| 1 | Providing Fixing IOT enabled MULTIJET/ TurbineWOLTMANN type machanical bulk flow meter specification of reputed make confirming to ISO 9001 certification with removalbe mechanism, having dry dial, magnetically coupled, hermetically sealed totalized, Class ’B’ as per ISO 4064 (International standards). Meters must be pre-equipped for AMR (Automated Meter Reading)capable of resisting pressure up to PN16, PVC/Cast Iron strainer, fittings, cuttings, threading, plumbing and elecricalaccessories engineering with all leads and lifts as per direction of Engineer In-Charge. |
| 2 | Bulk Flow meter Machanical Turbine Type |
| 3 | 20(mm) |
| 4 | 25(mm) |
| 5 | 32(mm) |
| 6 | 40(mm) |
| 7 | 50(mm) |
| 8 | 65(mm) |
| 9 | 80(mm) |
| 10 | 100(mm) |
| 11 | 125(mm) |
| 12 | 150(mm) |
| 13 | 200(mm) |
| 14 | METAL BOX: Providing Fixing MS Metal Sheet minimum 1.0 mm thick metallic Box size [30x30x30 cm] bottom less with MS ANGLE [25x25x5mm ] legs of 150 mm height properly anchored/ grouted in ground with CC 1:2:4 (cement concrete) as per specifications with LOCKING arrangments duly redoxide and paint on all side inside outside to house Bulk Flow meter with all leads and lifts as per direction of Engioneer In-Charge. |
| 15 | TURBIDITY SENSOR: Providing Fixing NEPHELOMETRIC Turbidity sensor based NEPHELOMETRIC measuring principle 90°NIR [Near In-fra Red] scattered light according to ISO 7027: 1999, measurement at wavelength 860 ?m with turbidity range [0-100 NTU] including all accessories like plumbing electrical, cabling, engineering with all leads and lifts as per direction of Engineer In-Charge. |
| 16 | Communication Devices: |
| 17 | LORA UNIT: Providing Fixing RTU [Remote Terminal Unit] operated with 5 V Li Ion battery for secured transfer of DATA from sensor/ Flowmeter with networking cellular LORA/ Wi-fi/NB Wi-fi ethernet RF range -400m-1000m (for LORA based RTU) Secured transmission of telemetry via MQTT/AMQP/HTTPS using TLS/DTLS/AES standards including memory card for storing DATA for a minimum of 30 days in case of power failures/loss of connectivity complete in all respect with certification with all leads and lifts as per direction of Engineer In-Charge. |
| 18 | LORA GATEWAY UNIT WITH NANO SIM: Providing Fixing DATA coommunication GATEWAY device with solar powered supply (shall be measured and paid seperatly) for DATA acquisition from RTU and Communication through secured transmission telemetry with standards protocol using LORA/Wi-Fi/NB Wi-Fi cellular /GPRS ethernet for connecting to Cloud server for at lease 2 months DATA back up as per detailed specifications with all leads and lifts as per direction of Enginmeer In-Charge. |
| 19 | Stop overflow loss [ESR level based pump automation] |
| 20 | Consumer Flow meter: Providing Fixing IOT enabled MULTIJET WOLTMANN type machanical bulk flow meter specification of reputed make confirming to ISO 9001 certification with removalbe mechanism, having dry dial, magnetically coupled, hermetically sealed totalized, Class ’B’ as per ISO 4064 (International standards). Meters must be pre-equipped for AMR (Automated Meter Reading)capable of resisting pressure up to PN16, PVC strainer, fittings, cuttings, threading, plumbing and elecricalaccessories engineering with all leads and lifts as per direction of Engineer In-Charge. (15mm) |
| 21 | Pressure Sensor: Providing Fixing Pressure sensor enable to transmit pressure having pressure range [0.1 to 60 bars] having minmium IP-67 protection from moist and harsh envirnment capable of transmitting analog digital output 4-20mA to RS485 Modbus RTU [Remote Terminal Unit] operating temperature range of [-40? to 125?] with complete acessories in all respect calibration certificate with all leads lifts as per direction of Engineer In-Charge. |
| 22 | Residual Chlorine sensor: Providing Fixing Residual Chlorine Sensor based on AMPEROMETRIC PRINCIPLE according to ISO 7393-2:2017 with a range od 0 to 05 ppm complete in all respect with all acessories with all leads lifts as per direction of Engineer In-Charge. |
| 23 | TV DISPLAY UNIT in GP: Providing Fixing LED TV DISPLAY UNIT minimum 43\" cm screen of reputed make/ BRAND [SAMSUNG, LG, SONI, PANNSONIC] approved from Himachal Pradesh State elctronic corporation [DISPLAY RESOLUTION]: 1920 X 1080 full HD brightness: 32\" 240 cd/m2, responce time 12ms or less, connectivity : 2 X HDMI in , X USB 2.0.1 X Components , 1XR 145, IX RS 232 built in Wi-Fi, Screen mirroring audio output RMS: 10 Watt X 2 or Better Warranty 3 years mounted to the wall with fixing standscomplete set will all acessories wiring cables, elecrical fittings networking cable linking with networking devices with all leads lifts as per direction of Engineer In-Charge. |
| 24 | SOLAR PANEL with Lead Acid Battery: Providing Fixing Reputred make and MNER approved Solar Panel Power Supply System to pressure sensor/ Communication GATEWAY device wiith 12V-10Watt SOLAR PANEL with 7.5 Ah ACID BATTERY properly mounted on GI pipe not less than 40 mm dia[light class] minimum 2.0 m height. the battery shall be properly fixed and encaged in a metal BOX duly painted on all side [inside outside]having locking arrangments complete in all respect wiring to the nearest sensor/ communication GATEWAY device with all leads and lifts as per direction of Engineer In-Charge. |
| 25 | SIGNAL IMPROVING DEVICE |
| 26 | Providing Training to thedepartmental personnel on site in assembly startup,operation,maintenance an/or repair of supplied goods,course topics will include sensor calibration,datalogges cenfiguration data downloading,data retrieval collection,troubleshooting,processing maintenance requirements and procedures for equipments and procedures for equipment configuration,installation,site testing and commissioning including kit containing course material in soft & hard copies as per technical specification. |
| 27 | Solan Block |
| 28 | Kandaghat Block |
| 29 | Nalagarh Block |
| 30 | Dharampur Block |
| 31 | OPERATION & MAINTENANCE COST for 1st 2 yrs Warranty Period +5 Year complete in all respect by maintaing all the instruments during warrantee period and maintenance period of 5 years with replacement/ repair of all damaged or non functioning units/ components including acessories. |
| 32 | Ist Year |
| 33 | Solan Block |
| 34 | Kandaghat Block |
| 35 | Nalagarh Block |
| 36 | Dharampur Block |
| 37 | 2nd Year |
| 38 | Solan Block |
| 39 | Kandaghat Block |
| 40 | Nalagarh Block |
| 41 | Dharampur Block |
| 42 | 3rd Year |
| 43 | Solan Block |
| 44 | Kandaghat Block |
| 45 | Nalagarh Block |
| 46 | Dharampur Block |
| 47 | 4th Year |
| 48 | Solan Block |
| 49 | Kandaghat Block |
| 50 | Nalagarh Block |
| 51 | Dharampur Block |
| 52 | 5th Year |
| 53 | Solan Block |
| 54 | Kandaghat Block |
| 55 | Nalagarh Block |
| 56 | Dharampur Block |