Tender For Providing Sewerage System In Village Siswal District Hisar Construction Of Pumping Station Rcc Collecting Tank , Screening Chamber 2.50 Mld , Construction Of 1 Stp Sbr Technology , Masonry Boundary Wall , Construction 2 Nos. Staff Rcc, Hisar-Haryana

Public Health Engineering Department-PHED has published Tender For Providing Sewerage System In Village Siswal District Hisar Construction Of Pumping Station Rcc Collecting Tank , Screening Chamber 2.50 Mld , Construction Of 1 Stp Sbr Technology , Masonry Boundary Wall , Construction 2 Nos. Staff Rcc. Submission Date for this Tender is 28-03-2023. Pump Supply Tenders in Hisar Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

36681387
Tender For Providing Sewerage System In Village Siswal District Hisar Construction Of Pumping Station Rcc Collecting Tank , Screening Chamber 2.50 Mld , Construction Of 1 Stp Sbr Technology , Masonry Boundary Wall , Construction 2 Nos. Staff Rcc
Open Tender
Indian
Haryana
Hisar
28-03-2023

Tender Details

Providing Sewerage System In Village Siswal District Hisar Construction Of Pumping Station Rcc Collecting Tank , Screening Chamber 2.50 Mld , Construction Of 1 Stp Sbr Technology , Masonry Boundary Wall , Construction 2 Nos. Staff Rcc

Key Value

Document Fees
INR 20000 /-
EMD
INR 986320.0 /-
Tender Value
INR 4.93 Crore /-

BOQ Items

Name of Work
Sl. No. Item Description
1ANNEXE BUILDING: Construction of HT / LT Panel room, PLC room, Centrifuge house, blower room and Lab cum office building including doors, windows and fittings with toilet block including all Sanitary fittings etc. as per drawings approved by SE at MPS and STP 250 Sqm covered area built up with RCC framed structure and brick work finished with vitrified glazed tiles flooring, powder coated aluminum frame made with 10 guage sheet having size 100mm x 45mm for chowkhat, 75mm x 45mm for door frame and 45mm x 45mm for window frame with 5mm thick glass AIS/Saint Gobain/ Modi Float Complete in All respect
2CC TV CAMERA: Providing and Installing 8 CCTV Cameras (4 Cameras for STP and 2 Cameras for each MPS and IPS) complete as per satisfaction of the Engineer– in- Charge, within 96 hours of signing the Agreement along with 90 days recording (DVR), 32 inch LED Screen, 16 Channel DVR at STP Site and 8 Channel DVR at MPS Site with connectors, cables, poles and power supply with online real-time output facility. The cameras at both the sites i.e. MPS and STP shall be synchronized at STP site complete in all Respect . i) At STP and MPS Site- 1 No. PTZ speed dome 360 degree 50X zoom camera, 3 No. 12 mm lens size, 1 Nos. 3.6mm lens size. Make: - CP Plus Internet Protocol minimum 5 MP WDR, Night vision color mode 2.4.2 12 mm very focal with extra IR. CCTV Cameras should be installed and commissioned before starting of the work Complete in all respect.
3A) STP 2.50 MLD: Design, construction, erection, testing and commissioning of 2.50 MLD capacity Sewage Treatment Plant based on Sequential Batch Reactor (SBR) Technology complete in all respect including Landscaping, MCC Panel Room, all other contingent ie. Electrical, Mechanical, Piping and Instrumentation work with PLC and SCADA arrangement for STP integrated with including furniture and laboratory equipment`s as per detail given in the bid document and following components Complete in all Respect. Supply and installation 2 Nos. fine Screens of suitable size for 2.50 MLD average flow with peak factor of 3 Complete in all respect. 2 No. High Mast of 9 mtr GI Octagonal pole of 4 mm thickness (T=100 mm, B=200mm, Base Plate = 320 x 320 x 20 mm), Window at 500 mm from Base Plate with 6 No. LED suitable size, outdoor type energy efficient lamps on each pole, 20 no. LED outdoor light with 7 m. high GI pole along road / path including all accessories complete in all respect. Supply and installation of 1 No. 3.65 m wide Main Gate of MS and 1.25 m. wide wicket gate at STP to the entire satisfaction of Engineer-in-charge. (Total weight not less than 500 kg). Providing and installing 2 No. centrifuges (1Working plus 1 Stand bye) including centrifuge feed pump, all fittings, instrumentations, electric panel board etc. as per design complete in all respect including packing dry sludge in 20 Kg. bag and supplying the same in market Kisan Sewa Kendra or as directed by Engineer-in-charge within the lead as pointed at clause 4.4.4 of the DNIT. B) EWQMS: Supply, Installation, Testing, Commissioning, Operation and Comprehensive Annual Maintenance of effluent quality monitoring system at 2.50 MLD capacity STP for online (continuous) measurement of PH, Total Suspended Solids (TSS), Chemical Oxygen Demand (COD), Biological Oxygen Demand (BOD) by single analyzer with various sensors (spectral measurement in the UV-VIS range 200-720mm) performing reagent and chemical free analysis with automatic cleaning of censor, signal cables and power cables, local data acquisition and display of data on continuous basis for up linking the data to CPCB, HSPCB and PHED, TUV approved complete in all respect as per Central Pollution Control Board (CPCB) guidelines for online continuous monitoring system for effluents and as contained in scope of work in the DNIT.A) Multi-parameter measuring converter, for connecting up to 18 intelligent sensors Scope including 8 analog inputs / outputs (4 inputs and 4 outputs) (0/4-20Ma), wide- range power supply Optical COD/BOD and TSS probe with spectral processing of the UV-VIS range, for measurement in the outlet / effluent of 2.50 MLD capacity STP at village Siswal with integrated with automatic cleaning Complete in all Respect. B) Robust digital pH/ORP sensor for pH/ORP electrodes, with built-in pre-amplifier and temperature sensor with Automatic Temperature Compensation (ATC) Cable length 100 Meter (minimum) Complete in all respect. C) Sensor adapter cable for all intelligent sensors, with IP68 water proof connection to the intelligent Sensor Net system. Cable length 100 meter (minimum)Complete in all Respect. Data transfer to CPCB, HSPCB and PHED. Providing GSM 3G, 4G modem with mobile network connectivity including network...
4MPS FOR 2.50 MLD STP: A)Design, construction, erection, testing and commissioning of MPS and following components. B) RCC Inlet chamber, screening chamber, collecting tank, , wet well sump suitable for 2.50 MLD average flow with peak factor 3 including Providing and installing 5 no. non clog sewage submersible pump sets ie. 1 No.of 5300 LPM, 2no. of 1800 and 2 no. of 900 LPM having minimum head of 15 m, equipped with suitable LT panel boards, all safety devices, automatic capacitor bank and suitable size submersible cable from LT panel to pumps complete in all respect C) K9 DI pipe of suitable dia at MPS including welding and screwing of flanges, ISI marked D.I. fittings, sluice valves, non returning valves as per requirements even for bye-pass arrangements complete in all respect D) 3 Nos. CI Gear Operated Sluice Gate with SS Spindle (SS 410) and seats (SS 304) (2 nos. for screen and 1 no. for partition of collecting tank) as per design E) Supply and installation of 2 mechanical coarse screens suitable for for 2.50 MLD average flow with peak factor of 3.0 complete in all respect F) All Other infrastructure except construction of staff quarter, Boundary wall, path ways / roads and work covered under Schedule -1A (HSR - Items) required to be executed at site to make the MPS functional is included in the scope of work for lump-sum job. G)All the pumping machinery, panel board, Level sensor etc shall be controlled by PLC and SCADA and shall be synchronized with PLC panels at MPS and STP site through broadband internet facility. H) Raw sewage will be available near boundary wall within the premises of proposed STP but the conveyance of sewage through DI pipe of suitable diameter, from this terminal point to the receiving Chamber of the MPS is included in the Turnkey contract. The Level of the MPS / STP will be as per bed level of existing incoming sewer at MPS. I)The size and quantities of all the above components will be as per approved structural/ Hydraulic / Mechanical/ Electrical design to be approved by Departmental before actual execution of work Complete in all Respect ....
5Operation and Maintenance of sewerage treatment plant complete scope of work mentioned in the DNIT as per schedule-IV for a period of 5 years after 12 months during defect liability period and 3 months trial run period. (will be charged to the A/mtc estimate). complete in all respects as per approved NIT. 1) Operation and maintenance during defect liability period after 3 month trial run period ( operation only)
61st year Operation and maintenance
72ndyear Operation and maintenance
83rd year Operation and maintenance
94th year Operation and maintenance
105th year Operation and maintenance
Disclaimer :