reflection 14% and internal reflection 17% so as to match the colour and shade of the IGUs in the vision panels etc., all complete for the required performance as specified, as per the architectural drawings, as per the approved shop drawings, as specified, and as directed by the Engineer- in - Charge. For payment, only the actual area of glass shall be measured in sqm. (Payment for fixing of Glass panels in the curtain glazing is included in cost of relevent item*).
4125.4 : Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4 -point cremone locking sets with stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge.
42FLOORING
438.2.2.2 : Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
44Providing and fixing machine cut, mirror/ eggshell polished, Granite stone work for wall lining (veneer work) including dado, skirting, risers of steps, etc., in required design and pattern wherever require, stones of different finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse sand) and fixing with chemical adhesive, including pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing, polishing etc. all complete as per Architectural drawings, and as directed by the Engineer-in-charge.a. 18mm thick Granite of any colour and shade
458.3.2 : Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer -in-Charge.Granite work
468.31 : Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineerin-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
47Extra for using or fixing glazed/ Ceramic/ Vitrified wall tiles with cement based high polymer modified quick-set tile adhesive ( Water based) conforming to IS : 15477, in average 3 mm thickness.
489.105.3 : Providing and fixing partition upto ceiling height consisting of G.I. frame and required board, including providing and fixing of frame work made of special section power pressed/ roll form G.I. sheet with Zinc coating of 120 gms/ (both side inclusive), consisting of floor and ceiling channel 50 mm wide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the spacing of 610 mm centre to centre with dash fastener of 12.5 mm dia meter 50 mm length or suitable anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34 mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling channel and placed at a spacing of 610 mm centre to centre by 6 mm dia bolts and nuts, including fixing of studs along both ends of partition fixed flush to wallwith suitable anchor fastener or metal screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of frame work by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300 mm centre to centre.The boards are to be fixed to the frame work with joints staggered to avoid through cracks, M.S. fixing channelof 99 mm width (0.9 mm thick having two flanges of 9.5 mm each) to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flat head screws, including jointing and finishing to a flush finish with recommended jointing compound, jointing tape, angle beads at corners (25 mm x 25 mm x0.5 mm), joint finisher and two coats of primer suitable for board as per manufacture"s specification and direction of engineer in charge all complete.66 mm overall thickness Partition with 8 mm thick double skin Calcium Silicate Board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process with Compressive Strength 225 kg/sq cm, Bending Strength 100 kg/sq cm
49FINISHES
5013.43.1 : Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
5113.60.1 : Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work
5213.80 : Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
53MINOR CIVIL WORKS
542.8.1 : Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
552.25 : Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
564.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
57Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to siteof laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. (Note :- Minimum Cement content is 330 kg/cum and no payment shall be made for extra cement however contractor shall be bound to use required cement quantity as per the approved mix design)All work upto plinth level
58Providing and fixing at or near ground level precast cement concrete in slabs,kerbs, edgings etc. as per approved pattern and setting in position with cement mortar 1:3 (1 cement : 3 coarse sand), including the cost of required centering, shuttering complete.1:1.5:3 ( 1 cement : 1.5 coarse sand (Zone III): 3 graded stone aggregate 20 mm nominal size)
595.9.1 : Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
605.9.2 : Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
615.22.6 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
6219.6.4 : Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 ( 1 cement : 2 fine sand) including testing of joints etc. complete:300 mm dia R.C.C. pipe
63CIVIL WORKS FOR PHE
6419.16 : Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS: 10910 on 12 mm dia steeel barconforming to IS:1786, having minimum cross section as 23 mm x 25 mm and over allminimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufactures permanent identification mark to be visible even after fixing including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 ( 1cement: 3 coarse sand: 6 graded stone aggregate 20 mm nominal size) Complete as per design
652.10.1.1 : Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within alead of 50 m:All kinds of soilPipes, cables etc, not exceeding 80 mm dia
662.10.1.2 : Excavating trenches of required width for pipes, cables, etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 m, including getting out the excavated soil. and then returning the soil as required, in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed, within alead of 50 m:Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia
6718.41.1A : Providing and filling sand of grading zone V or coarser grade, all - round the G.I. pipes in external workSub analysis item for sand filling component
684.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
69Supplying, Installation, Testing and Commissioning of the Ductile Iron Circular Manhole cover with Frame (Double seal with EPDM Gasket and SS Bolting arrangement lifting key holes & load tested as per IS:1726 & BS EN:124.600mm Dia. (Medium duty) (Minimum weight 68Kg).
70Supplying, Installation, Testing and Commissioning of the Ductile Iron Rectangular Manhole cover with Frame (Double seal with EPDM Gasket and SS Bolting arrangement lifting key holes &load tested as per IS:1726 & BS EN:124.600x 900. (Heavy duty) (Minimum weight 135Kg).
71Supplying, Installation, Testing and Commissioning of the Ductile Iron Circular Manhole cover with Frame (Double seal with EPDM Gasket and SS Bolting arrangement lifting key holes & load tested as per IS:1726 &BS EN:124.600mm Dia. (Heavy duty) (Minimum weight 75Kg).
72CIVIL WORK FOR MANHOLE
732.8.1 : Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
742.25 : Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
752.26.1 : Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil
764.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
775.1.2 : Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size
78Providing and fixing at or near ground level precast cement concrete in slabs,kerbs, edgings etc. as per approved pattern and setting in position with cement mortar 1:3 (1 cement : 3 coarse sand), including the cost of required centering, shuttering complete.1:1.5:3 ( 1 cement : 1.5 coarse sand (Zone III): 3 graded stone aggregate 20 mm nominal size)
795.22.6 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
805.9.1 : Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
815.9.2 : Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
825.9.6 : Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
8313.16.1 : 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
84Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In stringers, treads,landings etc. of stair cases, including use of chequered plate wherever required, all complete
85SH 2 - PUBLIC HEALTH ENGINEERING SYSTEM SANITARY FIXTURES, BATH FITTINGS AND ACCESSORIES
86Providing, fixing, testing, and commissioning at site White Vitreous China Extended Wall Mounted EWC,Complete Set with 3/6 LPF Dual Cistern, overall size 620 x 350 x 750 mm. or as per approved model and shape, including Cistern Fittings, Soft Close Seat Cover, bolts, nuts, washers, expansion/ rawl sleeves,gasket etc. complete, and fixing to wall, as per manufacturer"s instruction and to the approval of Engineer-in-charge.Model Hindware 20096 / Kerovit KO139W / Cera S1031101 or equivalent
87Providing, fixing, testing, and commissioning at site Disabled Toilet, Complete Set, including White Vitreous China Extended Wall Mounted EWC, Complete Set with 3/6 LPF Dual Cistern, overall size 620 x 350 x 750 mm. or as per approved model and shape, including Cistern Fittings, Soft Close Seat Cover,bolts, nuts, washers, expansion/ rawl sleeves, gasket etc. complete, and fixing to wall, One number Wash basin, Elbow Operated Pillar tap and with 1 Set of Hinged Arm, 760mm. long, 4 Set of Grab Rail, each of 600mm. long, and with all necessary accessories and fixed with Brackets Expansion/ Rawl Sleeves, Stainless Steel/ Brass Bolts/Screws, Nuts, Washers etc, including cutting and making good the walls and floors wherever required including, all as per manufacturer"s instruction and to the approval of Engineer in-charge.
88Supplying, installing, testing & commissioning at site in position Grab Bar up to 600mm complete.
8917.80 : Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx.size 610x390x370 mm having pre & post flushing with water ( 250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer - in-charge.
908.10.2 : Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in Charge and finished smooth.Granite Stone of approved shade
9117.7.4 : Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 550x400mm with single 15 mm C.P.brass pillar taps
9217.7.8 : Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Surgeon type wash basin of size 660x460 mm with a pair of 15 mm C.P. brass pillar taps with elbow operated levers
93Supplying, installing, testing & commissioning at site in position white / colour vitreous china wash basin (480x365x205mm) with C.I./MS brackets painted white, C.P brass waste coupling of standard pattern,32mm dia C.P, basin Pillarcock with aerator, including cutting & making good the walls wherever required complete.Wash basin below counter type with aerator PillarCock.
9417.11.2 : Providing and fixing white vitreous china laboratory sink with C.I brackets, C.P. brass chain with rubber plug 40 mm C.P brass waste and 40 mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required:Size 600x450x200 mm
95Providing, fixing, testing, and commissioning at site Single Lever Surgical Purpose Elbow Action Sink Mixer (Wall Mounted)with aerator Extended Operating Lever, Connecting legs & wall flanges, 15mm. nominal bore, including all necessary accessories, all as per manufacturer"s instruction and to the approval of the Engineer-in-charge. Model: Jaquar FLR-CHR-5166
96Hot & cold CP aerator wall mixer unit - Providing, Fixing, testing and commissioning Of Hot & cold CP wall mixer unit with long bend pipe for overhead shower with all accessories.
9718.22.1 : Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet:100 mm diameter
98Providing, fixing, testing, and commissioning at site Wall Mounted Shower Arm (220mm Length) with wall flange including cutting and making good the walls and floors wherever required, all as per manufacturer"s instruction and to the approval of Engineer-in-charge.
9918.52.1 : Providing and fixing C.P brass stop cock ( concealed) of standard design and of approved make conforming to IS: 893115 mm nominal bore
10018.51.1 : Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
10150.17.1.5 : Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
10218.53.1 : Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore
10318.21.2.1 : Providing and fixing uplasticised PVC connectionpipe with brass unions:45 cm length15 mmnominal bore
10417.10.1.1 : Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required:Kitchen sink with drain board510x1040 mm bowl depth 250 mm
10517.10.2.2 : Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required:Kitchen sink without drain board610x460 mm bowl depth 200 mm
106Providing, fixing, testing, and commissioning at site Kitchen Sink Cock with aerator, Wall Mounted Type 15mm. nominal bore, overall dimensions: 208x237mm, including all necessary accessories, all as per manufacturer"s instruction and to the approval of the Engineer-in-charge.
10717.71 : Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms
10850.17.1.1 : Supplying and fixing Stainless steel soap dish including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
10917.72 : Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms
110Providing and fixing C. P. Robe Hook,60mm. Dia.x 45mm. High.
11117.34.1 : Providing and fixing toilet paper holder:C.P. brass
11250.17.1.3 : Supplying and fixing CP Towel rod 60cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
11317.31 : Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
114Providing,fixing testing and commissioning 1½"x 40x300 Plastic P Trap (P Trap) for Sink. Adjusting pipe 120mm, drain elbow 220mm.
115INTERNAL DRAINAGE
116Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type B (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm),Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site.(For Soil & Waste pipes -Internal).110mm OD
11750.18.8.9.1 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chased and making good the wall etc. 110 mm pipe 6kgf/cm2
118Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type B (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters, rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site(For Soil & Waste pipes -Internal).75mm OD
119Supplying, Installing, Testing & Commissioning at site in position uPVC pipe of 6Kg/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, "Y",couplings, adapters & clamping with Universal clamps 1mtr spacing, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site (For Soil & Waste pipes -Internal). 63 mm (IS 4985,6kgf/cm2)
120Supplying, Installing, Testing & Commissioning at site in position uPVC pipe of 6Kg/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, "Y",couplings, adapters & clamping with Universal clamps 1mtr spacing, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site.(For Soil & Waste pipes -Internal).50 mm (IS 4985,6kgf/cm2)
12150.18.8.6.2 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 50 mm pipe 6 kgf/cm2
12250.18.8.5.2 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 40 mm pipe 6Kgf/cm2
123Supplying, Installing, Testing & Commissioning at site in position uPVC pipe of 10Kg/sq.cm (IS:4985) including injection moulded fittings with bosses where required eg 90 Degree bend, 45 Degree bends, "Y",couplings, adapters & clamping with Universal clamps 1mtr spacing, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site.32 mm OD (10kg/cm2)- for sunken drain
12450.18.8.4.1 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge.Concealed work, including cutting chases and making good the wall etc. 32 mm pipe 10Kgf/cm2
125Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of Type A (IS:13592) including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends, Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm),Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site (For Vent pipes -Internal).75mm OD
126Supplying, Installing, Testing & Commissioning at site in position uPVC pipe (SWR) of 4kg/cm2 (IS:4985)including injection moulded fittings with bosses where required eg 90 Degree, 45 Degree bends,Y, couplings, adapters,rodding eye & clamping with Universal clamps, Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete; and jointing with approved adhesive by manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site (For Vent pipes -Internal).63mm OD
12750.18.8.7.2 : Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc 63 mm pipe 4 kgf/ cm2
128Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, "Y", bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping).Core Cutting in RCC Structure shall measured separately.Clamping details - For Vertical Shafts G.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ""STD Powder Coated Clamping details - For Suspended lines.G.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.160mm OD
129Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, "Y", bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping).Core Cutting in RCC Structure shall measured separately.Clamping details - For Vertical ShaftsG.I."U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ""STD Powder CoatedClamping details - For Suspended linesG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.110mm OD
130Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type B(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, "Y", bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping).Core Cutting in RCC Structure shall measured separately.Clamping details - For Vertical ShaftsG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ""STD Powder CoatedClamping details - For Suspended linesG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.75mm OD
131Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type A(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, "Y", bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).Clamping details - For Vertical ShaftsG.I. "U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ""STD Powder CoatedClamping details - For Suspended linesG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.160 mm OD
132Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe (SWR) of Type A(IS:13592) including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, "Y", bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).Clamping details - For Vertical ShaftsG.I. ""U"" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ""STD Powder CoatedClamping details - For Suspended linesG.I. "U" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm), Threaded Rod(10mm), nuts, washers etc complete.110mm OD
133Supplying, Installing, Testing & Commissioning at site in position Ring uPVC pipe of 4kg/cm2 (IS:4985))including SWR jointing with Rubber Ring Seal (IS 5382) PVC Moulded (IS 14735 )fittings with bosses where required eg.Door tees, Door bends, "Y", bends, clamps, couplings, adapters, rodding eye and cowls with sealing grooves and clamping with Position, including cutting and making good the walls and floors as required at site (For Vertical & Horizontal Shaft piping for rainwater/Vent).Clamping details -For Vertical ShaftsG.I."U" bolts (8 mm thick) on G.I. slotted rails (1.6 / 2.5 mm thick) , Rail Leg 2 1/2 ""STD Powder CoatedClamping details - For Suspended linesG.I. ""U"" bolts (8 mm thick) on Heavy Duty G.I.slotted rails(2.5 mm thick) or Clamping with Universal clamps, Anchor fastners(10mm),Threaded Rod(10mm), nuts, washers etc complete.63 mm OD(4kg/cm2)
134Deep Seal uPVC fabricated Multi floor trap - Providing, Fixing, testing and commissioning at site in position Deep Seal (7”) uPVC Fabricated Multi Floor Trap, with suitable supporting on GI slotted rails (1.6mmthick) full threaded rod, Anchor fasteners etc. complete in all respects - 50/75 mm dia inlet/outlet (In Ceiling)
135uPVC fabricated Multi floor trap - Providing, Fixing, testing and commissioning at site in position uPVC Fabricated Multi Floor Trap, with thrust block support including complete cost o cutting chases and making good the walls in all respects - 50/75 mm dia inlet/outlet (In Sunken)
136Supplying, installing, testing & commissioning at site in position 110mm dia deep seal PVC P Trap with boss tee and access cap including all necessary fittings and supports complete.
137Providing and Fixing C.P. brass or stainless steel(SS-304) Square Flat cut single piece Gratings size 125x125 mm. Gratings for 110mm. Floor Traps.
138Heavyduty stainless steel cover for Concealed Floor Trap for Urinal - Providing and Fixing 125x125mm dia Heavyduty stainless steel cover for Concealed Floor Trap ISI 304 Cover, for Urinal
13917.35.1.3 : Providing and fixing soil, waste and vent pipes:100 mm diaHubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
140Heavyduty stainless steel cleanout cover - Providing and Fixing Heavy Duty Stainless Steel A ISI 304 Clean out Cover, sealed, threaded covers, including suitable in sert keys for opening, if required.
14117.38.1.3 : Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete.100 mm dia Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
14217.39.1.3 : Providing and fixing plain bend of required degree.100 mm diaHubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
14317.42.1.3 : Providing and fixing double equal plain junction of required degree.100x100x100x100 mmHubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
14417.44.1.3 : Providing and fixing single equal plain junction of required degree:100x100x100 mmHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
14517.49.1.3 : Providing and fixing double equal plain invert branch of required degree:100x100x100x100 mmHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
14617.50.1.3 : Providing and fixing single equal plain invert branch of required degree:100x100x100 mmHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
14717.56.1.3 : Providing and fixing terminal guard:100 mmHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
14817.60.1.3 : Providing and fixing trap of self cleansing design with screwed down or hinged grating without vent arm complete, including cost of cutting and making good the walls and floors:100 mm inlet and 100 mm outletHubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
14917.57A.1.1 : Providing and fixing shielded coupling for Hubless centrifugally cast iron pipeSS 304 grade coupling with EPDM rubber gasket
150Supply, fix at site in position, Rain Khurra (Rain Water Outlet) Dome Type with Cast Iron body, Aluminium Ring, Aluminium Dome, S.S. Screws etc. complete with Gratings, suitable for 110mm. of down pipes.100mm dia. for 110mm. PVC Down Pipe
151Supply, fix at site in position, Rain Khurra (Rain Water Outlet) Dome Type with Cast Iron body, Aluminium Ring, Aluminium Dome, S.S. Screws etc. complete with Gratings, suitable for 160mm. of down pipes.150mm dia. for 160mm. PVC Down Pipe
152Supply, fix at site in position, Rain Khurra (Rain Water Outlet) Side Wall Parapet Type in Cast Iron body,Aluminium Gratings, S.S. Screws etc. complete with Gratings, all as per Technical Specifications.100mm dia. for 110mm. PVC Down Pipe
153Supply, fix at site in position, Rain Khurra (Rain Water Outlet) Side Wall Parapet Type in Cast Iron body,Aluminium Gratings, S.S. Screws etc. complete with Gratings, all as per Technical Specifications.150mm dia. for 160mm. PVC Down Pipe
154WATER SUPPLY
15518.7.2 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall 20 mm nominal outer dia pipes
15618.7.1 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall 15 mm nominal outer dia pipes
15718.7.3 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall 25 mm nominal outer dia pipes
15818.7.4 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall 32 mm nominal outer dia pipes
15918.7.5 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall 40 mm nominal outer dia pipes
16018.7.6 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing.This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge.Internal work - Exposed on wall 50 mm nominal outer dia pipes
16118.8.1 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge.Concealed work, including cutting chases and making good the wall etc.15 mm nominal outer dia pipes
16218.8.2 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge.Concealed work, including cutting chases and making good the wall etc.20 mm nominal outer dia pipes
16318.8.3 : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge.Concealed work, including cutting chases and making good the wall etc.25 mm nominal outer dia pipes
164Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall - Ceiling and Shaft65 mm nominal outer dia. Pipes.
165Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work -Exposed on wall -- Ceiling and Shaft-15 mm nominal outer dia. Pipes.
166Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work -Exposed on wall - Ceiling and Shaft20 mm nominal outer dia. Pipes.
167Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings,fixing the pipe with Universal clamps/U bolt at 1.00 m spacing, Anchor fastners (8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work -Exposed on wall - Ceiling and Shaft25 mm nominal outer dia. Pipes.
168Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work -Exposed on wall - Ceiling and Shaft32 mm nominal outer dia. Pipes
169Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall - Ceiling and Shaft40 mm nominal outer dia. Pipes.
170Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, fixing the pipe with Universal clamps/U bolt at 1.00 m spacing,Anchor fastners(8mm), Threaded Rod(8mm), nuts, washers etc complete. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall - Ceiling and Shaft -50 mm nominal outer dia. Pipes.
171Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work -Exposed on wall - Ceiling and Shaft65 mm nominal outer dia. Pipes
172Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work -Exposed on wall - Ceiling and Shaft80 mm nominal outer dia. Pipes.
173Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work -Exposed on wall - Ceiling and Shaft100 mm nominal outer dia. Pipes.
174Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings,fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step uPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall - Ceiling and Shaft150 mm nominal outer dia. Pipes
17518.18.1 : Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:15 mm nominal bore
17618.18.2 : Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:20 mm nominal bore
17718.18.3 : Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:25 mm nominal bore
17818.17.2 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :32 mm nominal bore
17918.17.3 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :40 mm nominal bore
18018.17.4 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :50 mm nominal bore
18118.19.2.1 : Providing and fixing gun metal non-return valve of approved quality (screwed end):32 mm nominal bore Horizontal
18218.19.3.1 : Providing and fixing gun metal non-return valve of approved quality (screwed end):40 mm nominal bore Horizontal
18318.19.4.1 : Providing and fixing gun metal non-return valve of approved quality (screwed end):50 mm nominal bore Horizontal
18418.19.5.1 : Providing and fixing gun metal non-return valve of approved quality (screwed end):65 mm nominal bore Horizontal
185Brass Automatic Air Release Valves - Providing, Fixing, testing and commissioning at site in positions Brass Automatic Air Release Valves, of approved quality and make on the top of the vertical water supply pipes as per specification and drawing - 3/4"(20mm) dia
186Supplying, Installing & Testing at site in position Brass Float valve (PN 10) of approved make with PP float & nipple with brass threaded in-sert, brass back nuts, piston and bolts etc complete in all respect to the satisfaction of Project Manager. 40mm dia (1 ½”)
187Supplying, Installing & Testing at site in position Brass Float valve (PN10) of approved make with PP float & nipple with brass threaded in-sert, brass back nuts, piston and bolts etc complete in all respect to the satisfaction of Project Manager. 50mm dia (2”)
188Supplying, Installing & Testing at site in position Brass Float valve (PN10) of approved make with PP float & nipple with brass threaded in-sert, brass back nuts, piston and bolts etc complete in all respect to the satisfaction of Project Manager. 65mm dia (2 1/2”)
189SS ball valve 50mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. - 2”(50mm) dia
190SS ball valve 40mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. - 1½”(40mm)dia
191SS ball valve 32mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. - 1¼”(32mm) dia
192SS ball valve 25mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. - 1” (25mm) dia
193SS ball valve 20mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. - ¾” (20mm) dia
194SS ball valve 15mm dia - Providing, Fixing at site in position full way lever operated SS ball valve (screwed end)of SS body (316) of approved make with necessary MTA fittings in position as per drawings. - ½” (15mm) dia
195Providing and fixing C.I. Sluice Valve, PN-16, with IS: 14846 Mark, with required flanges, rubber fitting, bolts, nuts, Washers etc. complete. 100mm. PN-16
196CI Butterfly valve 250mm dia (PN 10) - Providing, Fixing at site in position CI Butterfly valve (PN 10) gear operated type of approved make with necessary PVC flanges, gaskets, nuts and bolts etc complete as per drawing - 10"(250mm)dia
19718.17.5 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :65 mm nominal bore
19818.17.6 : Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :80 mm nominal bore
199Providing and Fixing Ball Type Foot Valve. PN 10, with Cast Iron Body Nitrile Reinforced Ball, Screwed End, required in the Suction Lines of for Water Transfer and Distribution Pumps.65mm.
200Providing and Fixing Ball Type Foot Valve. PN 10, with Cast Iron Body Nitrile Reinforced Ball, Screwed End, required in the Suction Lines of for Water Transfer and Distribution Pumps.50mm.
201Supplying, installing,Testing & commissioning at site in position Multi Jet Water Meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser,retrofitable for pulse output and conforming to ISO-4064 Class B complete.Water meter 40mm
202Supplying, installing,Testing & commissioning at site in position Multi Jet Water Meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser,retrofitable for pulse output and conforming to ISO-4064 Class B complete.Water meter 50mm
203Supplying, installing,Testing & commissioning at site in position Multi Jet Water Meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser,retrofitable for pulse output and conforming to ISO-4064 Class B complete.Water meter 65mm
204Supplying, installing,Testing & commissioning at site in position Multi Jet Water Meter with unions of removable mechanism type, magnetically coupled, having dry dial, hermetically sealed totaliser,retrofitable for pulse output and conforming to ISO-4064 Class B complete.Water meter 80mm
205CI Y Strainer 2” (50mm) dia - Supply,Installation,Testing and Commisioning of CI Y-type stainer with drain plug, SS screen 304 complete in all respects.
206CI Y Strainer 2 ½” (65mm) dia - Supply,Installation,Testing and Commissioning of CI Y-type stainer with drain plug, SS screen 304 complete in all respects.
207CI Y Strainer 3” (80mm) dia - Supply,Installation,Testing and Commissioning of CI Y-type stainer with drain plug, SS screen 304 complete in all respects -
208CI Y Strainer 4” (100mm) dia - Supply,Installation,Testing and Commissioning of CI Y-type stainer with drain plug, SS screen 304 complete in all respects
209Exposed Pipe Work in Celling Void & at Terrace for Hot Water Services and Hot Water Return Pipework at Terrace shall be with 9mm. thick flexible closed cell elastomeric thermal insulation and additional protection with Poly Shield Coating all from Approved Manufactures, all as per Technical Specifications and to the approval of Engineer - in- charge. (For Hot water Piping)For 20mm. (3/4") pipe.
210Exposed Pipe Work in Celling Void & at Terrace for Hot Water Services and Hot Water Return Pipework at Terrace shall be with 9mm. thick flexible closed cell elastomeric thermal insulation and additional protection with Poly Shield Coating all from Approved Manufactures, all as per Technical Specifications and to the approval of Engineer - in- charge. (For Hot water Piping)For 25mm. (1") pipe.
211Exposed Pipe Work in Celling Void & at Terrace for Hot Water Services and Hot Water Return Pipework at Terrace shall be with 9mm. thick flexible closed cell elastomeric thermal insulation and additional protection with Poly Shield Coating all from Approved Manufactures, all as per Technical Specifications and to the approval of Engineer - in- charge. (For Hot water Piping)For 15mm. (1/2") pipe.
212Exposed Pipe Work in Celling Void & at Terrace for Hot Water Services and Hot Water Return Pipework at Terrace shall be with 9mm. thick flexible closed cell elastomeric thermal insulation and additional protection with Poly Shield Coating all from Approved Manufactures, all as per Technical Specifications and to the approval of Engineer - in- charge. (For Hot water Piping)For 40mm. (1 1/2") pipe.
213Exposed Pipe Work in Celling Void & at Terrace for Hot Water Services and Hot Water Return Pipework at Terrace shall be with 9mm. thick flexible closed cell elastomeric thermal insulation and additional protection with Poly Shield Coating all from Approved Manufactures, all as per Technical Specifications and to the approval of Engineer - in- charge. (For Hot water Piping)For 32mm. (1 1/4") pipe.
214MISCELLANEOUS
215Making holes in RCC beams, slabs floors etc, using core cutting machine, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC beams, slabs floors (Upto 300 mm thick)-160 mm dia
216Making holes in RCC beams, slabs floors etc, using core cutting machine, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC beams, slabs floors (Upto 300 mm thick) - 200mm dia.
217Making holes in RCC beams, slabs floors etc, using core cutting machine, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC beams, slabs floors (Upto 300 mm thick) - 110mm dia.
218Making holes in RCC beams, slabs floors etc, using core cutting machine, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC beams, slabs floors (Upto 300 mm thick) - 75mm dia.
219Making holes in RCC beams, slabs floors etc, using core cutting machine, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC beams, slabs floors (Upto 300 mm thick) - 50mm dia.
220Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound (Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick - For 160mm dia. pipe
221Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound (Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick -for 110mm dia pipe.
222Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required,complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick - 75mm dia.
223Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required,complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick- 63mm dia.
224Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound (Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick- 50mm dia
225Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required,complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick- 40mm dia
226Making holes in RCC beams, slabs floors etc, using core cutting machine, for laying pipes with standard clearance and rendering the same in RCC M 20, including nominal reinforcement wherever required, complete.The quoted rate shall also include water proofing compound(Conbextra GP-2 / GP-10) for complete sealing the same joints around the pipes for full depth etc to the satisfaction of the Project Manager including supply of all materials. RCC slabs (For Wash Basin, EWC & Floor Trap) 130 mm thick- 32mm dia.
227VALVES
22816.11.1.2 : Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Butterfly Valve ( Manual) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specifiedButterfly Valve ( Manual) of 150 mm dia
22916.11.1.4 : Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Butterfly Valve ( Manual) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specifiedButterfly Valve ( Manual) 100 mm dia
23016.11.1.5 : Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Butterfly Valve ( Manual) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specifiedButterfly Valve ( Manual) 80 mm dia
23116.11.1.6 : Supplying, fixing testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.Butterfly Valve ( Manual) with C I body SS disc nitrile sheet & O ring & PN 16 pressure rating as specifiedButterfly Valve ( Manual) 65 mm dia
232EXTERNAL DRAINAGE
233Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation including Supplying, Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete(excluding excavation)200mm OD
234Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation including Supplying, Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete(excluding excavation)160mm OD
235Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation including Supplying, Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete(excluding excavation)110mm OD
236Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(6kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation including Supplying, Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete (excluding excavation)75mm OD
237Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(4kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation including Supplying Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for rain water pipes) complete200mm OD
238Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(4kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation including Supplying Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for rain water pipes) complete160mm OD
239Supplying, Installing & Testing of pipes and conveying to position; and jointing to true lines and gradients, PVC pipe of IS 4985(4kg/cm2), jointing the pipe line as per specification, testing the pipe line after installation including Supplying, Installing specials like bends, couplers, sockets, connections etc. as per provisions of IS: 1742-1983 (Code of practice for building drainage) complete(excluding excavation)110mm OD
240Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.External work (Including excavation)20 mm nominal outer dia Pipes
241Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.External work (Including excavation)25 mm nominal outer dia Pipes
242Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.External work (Including excavation)32 mm nominal outer dia Pipes
243Providing and fixing uPVC Pipes, Sch. 40 (ASTM D 1785) and with Sch. 40 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.External work (Including excavation)40 mm nominal outer dia Pipes"
244Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2467) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.External work (Including excavation)50 mm nominal outer dia Pipes"
245Providing and fixing uPVC Pipes, Sch. 80 (ASTM D 1785) and with Sch. 80 (ASTM D 2466) Fittings, This includes jointing of pipes & fittings with one step uPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge.External work (Including excavation)65 mm nominal outer dia Pipes"
246Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching,refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 10Kgf/cm2
247Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching,refilling & testing of Joints complete as per direction of engineer in charge.90 mm dia 10Kgf/cm2
248Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching,refilling & testing of Joints complete as per direction of engineer in charge.75 mm dia 10Kgf/cm2
249Supply, installation, testing and commissioning of stainless steel coarse Screen (opening 10mm) suitable for screen chamber of size 500mmx500mm removable type including all material charges, labour transportation, loading unloading etc. Complete as per the direction of Engineer in charge.
250Supplying, Installing & Testing at site in position best quality PVC gully trap of size 160 X110mm outlet embedded in plain cement concrete 1:4:8 (20mm metal), all the above encased in a chamber of 300 X 300mm built with 115mm thick brick masonry using first class country bricks in CM 1:3 over a bed of CC 1:4:8 using 40mm size metal 100mm thick ,plastering with CM1:3,13mm thick inside, outside, exposed top surfaces and internal and top exposed surface finished smooth with a floating coat of neat cement, providing and fixing Ductile Iron(Hinged type) frame and cover of size 300 X 300mm weighing not less than 8 kgs load tested as per IS:1726 fixing the frame in PCC 1:2:4 using 20mm stone metal including painting the frame and cover with 2 coats of anticorrosive black bitumastic painting etc. complete all as specified and directed.
251PLUMBING PUMPS AND HEAT PUMPS
252Supply, Installation, Testing and Commissioning 2 nos, Vertical Centrifugal Pump Set, having SS Impeller and Shafts, CI/SS Casing, Mechanical Seal Each pumps should be capable to deliver 12.00lps @ 53mtr head, Head range 40 to 67 mtrs, ""F"" class Insulation, IE3 Rated Electric Motors, IP 55 Protection with Wall mounting Microprocessor based common control Panel to operate the pump set as ( 1Working + 1Standby ) Star Delta, having features of automatic pump change over in every Start/Stop, Dry run, Overload, Phase Reversal Protections etc. level controller for Auto Start/ Stop Function with sufficient length cable, Digital display, Pressure gauge - 2nos, Float Switches, Auto/Manuel Operation.
253Supply, Installation, Testing and Commissioning Pressure Booster Flushing Water Distribution System with Factory Assembled Packaged Pump Set, complete with 3 Vertical Multistage Inline Pumps, with S.S Impeller, Shafts, CI/SS Casing, One Working, One Assist and 1 Stand by Pumps, each of Capacity: 5M3/Hr @ 45 Mtr. Head, each, with 3Ph, ""F"" class Insulation, IE3 Rated Electric Motors, IP 55 Protection,VFD Drive, Automatic Microprocessor Based Control Panel, Pressure Transducer Sensors, Pressure Gauges, 200Ltr. Diaphragm Pressure Vessel, Individual Suction Lines, Common Delivery Manifolds,Isolating Valves, Non Return Valves, Pressure gauge, Fittings, Accessories etc, all a on common frame. .etc, all a on common frame. The Quoted Price for the Pump Set shall be inclusive of connected Electrical Work, all as per Technical Specifications.Each Pump Shall be capable of working with Negative Suction for Pumping Raw Water from a Depth of 3.5 Mtr, The Manufacturer can decide the Pumps accordingly.
254SEWAGE & WASTE WATER TRANSFER PUMPS AND ACCESSORIES Shall be Heavy Duty, Durable & Long Lasting Pumps with High Efficiency Electrical Motors, One Working + Cyclically Stand by with Microprocessor Based Control Panel, for Auto and Cyclic Operation, Float Switches, for Auto Start and Stop of Pumps, Feet / Base, Stainless Steel (Grade:304) Lifting Chains etc, complete. Required upto 35mm size solid handling.Impeller Material: Cast Iron FG 260Shaft Material: S.S AISI 410Capacity: 7.10LPS @ 13Mtr. Head, Head range 3.2 to 19.3 mtr, 3Ph, Complete Set."
255SEWAGE & WASTE WATER TRANSFER PUMPS AND ACCESSORIES Shall be Heavy Duty, Durable & Long Lasting Pumps with High Efficiency Electrical Motors, One Working + Cyclically Stand by with Microprocessor Based Control Panel, for Auto and Cyclic Operation, Float Switches, for Auto Start and Stop of Pumps, Feet / Base, Stainless Steel (Grade:304) Lifting Chains etc, complete. Required upto 35mm size solid handling.Impeller Material: Cast Iron FG 260Shaft Material: S.S AISI 410Capacity: 6LPS @ 11Mtr. Head, Head range 2.9 to 16.6 mtr, 3Ph, Complete Set
256SEWAGE & WASTE WATER TRANSFER PUMPS AND ACCESSORIES Shall be Heavy Duty, Durable & Long Lasting Pumps with High Efficiency Electrical Motors, One Working + Cyclically Stand by with Microprocessor Based Control Panel, for Auto and Cyclic Operation, Float Switches, for Auto Start and Stop of Pumps, Feet / Base, Stainless Steel (Grade:304) Lifting Chains etc, complete. Required upto 35mm size solid handling.Impeller Material: Cast Iron FG 260Shaft Material: S.S AISI 410Capacity: 3LPS @ 14Mtr. Head, Head range 2.9 to 16.6 mtr, 3Ph, Complete Set.
257FILTER FEED PUMP SET.Supply, Testing and Commission Filter Feed Pump Set, Submersible Type for Pumping Raw Water to Water Treatment Plant, 2 Pump System with One Working + 1 One Cyclically Stand by Pumps, each Pump of Capacity: 20M³/Hr. @ 15Mtr. Head, Head range 3 to 18.8 mtr,having CI Casing, SS Shafts, CF8 Impeller with 3Ph, complete with Microprocessor Based Control Panel,for Auto and Cyclic Operation, with all Protection (Digital display, Low &high voltage protection, dry run,phase reversal, pump over load, etc.), Level Sensors / Float Switches in Treated Water & Raw Water Tanks and Control Cabling / Wiring between Level Sensors / Float Switches and Control Panel, Delivery Manifold, Isolating Valves, Non Return valves, Pressure Gauge, Fittings, Stainless Steel (Grade:304)Lifting Chains, Accessories etc. all as per Technical Specifications.The Control Panel shall be capable operating the pumps (starts and stops) by sensing the level difference in water in the Treated Water Tank. Also; capable of ‘not starting or stopping the running pumps", when the water in the underground Raw Water Tank goes below the pre-set minimum level. The Pumps to be installed in the Underground Raw Water Tank and Common Control Panel in the Pump Room, in Basement Floor, approx. 50 Mtr. away from Raw Water Tank. The Underground Power Cabling between Pumps and Control Panel and Control Cabling between Control Panel & Level Sensor / Float Switch, in the Underground Raw Water Tank, shall be measured as a part of Electrical Work. The Quoted Price for the Pump Set shall be inclusive of all above requirement, necessary Level Sensors / Float Switches, Power Cabling, Control Cabling etc, except what measured as a part of Electrical Work, as detailed above.
258Providing, Fixing, Testing and Commission Submersible Type Dewatering Pump Set, complete set with 1 working Submersible non- clog pump, Solids handling: 10mm, and with Common Control Panel for auto and cyclic operation. Capacity 3.5lps at 13.5Mtrs. head each, Head range 5 to 17 mtr, Three Phase, with float switches/level sensors etc. necessary control valves, fittings and accessories, for discharging rain water from collection pits in basement floor, to lower strata. The price shall inclusive of all connected electrical work as detailed in the technical specification.Impeller - Cast Iron FG 260Cast Iron -S.S AISI 410
259Supply, installation, testing & commissioning of Solar assisted Heat pump, insulated pressurised SS storage tank, hot water expansion vessel, insulated piping between the system, valves & accessories required to complete the system in position with the following specification. Solar water heater output 1000 LPD and Heat Pump output capacity 1050 LPH 58 Deg C required Insulated Hot Water Storage Tank suitable for 6 bar pressure SS 316 - 1no, 2000 Litre – Horizontal/Vertical. COP of Heat pump 4. Circulation Pump between heat pump and storage tank, including control panel.Plumbing work Between storage tank and heat pump CPVC Pipe with suitable CPVC Fittings. Suitable Brass Fittings like NRV, Y Strainer, Air Vent, MTA, FTA, Flow Switches, Pipeline Insulation Electrical Work from Pump panel to heat pump 6 Square MM 4 core cable, 1.5 Square MM 3 core cable, 2.5 Square MM cable, Communication cable, 3 x 9Amps 3MP Contactors Coil Operated, PVC conduits for cables with suitable fittings etc., complete.
260Supplying, Installing, Testing & Commissioning at site hot water recirculation pump with suitable pressure switch, dry run protection & The Enclosure should be of IP 55 standards. The Panel should have BMS compatible thro RS 485 Communication( Modbus). Type : Thermostatic Controlled. Horizontal,multistage, end-suction centrifugal pump with axial suction port and radial discharge port. The shaft,impellers and chambers are made of stainless steel. The inlet and discharge parts are made of cast iron.It’s supporting up to 95 degree Celsius temperature, digital control panel with Time and Temperature settings facility.Flow for each pump in LPS : 1.1Head in mtr : 10Head Range : 9 - 18 mtrTotal no of pump: 1 SET ( 1Working + 1Standby )
261SH 3 - ELECTRICAL WORKS ELECTRICAL CONCEALED CONDUITING AND BOX FIXING
2621.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
2631.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
2641.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
265Supplying and fixing following size/ modules, GI box in recess etc. as required. 1 or 2 Module (75mm X 75mm)
266Supplying and fixing following size/ modules, GI box in recess etc. as required. 3 Module (100mm X 75mm)
267Supplying and fixing following size/ modules, GI box in recess etc. as required. 4 Module (125mm X 75mm)
268Supplying and fixing following size/ modules, GI box in recess etc. as required. 6 Module (200mm X 75mm)
269Supplying and fixing following size/ modules, GI box in recess etc. as required. 8Module (125mm X 125mm)
270Supplying and fixing following size/ modules, GI box in recess etc. as required. 12 Module (200mm X 150mm)
271POINT WIRING (BALANCE WORK)
2721.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
2731.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
2741.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
275Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C
2761.55.3 : Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
2771.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
2781.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
2791.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
2801.17.30 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
2811.22.2 : Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.100 mm X 100 mm X 60 mm deep
2821.22.15 : Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.250 mm X 300 mm X 60 mm deep
2831.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
2841.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
2851.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
2861.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
2871.26 : Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
2881.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
2891.27.2 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
2901.28.2 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
2911.28.3 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.4 Module
2921.28.4 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
2931.28.5 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module
2941.28.6 : Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.12 Module
2951.31 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
2961.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
2971.56 : Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings).
298Supplying and fixing suitable size GI box with modular plate and cover in FRLS on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
29990.10.3.23 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant ) 16A 3 pin plug top
30090.10.3.24 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )Step Fan regulator - type 2 M
301Supply & Fixing of Computer points with 3 Nos 3 pin 5/6 A Socket with 3 Nos 5/6 A switch with modular front plate and cover on surface/recess, including providing and fixing suitable size GI boxes/PVC boxes,its interconnections etc, as required complete.
302Wiring for stair case light points with 2.5 sq.mm FRLS PVC insulated copper conductor single core cable in and including surface / recessed medium class PVC conduit and all acessories required for complete installation etc , with 1 way modular switch, modular plate, suitable GI box medium class PVC conduit and all acessories required etc and earthing the point with 2.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required and instructed by engineer in charge/consultant.(Note -Staircase light point shall be controlled by a single switch located inside fire control room in ground floor as per latest fire norms)"- One light point controlled by one way switch (at ground floor)
303Wiring for stair case light points with 2.5 sq.mm FRLS PVC insulated copper conductor single core cable in and including surface / recessed medium class PVC conduit and all acessories required for complete installation etc , with 1 way modular switch, modular plate, suitable GI box medium class PVC conduit and all acessories required etc and earthing the point with 2.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required and instructed by engineer in charge/consultant.(Note - Staircase light point shall be controlled by a single switch located inside fire control room in ground floor as per latest fire norms)"- Loop wiring for Light point
304DISTRIBUTION BOARDS ISOLATORS AND BREAKERS
3052.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
3062.3.3 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
3072.4.1 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)4 way (4 + 12), Double door
3082.4.2 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)6 way (4 + 18), Double door
3092.4.3 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way (4 + 24), Double door
310Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way (4 + 36), Double door
3112.5.1 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB"s (but without MCB"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 way (4 + 12), Double door
312Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB"s (but without MCB"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 6 way (4 + 18), Double door
3132.5.3 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB"s (but without MCB"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)12 way (4 + 36), Double door
3142.14.1 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
3152.14.2 : Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
3162.15.1 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
3172.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
3182.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
3192.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
3202.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
321Supplying and fixing 40 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.40A TP MCB
3222.11 : Supplying and fixing single pole blanking plate inthe existing MCB DB complete etc. as required.
32390.14.10.4 : Supply, conveyance and fixing the following types & current rated control gears & switch gears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
324Supply and fixing of following FP 415V, isolators in sheet steel powder coated enclosure with door interlock and padlock facility on surface confirming to IEC 60947-3 complete with all accesories, connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation. 25A FP Isolator with enclosure
325Supply and fixing of following FP 415V, isolators in sheet steel powder coated enclosure with door interlock and padlock facility on surface confirming to IEC 60947-3 complete with all accesories,connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation. 32A FP Isolator with enclosure
326Supply and fixing of following FP 415V, isolators in sheet steel powder coated enclosure with door interlock and padlock facility on surface confirming to IEC 60947-3 complete with all accesories,connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation. 40A FP Isolator with enclosure
327Supply and fixing of following FP 415V, isolators in sheet steel powder coated enclosure with door interlock and padlock facility on surface confirming to IEC 60947-3 complete with all accesories,connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation. 63A FP Isolator with enclosure
328Supply and fixing of following FP 415V, isolators in sheet steel powder coated enclosure with door interlock and padlock facility on surface confirming to IEC 60947-3 complete with all accesories,connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation. 80A FP Isolator with enclosure
329Supply and fixing of following FP 415V, isolators in sheet steel powder coated enclosure with door interlock and padlock facility on surface confirming to IEC 60947-3 complete with all accesories,connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation. 100A FP Isolator with enclosure
330Supply and fixing of following FP 415V, isolators in sheet steel powder coated enclosure with door interlock and padlock facility on surface confirming to IEC 60947-3 complete with all accesories,connections, testing and commissioning etc as required and as instructed by engineer in charge also making good any damages made during installation. 250A, TPN Switch Disconnector Fuse Unit
3312.21 : Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
3322.22 : Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
3332.23.2 : Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. 2For 8 way, Double door SPN MCBDB
3342.23.3 : Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. 2For 10 way, Double door SPN MCBDB
3352.24.1 : Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 4 way, Double door TPN MCBDB
3362.24.2 : Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 6 way, Double door TPN MCBDB
3372.24.3 : Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.For 8 way, Double door TPN MCBDB
3382.25 : Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for tripple pole and neutral, sheet steel, Vertical MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.
339MV CABLE LAYING
3407.1.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade off following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mm
3417.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade off following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mm
3427.5.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
3437.5.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 35 sq. mm and upto 95 sq. mm
3447.5.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 95 sq. mm and upto 185 sq. mm
3457.5.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 185 sq. mm and upto 400 sq. mm
3467.7.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
3477.7.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
3487.7.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
3497.7.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
3507.8.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
3517.8.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
3527.8.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
3537.8.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
3547.10 : Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
355HT CABLE LAYING
3568.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mm
3578.3.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mm
3588.4.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.Above 120 sq. mm and upto 400 sq. mm
359MV AND HT CABLE JOINING AND END TERMINATION
3609.1.1 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
3619.1.3 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 16 sq. mm (22mm)
3629.1.21 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
3639.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
3649.1.23 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
3659.1.24 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
3669.1.25 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
3679.1.26 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
3689.1.27 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
3699.1.29 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
3709.1.30 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
3719.1.31 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
372Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 4 sq. mm
373Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 6 sq. mm (25mm)
3749.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
3759.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
3769.1.34 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
377HT PANEL, METERING AND TRANSFORMER
378HT PANEL -(detailed specification as per part C)
379Supply, erection, testing and commissioning of dust and vermin proof, floor mounted free standing cubicle type 11kV outdoor metering panel box(detailed specification as per part C)
380Supply, Installation, Testing and Commissioning of 500kVA,11kV/433V, 3 phase, Copper Winding, Air Natural Cooling,DYN-11 Dry Type Indoor Transformer, with vacuum type OLTC Tappings from 5% to - 15% in steps of 1.25%, with Incoming cable box suitable for 3Cx150 sq.mm XLPE cable and LV side suitable for 3 RX3.5CX400 Sq mm A2XFY Cable, as per IS 2026/IS 11171. Transformer losses shall be as per ECBC guidelines amended up to date.
381HT CABLE SUPPLY AND END TERMINATION
38210.4.4 : Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
383Supply of 3 core 150 sqmm 11KV stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments
384Supply of 3 core 300 sqm stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments
38510.5.4 : Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
386Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: 150 sq. mm
387LT CABLE SUPPLY
388Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5cx400sq.mm Al Cable
389Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured aluminium conductor power cable confirming to IS 7098 (part 1) upto date - 3.5x300 sq.mm
390Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5cx240sq.mm Al Cable
391Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5cx185sq.mm Al Cable
392Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5cx150sq.mm Al Cable
393Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5cx120sq.mm Al Cable
394Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.3.5cx95sq.mm Al Cable
395Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.3.5cx70sq.mm Al Cable
396Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.3.5cx50sq.mm Al Cable
397Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 3.5cx35sq.mm Al Cable
398Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.4cx25sq.mm Al Cable
399Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.4x16sq.mm Al Cable
400Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4x10sq.mm Al Cable
401Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4x6sq.mm Al Cable
402Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.4x4sq.mm Al Cable
403Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.2x16sq.mm Al Cable
404Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.2x6sq.mm Al Cable
405Supply and laying and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:7098 (Part-I) of the following sizes in meduin duty conduit / cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms amd making good the damages colour washing etc as required. and instructed by engineer at site/consultant. 1Cx70 Sq.mm Copper Flexible Cable
406Supply and laying and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:1554 (Part-I) 1964 of the following sizes in meduin duty conduit / cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms and making good the damages colour washing etc as required. and instructed by engineer at site/consultant. 12x2.5sq.mm Cu Control Cable
407Supply and laying and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:1554 (Part-I) 1964 of the following sizes in meduin duty conduit / cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms amd making good the damages colour washing etc as required. and instructed by engineer at site/consultant. 4x2.5sq.mm Cu Control Cable
408INSTRUMENTATION CABLE SUPPLY AND END TERMINATION
40990.12.24.9 : Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. 70 sq mm
410Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required. 4Cx2.5 Sqmm Control cable
411Supply of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required 12Cx2.5 Sqmm Control cable
412Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Copper conductor 2XFY power cable confirming to IS 7098 (part 1) amended up to date. 6C x 2.5sq.mm Cu Control Cable
413FAN & LIGHT FIXTURES
414Supply, installation, testing and commissioning of wall fan of 400mm sweep,1200 RPM, . Plastic body & blades with pull cords for speed regulation & wide oscillation control. Aerodynamically designed blades for high air efficiency.
415Supply of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor,class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope,copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers,temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
4161.44 : Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
417Supply, Installation, Testing and Commissioning of Integral LED aviation obstruction light with yellowpainted die-cast aluminium alloy housing, red coloured poly carbonate enclosure
41890.15.3.1 : Supply installation testing commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters
41990.15.3.5 : Supply installation testing and commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70 mm top diameter, 130 mm bottom diameter thickness 3mm base plate dimensions of 200x200x12 mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box etc. complete 7 Meters
420Supply of recess mounted LED Cleanroom fitting 40W(+/- 10% Tolerance) of CRCA powder coated housing, driver with power factor >0.9,THD<10%, rated life of 50,000 hours, system efficacy greater than or equal to 110 lm/W, including all necessary accessories as required for the light fixture. Chip make Cree/Osram/lumilled/Nichea
421Supply of 600 lumen round/ square(1ftX1ft) recessed fitting made of diecast aluminium body, polycarbonate diffuser, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea
422Supply of 1800 lumen round/ square(1ftX1ft) recessed fitting made of diecast aluminium, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea
423Supply of 1800 lumen round/ square surface mount fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea
42490.3.20.3 Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
425Supply of LED Tube Lights of 40W (+/- 10% Tolerance) with Aluminium Profile linear batten power factor >0.95,THD<10%, system efficacy greater than or equal to 100 lm/W, including all necessary accessories as required for the light fixture.Chip make Cree/Osram/lumilled/Nichea
426Supply of LED Mirror Lights of 10W (+/- 10% Tolerance) having driver with power factor >0.95,THD<10%,system efficacy greater than or equal to 80 lm, ANSI rated LEDs from reputed makes should be provided and including all necessary accessories as required for the light fixture. Chip make Cree/Osram/lumilled/Nichea
427Supply of Bulkhead of 10W(+/- 10% Tolerance) having power factor>0.95,THD<10%, system efficacy greater than or equal to 110 lm/W, ANSI rated LEDs from reputed makes should be provided and including all necessary acessories as required for the lightfixture . Chip makeCree / Osram / lumilled/ Nichea
428Supply of 3600 lumen square (2ft X 2ft) recessed fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, including all necessary accessories as required for the light fixture. Chip make Cree/Osram/lumilled/Nichea (UGR less than 19)
429Supply of 2400 lumen square (2ft X 2ft) recessed fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, including all necessary accessories as required for the light fixture. Chip make Cree/Osram/lumilled/Nichea
4301.41 : Installation, testing and commissioning of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
431DIESEL GENERATOR
432Supply, Installation, Testing and Commissioning of 500 kVA prime rated D.G set(detailed specification as per part C)
433Supply, Installation, Testing and Commissioning of 320 kVA prime rated D.G set(detailed specification as per part C)
434Supply, Installation, Testing and Commissioning of 160 kVA prime rated D.G set(detailed specification as per part C)
435LIGHTNING PROTECTION SYSTEM
436Supply, installation and testing of 3 meter air terminal with accessories, providing and fixing air terminals as per IEC -62305 part-3 16mm rod tapered to 10 mm aluminium rod 4 meter rod: Meets the technical specification according to DIN EN 50164 - 2 (VDE 0815 part 202). Meets the requirement of VDE0185/305 (IEC 62305) 101 VL 4000: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. System consist of Fang Fix with base and clamp on the top air terminal is erected. Fang fix clamp made of cable bracket, lightning tested for 100 KA 10/350 micro sec waveform. 2 nos of 16 KG stone of 365 mm diameter, high level of stability. Quick and easy mounting of interception rod using anchors.Concrete, frost-resistant, can be stacked, including all accessories as required for complete installation as instructed by engineer in charge.
437Supply and installation of 8mm solid aluminium round conductor: For concrete building Meets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202). Meets the requirement of VDE0185/305(IEC 62305) RD 8/ALU: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. Polyamide Conductor holder: With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder at 1 meter distance, including all accessories as required for complete installation as instructed by engineer in charge. Vertical run- Down conductor
438Supply and installation of 8mm solid aluminium round conductor: For concrete building Meets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202). Meets the requirement of VDE0185/305(IEC 62305) RD 8/ALU: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. Polyamide Conductor holder: With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder at 1 meter distance, including all accessories as required for complete installation as instructed by engineer in charge.Horizontal run-Parapet application
439Supply and installation of 8mm solid aluminium round conductor: For TERRACE APPLICATION Meets the technical specification according to DIN EN 50164-2 (VDE 0815 part 202). Meets the requirement of VDE0185/305(IEC 62305) RD 8/ALU: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. Stainless steel base with Polyamide Conductor holder top: Adjustable width from 185-260mm. Infinitely adjustable conductor holder. Fast installation using wing screw. Bottom section with 8.5mm diameter slot With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder at 1 meter distance
440Supply and fixing of cross connector / T connector: to route vertical down conductor /mesh formation made of stainless steel/hot dipped galvanised iron with necessary screws etc as required. Installed with 4 hexagonal bolts M8*25 with M8 hexagonal nuts and all accesories as required for complete installation
441Supply and fixing of expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. For round conductor Rd 8/ALU. Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised.Conforms to the requirements according to DIN VDE 0185-305 (IEC 62305) and all accesories as required for complete installation.
442Supply and Fixing Equipotential bonding rail for Lightning Arrestor applications (Test Joint). Equipotential bonding rail for equipotential bonding according to DIN VDE 0100-410/540 and lightning protection equipotetial bonding according to DIN VDE 0185-305. Base plate and cover hood from polystyrene.Colour: Black, UV resistant. Can be used outdoor also. Screw and crossbar made of VA. Capable of carring lightning current 100KA (10/350). Connection options: 7 x single or multi-core conductors to 25mm square or fine core conductors to 16mm square. 1 x round cable Rd 8-10. 1 x flat strip to FL 30 or round cable RD 8-10 including corrosion tapes and all accesories as required for complete installation as instructed by engineer in charge.
443Supply and laying hot dip Galvanised Steel Flat having 70 microns zinc 30X3 mm thick from earth electrode directly in ground as required. Hot Dip GI strip, corrosion resistant. Cross sectional area of 90mm square According to DIN EN 50164-2 (VDE 0185 part 202) Meets the requirement of VDE0185/305(IEC 62305) Zinc coating: 500 g/m square (70 micron coating) Should be tested and use exclusively for lightning protection earthing system and ring equipotential bonding including cross connectors and all accesories as required for complete installation as instructed by engineer in charge.
444Supply and fixing of PVC trapezoidal 1.5m long ducts including the fastening clamps and all accessories as required.
445Providing and fixing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate.
446Supply, installation and testing of maintenance free Earthing system(detailed specification as per part C)
447EARTHING
448Earthing with G.I. earth plate 1200 x 1200 x 12.5 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
449Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling, including necessary clamps and bolts etc and all accessories as required for complete installation as instructed by engineer in charge/consultant. 25x3 Cu strips tinned at the joints
4505.8 : Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
451Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling, including necessary clamps and bolts etc and all accessories as required for complete installation as instructed by engineer in charge/consultant. 32x3 Cu strips tinned at the joints
452Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling, including necessary clamps and bolts etc and all accessories as required for complete installation as instructed by engineer in charge/consultant. 32x6 Cu strips tinned at the joints
453Supply and laying the following sizes of Cu strips laid 0.6 m below ground level including excavating trench of suitable size and refilling, including necessary clamps and bolts etc and all accessories as required for complete installation as instructed by engineer in charge/consultant.40x6 Cu strips tinned at the joints
45490.16.3.9 : Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run) 25 x 3 mm copper strip
45590.16.3.10 : Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run) 25 x 6 mm copper strip
45690.16.1.3 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required(10 SWG)
45790.16.1.4 : Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required ( 8 SWG)
458RISING MAINS, BBT,TAP OFF BOXESAND AUTO TRANSFER SWITCHES
4593.13.1 : Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required400 amps 25 KA SC for 1 sec
4603.13.3 : Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with metal clad enclosure having IP-54 rating after fixing the tap off boxes and all accessories, made of 1.6mm thick steel sheet duly powder coated in convenient sections complete with 4 Nos aluminium bus bars having current density of 130 A/ sq cm at nominal current rating, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size (one on each side) including, G.I. clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required630 amps 50 KA SC for 1 sec
461Supplying, installing, connecting to existing Sandwich Type Bus Trunking/ risingmains, testing and commissioning of following capacity End Feed Unit for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with MCCB/ACB complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required 400 Amp 36kA FP MCCB, Thermal Magnetic Release
462Supplying, installing, connecting to existing Sandwich Type Bus Trunking/ risingmains, testing and commissioning of following capacity End Feed Unit for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick steel sheet enclosure duly powder coated with MCCB/ACB complete with necessary joints including clamping brackets, angle iron bracket, steel fasteners, connecting to earthing system etc. as required 630 Amp 36kA FP MCCB Thermal - Magnetic Release
463Supplying, installing, connecting to existing Sandwich Type Bus Trunking/ rising mains, testing and commissioning of following capacity Plug In/ Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with 1.6mm thick steel sheet enclosure duly powder coated MCCB and all accessories complete etc as required 63 A 25kA FP MCCB in Tap off box
464Supplying, installing, connecting to existing Sandwich Type Bus Trunking/ rising mains, testing and commissioning of following capacity Plug In/ Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C.supply with 1.6mm thick steel sheet enclosure duly powder coated MCCB and all accessories complete etc as required 80 A 25kA FP MCCB in Tap off box
465Supplying, installing, connecting to existing Sandwich Type Bus Trunking/ rising mains, testing and commissioning of following capacity Plug In/ Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C.supply with 1.6mm thick steel sheet enclosure duly powder coated MCCB and all accessories complete etc as required 100 A 25kA FP MCCB in Tap off box
466Supplying, installing, connecting to existing Sandwich Type Bus Trunking/ rising mains, testing and commissioning of following capacity Plug In/ Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with 1.6mm thick steel sheet enclosure duly powder coated MCCB and all accessories complete etc as required 125 A 25kA FP MCCB in Tap off box
467Supplying, installing, connecting to existing Sandwich Type Bus Trunking/ rising mains, testing and commissioning of following capacity Plug In/ Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply with 1.6mm thick steel sheet enclosure duly powder coated MCCB and all accessories complete etc as required200 A 25kA FP MCCB in Tap off box
468Supplying, installing, connecting to existing Sandwich Type Bus Trunking/ rising mains, testing and commissioning of following capacity Plug In/ Tap Off Box for use on 3 phase 4 wire 415 volts, 50Hz A.C.supply with 1.6mm thick steel sheet enclosure duly powder coated MCCB and all accessories complete etc. as required 250 A 25kA FP MCCB in Tap off box
469Supply, erection, testing and commissioning of following capacity auto transfer switch ATys M 3s C30 with enclosure, bus bars and all accessories required for complete operation as per the drawing. The ATS should be double break contact system for high short time withstand. ATS shall be with UV/OV,Phase sequence, Single phasing and frequency protections. 400A 4P ATS
470Supply, erection, testing and commissioning of following capacity auto transfer switch ATys M 3s C30 with enclosure, bus bars and all accessories required for complete operation as per the drawing. The ATS should be double break contact system for high short time withstand. ATS shall be with UV/OV,Phase sequence, Single phasing and frequency protections. 250A 4P ATS
471Supply, erection, testing and commissioning of following capacity auto transfer switch ATys M 3s C30 with enclosure, bus bars and all accessories required for complete operation as per the drawing. The ATS should be double break contact system for high short time withstand. ATS shall be with UV/OV,Phase sequence, Single phasing and frequency protections. 160A 4P ATS
472Supply, erection, testing and commissioning of following capacity auto transfer switch ATys M 3s C30 with enclosure, bus bars and all accessories required for complete operation as per the drawing. The ATS should be double break contact system for high short time withstand. ATS shall be with UV/OV,Phase sequence, Single phasing and frequency protections. 100A 4P ATS
473Supply, erection, testing and commissioning of following capacity auto transfer switch ATys M 3s C30 with enclosure, bus bars and all accessories required for complete operation as per the drawing. The ATS should be double break contact system for high short time withstand. ATS shall be with UV/OV, Phase sequence, Single phasing and frequency protections.63A 4P ATS
474UPS
475Supply, installation, and commissioning of 3x80kw UPS with PRS Configuration.(detailed specification as per part C)
476SAFETY ITEMS
477Supply and providing 2.5/3 mm thick and 1 m wide electrical grade chequered type rubber mat to withstand 11 kV dielectric strength conforming to IS 5429/1969
478Supply and providing 2/3 mm thick sythetic type and 1 m wide electrical grade chequered type rubber mat to withstand 3.3 kV dielectric strength conforming to IS 5429/1969.
479Supply & fixing Laminated drawings of electrical lay out and schematic drawing, shock treatment chart etc on a good laminated frame work.
480Supply and fixing anodised aluminum glass framed shock treatment chart of A3 size.
481Supply and fixing single line diagram, schematic diagrams etc. of A1 size including laminations etc. as required complete on wall.
482Supply and fixing single line diagram, schematic drawing etc of A0 size including lamination etc as required complete on wall.
483Supplying and Providing 15" long rubber hand gloves 15 kV.
484Supply and providing First Aid Box
485Supply and providing laminated First Aid chart duly framed and placed in a conspicuous location for clear vision.
486Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity.Co2 type Fire Extinguisher, made from brand new seamless steel cylinder, as per IS: 7285 and CCE approval, fitted with Discharge hose and horn and Wheel type valve with initial Charge and mounted on Rubber Wheels /wall mounted brackets as per IS: 16018 specification, bearing ISI Mark.4.5Kgs
487Supplying, installing and commissioning Portable Fire extinguishers of following type & capacity. "Clean Agent Modular Type Ceiling mounted Fire Extinguisher 5 Kgs Capacity made of Mild Steel Body of 1.6 mm thickness with pressure gauge, refillable device and safety release device CE Certified Brass valve suitable for A, B and C Classes of Fire complete with Charge of Clean agent (Gas) is also known as HFC Blend A, It is a blend of Hydro Fluoro carbon and organic detossificant essence P26. The sprinkler body will comprise of temperature sensitive quartsoid bulb of temperature rating of 680. The cylinder will be supplied with a proper mounting arrangement to mount it on the ceiling. The Extinguisher shall be externally epoxy powder coated as per IS: 5 Color Shade No. 538 (For Server room)" 5 Kgs
488Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 liter capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribedwith letters “FIRE” in black and gold or , duly painted over a coat of primer. Cost inclusive of providing 4 Nos of sand filled fire bucket and MS stand frame.
489Supply and providing 6mm thick MS chequered plates duly painted. Plates to be cut size as per site requirement
490CABLE TRAY
4914.6.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100 mm width X 50 mm depth X 1.6 mm thickness Details of cost for 30 metres
4924.7.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends " ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
4934.8.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
4944.10.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
4954.9.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ?Cross member? ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
4964.6.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness
4974.7.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends " ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
4984.8.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
4994.9.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ?Cross member? ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
5004.10.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
5014.6.3 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.225 mm width X 50 mm depth X 1.6 mm thickness
5024.7.3 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends " ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
5034.8.3 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
5044.9.3 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ?Cross member? ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
5054.10.3 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.225 mm width X 50 mm depth X 1.6 mm thickness
5064.6.4 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.300 mm width X 50 mm depth X 1.6 mm thickness
5074.7.4 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends " ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
5084.8.4 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
5094.9.4 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ?Cross member? ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
5104.10.4 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
5114.6.10 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.450 mm width X 62.5 mm depth X 2.0 mm thicknessICDDescriptionUnit
5124.7.10 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends " ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 mm width X 62.5 mm depth X 2.0 mm thickness
5134.8.10 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 mm width X 62.5 mm depth X 2.0 mm thickness
5144.9.10 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ?Cross member? ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 mm width X 62.5 mm depth X 2.0 mm thickness
5154.10.10 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.450 mm width X 62.5 mm depth X 2.0 mm thickness
5164.6.7 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.600 mm width X 50 mm depth X 2.0 mm thickness
5174.7.7 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends " ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended fromthe ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 mm width X 50 mm depth X 2.0 mm thickness
5184.8.7 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 mm width X 50 mm depth X 2.0 mm thickness
5194.9.7 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ?Cross member? ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 mm width X 50 mm depth X 2.0 mm thickness
5204.10.7 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.600 mm width X 50 mm depth X 2.0 mm thickness
521LT PANELS
522MAIN PANEL(detailed specification as per part C)
523DG Synchronisation Panel (detailed specification as per part C)
524HVAC MAIN PANEL (detailed specification as per part C)
525MEDICAL EQUIPMENT PANEL (detailed specification as per part C)
526COMMON SERVICE PANEL (detailed specification as per part C)
527EXISTING BUILDING FEEDER PANEL (detailed specification as per part C)
528PLUMBING PANEL (detailed specification as per part C)
529MEDICAL GAS PLANT PANEL (detailed specification as per part C)
530POWER LAUNDRY PANEL (detailed specification as per part C)
531CSSD PANEL (detailed specification as per part C)
532GF RAW POWER PANEL (detailed specification as per part C)
5331F RAW POWER PANEL (detailed specification as per part C)
5342F RAW POWER PANEL (detailed specification as per part C)
5355F RAW POWER PANEL -1 (detailed specification as per part C)
5365F RAW POWER PANEL- 2 (detailed specification as per part C)
537LIFT PANEL 1 (detailed specification as per part C)
538LIFT PANEL 2 (detailed specification as per part C)
5394F UPS PANEL (detailed specification as per part C)
540UPS INPUT PANEL (detailed specification as per part C)
541UPS OUTPUT PANEL (detailed specification as per part C)
542MISCELLANEOUS CIVIL WORKS
54310.2 : Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
544SH 4 - ELV SYSTEM DATA
545Information Outlet RJ 45 - Supply, fixing, fluke testing and commissioning of CAT6 Information Outlets (Key stone) with Shuttered Faceplate, Single port, white, jack, suitable PVC / GI Modular Box etc.including necessary connections with all accessories required for complete installation as directed by the Engineer in charge.
546Information Outlet RJ 45 - Supply, fixing, fluke testing and commissioning of CAT 6A Information Outlets (Key stone) with Shuttered Face plate, Single port, white, jack, suitable PVC / GI Modular Box etc.including necessary connections with all accessories required for complete installation as directed by the Engineer in charge..
547CAT6 Cable - Supplying and drawing of Category 6 LSZH cable consists of 4 pairs of solid insulated copper 23AWG, surface/ recessed medium class PVC conduit through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
548CAT 6A Cable - Supplying and drawing of Category 6A LSZH cable consists of 4 pairs of solid insulated copper 23AWG, surface/ recessed medium class PVC conduit through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
549OFC Cable - Supplying and drawing of 10 core MM (OM4) armoured Optical Fibre Cable (OFC) through wall/tray with all acessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.
550Patch Cable - User Side - Supply, fixing, testing and commissioning of CAT6 Patch Cable - 2 Meterlength etc. of approved make as required for complete installation.
551Patch Cable - Hub Side - Supply, fixing, testing and commissioning of CAT6 Patch Cable - 1 Meter of approved make as required for complete installation.
552Patch Cable - User Side - Supply, fixing, testing and commissioning of CAT6A Patch Cable - 2 Meter length etc. of approved make as required for complete installation.
553Patch Cable - Hub Side - Supply, fixing, testing and commissioning of CAT6A Patch Cable - 1 Meter of approved make as required for complete installation.
554Patch Cable - Hub Side - Supply, fixing, testing and commissioning of Multi Mode Fibre Patch Cable OM4- 2 Meter of approved make as required for complete installation.
555CLOSED CIRCUIT TELEVISION (CCTV)
556Camera for General Area - Dome - Supply, Installation, testing and commissioning of IP based 3.6 mm fixed lens, 2MP resolution,Power Over Ethernet (POE), H.264 / H.265, 1/2.8" Progressive Scan CMOS Day/Night, IR dome POE enabled camera, 20 to 30 meters IR range, 120 dB digital WDR with all connectors and necessary accessories for mounting in false ceiling as required for complete installation as directed by Engineer in charge
557Camera for Lift - Dome - Supply, Installation, testing and commissioning of IP based 2.8 mm fixed lens,2MP resolution, Power Over Ethernet (POE), H.264 / H.265, 1/2.8" Progressive Scan CMOS Day/Night, IR dome POE enabled camera, 20 to 30 meters IR range, 120 dB digital WDR with all connectors and necessary accessories for mounting in false ceiling as required for complete installation as directed by Engineer in charge.
558Camera - Bullet - Supply, Installation,testing and commissioning of Varifocal Bullet Camera with 2 MP, Power Over Ethernet (POE), H.264 / H.265, built-in IR LED, 2.8/3.6 mm to 9/12 mm, 20 to 30 meters IR range, IP 66 with all connectors and necessary accessories for mounting in false ceiling/True Ceiling as required for complete installation as directed by Engineer in charge.
559Network Video Recorder with Storage: Supply, installation, testing and commissioning of Channel Network Video Recorder with Recording Storage space server for 30 days, Supports 64 channels 720P resolution video recording at real time, NVR ONVIF supporting, Recording resolution of Max 4 MP, should support dual video HDMI output, H.265,H.264 at real time. Video storage expansionfor recording for complete installation with all accessories as required and directed by engineer in charge. (Consider the sufficient HDDs for 720p @ 20 FPS for 30 days continues recording for all channels). Storage calculation details shall be submitted.
560LED Display - Supply, installation, testing and commissioning of 43 inch full HD LED display for video wall arrangement for 24 x 7 Setup including necessary connection, HDMI cable, rating tray etc. as required for complete installation with all accessories as required and directed by engineer in charge.
561CAT6 Cable - Supplying and drawing of Category 6 LSZH cable consists of 4 pairs of solid insulated copper 23AWG, surface/ recessed medium class PVC conduit through wall/tray with all accessories as required for complete installation and as instructed by engineer incharge/consultant and making good all damages made for installation.
562Supply, installation, testing and commissioning of workstation with Intel i7 or above, 8 GB RAM, 2 GB graphics card, windows 10 or higher operating system and 1 TB HDD with software for CCTV integration.
563PUBLIC ADDRESSING SYSTEM (PAS)
564Ceiling Mounted Speaker - Supply, fixing, testing and commissioning of ceiling mount Metal Grille Speakers with inbuilt line matching transformer with power 6W with required accessories for installation as required.
565Wall Mounted Speaker - Supply, fixing, testing and commissioning of Cabinet Speakers with inbuilt line matching transformer with power 12W with a volume controller to adjust the volume individually as per the requirement with all accessories for complete installation as required. The volume controller shall be fixed separately as per the site condition for individual control. Cost inclusive of necessary interconnection including conduit, connection wire etc. required for complete installation.
566Supply installation testing and commissioning of volume controller to adjust the volume individually as per the requirement with all accessories for complete installation as required. The volume controller shall be fixed separately as per site conditions for individual control. Cost inclusive of necessary connections including all accessories (wires, conduits etc.) as required.
567Mixing Amplifier - Supply, fixing, testing and commissioning of 240 Watts Mixer Amplifier with necessary jacks and cable for connections and interconnection with all accessories required for installation as required.
568Power Amplifier - Supply, fixing, testing and commissioning of Power Amplifier of 480 Watts with necessary jacks and cable for connections and interconnection with all accessories required for installation as required.
569Controller - Supply, fixing, testing and commissioning of Master zone controller with routing zone capacity of additional 6 zones with all accessories and necessary connections including necessary cables and jacks as required for complete installation. The work also include integration with Fire Alarm System (FAS) including to play the pre-recorded message in case of fire and evacuation.
570Call Stations - Supply, fixing, testing and commissioning of 6 Zone Calling Station with mic as per the drawing as required for complete installation.
571Audio/Video player - Supply, installation, testing & commissioning of Audio/Video player with USB option with all accessories like jacks and codes for complete installation as required as directed by the Engineer in charge.
572Speaker Cable - Supplying and drawing of 2 Core, Twin Twisted, ATC tinned copper, overall sheathed, Armoured Speaker cable, 16 AWG for speakers through surface / Tray with all accessories as required for complete installation and as instructed by engineer incharge /consultant and making good all damages made for installation.
573ATTENDANCE MANAGEMENT SYSTEM
574Supply, Installation, Testing & Commissioning of Fingerprint cum Proximity card based Time & Attendance Device with below features as minimum or higher and with accessories as required to complete the system. Display Minimum 2.5" color type or better Keypad, LED Indicators etc.required- Finger Print Capacity - 5,000 or Higher (500 DPI) Identification Speed<0.5Card Capacity - 5,000 or Higher , Transaction/ Log Capacity1,00,000 or better, Card Reader Type125Khz/ 13.56 MHz (as suitable to match the proposed ACS system) CPU - 32 Bit Processor or better- Support for integration of 3rd party Payroll, HRMS/ EPR etc. applications.- Communication - TCP/IP (10/100)
575Supply, Installation, Testing & Commissioning Time & Attendance software with below features as minimum or higher and with accessories as required to complete the system Creation of Managements of Organizations/ Departments, Shifts, Overtime, leaves and leave policies, various attendance reports as required by the client, Customized reports etc. With Suitable license to connect and manage all the above mentioned features for minimum of 10 Devices and 500 Employees (Also with option for scalability) Support for integration of 3rd party Payroll, HRMS/ EPR etc.applications.
576VOICE
577Information Outlet RJ 11 - Supply, fixing, testing and commissioning of RJ11 Information Outlets (Key stone) with shuttered Faceplate, single port, white, jack, suitable PVC / GI Modular Box etc. including necessary connections with all accessories required for complete installation as directed by the Engineer in charge.
578Cable - Supplying and drawing of following 20 pair telephone cable consists of Compound annealed copper conductor, unarmoured telephone cable in surface / recessed medium class FRS PVC conduit through wall/tray with all accessories as required for complete installation and as instructed by engineer incharge /consultant and making good all damages made for installation.CAT 5 E Cable - Voice.
579Cable - Supplying and laying of following pair armoured telephone cable through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation. 10 Pair Telephone Cable
580Cable - Supplying and laying of following pair armoured telephone cable through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.20 Pair Telephone Cable
581Cable - Supplying and laying of following pair armoured telephone cable through wall/tray with all accessories as required for complete installation and as instructed by engineer in charge/consultant and making good all damages made for installation.100 Pair Telephone Cable.
582krone Box - Supply, erection, testing and commissioning of following pair krone Box with mounting frame, enclosure of ISI grade with lockable front cover with all accessories required for fixing the box with all accessories required for complete installation in wall as directed by the Engineer in charge.30pair
583krone Box - Supply, erection, testing and commissioning of following pair krone Box with mounting frame, enclosure of ISI grade with lockable front cover with all accessories required for fixing the box with all accessories required for complete installation in wall as directed by the Engineer in charge.30pair.
584krone Box - Supply, erection, testing and commissioning of following pair krone Box with mounting frame, enclosure of ISI grade with lockable front cover with all accessories required for fixing the box with all accessories required for complete installation in wall as directed by the Engineer in charge.100 Pair MDF Krone.
585Supply, Installation, Testing and Commissioning of "IP-PBX with 65 Analog extensions expandable up to 100 with minimum of 10 concurrent calls, 1 PRI interface, Failover Function, Web Interface, Call Dashboard, DISA, IVR, Call Hunt etc. including twonumbers master console phone & short key / Direct Station Selection (DSS) Console "Built-In Auto Answer PA Integration TDM/IP Coverage ISDN Compatibility Voice Mail IntegrationPaging Announcement Programmable Function Keys CallWaiting "
586Supply, installation, testing and commissioning of Basic user phone with necessary connection as required for complete installation as directed by the engineer in charge.
587Supply installation testing and commissioning of master telephone with necessary connections as required for complete installation as directed by the engineer in charge. Details attached in technical specification.
588Supply installation testing and commissioning of Direct station selection console with necessary programmable keys with LED.
589Surge Protection Device For EPABX: Supply, Installation, Testing and commissioning of SPD with enclosure, the surge protection device shall be suitable to protect telephone lines designed to with stand both lightning current and switching surges. Technology: GD tube, Nominal Voltage: 180 V, Pulsed Current (10/350 µs ) Iimp: 1 KA, Nominal Discharge Current (8/20 µs) phase In: 5KA, Maximum discharge current: 10 KA,Voltage Protection Level(sym)<700V, Response time<1n sec.
590Supply installation testing and commissioning of 24 – port voice patch panel with necessary cable manager for routing the cables inside the rack with all accessories required for complete installation.Details attached in technical specification.
591Providing and fixing of 2 meter long unshielded twisted pair cat 6 patch cords. Details attached in technical specification.
592ACTIVE COMPONENTS RACKS AND ACCESSORIES
593Supply, Installation, Testing and installation of Cat - 6, shuttered type, 24 port fully loaded patch panel with necessary cable manager for routing the cable inside rack with all accessories required for complete installation as required as directed by the engineer in charge.
594Supply, Installation, Testing and installation of Cat - 6, 24 port 10/100/1000 Mbps, layer 2 with 2 SFP, POE 195W or above, switch with rack mounting brackets, input connector shall be as per IEC-320-C14 with all accessories required for complete installation populated with 1G single SFP module for uplink as required as directed by the engineer in charge. The switch should be capable to provide sufficient power budget to IP cameras as per the requirement.
595Supply, Installation, Testing and installation of Cat - 6, 24 port 10/100/1000 Mbps, layer 2 with 2 SFP, switch with rack mounting brackets, input connector shall be as per IEC-320-C14 with all accessories required for complete installation populated with 1G single SFP module for uplink as required as directed by the engineer in charge. The switch should be capable to provide sufficient power budget to IP cameras as per the requirement.
596Supply, Installation, Testing and installation of Cat - 6, 24 port 10G Switch layer 2, switch with rack mounting brackets, input connector shall be as per IEC-320-C14 with all accessories required for complete installation populated with 1G single SFP module for uplink as required as directed by the engineer in charge. The switch should be capable to provide sufficient power budget to IP cameras as per the requirement.
597Supply, Installation, Testing and installation of 16/24 port 10G SFP Switch with rack mounting brackets, input connector shall be as per IEC-320-C14 with all accessories required for complete installation populated with . The switch should be capable to provide sufficient power budget to IP cameras as per the requirement.
598Supply installation testing and commissioning of 1 G fiber SFP + module Transceivers
599Supply installation testing and commissioning of 10 G fiber SFP + module Transceivers
600Supply, Installation, Testing and installation of 12 port Light Interface Unit (LIU) / Fibre Patch Panel, rack mountable with mounting brackets, loaded with Adaptors, Couplers Single Mode (MM) pigtails with splicing with all accessories required for complete installation as required as directed by the engineer in charge.
601Supply, Installation, Testing and installation of 24 port Light Interface Unit (LIU) / Fibre Patch Panel, rack mountable with mounting brackets, loaded with Adaptors, Couplers Single Mode (SM) pigtails with splicing with all accessories required for complete installation as required as directed by the engineer in charge.
602Supply, installation, testing and commissioning of 9U Rack with Front glass door, Rear Perforated door with handle Lock & key. Front/Rear 9U mounting angles, top, bottom open, RAL 9005, including necessary exhaust / circulation fan with all other accessories required for complete installation as directed by the engineer in charge.
603Supply, installation, testing and commissioning of 15U Rack with Front glass door, Rear Perforated door with handle Lock & key. Front/Rear 12U mounting angles, top, bottom open, RAL 9005, including necessary exhaust / circulation fan with all other accessories required for complete installation as directed by the engineer in charge.
604Supply, installation, testing and commissioning of 42U Rack DK_PS frame with Front glass door, Rear Perforated door with handle Lock & key, castors. Side and rear panels, Front / Rear 42U 800Wx1000D MM mounting angles, top, bottom open, RAL 9005, including necessary exhaust / circulation fan with all other accessories required for complete installation as directed by the engineer in charge.
6054.6.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.100 mm width X 50 mm depth X 1.6 mm thickness Details of cost for 30 metres
6064.6.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.150 mm width X 50 mm depth X 1.6 mm thickness
6074.7.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends " ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
6084.7.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends " ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
6094.8.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
6104.8.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
6114.9.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ?Cross member? ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
6124.9.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray ?Cross member? ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
6134.10.1 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.100 mm width X 50 mm depth X 1.6 mm thickness
6144.10.2 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Reducer" ( galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
615Networkable 2 door access controller with in readers with break glass push button and magnetic lock.
616Access control software with pay roll with license.
617SH 5 - HVAC WORKS WATER CHILLING PLANT
618Supply at site including local transport with full cover insurance, fire or any other contingencies, unload, store, handle, erect, balance, test and commission the entire water chilling plant as per specifications including all accessories as specified for water chilling plant. WATER COOLED TWIN SCREW VFD CHILLER - (R-134A/410) EACH WITH SEMI SEALED / SEALED, SINGLE / MULTIPLE COMPRESSOR OF MINIMUM CAPACITY 90 TR. Minimum Overall Chiller efficiency offered shall have COP 5.8, IPLV 7.1 at AHRI conditions as per ECBC+ building standard / ASHRAE / ARI 550/590 and with ASME U stamping. Summer Ambient conditions: DBT – 95 deg F, WBT- 82 Deg F Comprising of Screw Compressor as per specifications. Drive motors of IE3 ratings 415+/- 10% Volts 50 Hz AC supply and starter panel with VFD starter.(detailed specification as per part C)
619PUMPS AND COOLING TOWER
620Supply, installation, testing & commissioning the chilled water primary pumps as per specification including all accessories as specified and as required. Including Inertia base frame & fixing foundation with necessary fittings as required. End suction Chilled water long coupled Pump sets complete with TEFC sq.cage induction motor (WITH MECHANICAL SEAL) stainless steel shaft, bronze impeller, base plate couplings, pressure gauges (2 Nos. with syphon and gauge cock, anti vibration springs. guards etc. including insulation as per specifications. Pump efficiency shall be MINIMUM 75 % as per ECBC+ Buildings 2017. Capacity : 216 USgpm, 1440rpm, Head:45 feet, Motor:IE 3
621Supply, installation, testing & commissioning the chilled water secondary pumps as per specification including all accessories as specified and as required. Including Inertia base frame & fixing foundation with necessary fittings as required. End suction long coupled Chilled water Pump sets complete with TEFC sq.cage induction motor (WITH MECHANICAL SEAL) stainless steel shaft, bronze impeller, base plate couplings, pressure gauges (2 Nos. with syphon and gauge cock, anti vibration springs. guards etc. including insulation as per specifications. Pump efficiency shall be minimum 75 % as per ECBC+ Buildings 2017. Capacity:216 USgpm, 1440rpm, Head:90 feet, Motor:IE 3.
622Supply, Installation, testing & commissioning the condenser water pumps as per specification including all accessories as specified and as required. Including Inertia base frame & fixing foundation with necessary fittings as required. End suction long coupled Chilled water Pump sets complete with TEFC sq.cage induction motor (WITH MECHANICAL SEAL) stainless steel shaft, bronze impeller, base plate couplings, pressure gauges (2 Nos. with syphon and gauge cock, anti vibration springs. guards etc. including insulation as per specifications. Pump efficiency shall be minimum 75 % as per ECBC+ Buildings 2017.Capacity:360 USgpm, 1440rpm, Head:60 feet, Motor:IE 3.
623Supply, Installation, testing & commissioning the cooling towers as per specification including all accessories as specified and as required..... 90 TR - CTI/JCI approved induced draft, cross flow/counter flow cooling tower with vertical air discharge. EWT = 97.5 degree F, LWT = 90 degree F, WET bulb = 82 degree F, Flow rate = 360 USgpm , Motor rating - IE 3,VFD driven, Efficiency shall be as per ECBC + requirement specified in ECBC 2017.(detailed specification as per part C)
624DOUBLE SKIN AIR HANDLING UNITS WITH VFD, BY-PASS STARTER, PLUG FANS AND THERMAL BREAK
625Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used....10 TR, 4000 CFM, 4 row.Double Skin Ceiling Suspended AHU with mixing Box(detailed specification as per part C)
626Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used......6 TR, 2400 CFM, 4 row.Double Skin Ceiling Suspended AHU.(detailed specification as per part C)
627Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used......6 TR 3000 CFM, 4 row.Double Skin Ceiling Suspended AHU with mixing Box. (detailed specification as per part C)
628Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used.......6 TR 2400 CFM, 4 row.Double Skin Ceiling suspended AHU including heater of 2 x 3kW.(detailed specification as per part C)
629Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used. .......5 TR 2000 CFM, 4 row. Double Skin Ceiling suspended AHU including heater of 2 x 3kW. (detailed specification as per part C)
630Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connnections and control wiring with pressure sensors (minimum 2 Nos.) for complete instation. Only HVAC application VFD"s shall be used.. ......5 TR 2000 CFM, 4 row.Double Skin Ceiling Suspended AHU with mixing Box(detailed specification as per part C)
631Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used......... 20 TR, 8000 cfm, 4row. Double Skin Floor mounted Horizontal AHU with mixing Box.(detailed specification as per part C)
632Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete instation. Only HVAC application VFD"s shall be used.......18 TR 7200 CFM, 4 row.Double Skin Floor mounted Horizontal AHU with mixing Box(detailed specification as per part C)
633Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used.........15 TR 6000 CFM, 4 row.Double Skin Floor mounted Horizontal AHU with mixing Box. (detailed specification as per part C)
634Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connnections and control wiring with pressure sensors (minimum 2 Nos.) for complete instation. Only HVAC application VFD"s shall be used.......12 TR 4800 CFM, 4 row. Double Skin Floor mounted Horizontal AHU with mixing Box. (detailed specification as per part C)
635Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used.......10 TR 4000 CFM, 4 row.Double Skin Floor mounted Horizontal AHU with mixing Box. (detailed specification as per part C)
636Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete instation. Only HVAC application VFD"s shall be used. ...... 20 TR 8000 CFM, 4 row. Double Skin Floor mounted Horizontal AHU with mixing Box and fine filter. (detailed specification as per part C)
637Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connection and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFD"s shall be used.....18 TR 7200 CFM, 4 row. Double Skin Floor mounted Horizontal AHU with mixing Box and fine filter. (detailed specification as per part C)
638Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connnections and control wiring with pressure sensors (minimum 2 Nos.) for complete instation. Only HVAC application VFD"s shall be used.......10 TR 4000 CFM, 4 row. Double Skin Floor mounted Horizontal AHU with mixing Box and fine filter. (detailed specification as per part C)
639Supply, Installation, testing & commissioning the following Air Handling Units as per specification including all accessories as specified and as required for complete installation. The cost inclusive of VFD starter panel in a separate enclosure with necessary rating incomer contactor with by-pass starter system with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete instation. Only HVAC application VFD"s shall be used......4 TR 1600 CFM, 4 row.Double Skin Floor mounted Horizontal AHU with mixing Box and fine filter(detailed specification as per part C)
640TREATED FRESH AIR UNIT WITH HEAT RECOVERY WHEEL, VFD, SUPPLY & RETURN FANS - Supply at site, including, local transport, unload, store, handle, erect, balance and commission of the entire HRW as per specifications including all accessories as specified and as required. .... TFA - 16 TR AHU, 6.5 sq.ft./ 8 Row coil with 3225 CFM Supply fan, 3100 CFM Return fan and heater coil of 2 x 3KW. (detailed specification as per part C)
641FAN COIL UNITS WITH VALVE STATION
642Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and IE3 rated TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skinwith room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)-1 TR Hideway FCU
643Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and IE 3 rated TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)-1.5 TR Hideway FCU
644Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and IE 3 rated TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)-2 TR Hideway FCU
645Supply, installing, testing and commissioning of Fan Coil Units each complete with filters of 20 micron filtering capacity, coil section with chilled water cooling coil and fan section with forward curved multi blade centrifugal blower and IE 3 rated TEFC Sq.cage induction motor, extended drain pan copper connections from isolating ball valve to fan coil unit cooling coil complete with flare-nuts, nipple, brazing of pipe joints, etc. with expansion loop, providing and fixing GM ball valve (with SS ball) with Y strainer for inlet of cooling coils, pipe connection between drain outlet and drain piping with 2nos. hose S clamps, providing and fixing male-female Copper connections from isolating ball valve to fan coil unit cooling coil (15mm/19mm OD) complete flare-nuts nipple, brazing of pipe joints etc. with expansion loop, extended tray double skin with room thermostat cum fan speed selector switch. Including 2 Way Type PRESSURE INDEPENDENT VALVE (ON/OFF)-3.5 TR High static FCU
646Supply, installing, testing and commissioning of following cassette unit with drain pump, fresh air provision as per specification including all accessories as specified and as required-1 TR one way cassette unit
647Supply, installing, testing and commissioning of following cassette unit with drain pump, fresh air provision as per specification including all accessories as specified and as required-1.5 TR one way cassette unit
648Supply, installing, testing and commissioning of following cassette unit with drain pump fresh air provision as per specification including all accessories as specified and as required-3.5 TR four way cassette unit.
649Supply, Installation testing and commissioning of split / Packageair cooled Air-conditionerseach complete with scroll compressor, air cooled condensor, GSS casing, filters, cooling coils, fan motors, insulated copper refrigerant piping as per drawing, control wiring, refrigerant controls and accessories, including MICRO-PROCESSOR CONTROL with indication lampsfor the operation of the system withthermostat fixed in the respective rooms to adjust the temperature according to the equipments requirements with Micro- processor control panel for each machine. Tenderes to elaborate the features of Micro- processor panel. GI painted frame works for outdoor units making good of civil works. Refrigerant shall be R 410/R32. Price shall inclusive of all taxes, duties, installation, commissioning, Refrigerant piping as per Drawing.1 TR Hiwall Unit.
650CHILLED WATER PIPING AND VALVES
651Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications... ..... MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.200 mm dia. (detailed specification as per part C)
652Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications........ MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.150 mm dia.(detailed specification as per part C)
653Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications. ......MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.125 mm dia.(detailed specification as per part C)
654Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications. ........MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.100 mm dia. (detailed specification as per part C)
655Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications... .....MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.80 mm dia.(detailed specification as per part C)
656Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications.........MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.65 mm dia.(detailed specification as per part C)
657Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications............MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.50 mm dia. (detailed specification as per part C)
658Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications. ........MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.40 mm dia. (detailed specification as per part C)
659Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications..........MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.32 mm dia. (detailed specification as per part C)
660Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications. .......MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.25 mm dia. (detailed specification as per part C)
661Supply, receive, store, handle, install, test and commissioning of the following pre insulated chilled water MS class (B) pipes, including high tech supports complete with all fittings such as bends, tees, elbows, reducers flanges, special fittings, suspension hangers, supports etc. as required for installation as per site conditions and as per specifications. ........MS Class B, IS 3589, IS 1239 piping. RCC opening asgood as same. Wall opening as good as same.20 mm dia. (detailed specification as per part C)
662Site fabricated pipe (MS class B) with adequate structural support and with PUF injection insulation, GI cladding for part plant room, AHU room area, valve insulation with openable boxing for inspection.200 mm dia.
663Site fabricated pipe (MS class B) with adequate structural support and with PUF injection insulation, GI cladding for part plant room, AHU room area valve insulation with openable boxing for inspection.100 mm dia.
664Supply and fixing in position of condensate drain water AHU room drain pipe to the floor trap/nearest drain piping with 25 mm nitrile rubber insulation and with necessary fittings like traps, clamps, elbows, tees and reducers etc. Openings as good as same.32 mm dia. PVC.
665DRAIN WATER PIPING: Supply and fixing in position of condensate drain water AHU room drain pipe to the floor trap/nearest drain piping with 25 mm nitrile rubber insulation and with necessary fittings like traps, clamps, elbows, tees and reducers etc. Openings as good as same.25 mm dia. PVC.
666Supply, installation, testingcommissioning of the following type Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices PN 16 Rating.200 mm dia.
667Supply, installation, testing commissioning of the following type Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devicesPN 16 Rating.150 mm dia.
668Supply, installation, testing commissioning of the following type Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices PN 16 Rating.100 mm dia.
669Supply, installation, testing & commissioning of the following type Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking device, PN 16 Rating.80 mm dia.
670Supply, installation, testing commissioning of the following type Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices PN 16 Rating.65 mm dia.
671Supply, installation, testing commissioning of the following type Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices PN 16 Rating.50 mm dia.
672Supply, installation, testing commissioning of the following type forged Ball Valve, PN-20 gunmetal /cast alloy, including all necessary accessories and connections.40 mm dia.
673Supply, installation, testing commissioning of the following type forged Ball Valve, PN-20 gunmetal /cast alloy, including all necessary accessories and connections.32 mm dia.
674Supply, installation, testing commissioning of the following type forged Ball Valve, PN-20 gunmetal /cast alloy, including all necessary accessories and connections.25 mm dia.
675Supply, installation, testing commissioning of the following type forged Ball Valve, PN-20 gunmetal /cast alloy, including all necessary accessories and connections.20 mm dia.
676Supply, installation, testingcommissioning of the following type forged Ball Valve, PN-20 gunmetal /cast alloy, including all necessary accessories and connections.15 mm dia.
677Supplying, fixing, testing and commissioning of following size Drain valves with adequately supported as per specifications-40 mm.
678Supply, installation, testing commissioning of the following Non Return Valves as per the specifications and as required. Non Return valves up to 65mm size shall be of gun metal with screwed female ends. Valves of 65mm and above shall be of CI with flanged ends. PN 16 pressure rating, EPDM seal.Non- Return Valve of size:- 100 mm dia.
679BALANCING VALVE WITH PROVISION FOR FLOW MEASURMENT: Supply, installation, testing & commissioning of Balancing valve with built in measuring facility, C.I Body with EPDM seal, long pitch with protected out pipe insulation PN 16 pressure rating for chilled water as specified. Balancing Valve with 90 Deg C maximum operating temperature; built-in locking device for Tamper-Proof positioning; flanged connections; Valves shall have connections with isolation device for portable differential pressure meter with integral seals, Flow accuracy shall be 5%+/-, necessary insulation as per specification-100 mm dia.
680SUCTION GUIDE with strainer: Supply, installation, testing & commissioning of the following suction guides as per the specifications and as required.100 mm dia.
681Y STRAINER FOR AHU"s: Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications in the connected piping and adequately supported as per specifications-50 mm dia.
682Y STRAINER FOR AHU"s: Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications in the connected piping and adequately supported as per specifications-40 mm dia.
683Y STRAINER FOR AHU"s: Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications in the connected piping and adequately supported as per specifications-32 mm dia.
684Y STRAINER FOR AHU"s: Supplying, fixing, testing and commissioning of following Y- Strainer in the chilled water piping duly insulated to the same specifications in the connected piping and adequately supported as per specifications-25 mm dia.
68516.8 : Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
686THERMOMETERS: Supply, installation, testing and commissioning of 4 inch Dial type thermometers with Stem with Copper-plated steel, aluminum, or brass for thermowell installation and of length to suit installation, Stainless Steel U-Siphon as per specification.
687Supply, installation, testing & commissioning of differential pressure switch as per the specifications and as required.
688Supply, installation, testing & commissioning of the following motorized cut off valves as per the specifications and as required. Cl Body, minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, capable of accepting upto 10 V DC and upto 20mA electric signal and providing similar transduced feedback output to control system as required.100 mm dia.
689500L Pressurized Tank : Design, supply, installation, testing and commissioning of Pressurised chilled water expansion tank with insulation, Make up connection for closed loop system along with necessary pneumatic devices and accessories and MS & section supports in order to keep chilled water under pressure. The tank shall be precharged steel tank with replacable heavy duty butyl rubber bladder. The tank shall have 50mm system connection and 20mm drain and charging valve connection to facilitate on-site charging of tank. The tank shall be fitted with lifting rings and floor mounting skirt for vertical installation. The tank shall be constructed according to section 8 of ASME boiler and pressure vessel code and stamped 125psi working pressure.The contractor shall submit calculation regarding the above data. Pumps shall be of N+1 configuration. including with control wiring.
690Supply, installation, testing commissioning of a common air separator on the chilled water return line located at the pump suction and suitable for Secondary pump water flow; the separator shall be complete with high capacity air vent, flanges, service valve, non return valve, isolation butterfly valve for makeup water inlet.Capacity suitable for 648 USGPM and 200mm NB CHW Header line.
691AUTO AIR VENTS: Supply & install of airvents / purge valves at the highest points in chilled water piping complete each floorwith pipes nipple welded to pipe, hex nipple, socket, U-pipe connection at outlet ofair vent etc. as required.
692Supply and fix flexible connections with control rods for pumps and chiller.Size: 100 mm dia.
693TWO WAY TYPE PRESSURE INDEPENDENT BALANCING CUM MODULATING FLOW CONTROL VALVE: Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 to DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification-50 mm dia.
694TWO WAY TYPE PRESSURE INDEPENDENT BALANCING CUM MODULATING FLOW CONTROL VALVE: Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 & DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification-40 mm dia.
695TWO WAY TYPE PRESSURE INDEPENDENT BALANCING CUM MODULATING FLOW CONTROL VALVE: Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 & DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification-32 mm dia.
696TWO WAY TYPE PRESSURE INDEPENDENT BALANCING CUM MODULATING FLOW CONTROL VALVE: Supply, Installation, testing and commissioning of following size Pressure independent type 2 way modulating flow Control valves in a single Unit of Valves with PN16 Rating. DN 15 to DN 32 Brass Body Ext. Threaded, DN 40 & DN 50 Cast Iron Body Ext. Threaded, DN 65 to DN 100 Cast Iron body, Flanged Ends Connection Duly mounted with a BMS compatible Modulating actuator IP54 Type suitable for 24V AC for AHU/FCU as per specification-25 mm dia.
697CONDENSER WATER PIPING AND VALVES
698Supply, receive, store handle, install, test and commission the condenser water line with GI class (B) IS 3589 pipes complete with all fittings such as bends, tees, elbows, reducers, flanges, special fittings, suspension hangers, structural supports, etc. as reqd. for installation as per site conditions and as per specfiications. Opening as good as same.200 mm dia.
699Supply, receive, store handle, install, test and commission the condenser water line with GI class (B) IS 3589 pipes complete with all fittings such as bends, tees, elbows, reducers, flanges, special fittings, suspension hangers, structural supports, etc. as reqd. for installation as per site conditions and as per specfiications. Opening as good as same.125 mm dia.
700Supply, receive, store handle, install, test and commission the condenser water line with GI class (B) IS 3589 pipes complete with all fittings such as bends, tees, elbows, reducers, flanges, special fittings, suspension hangers, structural supports, etc. as reqd. for installation as per site conditions and as per specfiications. Opening as good as same.100 mm dia.
701Supply, installation, testing & commissioning of the following type Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices , PN 16 Rating.125 mm.
702Supply, installation, testing commissioning of the following type Butterfly valves as per the specifications and as required. Butterfly valve shall cast iron body with black nitrile seat. All butterfly valves shall be provided with locking devices & PN 16 Rating.100 mm.
703Supply, installation, testing & commissioning of the following Non Return Valves as per the specifications and as required. Non Return valves up to 65mm size shall be of gun metal with screwed female ends. Valves of 65mm and above shall be of CI with flanged ends. PN 16 pressure rating, EPDM seal.125 mm dia.
704Supply, installation, testing & commissioning of the following suction guides as per the specifications and as required.125 mm dia.
705Supply and fix flexible connections with control rods for pumps, cooling tower & condenser.125 mm NB.
706Supply, installation, testing & commissioning ofBalancing Valve, with built in measuring facility with C.I Body, 90 Deg C maximum operating temperature; built-in locking device for Tamper-Proof positioning; flanged connections;Valves shall have connections with isolation device for portable differential pressure meter with integral seals, Flow accuracy shall be 5%+/- 125 mm NB
707Supply, installation, testing and commissioning of Dial type thermometers with Stem with Copper-plated steel, aluminum, or brass for thermowell installation and of length to suit installation, Stainless Steel U-Siphon as per specification.
70816.8 : Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
709Supply, installation, testing & commissioning of differential pressure switch as per the specifications and as required.
710Supply, installation, testing & commissioning of the following motorized cut off valves as per the specifications and as required. Cl Body, Nylon coated DI disc, EPDM seal, minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, capable of accepting upto 10V DC and upto 20mA electric signal and providing similar transduced feedback output to control system as required.125 mm dia.
711DUCTING, GRILLS, DIFFUSER AND INSULATION
71216.12.1.1 : Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006
71316.12.1.2 : Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006
71416.12.1.3 : Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular dueling as per IS 655-2006
71516.15 : Supplying and Fixing of powder costed extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
716Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
717Supply and fixing of Square Supply air diffusers of powder coated Aluminium with opposed blade dampers with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600-SD: 450X450
718Supply and fixing of Square Supply air diffusers of powder coated Aluminium with opposed blade dampers with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600-SD: 375x375
719Supply and fixing of Square Supply air diffusers of powder coated Aluminium with opposed blade dampers with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600-SD: 300x300
720Supply and fixing of Square Supply air diffusers of powder coated Aluminium with opposed blade dampers with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600-SD: 225x225
721Supply and fixing of Square Return air diffusers of powder coated Aluminium with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600-RD: 450x450
722Supply and fixing of Square Return air diffusers of powder coated Aluminium with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600-RD: 375x375
723Supply and fixing of Square Return air diffusers of powder coated Aluminium with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600-RD: 300x300
724Supply and fixing of Square Return air diffusers of powder coated Aluminium with removable core as per drawings for the following neck sizes. The diffusers shall have extended flanges to match the grid tile of 600x600-RD: 225x225
725Supply installing, testing and commissioning of perforated aluminium grille for return with VCD and 10 Micron Filter in OT
726Supply, Fabrication, installation and testing of following size insulated flexible duct, complete with connecting rings, duct supports etc. as per standards and specification.350 mm dia.
727Supply, Fabrication, installation and testing of following size insulated flexible duct, complete with connecting rings, duct supports etc. as per standards and specification.300 mm dia.
728Supply, Fabrication, installation and testing of following size insulated flexible duct, complete with connecting rings, duct supports etc. as per standards and specification.250 mm dia.
729Supply installing, testing and commissioning of following Insulated Plenum Box made of 22g G.ISpigot Butterfly Dampers with necessary threaded rods for supporting for the following size-600 X 600 X 450 H
730Supply installing, testing and commissioning of following Insulated Plenum Box made of 22g G.I & Spigot & Butterfly Dampers with necessary threaded rods for supporting for the following size-450 X 450 X 450 H
731Supply installing, testing and commissioning of following Insulated Plenum Box made of 22g G.I & Spigot & Butterfly Dampers with necessary threaded rods for supporting for the following size-350 X 350 X 450 H
732Supply installing, testing and commissioning of following Insulated Plenum Box made of 22g G.I & Spigot & Butterfly Dampers with necessary threaded rods for supporting for the following size-300 X 300 X 300 H.
733Supply installing, testing and commissioning of Factory made fresh air dampers withlouvers and control lever, filter etc as required. (As per drawing)
734Supply installing, testing and commissioning of Factory made fresh air dampers having 20 micron filter with louvers and control lever. (For OT as per drawing)
735Supply, fixing, balance and commissioning of louvre type smooth supply air duct dampers made of extruded aluminium linkage, lever, brass bushings complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges, fixing arrangement etc, as per specifications. Al Volume control duct damper.
73616.20.1 : Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/ main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted.The damper shall also be closed in the event of fire signal complete as required and as per specifications.Fire damper
737Thermal insulation: Supply & fixing of 9 mm thick Class O nitrile rubber insulation with antimicrobial property with adhesive as per the recommendation of the manufacturer with density 45-55kg/m3
738Acoustic insulation: Supply & fixing of 10 mm thick Class 1 acoustic nitrile rubber insulation open cell with antimicrobial property with adhesive as per the recommendation of the manufacturer with density 140-180kg/m3
739Non AC area duct insulation: Supply & fixing of 19 mm thick Class O nitrile rubber insulation with antimicrobial property with adhesive as per the recommendation of the manufacturer with density 45-55kg/m3
740VENTILATION SYSTEM
741Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-80 CFM Exhaust blower
742Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-100 CFM Exhaust blower
743Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-150 CFM Exhaust blower
744Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-200 CFM Exhaust blower
745Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-250 CFM Exhaust blower
746Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-350 CFM Exhaust blower
747Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-400 CFM Exhaust blower
748Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-550 CFM Exhaust blower
749Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-700 CFM Exhaust blower
750Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-1000 CFM Exhaust blower
751Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-1200 CFM Exhaust blower
752Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-1400 CFM Exhaust blower
753Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-1450 CFM Exhaust blower
754Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-1500 CFM Exhaust blower
755Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-2000 CFM Exhaust blower
756Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-2500 CFM Exhaust blower.
757Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-2750 CFM Exhaust blower.
758Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-4250 CFM Exhaust blower
759Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-5000 CFM Fresh Air Fan.
760Axial Fans - for Toilet, Plant room exhaust & Fresh Air: Supply, installation, testing and commissioning Direct driven axial flow fans suitable for mounting on wall or duct in standard galvanized/ powder coated steel construction with required rating, static, single motor and flexible connection to connect with ducting / plenum, louvers with birdscreen-3750 CFM Fresh Air Fan.
76116.12.1.1 : Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006
76216.12.1.2 : Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006
763Supply, Fabrication, installation and testing of the flexible ducting, complete with connecting rings, duct supports, Plenum etc as per standards and specification.Size: 100mm dia.
764Supply and fixing the following aluminium grilles and diffusers as per specifications. Machine made, powder coated, supply and return air grilles and diffusers. Design to be approved.Supply / Return air grille / diffuser with VCD
765ADDITIONAL WORKS
766Roof(inside) insulation for exposed slabs : Supply & fixing of 12 mm thick class O nitrile rubber insulation with adhesive as per the recommendation of the manufacture with density 45-55kg/m3.
767UNDER DECK INSULATION - Supply & fixing of 9 mm thick class O nitrile rubber insulation with adhesive as per the recommendation of the manufacture with density 45 - 55kg/m3.
768ELECTRICAL WORKS
769MAIN PUMP PANEL- (detailed specification as per part C)
770PUMP PANEL WITH VFDFOR SECONDARY PUMPS-(detailed specification as per part C)
771AHU PANEL / SM DB L1- (detailed specification as per part C)
772AHU PANEL / SM DB L2- (detailed specification as per part C)
773AHU PANEL / SM DB L3- (detailed specification as per part C)
774AHU PANEL / SM DB L4- (detailed specification as per part C)
775AHU PANEL / SM DB L5- (detailed specification as per part C)
776AHU PANEL / SM DB L6- (detailed specification as per part C)
777AHU PANEL / SM DB L 7and 8- (detailed specification as per part C)
778AHU PANEL / SM DB L9 -(detailed specification as per part C)
779Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.4CX35sq.mm Al Cable.
780Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.4CX25sq.mm Al Cable.
781Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.4CX6sq.mm Al Cable.
782Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.4CX4sq.mm Al Cable.
783Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.3CX6sq.mm Al Cable.
784Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.3CX4sq.mm Al Cable.
785Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date.3CX2.5sq.mm Al Cable.
7867.8.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
787Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.2C x 1.5 sq. mm.
788Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.3C x 1.5 sq. mm.
789Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.6C x 1.5 sq. mm.
7909.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
7919.1.34 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
7929.1.35 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 35 sq. mm (32mm)
793Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.4CX6sq.mm Al Cable.
794Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.4CX4sq.mm Al Cable.
795Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.3CX6sq.mm Al Cable.
796Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.3CX4sq.mm Al Cable.
797Supply and laying the following sizes of earthing bare copper/strips on cable tray or wall surface, including necessary clamps (each clamp not exceeding 60 cm) and bolts etc as requiredfor complete installation as instructed by engineer in charge/consultant.Copper wire No.10 SWG.
798Supply and laying the following sizes of earthing bare copper/strips on cable tray or wall surface, including necessary clamps (each clamp not exceeding 60 cm) and bolts etc as requiredfor complete installation as instructed by engineer in charge/consultant.Copper wire No.8 SWG.
799BUILDING MANAGEMENT SYSTEM
800SITC of A4 Colour Laser printer
801SITC of Central core Computer- PC (Intel i7 Processor) , 8 GB RAM, 2 GB Graphics card, DVD Writer, 22" LED monitor, 1 TBHDD, Microsoft mouse, Keyboards, 2 serial, 1 parallel port/KB, Windows 10 or higher operating system,Minimum 5 yearslicensed antivirus software
802Supply, Installation, Testing and Commissioning of Building Management System Graphic User Interface software with 3 user client license, user groups, user profiles and scopes, alarm handling, scheduling, trending, reporting engine, database system, system activity log, historical data management, real time zoom enabled vector graphics, system backup and restore, HTML based documentation and help, SMS/EMail facility complete in all respects as per tender specification. Graphical Software complete to cater to hardware points as specified in the Data Point Summary as well as Third Party Software Integrated Systems.
803SITC of Interface for integrating Third Party Systems. (All Systems to provide data on MODBUS RTU with values shown on MODSCAN or BacNET shown on BacNET explorer). Chiller System - 3 Chiller (50 points/chiller)
804SITC of Interface for integrating Third Party Systems. (All Systems to provide data on MODBUS RTU with values shown on MODSCAN or BacNET shown on BacNET explorer). Secondary Pumps System (10 Points/Pump)
805SITC of Interface for integrating Third Party Systems. (All Systems to provide data on MODBUS RTU with values shown on MODSCAN or BacNET shown on BacNET explorer). Variable Frequency Drives for AHU"s (10 Points per VFD)
806SITC of Networkable DDC Controllers as per Data Point Summary (1- 5 ) with enclosure with all necessary wiring and accessories
807SITC of Immersion Type Temperature Sensor
808SITC of Outside Air Temperature & RH Sensor
809SITC of Level Switch for expansion tank ( 2 point)(depth of tank - 1 mtr.)
810SITC of Differential Pressure Switch
811SITC of Level Switch for cooling tower
812Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 2 AHU / DDC
813Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 1 AHU / DDC
814Supply, Installation, testing & commsssioning of the DDC Controllers with enclosure with all necessary wiring and accessories, consider 3 AHU / DDC
815SITC of Differential Pressure Switch across filter for Air Handling Units - 11 Nos.
816SITC of Return air Temperature Sensor for Air Handling Units - 11 Nos.
817SITC of Differential Pressure Switch across filter - pre filter and fine filter for Air Handling Units with Fine filter- 6 Nos
818SITC of Return air Temperature Sensor for Air Handling Units with Fine filter- 6 Nos
819SITC of Differential Pressure Switch across filterfor Air Handling Units with heater - 2 Nos.
820SITC of Return air Temperature Sensor for Air Handling Units with heater - 2 Nos.
821SITC of RH Sensor Room type for Air Handling Units with heater - 2 Nos.
822SITC of Differential Pressure Switch across filter -Pre filter,fine filter and Hepa filter for Air Handling Units - 7 Nos. - OT
823SITC of Return air Temperature Sensor for Air Handling Units - 7 Nos. - OT
824SITC of RH Sensor Room type for Air Handling Units - 7 Nos. - OT
825SITC of Differential Pressure Switch across filter for AHU with Heat Recovery Wheel - 1 Nos
826SITC of Return air Temperature Sensor for AHU with Heat Recovery Wheel - 1 Nos
827SITC of RH Sensor Room type for AHU with Heat Recovery Wheel - 1 Nos
828SITC of Signal Cabling - 2 Core 1.0 sq.mm. shielded FRLS armoured cable
829SITC of Signal Cabling - 4 Core 1.0 sq.mm. shielded FRLS armoured cable
830SITC of Signal Cabling - 8 Core 1.0 sq.mm. shielded FRLS armoured cable
831SITC of Communication Cabling - 2 Core 1.5 sq.mm. shielded FRLS armoured cable or CAT6 armoured cable
832SITC of Power Cable - 3 C X 2.5 Sq.mm. -ATC Armoured Cable
833SITC of Cable Trays (150mm X 50mm) - approx
834SITC of 5 Amps Power Sockets
835SITC of 3 KVA UPS - Min 1 Hr minutes back up for the system)
836SH 6 - FIRE FIGHTING WORKS FIRE HOSE REEL AND HYDRANT SYSTEM
837Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS:12585 -20 mm nominal internal dia gun metal globe valve & nozzle Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m
838Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel,ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required:Single headed Stainless steel.
839Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :3 way - 150 mm dia M.S. Pipe
840Supply, installation, testing and commissioning of Fire Brigade Draw Off Outlet C.I. body, having 3Gunmetal, 63mm. female instantaneous inlet, conforming to IS: 903, with non return valves, 25mm. drainvalve, flanged outlet, 3 nos. of rubber blank caps and G.I. chains.
841Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplingsduly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Stainless Steel (Grade 304)
842Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter sizenozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required: Stainless Steel (Grade 304)
843Supply and fix at site in position Fire Hose Cabinet, wall / pole mounting type, 30” x 24” x 10” size, toaccommodate two 15m length of delivery hose and branch pipe, acrylic fronted double door, with lock, 2keys and a break glass recess for keys, painted Fire Red. The price shall be inclusive of fixing accessories and as per requirement.
844Supply and fix at site in position Weather Proof Fire Hose Cabinet, wall / pole mounting type, 30” x 24” x10” size, to accommodate two 15m length of delivery hose and branch pipe, acrylic fronted double door,with lock, 2 keys and a break glass recess for keys, painted Fire Red. The price shall be inclusive of fixing accessories and pole for mounting, all as per requirement.
845AUTOMATIC FIRE SPRINKLER SYSTEM
846Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degreecentigrade with required accessories.68 Degree centigrade Pandent Sprinkler.
847Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degreecentigrade with required accessories.68 Degree centigrade Upright Sprinkler.
848Providing, fixing, testing and commissioning of Standard Coverage, Quick Response Automatic FireSprinkler, K- Factor: 5.6 (80 Metric) or equal to the approval of system consultant / engineer - in - charge,with necessary accessories and fittings.Pendant Type, 79 Degree C Rating.
849Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : Horizontal side wall sprinkler.
850Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required
851Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steelcomplete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center racket, stockbar of following sizes complete as required.1000 mm length with all connecting system and accessories.
852Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steelcomplete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.700mm.
853Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 50 mm dia.
854Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 150 mm dia.
855Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. 100 mm dia.
856FIRE PUMP AND ACCESSORIES
857MAIN PUMP - Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(b) Suitable HP Squirrel cage inductionmotor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, ACsupply with IP 55 protection for enclosure, horizontal foot mounted type with Class-"F" insulation,conforming to IS-325.(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Suitable cement concrete foundation duly plastered with anti vibration pads. 2280LPM at 75 metre Head and High efficient IE-3 rated.
858SPRINKLER PUMP - Supplying, installation, testing and commissioning of Electric driven Sprinkler Pumpsuitable for automatic operation and consisting of following, complete in all respects, as required : (a)Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-"F" insulation,conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration pads. 2280 LPM at 75 metre head and High efficient
859JOCKEY PUMP - Supplying, installation, testing and commissioning of electric driven pressurizationpump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520.Suitable HP squirrel cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-"F" insulation,conforming to IS : 325.M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.Suitable cement concrete foundation duly plastered and with anti vibration pads.180 LPM at 80mtrs head and with high efficient IE3 rated motor.
860DIESEL PUMP - Supplying, installation, testing and commissioning of diesel engine driven main firepump suitable for automatic operation and consisting of following, complete in all respects, as required……..2280 LPM at 75 metre head (detailed specification as per part C)
861Supply, erection, commissioning of additional length of Exhaust Pipes with long radius bend from silencerwith necessary clamps, fixtures, civil works andthermal insulation with 50 mm thick glass wool and with 1.0 mm thick aluminium sheet cladding of following adequate size including suitable rain cap for top to avoid rain water entry.(detailed specification as per part C)
862MOTOR CONTROL PANEL -(detailed specification as per part C)
863Supply, installation, testing and commissioning of Pressure Switches with pressure rating suitable for above Fire Pumps, with a differential of 0.2 to 1.6 Bar, as per Technical Specifications.
864Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required.
865FIRE PIPES, VALVES, AND ACCESSORIES
866Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 250 mm dia.
867Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 200 mm dia.
868Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 150 mm dia.
869Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 100 mm dia.
870Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 80 mm dia
871Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 65 mm dia.
872Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 50 mm dia.
873Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting withtwo or more coats of synthetic enamel paint of required shade complete as required : 40 mm dia
874Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 32 mm dia.
875Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : 25 mm dia
876Providing laying, testing & commissioning of "C" class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coal tar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.80 mm dia.
877Providing laying, testing & commissioning of "C" class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 100 mm dia.
878Providing laying, testing & commissioning of "C" class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 150 mm dia.
879Providing laying, testing & commissioning of "C" class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/as
880Providing, fixing, testing and commissioning of Forged Ball Valve, PN-20 gunmetal /cast alloy, including necessary accessories and connections.25 mm.
881Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non-rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required: 50 mm dia
882Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 250 mm dia.
883Supplying, fixing, testing and commissioning of butterfly valve of PN 16 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 200 mm dia.
884Supplying, fixing, testing and commissioning of butterfly valve of PN 16 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 150 mm dia.
885Supplying, fixing, testing and commissioning of butterfly valve of PN 16 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 100 mm dia.
886Supplying, fixing, testing and commissioning of butterfly valve of PN 16 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : 65 mm dia
887Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS:5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :50mm dia
888Providing, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16,conforming to IS: 13095 with required companion flanges nuts, bolts etc. complete.150mm.
889Providing, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16,conforming to IS: 13095 with required companion flanges nuts, bolts etc. complete.200mm.
890Providing, fixing, testing and commissioning of Non Return Valve, Wafer Swing Check type, PN-16,conforming to IS: 13095 with required companion flanges nuts, bolts etc. complete.250mm
891Providing, fixing, testing & commissioning of installation control valve of cast iron body,brass/bronzeworking parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressuregauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required: 150mm dia
892Supply, installation, testing and commissioning of Air Release Valve Gunmetal, conforming to IS903:1993, having rubber ball with sealing seat and with 25mm. BSP threaded male inlet, including necessary accessories and connections.
893Providing and fixing C. I. Gate Valve with Non Rising Stem & Cap Top, PN-16, confirming to IS: 14846 with ISI Mark and with required companion flanges, rubber insertions, bolts, nuts, Washers etc. complete. The Price shall be inclusive of ‘Fabricated Key" for Operation from Ground Level, as per Technical Specifications.100mm.
894Providing and fixing C. I. Gate Valve with Non Rising Stem & Cap Top, PN-16, confirming to IS: 14846 with ISI Mark and with required companion flanges, rubber insertions, bolts, nuts, Washers etc. complete. The Price shall be inclusive of ‘Fabricated Key" for Operation from Ground Level, as per Technical Specifications.150mm.
895Providing and fixing Ductile Iron Gate Valve, Rising Spindle, OS & Y Type, Body: ASTM A536, 65-45-12, Flanged to BS5163, PN16, UL Listed / FM Approved with Tamper / Supervisory Switches and with required flanges, rubber insertions, bolts, nuts, Washers etc. complete.150mm.
896Providing and fixing Ductile Iron Gate Valve, Rising Spindle, OS & Y Type, Body: ASTM A536, 65-45-12, Flanged to BS5163, PN16, UL Listed / FM Approved with Tamper / Supervisory Switches and with required flanges, rubber insertions, bolts, nuts, Washers etc. complete.200mm.
897Providing and fixing Ductile Iron Gate Valve, Rising Spindle, OS & Y Type, Body: ASTM A536, 65-45-12, Flanged to BS5163, PN16, UL Listed / FM Approved with Tamper / Supervisory Switches and with required flanges, rubber insertions, bolts, nuts, Washers etc. complete.250mm.
898Providing and fixing sight glass assembly of brass body and brass ball with chrome plated, steel handle, PN16 or above, UL Listed/ FM Approved. Test and drain valve shall be with compact 3 position ball valves with drain orifice having K-factor 5.6 and a sight glass. 3 positions consist of OFF, TEST and DRAIN. Test and drain valves shall be provided for test as well as express drain functions in wet sprinkler systems with grooved end connection ends. The Test and Drain Valve shall be in Brass ASTM B584 material of construction. These have integral tamper resistant sight glass.25 mm.
899Supply, installation, testing and commissioning of 4" dia. Bourdon Type Pressure Gauge, with ISI Mark or of equivalent International Standards.Weather / Water Proof, Type with shut off cock and connection Pipe.
900Supply, installation, testing and commissioning of 4" dia. Bourdon Type Pressure Gauge, with ISI Mark or of equivalent International Standards.Standard Type for indoor use with shut off cock and connection Pipe.
901INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM
902Supplying, installation, testing and commissioning of micro processor based intelligent addressable mainfire alarm panel......The Panel shall have 4 Loop Capacity and shall be expandable up to 5 Loop, all as per Technical Specifications(detailed specification as per part C)
903Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.
904Providing, fixing, test and commission Intelligent Addressable Multi Sensor Detectors. The detectors shallhave multiple sensitivity (adjustable at site) levels, programmable for timed automatic sensitivity selection complete with Standard Base, junction box and other accessories as required. Detectors shall be UL listed.
905Providing, fixing, test and commission Intelligent Addressable Multi Sensor Detectors (Above Ceiling).The detectors shall have multiple sensitivity (adjustable at site) levels, programmable for timed automatic sensitivity selection complete with Standard Base, junction box and other accessories as required. Detectors shall be UL listed.
906Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate ofrise cum fixed temperature thermistor complete with base as required.
907Supplying, installation, testing & commissioning of addressable manual call point complete as required.
908Providing, fixing, test and commission Intelligent Addressable Weather/Water Proof/Corrosion Resistanttype Intelligent Addressable Manual Call Point having an integrally mounted addressable module that monitors and reports contact status, IP67 rated, complete as per technical specifications.
909Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required
910Providing, fixing, testing and commission Weather/Water Proof/ Corrosion Resistant Conventional TypeHorn/Strobe, Rated at 82 dB @3Mtr. for audible annunciation and 75Candela flashing at 1Hz. for visual indication, IP: 66 Rated, complete as per technical specifications.
911Providing, fixing, testing and commission Intelligent Addressable Input/Monitor Module, as per specification for interface with Flow Switches, Fire Pumps, Supervisory Switches, Alarm Valve, Water Tank Level etc.
912Providing, fixing, testing and commission Intelligent Addressable control / Relay Module, as perspecification for interface with Lift Panel, Water Curtain Partition, AHUs, Ventilation System, Smoke Management System, Power Distribution, Public Address System etc.
913Supplying, installation, testing & commissioning of fault isolator complete with base as required.
914Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copperconductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
915FIRE EXTINGUISHERS
916Providing, fixing, commission and install in position following Portable Fire Extinguisher as per BIS 2190 and BIS: 15683:2006 and with relevant ISI Stamping/Marking.CO2 - 2.0 Kg.
917Providing, fixing, commission and install in position following Portable Fire Extinguisher as per BIS 2190and BIS: 15683:2006 and with relevant ISI Stamping/Marking.CO2 - 4.5Kg.
918Providing, fixing, commission and install in position following Portable Fire Extinguisher as per BIS 2190and BIS: 15683:2006 and with relevant ISI Stamping/Marking.ABC Dry Chemical, Store Pressure Type -2 Kg.
919Providing, fixing, commission and install in position following Portable Fire Extinguisher as per BIS 2190and BIS: 15683:2006 and with relevant ISI Stamping/Marking.ABC Dry Chemical Powder, Store Pressure Type - 4 Kg.
920Providing, fixing, commission and install in position following Portable Fire Extinguisher as per BIS 2190and BIS: 15683:2006 and with relevant ISI Stamping/Marking.Water CO2, Cartridge Type - 9 Ltr.
921Providing, fixing, commission and install in position following Portable Fire Extinguisher as per BIS 2190and BIS: 15683:2006 and with relevant ISI Stamping/Marking.Clean Agent HCFC 123, 4.0 Kg.
922Providing, fixing, commission and install in position following Portable Fire Extinguisher as per BIS 2190and BIS: 15683:2006 and with relevant ISI Stamping/Marking.Foam Type, Cartridge Type, 9 Ltr.
923Providing, fixing, commission and install in position following Portable Fire Extinguisher as per BIS 2190 and BIS: 15683:2006 and with relevant ISI Stamping/Marking.Fire Bucket including Fabricated M. S. Stand (Approx. quantity).
924TALK BACK SYSTEM
925Supply, installation, testing & commisioning of automatic control console of 8 zones micro process basedcomplete with floor to floor announcing and talk back facilities with the following features and made functional: (a) Feather type key pads to select the zones. (b) Moulded plastic attractive enclosure. (c)Backlight Liquid Crystal Display(LCD) (d) User friendly interactive display. (e) Announcement selector -PH Switch. (f) Listen selector switch. (g) All Call switch to select all zones simultaneously for announcement (h) Zones Call Display On the LCD With Audio Alarm.
926Controller Unit with 120 W amplifier, Goose neck type microphone and with the following features: (i) Builtin Power supply. (ii) Zone Selector switching Circuit (iii)Terminal blocks to terminate zones wires, amplifier wires etc., (iv) Zone Call processing Circuit etc and made functional. Panel to be installed in the Fire Control Room.
927Supply, installation, testing and commisioning of Public Address speaker with talk back facility 6 Wattswith L M T and call switch, made out of powder coated CRCA sheet, wall mounting type and to be installed at a height of not less than 150 CM from the finished floor levels, suitable for concealed mounting.
928Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
929SIGNAGES
930Fire Exit Light - Laser type, with High Glow LED Light, size: 300x150mm or nearby, as per conventionaldesign/colour code panel conforming to IS 9457 Ceiling Mounting type with hanging clamps, on/off switch, Red / Green Colour option, power consumption: 18 Watt or less with all accessories required for complete installation as directed by the engineer inc charge. Power supply shaould be provided with UPS back-up.
931Signage Printed "IN CASE OF FIRE, USE STAIRS UNLESS INSTRUCTED OTHERWISE" of 1.25cm.height letters in red with white back ground and standard size (500x225 mm) as per conventional design/colour code on 3 mm thick aluminium composite panel, conforming to IS 9457. The signage will be either fixed on the wall with the help of screws and double tape or hanged from the false ceiling with the help of chain and screws etc. complete as required as per the technical specification.
932Floor Identification Signage ( ie, GROUND FLOOR, FIRST FLOOR, etc.) at each stair enclosure on everyfloor, indicating the floor number in words, of standard size (500x225mm) as per conventional design/colour code on 3mm thick aluminium screws and double tape of hanged from the false ceiling with the help of chain and screws etc. complete as required as per the technical specification
933Floor Identification Signage (MAIN STAIRCASE, FIRE STAIRCASE, FIRE ASSEMBLY POINT, PUMPROOM, FIRE CONTROL ROOM, ELECTRICAL ROOM, FIRE LIFT, PASSENGER LIFT Etc.) standard size (500x225 mm as per conventional design / colour code on 3 mm thick aluminium composite panel, conforming to IS 9457. The signage will be either fixed on the wall with the help of chain and screws etc. complete as required as per the technical specification.
934Supply and installation of photoluminescent glow signage containing standard instructions to the occupants in case of Fire emergency (FIRE ORDER),of standard size (600x800mm minimum) as per conventional design/ colour code on 3 mm thick aluminium composite panel and conforming to IS 9457, IS12349, IS12407. The signage will be either fixed on the wall with the help of screws and double tape or hanged from the false ceiling with the help of chain and screws etc. complete as required as per the technical specification.
935Supply and fixing (in appropriate location) of Fire emergency evaluation plan (colour) printed in photopaper of size A2 sand -witched in clear acrylic sheets fixed using SS studs and other accessories complete as required as per the technical specification and confirming to IS 9457,IS 12349, IS 12407 Evacuation plan shall be prepared by the contractor and got approved from client/ consultant.
936CIVIL WORK
937Supplying and fixing C.I with out frame for manholes:560 mm diameter ( heavy duty) the weight of the cover to be not less than 108 kg
938FIRE DOORS
939Supply, installation, testing and commissioning of 2hr fire rated fire door of size 2000mmx2400mm with 46mm thick shutter manufactured from 1.2mm thick GI sheet sandwiching with Honey comb insulation material. The door frames manufactured from 1.6mm thick GI sheet pressed from single rebate profile of size 100mmx57mm. The door frame and double leaf door is finished with powder coating of 50 micron approved shade.Fire doors are inclusive of vision panel with 6mm thick 2hr fire rated glass of size 200mmx300mm, panic bar/latch (double point), external lever handle, surface door closer, dash fastener and other accessories required for the full functioning of the Fire rated Doors
940Supply, installation, testing and commissioning of 2hr fire rated fire door of size 1200mmx2400mm with 46mm thick shutter manufactured from 1.2mm thick GI sheet sandwiching with Honey comb insulation material. The door frames manufactured from 1.6mm thick GI sheet pressed from single rebate profile of size 100mmx57mm. The door frame and single leaf door is finished with powder coating of 50 micron approved shade.Fire doors are inclusive of vision panel with 6mm thick 2hr fire rated glass of size 200mmx300mm, panic bar/latch (double point), external lever handle, surface door closer, dash fastener and other accessories required for the full functioning of the Fire rated Doors.
941Supply, installation, testing and commissioning of 600mmx1500mm shaft door having 2hr fire rating with 46mm thick Shutter and outer frame of size 100x57mm. Shutter should be manufactured from 0.8mm thick GI sheet sandwiching with Honey comb insulation material. The door frames are manufactured from 1.2mm thick GI sheet. The door frame and single leaf door should be finished with powder coating of 50micron approved shade. Fire doors are inclusive of ball bearing SS hinges, mortice shaft lock and SS flush handle of size 120x40mm etc.as per the direction of Engineer -in charge.
942Supply, installation, testing and commissioning of 800mmx1500mm shaft door having 2hr fire rating with 46mm thick Shutter and outer frame of size 100x57mm. Shutter should be manufactured from 0.8mm thick GI sheet sandwiching with Honey comb insulation material. The door frames are manufactured from 1.2mm thick GI sheet. The door frame and single leaf door should be finished with powder coating of 50micron approved shade. Fire doors are inclusive of ball bearing SS hinges, mortice shaft lock and SS flush handle of size 120x40mm etc.as per the direction of Engineer -in charge.
943Supply, installation, testing and commissioning of 900mmx1500mm shaft door having 2hr fire rating with 46mm thick Shutter and outer frame of size 100x57mm. Shutter should be manufactured from 0.8mm thick GI sheet sandwiching with Honey comb insulation material. The door frames are manufactured from 1.2mm thick GI sheet. The door frame and single leaf door should be finished with powder coating of 50micron approved shade. Fire doors are inclusive of ball bearing SS hinges, vision panel with 5mm thick toughned glass of size 450mmx750mm, mortice shaft lock and SS flush handle of size 120x40mm etc.as per the direction of Engineer -in charge
944Supply, installation, testing and commissioning of 1200mmx1500mm shaft door having 46mm thick Shutter and outer frame of size 100x57mm. Shutter should be manufactured from 0.8mm thick GI sheet sandwiching with Honey comb insulation material. The door frames are manufactured from 1.2mm thick GI sheet. The door frame and single leaf door should be finished with powder coating of 50micron approved shade. Fire doors are inclusive of ball bearing SS hinges, vision panel with 5mm thick toughned glass of size 450mmx750mm, mortice shaft lock and SS flush handle of size 120x40mm etc.as per the direction of Engineer -in charge
945FIRE SEALANT
946Supply and Fixing of load bearing Fire stop mortar with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, for openings in floors or slabs after passing service lines…. (detailed specification as per part C)
947Providing a intumescent, flexible firestop wrap strip for plastic pipe, insulated pipe and various nonmetallic penetrations from 2"" to 6"" diameter…..Plastic Pipe diameter of 2.5"" (Firestop Wrap),Min. recommended hole dia. in wall/floor: 92 mm. (detailed specification as per part C)
948Providing a intumescent, flexible firestop wrap strip for plastic pipe, insulated pipe and various nonmetallic penetrations from 2"" to 6"" diameter……..Plastic Pipe diameter of 3"" (Firestop Wrap), Min. recommended hole dia. in wall/floor: 112 mm. (detailed specification as per part C)
949Providing Acrylic Firestop Sealant in gaps between periphery of the ducts to provide minimum 2 hours fire rating when subject to the test conditions of UL 2079 standards. …... (detailed specification as per part C)
950Providing expanding fire stop foam with minimum 2 hours fire rating when tested in accordance with UL1479, for horizontal openings in floors or slabs after passing service lines like cable trays or cables/cable bundles……... (detailed specification as per part C)
951SH 7 - ELEVATOR SYSTEM VERTICAL TRANSPORTATION SYSTEM
952Design, fabrication, supply. installation, testing and commissioning of electric traction type with machine room type , Stainless steel 26 Pax (1768 Kg) Hospital elevator (Including freight & landing charges,insurance and all applicable taxes and duties in country of origin and in India etc. except GST) and type suitable for operation on 415 V±10%, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency micro-processor type traction control, speed of 1.5 Mtr/sec, electromagnetic brake system, Simplex mode operation, operating panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency light, intercom suitable for hook up to Purchasers’ EPABX,infrared ray sensing door protection for full height, reverse phase relay on controller, fireman"s switch at initial landing floor, LCD/LED car positions and direction indication in car and landings. And at all floors with UP/DOWN direction, shaft wiring and lighting with accessories, braille buttons, audio announcement along with pre-recorded message as approved by Engineer-in-Charge, all accessories including Automatic Rescue Device (ARD) with dry maintenance free sealed batteries and Manual Emergency Rescue Device and all electrical components with wiring from the single point power supply provided at top landing near the elevator door complete as required. The drives of elevator shall meet the requirements of IEEE 519/2014. The traction motor (having efficiency equivalent to IE3 or better as in IS 12615) of machine room elevator shall be of gearless type and placed inside the machine room complete as per technical specifications. Having automatic centre/side opening stainless steel doors, Matt finish stainless steel car enclosure provided with stainless steel handrails on three sides, 2 mm fluted SS flooring as applicable in accordance of following details- 7 stops, 7 openings and entrance & exit at same side and suitable for travel height of 30 meter approximate. (Shaft Size 2500mm (width) x 3500mm (depth)) with door opening of 1200 mm (width) and 2100 mm (height). The equipment should be BMS compatible. All fabrication and procedures shall confirm to relevant IS standards/Code and complete in all respects as per technical specifications.
953Design, fabrication, supply. installation, testing and commissioning of electric traction type, without machine room type , Stainless steel, 2T capacity goods cum bed Hospital elevator (Including freight & landing charges, insurance and all applicable taxes and duties in country of origin and in India etc. except GST) and type suitable for operation on 415 V±10%, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency micro-processor type traction control, speed of 1 Mtr/sec, electromagnetic brake system, Simplex mode operation, operating panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency light, intercom suitable for hook up to Purchaser’s EPABX, infrared ray sensing door protection for full height, reverse phase relay on controller, fireman"s switch at initial landing floor, LCD/LED car positions and direction indication in car and landings. And at all floors with UP/DOWN direction, shaft wiring and lighting with accessories, braille buttons, audio announcement along with pre-recorded message as approved by Engineer-in-Charge, all accessories including Automatic Rescue Device (ARD) with dry maintenance free sealed batteries and Manual Emergency Rescue Device and all electrical components with wiring from the single point power supply provided at top landing near the elevator door complete as required. The drives of elevator shall meet the requirements of IEEE 519/2014. The traction motor ( having efficiency equivalent to IE3 or better as in IS 12615) of machine room elevator shall be of gearless type and placed inside the machine room complete as per technical specifications. Having automatic centre/side opening stainless steel doors, Matt finish stainless steel car enclosure provided with stainless steel handrails on three sides, 2 mm fluted SS flooring as applicable in accordance of following details- 9 stops, 9 openings and entrance & exit at same side and suitable for travel height of 30 meter approximate. (Shaft Size 2500mm (width) x 3500mm (depth)) with door opening of 1500 mm (width) and 2100 mm (height). The equipment should be BMS compatible. All fabrication and procedures shall confirm to relevant IS standards/Code and complete in all respects as per technical specifications
954SH 8 A - MISCELLANEOUS WORKS False ceiling works
95512.52.1 : Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) ... (detailed specification as per part C)
95612.52.2 : Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) .... (detailed specification as per part C)
957Aluminium Non perforated false ceiling - Providing & Fixing true horizontal level swing down suspended ceiling comprising of approved make Aluminum Clip in Swing Down with double pip self-leveling feature and special tabs to allow swing down of tile to enable plenum access with plain visual consisting of 600X600 mm clip in plain tiles of 0.7mm uniform thickness Aluminum with bevel edge in approved color precoated with primer coat at the rear side with Light Reflectance > 60%......... (detailed specification as per part C)
958SH 8 B - MISCELLANEOUS WORKS WATER TREATMENT PLANT AND SEWAGE TREATMENT PLANT
959Supply, Installation, testing and commission Water Pre-Treatment Plant Capacity: 20M3 /Hr, for continuous operation of 10 Hr, complete with High Pressure Sand Filter, Activated Carbon Filter,with Multiport valves, Chemical Dosing etc as per final requirement, connected Pipe Work etc, all as per Technical Specifications.Filter Feed Pumps shall be measured seperately.
960Supply, installation, testing and commissioning of Sewage Treatment Plant (MBBR Type) of 150 KLD capacity with Ultra Filter.All Plumbing and Electrical panel, Cabling included as per attached specifications (Detailed Technical Specification Attached)
961Operation and maintenance of the 150 KLD STP and 20m3/hr WTP for three years. (Consumables are the client scope).
962SH 9 - Medical Gas Pipeline System
963SITC of Oxygen Manifold - 2 banks x 10 cylinders.
964SITC of Fully Automatic Oxygen Control Panel with minimum flow rate of 1000 LPM.
965SITC of Emergency Oxygen Manifold - 2 banks x 5 cylinders.
966SITC of Oxygen Flowmeters with humidifier bottle.
967SITC of Nitrous Oxide Manifold - 2 banks x 1 cylinders.
968SITC of Fully automatic Gas Control Panel for Nitrous Oxide with a minimum flow rate of 300 LPM.
969SITC of Emergency Nitrous Oxide Manifold - 1 bank x 1 cylinders.
970SITC of Carbon Dioxide Manifold - 2 banks x 1 cylinders.
971SITC of Fully automatic Gas Control Panel for Carbon Di Oxide with minimum flow rate of 300 LPM.
972SITC of Emergency Carbon Dioxide Manifold - 1 bank x 1cylinders.
973SITC of Compressed air plant system having minimum free air delivery of 1000 LPM with complete accessories as mentioned in technical specifications.
974SITC of vacuum plant system having minimum free air aspirated of 1500 LPM at 450 mmHg with complete accessories as mentioned in technical specifications.
975Ward Vacuum Units
976Theatre Vacuum Units
977SITC of Electrical Panel for Vacuum Pump
978SITC of ICU Terminal Units - Imported - O2
979SITC of ICU Terminal Units - Imported - Air
980SITC of ICU Terminal Units - Imported - VAC
981SITC of Ward Terminal Units - Indigenous - O2
982SITC of Ward Terminal Units - Indigenous - N2O
983SITC of Ward Terminal Units - Indigenous - Air
984SITC of Ward Terminal Units - Indigenous - Air 7 bar
985SITC of Ward Terminal Units - Indigenous - Vac
986SITC of Matching Probe - O2
987SITC of Matching Probe - N2O
988SITC of Matching Probe - Air
989SITC of Matching Probe - Air 7 bar<
990SITC of Matching Probe - VAC
991SITC of Master Plant Alarm Panel (post source), BMS compatible
992SITC of Area Valve Service Units with Alarm Systems - 6 Services
993SITC of Area Valve Service Units with Alarm Systems - 4 Services
994SITC of Area Valve Service Units with Alarm Systems - 3 Services
995SITC of Area Valve Service Units with Alarm Systems - 2 Services
996SITC of Copper pipe - per mtr. - 12mm
997SITC of Copper pipe - per mtr. - 15mm
998SITC of Copper pipe - per mtr. - 22mm
999SITC of Copper pipe - per mtr. - 28mm
1000SITC of Copper pipe - per mtr. - 35mm
1001SITC of Copper pipe - per mtr. - 42mm
1002SITC of Copper pipe - per mtr. - 54mm
1003SITC of Copper pipe - per mtr. - 76mm
1004SITC of Ball Valves - 15mm
1005SITC of Ball Valves - 22mm
1006SITC of Ball Valves - 28mm
1007SITC of Ball Valves - 35mm
1008SITC of Ball Valves - 42mm
1009SITC of Ball Valves - 54mm
1010SITC of Ball Valves - 76mm
1011SITC of Bed Head Units - 1000 mm for Wards
1012SITC of Bed Head Units - 1500 mm for ICU Category.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail