Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Excavationinfoundations , trenches etc.,inearthwork , liftup to 1.50metres.Stackingtheeacavated soil not more than 3 metres clear from the edge of the excavation and then returning thestackedsoil in 15 cm. (fifteencentimetres)layers , whenrequiredintoplinth andsidesof foundations etc., conslolidating each of the disposited layer by ramming and watering and then disposing off all excavated soil as directed with in the load of 20 mtrs. Pick and Jumper work etc. complete as perthe directionof the Engineer - in - Charge. |
| 2 | Pumping and Machinery: Booster Stage.Supply, erection, testing & commissioning of horizontal spindle,horizontal split casing,radial split Single, /Multistages centrifugal pumpsor combination of pumps, in series/parallel of recommended make such as Mather and Platt/KSB//Becon weir/Kirloskar/ BE/Jyotior any other make approved from Jal Shakti Vibhag as per BIS 1520-1980 with upto date ammendments read with BIS 9137-1978 or latest edition to suitable for lifting clear water for under mentioned characteristics with bronze impellers/ priming funnels casing ring and shaft sleaves or bronze. shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base platel (base plate to be from the manufacturers of the pumping unit only) to slip ring/squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/Bhel/NGEF/ GEC/Siemen/Jyoti/ABBor any other make approved from Jal Shakti Vibhag suitable for operation on 415(+) /-5% volts, 50 cycles/ second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-)25% of the duty point head. The motor should be as per IS:325-1978with upto date ammendments read with IS:900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements(a) Pump: Specification 1) Make 2) Model3) No of Stages 4) Material(Manufactured certificate to be appended performances) i) Head(H) mtr.ii) DischargeLPSiii) BHP Absorbed HP iv) Effeciency (n) v) NPSH b) Motori) Makeii) Model iii) Motor ratingiv) Speedv) Insulation. |
| 3 | i) Discharge (Q)5.02 LPS each pump. ( 2 no. pumps working at a time Simultaneously ) |
| 4 | ii) Total Dynamic head30.94 mtrs. |
| 5 | a) LWL of sump well (h) 1447 mtr. |
| 6 | b) Shaft level1447 mtr. |
| 7 | c) Level at discharge point 1472 mtr. |
| 8 | d) suction lift (+) head 30.94mtr. |
| 9 | e) Discharge head25 mtr. |
| 10 | f) Static head25 mtr. |
| 11 | iii) Rising main |
| 12 | a) Length 60 mtr. |
| 13 | b) Dia 100mm. |
| 14 | iv) Pumping hour20 hours. |
| 15 | v) Altitude of installation above MSL mtr. |
| 16 | vi) Characterstics of water. Clear cold water |
| 17 | a) Temperature 0C. |
| 18 | b) Ambient temp. 0C. |
| 19 | c) Turbiduty JTU |
| 20 | d) Alkanality |
| 21 | e) Size of the solidNILmm. |
| 22 | f) Other |
| 23 | ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB. ICTC Switch MakeTypeCapacity |
| 24 | Providing M.S Sheet 16 SWG steel fabricatedfloor mounted closed almirah type switch board including angle iron post of suitableheight and size ISA 40x40x6mm duly painted comprising and capable of mounting the followingaccessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer-in-charge.Panel/Switch Board i) Drawing ii) Layout Plan |
| 25 | MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in coming feeder for motors offered by the tenderer conformaing to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.ACB/OCB i) Makeii) Typeiii) Rangeiv) Capacity |
| 26 | Earth leakage circuit braker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 with upto date ammendments and of suitable range with which should have control box , oprating handel and trip/rest bush button / off indicators,re-indicating off spring condition of the circuit braker for over current protection.The curcuit should be equipped with magnet thermal release with metallic tap CTS.It should also be fitted earth fault for trippping of breaker on occurance of earth fault on/of braker load side.ELCBi) Make ii) Typeiii) RangeVoltage relay meter i) Makeii) Typeiii) Range |
| 27 | Voltmeter AC supply,100mm circular dia1Auto electric/AE/IMP/Havells make of suitable range for above motor with selector switches conforming to BIS 4064-1978 with up to date ammendments. Volt Meteri) Makeii) Type iii) Range |
| 28 | Supply & errection of floor/wall mounted power factor capacitor conforming to BIS 2834-1986 latest with upto date ammendmentPower factor meter TypeMake |
| 29 | Frequecy meter of standard make as per relevent IS code with upto date ammendments Frequency Meter i)Make ii) Type iii) Range |
| 30 | Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating for full length for naturalnphase as per IS 8084-1976 and IS 11353-1985 read with BIS-5578-with upto date ammendments. Bus bar chanberi) Make ii) Typeiii) Rating. |
| 31 | ICTC switches with HRC fuses of Kilburn/L&T/Siemens/Standard/ Havels make and of suitable capacity as per IS 4064-1978 with upto date ammendments.ICTC Switchesi) Typeii) Makeiii) Capacity |
| 32 | Three phase indicator lamp complete with toggie switches for indivisual motor as per IS:3452 (P-l&lll) with up to date ammendments.Three phase indicator i)Typeii) Makeiii) Capacity. |
| 33 | Ammeter AC supply,100mm circular dia1Auto electric/AE/IMP/Havells make of suitable range for above motor with selector switches conforming to BIS 1248-1983 latest with up to date ammendments.Ammeter i) Type ii) Make iii) Range. |
| 34 | Supply & errection of floor/wall mounted power factor capacitor conforming to BIS 2834-1986 latest with upto date ammendment BHEL/GEC/Machneil/Masger/Bajaj make to raise the pervailing power factor at site to 0.95 for direct connection to induction motor individually, or requird KVAR according to Himachal Pradesh of motor offered including cable siemens/ Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.Capacitor i) Typeii) Makeiii) Range. |
| 35 | Hour rum meter of reputed make. |
| 36 | Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standared make such as MEI/Kilburn/Jyoti/Siemens conforming to BIS-8544-1979 leateswith up to date ammendments for squirrel cage/slipering motor(make to be specified by the tenderers) mounted on panel board with magnetic typeover load release & dashpot, time log , under voltage release wfith initial oil filling. Single phase preventeri) Typeii) Make |
| 37 | Providing and fixing cast iron flanged/screw type stainer as per IS 4038-1986 with upto date ammendments of Kiloskar/GIED/ Kilburn/ Karter valve Mechneil/ Kilburn leader make 65mm dia. Foot Valvei) Make |
| 38 | Providing and fixing cast iron double flanged sluice valve of class II 65mm dia of leader/ Behl Kirlsker/GIED/ Kilburn/Fouress makesuction side as per the relevent IS code. Sluice Valvei) Make |
| 39 | Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of reputed make of suitable size cast iron /cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52kg/cm^2. The sluice valve shall conform to BIS 780-1984 latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2) as per BS 1414 Sluice Valvei) Make ii) Class iii) Sheet Pressureiv) Material |
| 40 | Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of suitable size cast iron /cast steel double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 52Kg/cm/^2The reflux valve shall conform to BIS 5312-1984 (part I) latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 5312 then the reflux valves shall be cast steel conforming to class 150 ASA (Seat pressure 231Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2)) as per BSI 1414 Reflux Valvei) Make ii) Classiii) Sheet Pressureiv) Material |
| 41 | Providing and fixing double flanged cast steel reflux valve of Leader/BHEL/Kilosker/Kilburn/ GLED/Fouress make and of 50mm dia for rising main having byepass arrangement for rising main andcapable withstanding the normal steel pressure as per IS 780-1984 with up to date ammendments class ASA to be mentioned by the firm. Reflux ValveCast Steel 125mm diai) Make ii) ClassASA 300iii) Sheet Pressureiv) Material |
| 42 | Supply of standard make 100mm dia circular dial pressure of suitable range Fiebeg/ Bourden/Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments. Pressure Guagei) Make ii) Range |
| 43 | Providing, laying, testing & commissioning at site in trenches bevelled endedconforming to IS/ISO:3183-2007 latest having wall thickness & per Rmt. weight as mentioned below & capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.5 mtr. The pipe ends shall be bevelled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable and with uptodate ammendements (leak proof) in three layers at site of work welding rods of Advani/oerliken make/ISI marked (welding rods 3mm to 4mm) and all allied accessories whatever required for welding at site, tail please, tees, bends & other special manufactured from parent pipes as applicable to the particular reach and of approved specification as per site conditions andcutting of pipe wherever required as per site requirement including carriage in all leads & lifts and as directed by the Engineer-in-charge. The pipe shall have zinc coating inside & out side confirming to IS-4736-1986 or latest with upto date ammendments & shall be engraved with API- X 46 etc. The sizes of various components to be as under:l) Suction Pipe---------- mm dia ii) Delivery Pipe ---------- mm dia iii) Common Header----------mm dia.and will be extended up to 5 mtr from the outer wall of the pump house in th direction to be jointed.Suction Pipe i) Material ii) Grade iii) Thicknessiv) Pressure Rating- Delivery pipe and common headeri) Material ii) Gradeiii) Thicknessiv) Pressure Rating |
| 44 | Providing and laying copper PVC insulated armoured power cable (One vable carrying all the three phasees) of suitable size and capacity to motors and all other electrical equipments as per IS:1554 (P-1) 1988 or latest with up to date ammendments of seimence/Gloster/IEC/EICO/National/Grandly make including all other accessories such as thimbles, flexible pipe, solder, nut & bolts, vable gland etc. laid in pipe or trenches under floor. i) Size ii) Makeiii) Type Copper iv)Capacity v) Core 3 |
| 45 | P/L double loop earthing with crpper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendmentsfor above motors & other electrical equipment. i) Size ii) Makeiii) Type Copper iv)Capacity v) Core 3 |
| 46 | Pumping and Machinery: 1st- Stage. Supply, erection, testing & commissioning of horizontal spindle,horizontal split casing,radial split Single, /Multistages centrifugal pumpsor combination of pumps, in series/parallel of recommended make such as Mather and Platt/KSB//Becon weir/Kirloskar/ BE/Jyotior any other make approved from Jal Shakti Vibhag as per BIS 1520-1980 with upto date ammendments read with BIS 9137-1978 or latest edition to suitable for lifting clear water for under mentioned characteristics with bronze impellers/ priming funnels casing ring and shaft sleaves or bronze. shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base platel (base plate to be from the manufacturers of the pumping unit only) to slip ring/squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/Bhel/NGEF/ GEC/Siemen/Jyoti/ABBor any other make approved from Jal Shakti Vibhag suitable for operation on 415(+) /-5% volts, 50 cycles/ second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-)25% of the duty point head. The motor should be as per IS:325-1978with upto date ammendments read with IS:900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements(a) Pump: Specification1) Make2) Model 2) Model3) No of Stages 4) Material(Manufactured certificate to be appended performances) i) Head(H) mtr. ii) Discharge iii) BHP Absorbediv) Effeciency (n) v) NPSH b) Motor i) Makeii) Model iii) Motor ratingiv) Speedv) Insulation. |
| 47 | i) Discharge (Q) 3.57 LPS each pump.( 2 no. pumps working at a time Simultaneously ) |
| 48 | ii) Total Dynamic head 833.87 mtrs. |
| 49 | a) LWL of sump well (h) 1467 mtr. |
| 50 | b) Shaft level1467mtr. |
| 51 | c) Level at discharge point 2230 mtr. |
| 52 | d) suction lift (+) head833.87 mtr. |
| 53 | e) Discharge head 833.87 mtr. |
| 54 | f) Static head763 mtr. |
| 55 | iii) Rising main |
| 56 | a) Length 4600 mtr. |
| 57 | b) Dia 100mm. |
| 58 | iv) Pumping hour20 hours. |
| 59 | v) Altitude of installation above MSL mtr. |
| 60 | vi) Characterstics of water. Clear cold water |
| 61 | a) Temperature 0C. |
| 62 | b) Ambient temp. 0C. |
| 63 | c) Turbiduty JTU |
| 64 | d) Alkanality |
| 65 | e) Size of the solidNILmm. |
| 66 | f) Other |
| 67 | ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB. ICTC Switch MakeTypeCapacity |
| 68 | Providing M.S Sheet 16 SWG steel fabricatedfloor mounted closed almirah type switch board including angle iron post of suitableheight and size ISA 40x40x6mm duly painted comprising and capable of mounting the followingaccessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer-in-charge. Panel/Switch Board i) Drawing ii) Layout Plan |
| 69 | MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in coming feeder for motors offered by the tenderer conformaing to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.ACB/OCB i) Makeii) Typeiii) Rangeiv) Capacity |
| 70 | Earth leakage circuit braker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 with upto date ammendments and of suitable range with which should have control box , oprating handel and trip/rest bush button / off indicators,re-indicating off spring condition of the circuit braker for over current protection.The curcuit should be equipped with magnet thermal release with metallic tap CTS.It should also be fitted earth fault for trippping of breaker on occurance of earth fault on/of braker load side.ELCBi) Make ii) Typeiii) RangeVoltage relay meter i) Makeii) Typeiii) Range |
| 71 | Voltmeter AC supply,100mm circular dia1Auto electric/AE/IMP/Havells make of suitable range for above motor with selector switches conforming to BIS 4064-1978 with up to date ammendments. Volt Meteri) Makeii) Type iii) Range |
| 72 | Supply & errection of floor/wall mounted power factor capacitor conforming to BIS 2834-1986 latest with upto date ammendmentPower factor meter TypeMake |
| 73 | Frequecy meter of standard make as per relevent IS code with upto date ammendmentsFrequency Meter i)Make ii) Type iii) Range |
| 74 | Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating for full length for naturalnphase as per IS 8084-1976 and IS 11353-1985 read with BIS-5578-with upto date ammendments.Bus bar chanberi) Make ii) Typeiii) Rating. |
| 75 | ICTC switches with HRC fuses of Kilburn/L&T/Siemens/Standard/ Havels make and of suitable capacity as per IS 4064-1978 with upto date ammendments. ICTC Switchesi) Typeii) Makeiii) Capacity |
| 76 | Three phase indicator lamp complete with toggie switches for indivisual motor as per IS:3452 (P-l&lll) with up to date ammendments. Three phase indicator i)Typeii) Makeiii) Capacity. |
| 77 | Ammeter AC supply,100mm circular dia1Auto electric/AE/IMP/Havells make of suitable range for above motor with selector switches conforming to BIS 1248-1983 latest with up to date ammendments. Ammeter i) Type ii) Make iii) Range. |
| 78 | Supply & errection of floor/wall mounted power factor capacitor conforming to BIS 2834-1986 latest with upto date ammendment BHEL/GEC/Machneil/Masger/Bajaj make to raise the pervailing power factor at site to 0.95 for direct connection to induction motor individually, or requird KVAR according to Himachal Pradesh of motor offered including cable siemens/ Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer. Capacitor i) Typeii) Makeiii) Range. |
| 79 | Hour rum meter of reputed make. |
| 80 | Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standared make such as MEI/Kilburn/Jyoti/Siemens conforming to BIS-8544-1979 leateswith up to date ammendments for squirrel cage/slipering motor(make to be specified by the tenderers) mounted on panel board with magnetic typeover load release & dashpot, time log , under voltage release wfith initial oil filling. Single phase preventeri) Typeii) Make |
| 81 | Providing and fixing cast iron flanged/screw type stainer as per IS 4038-1986 with upto date ammendments of Kiloskar/GIED/ Kilburn/ Karter valve Mechneil/ Kilburn leader make 65mm dia. Foot Valvei) Make |
| 82 | Providing and fixing cast iron double flanged sluice valve of class II 65mm dia of leader/ Behl Kirlsker/GIED/ Kilburn/Fouress make nsuction side as per the relevent IS code.Sluice Valvei) Make |
| 83 | Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of reputed make of suitable size cast iron /cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52kg/cm^2. The sluice valve shall conform to BIS 780-1984 latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2) as per BS 1414Sluice Valve i) Make ii) Class iii) Sheet Pressureiv) Material |
| 84 | Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of suitable size cast iron /cast steel double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 52Kg/cm/^2The reflux valve shall conform to BIS 5312-1984 (part I) latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 5312 then the reflux valves shall be cast steel conforming to class 150 ASA (Seat pressure 231Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2)) as per BSI 1414 Reflux Valvei) Makeii) Classiii) Sheet Pressureiv) Material |
| 85 | Providing and fixing double flanged cast steel reflux valve of Leader/BHEL/Kilosker/Kilburn/ GLED/Fouress make and ofdia for rising main having byepass arrangement for rising main andcapable withstanding the normal steel pressure as per IS 780-1984 with up to date ammendments class ASA to be mentioned by the firm. Reflux Valve i) Make ii) Classiii) Sheet Pressureiv) Material |
| 86 | Supply of standard make 100mm dia circular dial pressure of suitable range Fiebeg/ Bourden/Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.Pressure Guagei) Make ii) Range |
| 87 | Providing, laying, testing & commissioning at site in trenches bevelled endedconforming to IS/ISO:3183-2007 latest having wall thickness & per Rmt. weight as mentioned below & capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.5 mtr. The pipe ends shall be bevelled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable and with uptodate ammendements (leak proof) in three layers at site of work welding rods of Advani/oerliken make/ISI marked (welding rods 3mm to 4mm) and all allied accessories whatever required for welding at site, tail please, tees, bends & other special manufactured from parent pipes as applicable to the particular reach and of approved specification as per site conditions andcutting of pipe wherever required as per site requirement including carriage in all leads & lifts and as directed by the Engineer-in-charge. The pipe shall have zinc coating inside & out side confirming to IS-4736-1986 or latest with upto date ammendments & shall be engraved with API- X 46 etc. The sizes of various components to be as under:l) Suction Pipe---------- mm dia ii) Delivery Pipe ---------- mm dia iii) Common Header----------mm dia.and will be extended up to 5 mtr from the outer wall of the pump house in th direction to be jointed. Suction Pipe i) Material ii) Grade iii) Thicknessiv) Pressure Rating- Delivery pipe and common headeri) Material ii) Gradeiii) Thicknessiv) Pressure Rating |
| 88 | Providing and laying copper PVC insulated armoured power cable (One vable carrying all the three phasees) of suitable size and capacity to motors and all other electrical equipments as per IS:1554 (P-1) 1988 or latest with up to date ammendments of seimence/Gloster/IEC/EICO/National/Grandly make including all other accessories such as thimbles, flexible pipe, solder, nut & bolts, vable gland etc. laid in pipe or trenches under floor. i) Size ii) Makeiii) Type Copper iv)Capacity v) Core 3 |
| 89 | P/L double loop earthing with crpper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendmentsfor above motors & other electrical equipment.i) Size ii) Makeiii) Type Copper iv)Capacity v) Core 3 |
| 90 | Pumping and Machinery: 2nd Stage.Supply, erection, testing & commissioning of horizontal spindle,horizontal split casing,radial split Single, /Multistages centrifugal pumpsor combination of pumps, in series/parallel of recommended make such as Mather and Platt/KSB//Becon weir/Kirloskar/ BE/Jyotior any other make approved from Jal Shakti Vibhag as per BIS 1520-1980 with upto date ammendments read with BIS 9137-1978 or latest edition to suitable for lifting clear water for under mentioned characteristics with bronze impellers/ priming funnels casing ring and shaft sleaves or bronze. shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base platel (base plate to be from the manufacturers of the pumping unit only) to slip ring/squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/Bhel/NGEF/ GEC/Siemen/Jyoti/ABBor any other make approved from Jal Shakti Vibhag suitable for operation on 415(+) /-5% volts, 50 cycles/ second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-)25% of the duty point head. The motor should be as per IS:325-1978with upto date ammendments read with IS:900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements (a) Pump: Specification1) Make 2) Model 2) Model3) No of Stages 4) Material(Manufactured certificate to be appended performances) i) Head(H) ii) Dischargeiii) BHP Absorbediv) Effeciency (n) v) NPSH b) Motor i) Makeii) Model iii) Motor ratingiv) Speedv) Insulation. |
| 91 | i) Discharge (Q) 2.72 LPS each pump.( ( 2 no. pumps working at a time Simultaneously ) |
| 92 | ii) Total Dynamic head 320.15 mtrs. |
| 93 | a) LWL of sump well (h) 2227 mtr. |
| 94 | b) Shaft level2227 mtr. |
| 95 | c) Level at discharge point 2527 mtr. |
| 96 | d) suction lift (+) head 320.15mtr. |
| 97 | e) Discharge head320.15 mtr. |
| 98 | f) Static head300 mtr. |
| 99 | iii) Rising main |
| 100 | a) Length 1900 mtr. |
| 101 | b) Dia100 mm. |
| 102 | iv) Pumping hour20 hours. |
| 103 | v) Altitude of installation above MSL mtr. |
| 104 | vi) Characterstics of water. Clear cold water |
| 105 | a) Temperature 0C. |
| 106 | b) Ambient temp. 0C. |
| 107 | c) Turbiduty JTU |
| 108 | d) Alkanality |
| 109 | e) Size of the solidNILmm. |
| 110 | f) Other |
| 111 | ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB. ICTC Switch MakeTypeCapacity |
| 112 | Providing M.S Sheet 16 SWG steel fabricatedfloor mounted closed almirah type switch board including angle iron post of suitableheight and size ISA 40x40x6mm duly painted comprising and capable of mounting the followingaccessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer-in-charge. Panel/Switch Board i) Drawing ii) Layout Plan |
| 113 | MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in coming feeder for motors offered by the tenderer conformaing to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.ACB/OCB i) Makeii) Typeiii) Rangeiv) Capacity |
| 114 | Earth leakage circuit braker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 with upto date ammendments and of suitable range with which should have control box , oprating handel and trip/rest bush button / off indicators,re-indicating off spring condition of the circuit braker for over current protection.The curcuit should be equipped with magnet thermal release with metallic tap CTS.It should also be fitted earth fault for trippping of breaker on occurance of earth fault on/of braker load side.ELCBi) Make ii) Typeiii) RangeVoltage relay meter i) Makeii) Typeiii) Range |
| 115 | Voltmeter AC supply,100mm circular dia1Auto electric/AE/IMP/Havells make of suitable range for above motor with selector switches conforming to BIS 4064-1978 with up to date ammendments.Volt Meteri) Makeii) Type iii) Range |
| 116 | Supply & errection of floor/wall mounted power factor capacitor conforming to BIS 2834-1986 latest with upto date ammendmentPower factor meter TypeMake |
| 117 | Frequecy meter of standard make as per relevent IS code with upto date ammendments Frequency Meter i)Make ii) Type iii) Range |
| 118 | Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating for full length for naturalnphase as per IS 8084-1976 and IS 11353-1985 read with BIS-5578-with upto date ammendments. Bus bar chanberi) Make ii) Typeiii) Rating. |
| 119 | ICTC switches with HRC fuses of Kilburn/L&T/Siemens/Standard/ Havels make and of suitable capacity as per IS 4064-1978 with upto date ammendments. ICTC Switchesi) Typeii) Makeiii) Capacity |
| 120 | Three phase indicator lamp complete with toggie switches for indivisual motor as per IS:3452 (P-l&lll) with up to date ammendments. Three phase indicator i)Typeii) Makeiii) Capacity. |
| 121 | Ammeter AC supply,100mm circular dia1Auto electric/AE/IMP/Havells make of suitable range for above motor with selector switches conforming to BIS 1248-1983 latest with up to date ammendments.Ammeter i) Type ii) Make iii) Range. |
| 122 | Supply & errection of floor/wall mounted power factor capacitor conforming to BIS 2834-1986 latest with upto date ammendment BHEL/GEC/Machneil/Masger/Bajaj make to raise the pervailing power factor at site to 0.95 for direct connection to induction motor individually, or requird KVAR according to Himachal Pradesh of motor offered including cable siemens/ Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.Capacitor i) Typeii) Makeiii) Range. |
| 123 | Hour rum meter of reputed make. |
| 124 | Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standared make such as MEI/Kilburn/Jyoti/Siemens conforming to BIS-8544-1979 leateswith up to date ammendments for squirrel cage/slipering motor(make to be specified by the tenderers) mounted on panel board with magnetic typeover load release & dashpot, time log , under voltage release wfith initial oil filling.Single phase preventeri) Typeii) Make |
| 125 | Providing and fixing cast iron flanged/screw type stainer as per IS 4038-1986 with upto date ammendments of Kiloskar/GIED/ Kilburn/ Karter valve Mechneil/ Kilburn leader make 65mm dia. Foot Valvei) Make |
| 126 | Providing and fixing cast iron double flanged sluice valve of class II 65mm dia of leader/ Behl Kirlsker/GIED/ Kilburn/Fouress make n suction side as per the relevent IS code. Sluice Valve i) Make |
| 127 | Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of reputed make of suitable size cast iron /cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52kg/cm^2. The sluice valve shall conform to BIS 780-1984 latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2) as per BS 1414Sluice Valve i) Makeii) Classiii) Sheet Pressureiv) Material |
| 128 | Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of suitable size cast iron /cast steel double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 52Kg/cm/^2The reflux valve shall conform to BIS 5312-1984 (part I) latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 5312 then the reflux valves shall be cast steel conforming to class 150 ASA (Seat pressure 231Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2)) as per BSI 1414Reflux Valve i) Make ii) Class iii) Sheet Pressureiv) Material |
| 129 | Providing and fixing double flanged cast steel reflux valve of Leader/BHEL/Kilosker/Kilburn/ GLED/Fouress make and ofdia for rising main having byepass arrangement for rising main andcapable withstanding the normal steel pressure as per IS 780-1984 with up to date ammendments class ASA to be mentioned by the firm. Reflux Valvei) Make ii) Classiii) Sheet Pressureiv) Material |
| 130 | Supply of standard make 100mm dia circular dial pressure of suitable range Fiebeg/ Bourden/Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments. Pressure Guagei) Make ii) Range |
| 131 | Providing, laying, testing & commissioning at site in trenches bevelled endedconforming to IS/ISO:3183-2007 latest having wall thickness & per Rmt. weight as mentioned below & capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.5 mtr. The pipe ends shall be bevelled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable and with uptodate ammendements (leak proof) in three layers at site of work welding rods of Advani/oerliken make/ISI marked (welding rods 3mm to 4mm) and all allied accessories whatever required for welding at site, tail please, tees, bends & other special manufactured from parent pipes as applicable to the particular reach and of approved specification as per site conditions andcutting of pipe wherever required as per site requirement including carriage in all leads & lifts and as directed by the Engineer-in-charge. The pipe shall have zinc coating inside & out side confirming to IS-4736-1986 or latest with upto date ammendments & shall be engraved with API- X 46 etc. The sizes of various components to be as under:l) Suction Pipe---------- mm dia ii) Delivery Pipe ---------- mm dia iii) Common Header----------mm dia.and will be extended up to 5 mtr from the outer wall of the pump house in th direction to be jointed. Suction Pipe i) Material ii) Grade iii) Thicknessiv) Pressure Rating- Delivery pipe and common headeri) Material ii) Gradeiii) Thicknessiv) Pressure Rating |
| 132 | Providing and laying copper PVC insulated armoured power cable (One vable carrying all the three phasees) of suitable size and capacity to motors and all other electrical equipments as per IS:1554 (P-1) 1988 or latest with up to date ammendments of seimence/Gloster/IEC/EICO/National/Grandly make including all other accessories such as thimbles, flexible pipe, solder, nut & bolts, vable gland etc. laid in pipe or trenches under floor.i) Size ii) Makeiii) Type Copper iv)Capacity v) Core 3 |
| 133 | P/L double loop earthing with crpper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendmentsfor above motors & other electrical equipment. i) Size ii) Makeiii) Type Copper iv)Capacity v) Core 3 |
| 134 | Pumping and Machinery: 1st Stage A Supply, erection, testing & commissioning of horizontal spindle,horizontal split casing,radial split Single, /Multistages centrifugal pumpsor combination of pumps, in series/parallel of recommended make such as Mather and Platt/KSB//Becon weir/Kirloskar/ BE/Jyotior any other make approved from Jal Shakti Vibhag as per BIS 1520-1980 with upto date ammendments read with BIS 9137-1978 or latest edition to suitable for lifting clear water for under mentioned characteristics with bronze impellers/ priming funnels casing ring and shaft sleaves or bronze. shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base platel (base plate to be from the manufacturers of the pumping unit only) to slip ring/squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/Bhel/NGEF/ GEC/Siemen/Jyoti/ABBor any other make approved from Jal Shakti Vibhag suitable for operation on 415(+) /-5% volts, 50 cycles/ second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-)25% of the duty point head. The motor should be as per IS:325-1978with upto date ammendments read with IS:900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements (a) Pump: Specification1) Make2) Model 2) Model3) No of Stages 4) Material(Manufactured certificate to be appended performances) i) Head(H) ii) Discharge iii) BHP Absorbed iv) Effeciency (n) v) NPSH b) Motor i) Makeii) Model iii) Motor ratingiv) Speedv) Insulation. |
| 135 | i) Discharge (Q) 3.28 LPS each pump.( ( ( 2 no. pumps working at a time Simultaneously ) |
| 136 | ii) Total Dynamic head504.07 mtrs. |
| 137 | a) LWL of sump well (h) 1467mtr. |
| 138 | b) Shaft level1467 mtr. |
| 139 | c) Level at discharge point 1940 mtr. |
| 140 | d) suction lift (+) head504.07mtr. |
| 141 | e) Discharge head504.07 mtr. |
| 142 | f) Static head473 mtr. |
| 143 | iii) Rising main |
| 144 | a) Length 2200 mtr. |
| 145 | b) Dia100 mm. |
| 146 | iv) Pumping hour 20 hours. |
| 147 | v) Altitude of installation above MSL mtr. |
| 148 | vi) Characterstics of water. Clear cold water |
| 149 | a) Temperature 0C. |
| 150 | b) Ambient temp. 0C. |
| 151 | c) Turbiduty JTU |
| 152 | d) Alkanality |
| 153 | e) Size of the solidNILmm. |
| 154 | f) Other |
| 155 | ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as BIS 4064-1978 with upto date ammendments immediately after the power meter of HPSEB. ICTC Switch MakeTypeCapacity |
| 156 | Providing M.S Sheet 16 SWG steel fabricatedfloor mounted closed almirah type switch board including angle iron post of suitableheight and size ISA 40x40x6mm duly painted comprising and capable of mounting the followingaccessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer-in-charge. Panel/Switch Board i) Drawing ii) Layout Plan |
| 157 | MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in coming feeder for motors offered by the tenderer conformaing to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.ACB/OCB i) Makeii) Typeiii) Rangeiv) Capacity |
| 158 | Earth leakage circuit braker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 with upto date ammendments and of suitable range with which should have control box , oprating handel and trip/rest bush button / off indicators,re-indicating off spring condition of the circuit braker for over current protection.The curcuit should be equipped with magnet thermal release with metallic tap CTS.It should also be fitted earth fault for trippping of breaker on occurance of earth fault on/of braker load side. ELCBi) Make ii) Typeiii) RangeVoltage relay meter i) Makeii) Typeiii) Range |
| 159 | Voltmeter AC supply,100mm circular dia1Auto electric/AE/IMP/Havells make of suitable range for above motor with selector switches conforming to BIS 4064-1978 with up to date ammendments. Volt Meteri) Makeii) Type iii) Range |
| 160 | Supply & errection of floor/wall mounted power factor capacitor conforming to BIS 2834-1986 latest with upto date ammendmentPower factor meter TypeMake |
| 161 | Frequecy meter of standard make as per relevent IS code with upto date ammendments Frequency Meter i)Make ii) Type iii) Range |
| 162 | Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating for full length for naturalnphase as per IS 8084-1976 and IS 11353-1985 read with BIS-5578-with upto date ammendments. Bus bar chanberi) Make ii) Typeiii) Rating. |
| 163 | ICTC switches with HRC fuses of Kilburn/L&T/Siemens/Standard/ Havels make and of suitable capacity as per IS 4064-1978 with upto date ammendments. ICTC Switchesi) Typeii) Makeiii) Capacity |
| 164 | Three phase indicator lamp complete with toggie switches for indivisual motor as per IS:3452 (P-l&lll) with up to date ammendments. Three phase indicator i)Typeii) Makeiii) Capacity. |
| 165 | Ammeter AC supply,100mm circular dia1Auto electric/AE/IMP/Havells make of suitable range for above motor with selector switches conforming to BIS 1248-1983 latest with up to date ammendments. Ammeter i) Type ii) Make iii) Range. |
| 166 | Supply & errection of floor/wall mounted power factor capacitor conforming to BIS 2834-1986 latest with upto date ammendment BHEL/GEC/Machneil/Masger/Bajaj make to raise the pervailing power factor at site to 0.95 for direct connection to induction motor individually, or requird KVAR according to Himachal Pradesh of motor offered including cable siemens/ Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.Capacitor i) Typeii) Makeiii) Range. |
| 167 | Hour rum meter of reputed make. |
| 168 | Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standared make such as MEI/Kilburn/Jyoti/Siemens conforming to BIS-8544-1979 leateswith up to date ammendments for squirrel cage/slipering motor(make to be specified by the tenderers) mounted on panel board with magnetic typeover load release & dashpot, time log , under voltage release wfith initial oil filling.Single phase preventeri) Typeii) Make |
| 169 | Providing and fixing cast iron flanged/screw type stainer as per IS 4038-1986 with upto date ammendments of Kiloskar/GIED/ Kilburn/ Karter valve Mechneil/ Kilburn leader make 65mm dia. Foot Valvei) Make |
| 170 | Providing and fixing cast iron double flanged sluice valve of class II 65mm dia of leader/ Behl Kirlsker/GIED/ Kilburn/Fouress make n suction side as per the relevent IS code.Sluice Valve i) Make |
| 171 | Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of reputed make of suitable size cast iron /cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52kg/cm^2. The sluice valve shall conform to BIS 780-1984 latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2) as per BS 1414Sluice Valvei) MakeKirloskar/Leader/KSBii) Class iii) Sheet Pressureiv) Material |
| 172 | Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of suitable size cast iron /cast steel double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 52Kg/cm/^2The reflux valve shall conform to BIS 5312-1984 (part I) latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 5312 then the reflux valves shall be cast steel conforming to class 150 ASA (Seat pressure 231Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2)) as per BSI 1414 Reflux Valve i) Make ii) Classiii) Sheet Pressureiv) Material |
| 173 | Providing and fixing double flanged cast steel reflux valve of Leader/BHEL/Kilosker/Kilburn/ GLED/Fouress make and of 50mm dia for rising main having byepass arrangement for rising main andcapable withstanding the normal steel pressure as per IS 780-1984 with up to date ammendments class ASA to be mentioned by the firm. Reflux Valvei) Makeii) Classiii) Sheet Pressureiv) Material |
| 174 | Supply of standard make 100mm dia circular dial pressure of suitable range Fiebeg/ Bourden/Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments. Pressure Guagei) Make ii) Range |
| 175 | Providing, laying, testing & commissioning at site in trenches bevelled endedconforming to IS/ISO:3183-2007 latest having wall thickness & per Rmt. weight as mentioned below & capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.5 mtr. The pipe ends shall be bevelled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable and with uptodate ammendements (leak proof) in three layers at site of work welding rods of Advani/oerliken make/ISI marked (welding rods 3mm to 4mm) and all allied accessories whatever required for welding at site, tail please, tees, bends & other special manufactured from parent pipes as applicable to the particular reach and of approved specification as per site conditions andcutting of pipe wherever required as per site requirement including carriage in all leads & lifts and as directed by the Engineer-in-charge. The pipe shall have zinc coating inside & out side confirming to IS-4736-1986 or latest with upto date ammendments & shall be engraved with API- X 46 etc. The sizes of various components to be as under:l) Suction Pipe---------- mm dia ii) Delivery Pipe ---------- mm dia iii) Common Header----------mm dia.and will be extended up to 5 mtr from the outer wall of the pump house in th direction to be jointed. Suction Pipe i) Material ii) Grade iii) Thicknessiv) Pressure Rating- Delivery pipe and common headeri) Material ii) Gradeiii) Thicknessiv) Pressure Rating |
| 176 | Providing and laying copper PVC insulated armoured power cable (One vable carrying all the three phasees) of suitable size and capacity to motors and all other electrical equipments as per IS:1554 (P-1) 1988 or latest with up to date ammendments of seimence/Gloster/IEC/EICO/National/Grandly make including all other accessories such as thimbles, flexible pipe, solder, nut & bolts, vable gland etc. laid in pipe or trenches under floor. i) Size ii) Makeiii) Type Copper iv)Capacity v) Core 3 |
| 177 | P/L double loop earthing with crpper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendmentsfor above motors & other electrical equipment.i) Size ii) Makeiii) Type Copper iv)Capacity v) Core 3 |
| 178 | Providing, laying, jointing, testing& commissioning at site in trenches galvanized APIpipe pipesbeveled ended IS/ISO:3183-2007pipe conforming to IS/ISO:3183-2007 with latest up-to-dateamendments, having wall thickness as mentioned below & capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.5 mtr. The pipe ends shall be beveled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable and with up-to-dateamendments(leak proof) in three layers at site of work with welding rods ofAdvani/oerliken make/ISI marked(welding rods 3mm to 4mm ) and all allied accessories whatever required for welding at site including special short pieces, reducers, tail pieces,tees, bends & other specials manufactured from parent pipes as applicable to the particular reach and of approved specification as per site conditions. And cutting of pipes wherever required as per site requirement including carriage in all leads & lifts and as directed by the Engineer-in-Charge. The laying of pipe shall include all operation such as cutting, welding, jointing, providing and fixing of MS flanges, fabrication of bends, tees,valves etc. Including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respect to the satisfaction of engineer-in-charge. The fabricated bends shall have three or four cuts having its radius not less thanfive times the dia of pipe.The pipe shall have zinc coating inside&outside confirming to IS-4736-1986 or latest with up to date amendments& shall be engraved with as mentioned bolw. The laying shall confirm to BIS 5822-1970 or latest with up to date amendments to the entire satisfaction of Engineer In charge (Earth work & cost of MS flanges after 100meter length shall be measured and paid for separately.) including all leads, lifts and carriage of materials at site and as per direction and to the entire satisfaction of the Engineer-in Charge complete in all respects. |
| 179 | Stage 1stRD-0 to 3900API-X 70 W.T 4.80mm100mm dia. |
| 180 | Stage 2ndRD-0 to 900L-210 W.T 4.80mm100mm dia. |
| 181 | Stage 1st. A RD-0 to 1800 API-X42W.T 4.80mm 100mm dia. |
| 182 | Laying, testing and commissioning at site in trenches bevelled ended BIS marked GI Heavy conforming to IS 1239 or it equivalent latest with uptodate ammendments of following dia of Heavy/ Medium class, having wall thickness and weight per Rmt. as mentioned below and capable of withstanding required test pressure as presscribed in BIS/IS)code, in random lengths of 5.5 to 6.5mtr. The pipes ends shall be bevelled suitable for butt welding, including the cost of ointing with butt welding confirming to IS 816-1969 or latest as appliable and with upto date ammendments (leak proof) in three layers at site of work with welding rods of Advani/Oerliken make/ISI marked(welding rods 3mm to 4mm) and all allied accessories whatever required for welding at site, tail pieces, tees bends & other specials manufactured from parent pipes as applicable to the particular reach & of approved specificatin as per site conditions and cutting of pipes wherever required as per site requirment i/c carriage in all leads & lifts and as directed by the Engineer-in-charge. |
| 183 | Booster StageRD-0 to 60 Medium Class 100 mm dia. |
| 184 | Stage 1st.RD-3900 to 4500Heavy Class100mm dia. |
| 185 | RD-4500 to 4600MediumClass100mm dia. |
| 186 | Stage 2nd. RD-900 to 1200Heavy Class100mm dia. |
| 187 | RD-1200 to 1900MediumClass100mm dia. |
| 188 | Stage 1stARD-1800 to 2100Heavy Class100mm dia. |
| 189 | RD-2100 to 2200MediumClass100mm dia. |
| 190 | Providing and welding MS flanges as per table below conforming to IS:6392-1971( latest upto date amendments) and welding of flanges with pipes as per IS: 816-1965 with a electrode as per IS: 814-1967 including required Nos. and size of MS nuts and bolts as per IS: 1369-1967 and compressedasbestos fiber jointless gaskets sheet not less than 3mm thick as per IS: 2712-1965. The welding of flanges to be done in three layers ( two out side+one inside)to make the joints leak proof and to the entire satisfaction of the Engineer-in-charge. |
| 191 | Stage 1st.API-X70 FT 34T 4.80100 mm dia. |
| 192 | API-X 70 FT 28 T 4.80100 mm dia. |
| 193 | Stage2nd L 210 FT28T 4.80100 mm dia. |
| 194 | L 210 FT 17 T 4.80 100 mm dia. |
| 195 | Stage 1stA API-X42 FT28T 4.80100 mm dia. |
| 196 | API-X42 FT 17 T 4.80 100 mm dia. |
| 197 | Laying, jointing & testing of GMS pipe plainendedpipeswith bevelled edge and capabale of with standing required test pressure,in random length of 5.5-6.5 meters i/c testing and commissioning and cost of jointing material sucha as MS Flange confirming to IS 6392-1971(leak proof) a/w nut boltand washers of IS 1963 specification i/c rubber/asbestos fibre sheet gasket 3mm thick conforming to relevant ISspecification & as per the direction ofthe Engineer in charge earth work in trenches to be measured and paid for sepratelyi/c allleads, lifts and carriage of materials at site. |
| 198 | Booster StageMedium ClassFT 5 100 mm dia. |
| 199 | Stage 1stHeavy ClassFT 5100mm dia. |
| 200 | Stage 2nd HeavyClassFT 5100mm dia. |
| 201 | Stage 1stA Heavy ClassFT 5 100 mm dia. |