Provision Of Solar Power Plant Of Capacity 55 Kw In Adm Area-I At Cbs Gharota Complex Under Ge(S) Mamun, mamun-Punjab

Military Engineer Services-MES has published Provision Of Solar Power Plant Of Capacity 55 Kw In Adm Area-I At Cbs Gharota Complex Under Ge(S) Mamun. Submission Date for this Tender is 25-03-2023. Solar Power Plants Tenders in mamun Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

36484123
Corrigendum : Provision Of Solar Power Plant Of Capacity 55 Kw In Adm Area-I At Cbs Gharota Complex Under Ge(S) Mamun
Open Tender
Indian
Punjab
mamun
25-03-2023

Tender Details

Provision Of Solar Power Plant Of Capacity 55 Kw In Adm Area-I At Cbs Gharota Complex Under Ge ( S ) Mamun

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 06-Mar-2023 Amendment No 01 BOQ 18-03-2023
2 18-Mar-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 25-03-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 85200.0 /-
Tender Value
INR 42.60 Lakhs /-

BOQ Items

Name of Work: PROVN OF SOLAR POWER PLANT OF CAPACITY 55 KW IN ADM AREA-I AT CBS GHAROTA COMPLEX UNDER GE(S) MAMUN (JOB NO M/06/LBW/2022-23)
Sl. No. Item Description
1Design, supply, erecting, installing, testing and commissioning of solar PV plant with cumulative capacity of 10 KW off grid connected with out Battery Bank and including fixing accessories, fasteners, nuts, bolts, of stainless steel -304 Grade, complete with and including following all as per specified and directed by GE. (a)Solar Module of size as per manufacturer. (b)IEC/MNRE approved Mono-crystalline type module. (c)Module wattage not less than 450Wp half cut. (d) Technical specification shall be approved before placing order. (e)Module Efficiency not less than 20.7%, each (f) Module weight as per manufacturer recommendation. (g)PV modules must be warranted for their output peak watt capacity, which shall not be less than 90% of the initial value at the end of 10 years and 80% of the initial value at the end of 25 years. (h)The make of solar panel shall be indigenous & MNRE approved. Certificate for the same along with technical specification shall be produced to GE before placing order. (j) Contractor is advised to visit the site before quoting rates. Note:-(i) Any necessary item required for functioning of Solar plant but not catered in the contractwill be deemed to beincluded in the quoted rate and nothing extrawill be admissible on this account. (ii) Frame work to support solar modules to be measured and paid separately under respective item of BoQ.
2Design, supply, erecting, installing, testing and commissioning of solar PV plant with cumulative capacity of 15 KW off grid connected with out Battery Bank and including fixing accessories, fasteners, nuts, bolts, of stainless steel -304 Grade, complete with and including following all as per specified and directed by GE. (a)Solar Module of size as per manufacturer. (b)IEC/MNRE approved Mono-crystalline type module. (c)Module wattage not less than 450Wp half cut. (d) Technical specification shall be approved before placing order. (e)Module Efficiency not less than 20.7%, each (f) Module weight as per manufacturer recommendation. (g)PV modules must be warranted for their output peak watt capacity, which shall not be less than 90% of the initial value at the end of 10 years and 80% of the initial value at the end of 25 years. (h)The make of solar panel shall be indigenous & MNRE approved. Certificate for the same along with technical specification shall be produced to GE before placing order. (j) Contractor is advised to visit the site before quoting rates. Note:-(i) Any necessary item required for functioning of Solar plant but not catered in the contractwill be deemed to beincluded in the quoted rate and nothing extrawill be admissible on this account. (ii) Frame work to support solar modules to be measured and paid separately under respective item of BoQ.
3Design, supply, erecting, installing, testing and commissioning of solar PV plant with cumulative capacity of20 KW off grid connected with out Battery Bank and including fixing accessories, fasteners, nuts, bolts, of stainless steel -304 Grade, complete with and including following all as per specified and directed by GE. (a)Solar Module of size as per manufacturer. (b)IEC/MNRE approved Mono-crystalline type module. (c)Module wattage not less than 450Wp half cut. (d) Technical specification shall be approved before placing order. (e)Module Efficiency not less than 20.7%, each (f) Module weight as per manufacturer recommendation. (g)PV modules must be warranted for their output peak watt capacity, which shall not be less than 90% of the initial value at the end of 10 years and 80% of the initial value at the end of 25 years. (h)The make of solar panel shall be indigenous & MNRE approved. Certificate for the same along with technical specification shall be produced to GE before placing order. (j) Contractor is advised to visit the site before quoting rates. Note:-(i) Any necessary item required for functioning of Solar plant but not catered in the contractwill be deemed to beincluded in the quoted rate and nothing extrawill be admissible on this account. (ii) Frame work to support solar modules to be measured and paid separately under respective item of BoQ.
4Supply, fixing, testing and commissioning of minimum 10 Kw 50 Hz, 3 phase 415V, IP protection IP65 , Input(DC) PV power 14630 Wp, Max DC power per MPPT 6200 W and Max output(AC)power 11000VA, Max output current 15.9 Amps suitable to convert DC power of solar PV module/array/battery bank to AC for further feeding to existing system.The input D.C. tech specification of inverter are as under:- (i) Operating temperature :- 25ºC to + 60ºC (ii) Relative humidity (Non condensing) upto 95%. (iii)The inverters shall have minimum protection to IP65 and minimum European efficiency 98% load as per IEC 61683 standard.. (iv) The inverter shall consist of associated control, protection, data loging device and remote monitoring hardware. Derating factor will be considered for Garota area (Punjab) . (v) The inverter shall adjust voltage and frequency levels to suit the existing DG Sets/AC power supply. (vi) The inverter shall be self-commulated with pulse width modulation (PWM) technology and shall be capable of synchronize maximum within 1 minute. (vii) Full power MPPT Viltage Range (480V to 850V). (viii) Out put rated power 10000W, Max Ac power 11000 VA, Max output current 15.9 A, Nominal Grid voltage 3/N/PE, 230 Vac/400 Vac, Nominal frequency -50 - 60 Hz, Grid frequency range 45 Hz to 55 Hz, Active power adjst range - 0-100%, power factor 1(Adjustable +/-0.8). (ix) Max efficiency - 98.3%, Safety protection Anti islanding,RCMU, Ground fault monitoring, Operation data storage - 25 yrs. (x)Std communication mode RS485 WiFi/GPRS (optional), SD card, Noise<29 dB, LCD Display.
5Supply, fixing, testing and commissioning of minimum 15 Kw 50 Hz, 3 phase 415V, IP protection IP65, Input(DC) PV power 19950 Wp, Max DC power per MPPT 11000 W and Max output(AC)power 16500VA, Rated power 15000W Max output current 24 Ampssuitable to convert DC power of solar PV module/array/battery bank to AC for further feeding to existing system.The input D.C. tech specification of inverter are as under:- (i) Operating temperature :- 25ºC to + 60ºC (ii) Relative humidity (Non condensing) upto 95%. (iii)The inverters shall have minimum protection to IP65 and minimum European efficiency 98% load as per IEC 61683 standard.. (iv) The inverter shall consist of associated control, protection, data loging device and remote monitoring hardware. Derating factor will be considered for Garota area (Punjab) . (v) The inverter shall adjust voltage and frequency levels to suit the existing DG Sets/AC power supply. (vi) The inverter shall be self-commulated with pulse width modulation (PWM) technology and shall be capable of synchronize maximum within 1 minute. (vii) Full power MPPT Viltage Range (300V to 840V). (viii) Out put rated power 15000W, Max Ac power 16500 va, Max output current 24 A, Nominal Grid voltage 3/N/PE, 230 /380 Vac, Nominal frequency -50 - 60 Hz, Grid frequency range 45 Hz to 55 Hz, Active power adjst range - 0-100%, power factor>0.99. (ix) Max efficiency - 98.3%, Safety protection Anti islanding,RCMU, Ground fault monitoring, Operation data storage - 25 yrs. (x)Std communication mode RS485 WiFi/GPRS (optional), SD card, Multi function relay, Noise<45 dB, LCD Display.
6Supply, fixing, testing and commissioning of minimum 20 Kw 50 Hz , 3 phase 415V, IP protection IP65, Input(DC) PV power 26600 Wp, Max DC power for sigle of MPPT 13000 W and Max output(AC)power 20000 W, Max output current 32 Amps suitable to convert DC power of solar PV module/array/battery bank to AC for further feeding to existing system.The input D.C. tech specification of inverter are as under:- (i) Operating temperature :- 25ºC to + 60ºC (ii) Relative humidity (Non condensing) upto 95%. (iii)The inverters shall have minimum protection to IP65 and minimum European efficiency 98% load as per IEC 61683 standard.. (iv) The inverter shall consist of associated control, protection, data loging device and remote monitoring hardware. Derating factor will be considered for Garota area (Punjab) . (v) The inverter shall adjust voltage and frequency levels to suit the existing DG Sets/AC power supply. (vi) The inverter shall be self-commulated with pulse width modulation (PWM) technology and shall be capable of synchronize maximum within 1 minute. (vii) Full power MPPT Viltage Range (480V to 850V). (viii) Out put rated power 20000W, Max Ac power 22000 va, Max output current 32 A, Nominal Grid voltage 3/N/PE, 220 /380 Vac, Nominal frequency -50 - 60 Hz, Grid frequency range 45 Hz to 55 Hz, Active power adjst range - 0-100%, power factor>0.99. (ix) Max efficiency - 98.2%, Safety protection Anti islanding,RCMU, Ground fault monitoring, Operation data storage - 25 yrs. (x)Std communication mode RS485 WiFi/GPRS (optional), SD card, Multi function relay,Noise<30 dB, LCD Display.
7Supply, fixing, testing and commisioning Array Junction Box (DCDB) with Photovoltaic fuse (1000 VDC 20A) , MCB and surge protection device (SPD Type-2) suitable for 10 Kw solar modules and invertor complete all as specified and directed.
8Supply, fixing, testing and commisioning Array Junction Box (DCDB) with Photovoltaic fuse (1000 VDC 30A) , MCB and surge protection device (SPD Type-2) suitable for 15 Kw solar modules and invertor complete all as directed and directed.
9Supply, fixing, testing and commisioning Array Junction Box (DCDB) with Photovoltaic fuse (1000 VDC 40A), MCB and surge protection device (SPD Type-2) suitable for 20 Kw solar modules and invertor complete all as directed and directed.
10Design, supply, fixing support structure of MS C channel not less than 3 mm thickness hot dipped galvanised (80microns) including PCC foundation for civil works (excavation,grouting PCC etc.) and fixing the mounting arrangement suitable for 10/15/20 Kw solar module on ground for solar tree/parking shedto withstand minimum horizontal wind speed at 170Km/Hr, the mounting structure is of mild steel hot dipped galvanised. The array structure shall be so designed that it will occupy minimum speed without sacrificing the output from solar PV panels. Nuts, bolts, supporting structures including module mounting structures shall have to be adequately protected from atmosphere & weather prevailing in area. All fasteners shall be of stainless steel of grade SS316. Two Nos of anti theft fasteners of stainless steel on two diagonally opposite corners of each modules shall be provided, complete all as specified and directed.
11Supply, fixing, testing and commisioning ACDB (AC Distribution Board) Panel with MCB (32Amp "C" Curve 4 Pole) for incoming and outgoing, multi function energy meter and surge protection device (SPD type-2) suitable for 10 Kw solar modules and invertor complete all as directed and directed.
12Supply, fixing, testing and commisioning ACDB (AC Distribution Board) Panel with MCB (40 Amp "C" Curve 4 Pole) for incoming and outgoing, multi function energy meter and surge protection devicesuitable for 15 Kw solar modules and invertor complete all as directed and directed.
13Supply, fixing, testing and commisioning ACDB (AC Distribution Board) Panel with MCB (63 Amp "C" Curve 4 Pole) for incoming and outgoing, multi function energy meter and surge protection devicesuitable for 20 Kw solar modules and invertor complete all as directed and directed.
14Supply, fixing, testing and commisioning Solar DC tin coated Copper Cable 6 mm²single core, 1800V DC and including suitable size heavy duty in PVC Conduit/ tray and fixing with clamps, lugs etc. complete all as specifiedand directed.
15Supply, fixing, testing and commisioning Solar DC tin coated Copper Cable 10mm²single core, 1800V DC and including suitable size heavy duty in PVC Conduit/ tray and fixing with clamps, lugs etc. complete all as specifiedand directed.
16Supply, fixing, testing and commisioning MC4/RJ Connector & Cap, Male-Female connectorswith UV Resistant Cable Ties Complete all as specified and directed.
17Supply and fixing of LT 3 Phase-4W direct connected Energy Meter 10-60 Amps, Accuracy class-1.0 with Polycarbonate meter box with hing type locking arrangement. The meter must be having LCD type display including metalic chamber box for installation of meter made out of MS sheet thickness not less than 3.15 mm having minimum dimension 0.5X0.5X1 Mtr duly supported on 4 legs of angle iron of size not less than 50X50X6 mm and length 45 cm duly welded with chamber box and grounded in PCC M-20. The chamber box shall have clearance from ground 30 cm and chamber shall have provision of suitable size cable glands for incomming and outgoing cable,complete all as specified and directed. .
18Design, supply & fixing of Lightning Arrestor conventional having coverage area 25 Mtrs radious suitable for 10/15/20 KW Solar Panels with required number of suitable Early Streamer Emission (ESE) lightning arrestors installed in the array field. Lightning arrestors/surge arrestors shall conform to IEC 60099-4 or IS:3070 except to the extent modified in the specifications. Arrestors shall be of hermetically sealed units, self-supporting construction, suitable for mounting on lattice type support with the following :- (i) The air terminal should be capable of racking the lightning stroke 60 micro seconds earlier as compare to passive lightning rod. (ii) The air terminal is Early Streamer Emission (E.S.E.) type which shall be fixed at the top of a GI elevation pole with base so as be at least 2 meters above the structure to be protected. Its height above roof level would be dependent on the level of protection and the protection rad required (iii) The air terminal should be working on the principle of early streamer emission using non-radioactve technology, needing no external power source. (iv) The air terminal is of Alumn/Copper and it has qualified diameter to resist high values of lightning currents. (v) Roof connecting pipe of suitable dimention should be capable of withstand in lightning strikes . The terminal adaptor having suitable size and necessary civil works required for fixing of pipe shall be included in the quoted rates.
19Material and labour for 25x4mm Aluminium strip as Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required all as specified and directed .
20Material & Labourfor earthing complete with galvanised steel earth plate electrode, 600mm x 600mm x 6mm thick, buried directly in theground (earth pit not less than 2.25m deep below normal (ground level) with top edge of the plate not less than 1.50m below ground level connected to galvanized iron strip of 25x4mmas earth leadby means of bolts, nuts and washers of GI up to test point, GI light grade pipe 40mm bore as protection pipe, GI watering pipe 20mm bore light grade with funnel and wire mesh, charcoal and salt, 40mm thick pre-cast RCC (1:2:4) type B-0 (Nominal mix) cover reinforced with (weighing n.less than 4 Kg/Sqm) with suitable steel handle, and angle iron 40X40X3mm frame and chamber of PCC (1:3:6) type C-0 (including earth work in any type of soil, removal of surplus soil to a distance n.exc.50m) and connecting, testing on completion, all as shown on electric plate No. 03 of SSR-2009 Part-I, complete all as directed. Notes: 1.Earth strip & protection pipes length upto & including 7.50 metre is deemed included in unit rate quoted by the contractor. 2.Earth filling shall be done by vegitable soil. 3.Soil shall be free from stone, boulders, aggregate, gravels .
21Material & Labour for earthing complete with galvanised steel earth plate electrode, 600mm x 600mm x 6mm thick, buried directly in theground (earth pit not less than 2.25m deep below normal (ground level) with top edge of the plate not less than 1.50m below ground level connected to galvanized earth lead wire 4mmdia as earth leadby means of bolts, nuts and washers of GI up to test point, GI light grade pipe 40mm bore as protection pipe, GI watering pipe 20mm bore light grade with funnel and wire mesh, charcoal and salt, 40mm thick pre-cast RCC (1:2:4) type B-0 (Nominal mix) cover reinforced (weighing n.less than 4 Kg/Sqm) with suitable steel handle, and angle iron 40X40X3mm frame and chamber of PCC (1:3:6) type C-0 (including earth work in any type of soil, removal of surplus soil to a distance n.exc.50m) and connecting, testing on completion, all as shown on electric plate No. 03 of SSR-2009 Part-I, complete all as directed. Notes: 1.Earth strip & protection pipes length upto & including 7.50 metre is deemed included in unit rate quoted by the contractor. 2.Earth filling shall be done by vegitable soil. 3.Soil shall be free from stone, boulders, aggregate, gravels .
22Supply, installation, testing and commissioning out door type cubical panel board outer shell made out of3.15 mm thick MS sheet and inner shell made out of 3.15mm thick CRCA sheet and MS angle of suitable size on PCC 1:2:4 type B-1 platform frame factory fabricated with front and back open able double door systemlouvers and air vent gasket for natural flow of air “U” type gasket shall be used to make the outer shell completely vermin proof .suitable for 3 phase 4 wire 415 Volt, 50 Hz, factory fabricated (Factory approved from CPRI)having modern fabrication and followed by powder coat painting comprising of the following:-(Adm Area - I) (a) MCCB 415 volts .4P ,160 Amps 36 KA(incoming)-01 No (b) MCB 415 volts .4P, 63 Amps 10 KA (O/G)-02 Nos (For Cook House & living shelters) (c.) MCB 230 volts .DP, 63 Amps 10 KA(O/G)-05 Nos ( for living accn) (d) Bus bar chamber with and including Aluminium strips (set 4 nos) suitable for 200 ampsduly mounted on porcelain insulators-01 Set (e)DigitalAmp meter 3 phaseprogrammebale type with suitable CT"s200 Amp - 01 Set (f)Digitalvolt meter 3 phaseprogrammebale type suitable for 500 Volt -01 Set (g) LED Phase indicator R, Y & B -01 Set
23Supply and laying and testing cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with stranded aluminium conductor,1100Voltsgradeof size 50 Sq mm 3.5 core, complete all as specified and as directed.
24Supply and laying and testing cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with stranded aluminium conductor,1100Voltsgradeof size 16 Sq mm 2.0 core, complete all as specified and as directed.
25Supply and laying and testing cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured electric power cables (heavy duty) with stranded aluminium conductor,1100Voltsgradeof size 10 Sq mm 2.0 core, complete all as specified and as directed.
26Excavating in trenches in any type of soil, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation of poles, trenches for laying of cable,or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and getting out complete all as specified and directed.
27Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm each all as required and directed.
28Removing excavated material to a distance not exceeding 50 Mtr and deposting where directed at a level not exc. 1.5 mtr above the starting point.
29Material & Labour for sand cushioning with a layer of sand 80mm thickbefore laying of cable and 150mm thick after laying of cable to trenches complete all as specified and directed.
30Material & Labour of brick sub class "B" laid dry in trenches over the cable adjoining each other widthwise for cable protection complete all as specified and as directed.
31Material and Labour for40 mm bore steel tubing light grade ISI marked for protection of cable including necessary joints complete all as specified and as directed.
32Supply and fixing of on load changeover switch 4 pole, 415 volts, up to 40 - 63 Amps with sheet metal enclosure operated in side Handle type, complete all as specified and as directed.
33Supply and fixing of on load changeover switch 4 pole, 415 volts, up to 40 - 63 Amps with sheet metal enclosure operated in side Handle type, complete all as specified and as directed.