| 1 | Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 3 star rating and EER 3.2 ofcapacity 1.5 Ton complete all as specified and directed by Engr-in-Charge. |
| 2 | Supply and install hi wall split units indoor/ outdoor complete with cordless remote control unit and with cooling and heating function with star rating ofcapacity 1.5 Ton complete all as specified and directed by Engr-in-Charge. |
| 3 | Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with star rating and EER 3.2 ofcapacity 2.0 Ton complete all as specified and directed by Engr-in-Charge. |
| 4 | Supply and install Cassette type units indoor/outdoor complete with cordless remote control unit and with in built Heating and Cooling arrangement and Digital Inverter twin rotary compressor, single phase units 220V - 240V, 50 Hz of capacity 3.0 Ton complete all as specified and directed by Engr-in-Charge. |
| 5 | Supply and fixing room window type air conditioner electric driven (single phase), cooling capacity 4500 K Cal per hour (1.5 Ton) star rated complete all as specified and directed by Engr-in-Charge. |
| 6 | Supply, installation, commissioning of Water cooler partially stainless steel, electric driven single phase having approx storage and nominal cooling capacity 40/80 Ltr complete all as specified and directed by Engr-in-Charge. |
| 7 | Supply, installation, commissioning of Water cooler partially stainless steel, electric driven single phase having approx storage and nominal cooling capacity 150 / 150Ltr complete all as specified and directed by Engr-in-Charge. |
| 8 | Supply, installation, commissioning of Water cooler partially stainless steel, electric driven single phase having approx storage and nominal cooling capacity 60 / 120Ltr complete all as specified and directed by Engr-in-Charge. |
| 9 | Supply and fix refrigerator, electric driven (single phase), capacity 310 Litres, BEE star rated, Inverter Frost Free, Double Door, complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply, installation, commissioning of Metal Top Deep Freezer single phase 240 volt, 50 Hzof capacity 310 Ltr complete all as specified and directed by Engr-in-Charge. |
| 11 | Supply and install hi wall split units indoor/ outdoor complete with cordless remote control unit and with cooling and heating function of capacity 2.0 Ton complete all as specified and directed by Engr-in-Charge. |
| 12 | Design, Supply, Installation and Testing of Ductable (AIR COOLED) Air conditioners fitting with scroll compressors complete with all fittings, inbuilt electric control Panel & microprocessor controls of capacity 8.5 Ton or nearest size complete all as specified and directed by Engr-in-Charge.Note:The specifications and drawing of Duct is to be submitted by the Contractor and approved by GE before installation ofAir conditioners. |
| 13 | Supply and fixing of Refrigerant piping complete with all fittings such as bends, tees, elbows etc including insulation as per specifications for the item Srl No 12 above complete all as specified and directed by Engr-in-Charge. |
| 14 | Supply and fixing GI duct as per technical specificatons and drawings complete with all fitting, accessories, dampers, vanes, takeoffs, canvas connections transformation. The rate shall include suspension and supporting arrangement with angle iron and dash fasteners of thickness 0.80mmcomplete all as specified and directed by Engr-in-Charge. |
| 15 | Supply and fixing Supply and Return grills & diffusers as per specifications and drawing complete all as specified and directed by Engr-in-Charge. |
| 16 | Supply and fixing Fire retardant non porous double layer flexible connection between each indoor unit and duct complete all as specified and directed by Engr-in-Charge. |
| 17 | Supply and fixing Acoustic lining for Duct with 12 mm thick fiberglass (density 48kg/cum) stick using shalikote primer hot bitumen and mechanically fastened, covered with RP tissue and 30G aluminum perforated sheet. Acoustic lining shall be rigid board Twiga 300 complete all as specified and directed by Engr-in-Charge. |
| 18 | Supply and fixing Duct thermal insulation with 13 mm thick Nitrile rubber with black BOPP tape 75 mm wide complete all as specified and directed by Engr-in-Charge. |
| 19 | Supply and fixing Drain piping with necessary fittings such as elbow, reducers complete all as specified and directed by Engr-in-Charge |
| 20 | Material and labourfor Communication wire for Interlocking between IDU & ODU including electrical contactor near each outdoor unit complete all as specified and directed by Engr-in-Charge |
| 21 | Material and labour for Gas charging and Testing with Nitrogen of Ductable Air Conditioner complete all as specified and directed by Engr-in-Charge. |
| 22 | Supply and installing of the electric water storage heater of ABS body type, 25 ltr capacity, 5 Star rated of ABS body vertical type glass lined of inner tank and heating element, syphon assembly, NRV and having the wall mounting arrangement, thermostate, indicators and thermally insulated stainless steel tank of glass lined inside the tank and heating element including steel braided flexible connection for pipe of size 15mm dia bore with GI hexagonal adopters, Nuts on both sides and mounting on wall with suitable size of anchor bolts with complete connection of water including after installation testing complete all as specified and directed by Engr-in-Charge. |
| 23 | Supply and installing of the electric water storage heater of ABS body type, 50 ltr capacity, 5 Star rated of ABS body vertical type glass lined of inner tank and heating element, syphon assembly, NRV and having the wall mounting arrangement, thermostate, indicators and thermally insulated stainless steel tank of glass lined inside the tank and heating element including steel braided flexible connection for pipe of size 15mm dia bore with GI hexagonal adopters, Nuts on both sides and mounting on wall with suitable size of anchor bolts with complete connection of water including after installation testing complete all as specified and directed by Engr-in-Charge. |
| 24 | Material and labourfor point wiring with two single core 2.5 sqmm cable (nominal area) stranded copper conductor, PVC insulated unsheathed cable, 1100 V grade in and including concealed PVC conduit of size not less than 20mm dia with sunken type pressed steel terninal box 1.6 mm thick of suitable size, duly painted with one coat of red oxide primer andtwo coats of black bituminous paint for mounting fittings / junction boxes and wiring to be terminated in pressed steel sunken boxes including all accessories and using single core 1.5 Sqmm (nominal area) stranded copper conductor, PVC insulated unsheathed cable as in earth wire (green colour) connected to common earth dully complete for one 15 Amp 5 Pin switch socket point on an independent board complete all as specified and directed by Engr-in-Charge. |
| 25 | Material and labour for concealed sub main wiring using two single core PVC insulated, unseathed FRLS multi stranded copper conductor cable of size 2.5 Sqmm of voltage rarting upto and including 1100 volts drawn in and including concealed PVC conduit of dia not less than 25mm with all fittings and accessories, along with one run of PVC (green colour) insulated, unsheathed, FRLS multi stranded copper conductor of size 1.5 Sqmm as earth continuity conductor complete all as specified and directed by Engr-in-Charge.Note : Two run of single core PVC cable with one run of earth conductor and conduit shall be measured as one unit) |
| 26 | Supply and fixing Switch piano flush type single pole, one way 15 Amps 230 Volts AC circuitcomplete all as specified and directed by Engr-in-Charge. |
| 27 | Supply and fixing socket outlet 2 in 1, 3 Pin 5 & 15 Amps, 230 Volts AC circuitcomplete all as specified and directed by Engr-in-Charge. |
| 28 | Supply and fixing on wall pipe GI medium grade of size 15mm dia with all fittings such as tees, bends, elbows, reducers, nipples, sockets etc, cutting/opening/threading of existing steel water tubing, fixed properly in concealled to wall / Tiles surface and making / matching good the surface as the existing colours, materials including bib tabs,stop valve as per site requirement complete all as specified and directed by Engr-in-Charge.Note for Item Srl No. 1 to 23:1.All Old and UNSV items complete including Compressors and other accessories serviceable / UNSV removed from location / site / Bldg are to be kept in MES Store for further disposable by MES executives. 2. The site is to make good surface as to the existing surface and the rates are deemed to be included in the quoted rates. |
| 29 | Material and labourfor point wiring with two single core 2.5 sqmm cable (nominal area) stranded copper conductor, PVC insulated unsheathed cable, 1100 V grade in and including concealed PVC conduit of size not less than 20mm dia with sunken type pressed steel terninal box 1.6 mm thick of suitable size, duly painted with one coat of red oxide primer andtwo coats of black bituminous paint for mounting fittings/ junction boxes and wiring to be terminated in pressed steel sunken boxes including all accessories and using single core 1.5 Sqmm (nominal area) stranded copper conductor, PVC insulated unsheathed cable as in earth wire (green colour) connected to common earth dolly completefor one 3 pin socket outlet, 15 amp independent complete all as specified and directed by Engr-in-Charge. |
| 30 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
| 31 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4.0 core complete all as specified and directed by Engr-in-Charge. |
| 32 | Excavation in trenches n.exc 1.5m wide and n.exc 1.5m deep and getting out in any type of soil for laying of cable completeall as specified and directed by Engineer-in-charge. |
| 33 | Returning filling in (soil) including spreading levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified and directed by Engr-in-Charge. |
| 34 | Removal of excavated soil to a distance n.exc 50 m anddepositing where directed at a level not exc 1.5 mtr above the ground level/starting point completeall as specified and directed by Engineer-in-charge. |
| 35 | Sand cushioning to under ground cable 8 cm thick layer below the cable and 15cm thick above the cable complete all as specified and directed by Engr-in-Charge. |
| 36 | Sub Class\"B\"brickcovering protectionto the eletric cablelaiddry flat transversallyalongthe lengthof cableon sandcushioningwith widthequal to lengthof brickcompleteall as specified and directed by Engineer-in-charge. |
| 37 | Cutting of bituminous road / floor for laying of pipe / cables not exceeding 1.5 meter wide and not exceeding 1.5meterdeep including refilling / with material andwatering well ramming / compacting and making good with PCC 1:2:4, type B-1, 100 mm thick complete all as specified anddirected by Engr-in-Charge. |
| 38 | Supply and fixing of GI pipe medium grade, forroad crossing / on wall / on pole for cableprotection of size 40 mm dia complete all as specified anddirected by Engr-in-Charge. |
| 39 | Supply & fixing MCCB DB VTPN 4 ways,with metal double door ,IP -43 protection suitable for MCCB as incommer and MCB as out going,VTPN DB\"s 415 volt 3 phase complete with appropriate size copper bus bar and neutral link of complete with one MCCB 4 pole 415 volts 63 amps 25 KA ( as required at site ) and including cutting chases to wall for fixing of DB and making good distrubed wall/surface all as required at site i.e complete all as specified anddirected by Engr-in-Charge. |
| 40 | Supply and fixing of MCB single pole, 240 volts, 5 to 32 Amps, complete all as specified anddirected by Engr-in-Charge. |
| 41 | Supply and fixing of MCB single pole and neutral, 240 volts, 5 to 30 Amps, complete all as specified anddirected by Engr-in-Charge. |
| 42 | Supply and fixing of 17 tempra plug and socket DBs for provision of FP RCCBs 32 A complete all as specified anddirected by Engr-in-Charge. |
| 43 | Sub main wiring complete with 2 runs of 4 Sqmm single core PVC insulated unsheathed cable 1100 V,FR grade with multistranded copper conductor ISI marked drawn through PVC rigid conduit andaccessories fixed on surface/wall celing etc including provision of 1 run of 2.5 Sqmm PVC insulated unsheathed cable with multistranded copper conductor as earth continuity complete all as specified anddirected by Engr-in-Charge. Note : Two runs of copper conducterand one runs of earth copper conductershall be measured as one length. |
| 44 | Sub main wiring complete with 4 runs of 6 Sqmm single core PVC insulated unsheathed cable 1100 V,FR grade with multistranded copper conductor ISI marked drawn through PVC rigid conduit andaccessories fixed on surface/wall celing etc including provision of 2 run of 4 Sqmm PVC insulated unsheathed cable with multistranded copper conductor as earth continuity complete all as specified anddirected by Engr-in-Charge. Note : Two runs of copper conducterand one runs of earth copper conductershall be measured as one length. |
| 45 | Supply, install, test and commissioning in replacement of outdoor factory made powder coated cubical type double door , compartmentalised LT feeder pillar box of size 0.90x0.45x1.2m complete weather proof and verminproof conforming to IP-54 made out of 3.15mm thick CRCA sheet including provisions for ventilation and cable termination alley all as per IS.It should be mounted on 40 x40 x 6mm angle frame with a clearance of at least 0.45mtrs above GL and 0.30mtrs below ground including required PCC for foundation and coping.Markings should be made with vinyl sheet indicator to identify incoming and outgoing circuits. Feeder pillar box shall be comprising of following.a) MCCB, 4 pole, 125 Amps, 25KA with thermal magnetic relaese - 1 No. ( incoming)b) MCCB 4 Pole 63 Amps, 16 KA with thermal magnetic relaese - 03 Nos.(out going)c) LED phase indicating lamp - 01 Set. d) Copper Bus bar 3 phase 4 wire of capacity 250Amps - 01 Set |