Tender For Increasing Capacity Of 33/11 Kv Sub Station Gosaiganj (Urban) From 1X5 Mva To 2X5 Mva In Distt Ayodhya On Semi Turnkey Basis In The Jurisdiction Of Eswd, Ayodhya Under Superintending Engineer Electricity Works Circle, Mvvnl, Ayodhya, ayodhya-Uttar Pradesh

Madhyanchal Vidut Vitran Nigam Limited has published Tender For Increasing Capacity Of 33/11 Kv Sub Station Gosaiganj (Urban) From 1X5 Mva To 2X5 Mva In Distt Ayodhya On Semi Turnkey Basis In The Jurisdiction Of Eswd, Ayodhya Under Superintending Engineer Electricity Works Circle, Mvvnl, Ayodhya. Submission Date for this Tender is 02-03-2023. Coats and Jackets Tenders in ayodhya Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

36483055
Tender For Increasing Capacity Of 33/11 Kv Sub Station Gosaiganj (Urban) From 1X5 Mva To 2X5 Mva In Distt Ayodhya On Semi Turnkey Basis In The Jurisdiction Of Eswd, Ayodhya Under Superintending Engineer Electricity Works Circle, Mvvnl, Ayodhya
Open Tender
Indian
Uttar Pradesh
ayodhya
02-03-2023

Tender Details

Increasing Capacity Of 33 / 11 Kv Sub Station Gosaiganj ( Urban ) From 1X5 Mva To 2X5 Mva In Distt Ayodhya On Semi Turnkey Basis In The Jurisdiction Of Eswd, Ayodhya Under Superintending Engineer Electricity Works Circle, Mvvnl, Ayodhya - 90 Lbs Rail Pcs For T / F ( 44.64 Kg / M ) 3 33 Kv Post Insulator 4 33 Kv Bus Isolator 5 33 Kv Vcb 800A, 750 Mva 6 C.T. O / D 33 Kv Ctr 200 / 100 / 1-1 7 33 Kv Lightening Arrestor 8 Acsr Dog Conductor 9 Singe T / F Control Pannel 10 11 Kv Incoming Switch Gear 600 / 300 / 5A, 350 Mva 11 11 Kv Out Going Switch Gear 200 / 100 / 5A0250mva 12 11 Kv 3 Core Cable 3X300 Mm Xlpe 13 11 Kv Cable 3X185 Sq. Mm Xlpe 14 11 Kv Cable Jointing Kit Indoor 3X300, 3X185 Sq.Mm. Xlpe 15 M.S. Channel 125X65 , 7X75x6 Mm ( For Structures ) 16 St Pole 11Mtr 17 M.S.Angle Iron 65X65x6 Bracing 2700 Mm 18 11 Kv Top Channel 100X50x2240 Mm 19 11 Kv Disc Insulator T&C Type 20 11 Kv Polymer Pin Insulator 21 Stay Wire 7 / 10 22 11 Kv Disc Insulator T&C Type 23 R.S. Joist 150X150 Mm 24 6 Swgwire 25 Plinth Of 5Mva, 33 / 11 Kv T / Fsconstruction Of Plinth Of Size 3.46X3.46 Mtr For5 Mva T / F Having 0.4 Mtr Above Ground Level. The Work Includes Excavation Of Foundation, Base Concreting In C.C. 1:6:12 Ratio ( Cement, Fine Sand And Brick Ballast ) 1St Class Bricks Work In Cement Mortar Of Ratio 1:4 Foundation, C.C. In 1:4:8 Ratio ( Cement, Fine Sand And Brick Ballast ) And Rcc Working Ratio 1:2:4 ( Cement, Coarse Sand And Stone Grit Of 20 Mm Gauge ) Using Ms Bars Of 10 Mm Dia ( Tor ) In Reinforcement Including Its Cutting, Bending And Binding In Required Shape. The Work Also Includes Laying Of 2 Nos. 3.46 Mts Long Each Rail Pieces Complete With Cutting, Welding And Proper Fitting Etc. The Plinth Will Be Made As Per Drawing And Shall Be Plastered / Finished On Top And Side Of The Plinth. ( All The Material Will Be Supplied By The Contractor Except Rail Piece ) 26 Bus Isolator Structurefabrication Of Isolator Structures 3.5Mtr In Height As Per Drawing No. Res 39 Digging Of Two Nos. Pits Of Size 1.075 X 0.9 X0.3 Mtr Providing Stone Pad At The Bottom Of The Pit And Grouting Pad At The Bottom Of The Pit And Grouting Of Two Legs Of The Isolator Structure In Cc ( Cement, Coarse Sand And Stone Grit Of 20 Mm Gauge ) Of Ratio 1:4:8 In Block Of 1.075 Mtx 0.3 Mtr Including Supply Of All T&P Complete In All Respect. The Work Includes Dragging, Shifting Upto 40 Mtr. Raising And Erecting The Two Legs With Runner Of Isolator In Proper Allingment Level And Plumb. Plinths Of The Isolator Structure Shall Be Properly Finished With Champering Of Edges. 27 Lightening Arrestor / Post Insulatorfabrication Of 2 No Lightening Arrestor Structure& 1 Set Of Post Insulatorstructure Per Drawing No. Res 39 Digging Of Two Nos. Pits Of Size 1.075 X 0.3 X0.3 Mtr Providing Stone Pad At The Bottom Of The Pit And Grouting Of Two Legs Of The Above Structure In Cc ( Cement, Coarse Sand And Stone Grit Of 20 Mm Gauge ) Of Ratio 1:4:8 In Block Of 1.075 Mtr X 0.3 Mtr X 0.3 Mtr Including Supply Of All T&P Complete In All Respect. The Work Includes Dragging, Shifting Upto 40 Mtr. Raising And Erecting The Two Legs With Top Frame Above StructureS In Properallingment Level And Plumb. Plinths Of All The Structure Shall Be Properly Finished With Champering Of Edges Etc. 28 Fabricatin Of Ctstructure Fabrication Of Ct Structure As Per Drawing No. Res 39 Digging Of Two Nos. Pits Of Size 1.075 X 0.3 X0.3 Mtr Providing Stone Pad At The Bottom Of The Pit And Grouting Of Two Legs Of The Above Structure In Cc ( Cement, Coarse Sand And Stone Grit Of 20 Mm Gauge ) Of Ratio 1:4:8 In Block Of 1.075 Mtr X 0.3 Mtr X 0.3 Mtr Including Supply Of All T&P Complete In All Respect. The Work Includes Dragging, Shifting Upto 40 Mtr. Raising And Erecting The Two Legs With Top Frame Above StructureS In Properallignment Level And Plumb. Plinths Of All The Structure Shall Be Properly Finished With Champering Of Edges Etc. ( All The Material Will Be Supplied By The Contractor Except Steel Section ) 29 Plinth For 33Kv Vcbconstruction Of Plinth Of Size 2.0X1.5X0.9 ( Mtr ) Suitable For Erection Of Super Structure For 33 Kvvcb Including Grouting Of Anchor Bolts In Proper Allingment And Level. Scope Of Work Includes Excavation Of Foundation Base Concreting In Cc 1:6:12 ( Cement, Fine Sand And Brick Ballast ) 1St Class Brick Work In Cement Mortor Of Ratio 1:4 Cc In Ratio 1:4:8 And Rcc Work In Ratio 1:2:4 ( Cement, Coarse Sand And Stone Grit Of 20 Mm Gauge ) As Per Drawing 30 H.T. Cable Layinglaying & Dressing Of 11 Kv, 3X300 And 3X185 Sq.Mm Xlpe Cable Underground From 5 Mva T / F To 11 Kv Incoming Switchgear In The Trench 450Mm Wide, 900Mm Deep, Providing 150Mm Fine Sand Cushion Bench And 150Mm Fine Sand Cushion Above The Cable. The Cable Shall Be Duly Protected By 1St Class Bricks Two Either Side And Third On Top Of The Cables, Laid In Series One After The Other, The Work Includes Supplying Offine Sand And Bricks, Refillingand Rammingof The Left Out Soil, Closing The Trench And Leveling. Spare Cable Shall Be Left And Buried In The Trench In The Safe Of Rings At Both Ends. Cable Laying Work Includes Unrolling, Cutting, Meggering And Sealing Both End Of The Cable. ( All The Material Will Be Supplied By The Contractor ) 31 Bus Bar Gantrydigging Of 1 Nos Pits Of Size 2.2Mt X1.4Mt X 0.75Mtr Providing Stone Pad At The Bottom Of The Trench And Grouting Of The 1 Legs Of The Bus Bar Gantry In Cc ( Cement, Coarse Sand And Stone Grit Of 20Mm Gauge ) In The Ratio 1:3:6 Including Supply Of All T&P Shuttering Etc. In A Block Of Size 2.2 Mtx1.4 Mtx0.75 Mt. The Work Consists Of Dragging , Shifting Up To 40 Mtr Raising And Erecting The Two Pre Fabricated Legs Of Bus Gantry In Proper Allingment Level And Plumb. The Plinths Of The Termainal Gantry Shall Be Properly Finished With Champeringof Edges. The Work Includes Extension Fabrication Of Bus Bar Gantry 6.23 Mtrlong As Per Respo Drawing No.38 32 Erection And Installation Of 33 / 11 Kv 5 Mva Transformerdragging Of 33 / 11Kv 5Mva T / F From Dump Site To Road Site And Shifting Of The T / F From Road Site To New Constructed Plinth Distance About 150Mtr , Along With Loading, Unloading And Carriage, Fixing And Fitting Of All The Accessiories And Filling Of T / F Oil To The Desired Level And Insuring That There Is No Leakage. Erection And Installation Of 33 / 11 Kv, 5 Mva Transformer In A Leveled Position On The Plinth. 33 Installation Of Post Insulator Installation Ofpost Insulator On The Post Insulator Structure . The Work Includes Fabrication For Proper Fixing If Required. 34 Installation Of Bus Isolators Assembling And Installation Of Bus Isolator On The Isolator Structure , Adjusting Of Opening Mechanism In Proper Alignment So As To Ensured Smooth Operation Of The Same. In Case Of Line Isolator Proper Operation Of Earth Links Shall Also Be Ensured. The Work Includes Fabrication For Proper Fixing If Required. 35 Installation Of 33 Kv Vcbinstallation Of 33 Kv 750 Mva 800 Amp Vcb On 33 Kv Vcb Structure Along With Earthing By G.I. Strip 50X6 Mm Size With Main Earthmat Of Switchyards Complete In All Respect Including Commissioning. 36 Installation Of Ct Installation Of 3 Nos Cts Of Ratio 200 / 100 / 1Aon The Cts Structure. The Work Includes Fabrication For Proper Fixing If Required. ( All The Material Will Be Supplied By The Contractor Except Steel Section ) 37 Installation Of Lightening Arrestorsassembling And Installation / Mounting Of Three Nos.Lightening Arrestors On The L.A. Structure / Complete With Making Earth Connection ( Separate ) And Line Connections. The Work Includes Fabrication For Proper Fixing If Required. 38 33Kv Bus Bar & Stringing.Stringing Of 33Kv Bus Bar By Using And Laying Of Acsr Dog Conductor Including Fixing Of Disc Insulator. Strings And Tension Fitting Complete With Sagging Of Bus Bar Etc. And Making Vertical / Horizontal Jumperconnection Through Pg Clamps And Connecting All The Equipments With Each Other Through Connecting Clamps. 39 33Kv Bay Bus Bar & Stringing.Stringing Of 33Kv Bay Bus Bar By Using And Laying Of Acsr Dog Conductor Including Making Vertical / Horizontal ( Y-Shape ) Jumperconnection Through Pg Clamps And Connecting All The Equipments ( Bus Isolator, P.I. , C.T. , Vcb, L.A & T / F ) With Each Other Through Connecting Clamps. ( All The Material Will Be Supplied By The Contractor ) 40 Shifting Carefully And Installation Ofsingle / Double Transformer Control Pannel In Control Roomand Its Proper Connection. 41 Installation Of Switchgears In Control Roomshifting Carefully And Safely 11 Kv Incomingswitchgear, 11 Kv Outgoing Switchgear And 11 Kv Bus Coupler From Out Side Of The Switch Gear Room, As Per Direction Of Engineer Incharge, Placing And Fixing Of Switchgear On Foundation Providing Nuts & Bolt Of Proper Size In Proper Position And Alignment And Mountting Of P.T. On Incoming S / G. 42 Installation Of Heat Shrinkable Type Cable Jointing Kits In Door And O / D End Terminationjoint Suitable For 11Kv Xlpe Cable Confirming To Is Esi-09-13-Is-13573 Of 1992 Amendment I&Ii Vde-0278 Of Latest Version There Of If Any. 43 Construction Of 11 Kv Double Poleerection & Grouting Of 2 Nos 11Mtr Stp Support For Making Dp Structure Including Fabrication, Fixing Of Ms Channel, M.S. Angle, Disc Insulators / Pin Insulators Etc. The Work Includes Suply And Fixing Of Necessary Clamp With Nut, Bolts And Washers. Complete In All Respect. ( All The Material Will Be Supplied By The Contracto Rexcept Steel Section ) 44 Grouting Of Following Structure By Digging Of Pit 1.83 Mtr Deep For 11 Mtr Stp, With 1:4:8 Ratio Cement, Sand & First Class Brickballast0.285 Cu Mtr For 11 Mtr Stp, Plinthing 0.3 Mtr Above G / L And Proper Plastering. 45 Providing And Fixing Of Earth Rod For Earthing Of Support By G.I. Wire 6 Swg As Per Norms. ( All Materialwill Be Arranged By The Contractorlike Earth Rod And 6 Swg Wire ) 46 Painting Of Structurepainting Of 11 Mtr St Pole With One Coat Of Ready Mixed Primer And 2 Coats Of Al.Paint Of Good Quality Including Cost Of Material, Labour And T&P Complete In All Respect. 47 Nozeling And Grouting Of Stay Set. ( All The Civil Material And Stay Set Will Be Arranged By The Contractor Excluding Stay Wire ) 48 Cable Stand-Fabrication And Erection Of Cable Support Made Of Two Pieces Of M.S. Strip 65X65x6 Mm, 3.0 Mtr Long Joined To Each Other By Means Of 5 Nos M.S. Flat 50X6 Mm Pieces Of Size 150 Mm Long Each By Welding At Equal Intervals As Per Drawing And Grouting In A Block Of Size300x300x700 Mm Complete With One Coat Of Ready Mixed Primer And Two Coats Of Al. Paint. This Includes Providing Of Four Nos. M.S.Clamp Made Of M.S. Flat For Holding The Cable Including Nuts And Bolts And Fixing Of Xlpe Cable. 49 Nutral Stand- Fabrication And Grouting Of M.S. Channel 100X50x6 Mm In L Shape & In Proper Size And Allignment To Provide Support For The Two Separate Earthing Strips For Power Transformer Neutral Including Supply & Fixing Of Two Nos. Flexible Copper Bonds For Neutral Earthing. 50 Pipe Earthing- Special Earthing By Way Of Boring And Lowering Of B Class G.I. Pipe 50 Mm Dia 20Mtr Longfrom Ground Upto The Water Level Andit Will Be Connected To The G.S. Strip 50X6 Mm ( Providing & Laying Of G.S. Strip Including Cutting, Welding, Bending Etc. ) For Equipments ( L.A, T / F, C.T., Vcb.Etc ) . The Earth Strip Will Be Welded To The G.I. Pipe. The Work Also Includes Cap & Clamps For Pouring Water, The Cost Of All Material With All Labour & T&P Etc. Complete In All Respect. ( All The Material Will Be Supplied By The Contractor ) 51 Providing 4 No. Of 3 Mtr 32Mmround Bar Drive In To Earth At Mimi 3 Mtr Distence And Connecting It By 50X6 Mm Ms Flat And Connectig To All Indor Or Out Door Equpment / Structure As Per Instruction Of Site In Charge. ( All Tha Material Will Be Supplied By The Contrector. ) 52 Hosting Of 11 Kv Cable On Existing / Erected Support With Provision Of Ms Pipe 150 Mm Dia 3 Mtr Long Suitable For 3X185 Sq Mm Cable Fixing Of Proper Support And Its Clamping , Providing Long Barral Lugs 6 Nos And P.G. Clamps & Y Shapejumpering Properly And 02 Nos. Supporting Angle 65X65x6, 2800 Mm As Per Resspo Norms. ( All Material Will Be Supplied By The Contractor Like Ms Pipe , P.G. Clamps, Al. Lug And Supporting Angle 65X65x6, 2800 Mm ) . 53 Supply & Laying Of 6X2.5 Sq.Mm. Sq. Control Cable From Power T / F To Controle Board In The Ground As Per Respo Norm With Proper Connection Vcb, Ct & Control Pannel With T / F To Battery And Battrey Charger, Bucholz Relay, Low Higher And Winding Temperture Protection Alarm Etc With Including All The Civil Material. ( All The Material Will Be Supplied By The Contracto ) 54 Supply & Laying Of 4X2.5 Sq.Mm. Sq. Control Cable From Power T / F To Controle Board In The Ground As Per Respo Norm With Proper Connection Vcb, Ct & Control Pannel With T / F To Battery And Battrey Charger, Bucholz Relay, Low Higher And Winding Temperture Protection Alarm Etc With Including All The Civil Material. ( All The Material Will Be Supplied By The Contracto ) 55 Supply & Laying Of 2X2.5 Sq.Mm. Sq. Control Cable From Power T / F To Controle Board In The Ground As Per Respo Norm With Proper Connection Vcb, Ct & Control Pannel With T / F To Battery And Battrey Charger, Bucholz Relay, Low Higher And Winding Temperture Protection Alarm Etc With Including All The Civil Material. ( All The Material Will Be Supplied By The Contracto ) 56 Commissioning Of 5 Mva T / F And Its Eqipments Installed In Switchyards And 11 Kv Incoming And Outgoing Pannels Complete In All Respect Upto Energising 57 Providing Of Hand Gloves 58 Providing Of Rubber Matting One Side Chequered And Other Side Plane Size 59 Digging And Lockting The Earth Mate And Outdoor Structures Earthing By M.S. G.I Flat. 50X6 Mm The Job Include Cutting, Bending. ( All The Material Will Be Supplied By The Contractor. ) 60 Supply, Fixing & Erection 24 Volt Battery Bank & Battery Charger With Cabinet. 61 Painting Ofsub Station Structures ( Old+New ) With One Coat Of Ready Mixed Primer And 2 Coats Of Al.Paint Of Good Quality Including Cost Of Material, Labour And T&P Complete In All Respect. 62 Breaking The Concrete Fencing / Boundary Wall In The Switchyard Of Sub. Station For Moving 5 Mva Transformer In Switchyard After Complition The Work Covered And Restore The Wall 63 Fixing And Making Bus Bar Connection In Between I / C And O / Gswitchgears After Cleaning And Tapping With H.T. Tape, Empire Tape And Pvc Tape Properly Providing And Fixing Of 6Mm Thick Bakelite Seperators And Plugging Of All Opening And Holes With Plastic Compound. Complete Work Including Cost Of All Materialstrictly To The Satisfaction Of Site Incharge. 64 High Pressure Testing Of 11 Kv 3X185 And 3X300 Sq Mm Xlpe Cable. ( Required Testing Equipmennts Will Be Arranged By The Contractor )

Key Value

Document Fees
INR 3540 /-
EMD
INR 15000.0 /-
Tender Value
INR 14.82 Lakhs /-

BOQ Items

Name of Work : INCREASING CAPACITY OF 33/11 KV SUB STATION GOSAIGANJ (URBAN) FROM 1X5 MVA TO 2X5 MVA IN DISTT AYODHYA ON SEMI TURNKEY BASIS IN THE JURISDICTION OF ESWD, AYODHYA UNDER SUPERINTENDING ENGINEER ELECTRICITY WORKS CIRCLE, MVVNL, AYODHYA
Sl. No. Item Description
1Carriage of all the concerning material from Store Centre Under the Jurisdiction of EE, ESD Ayodhya to dump site/JE"s Store and from dump site/JE"s Store to the site of work.
290 lbs rail Pcs for T/F ( 44.64 Kg/m)
333 KV Post Insulator
433 KV Bus Isolator
533 KV VCB 800A, 750 MVA
6C.T. O/D 33 KV CTR 200/100/1-1
733 KV Lightening Arrestor
8ACSR Dog Conductor
9Singe T/F control pannel
1011 KV Incoming switch gear 600/300/5A, 350 MVA
1111 KV Out going switch gear 200/100/5A0250MVA
1211 KV 3 Core Cable 3x300 mm XLPE
1311 KV Cable 3x185 sq. mm XLPE
1411 KV cable jointing kit indoor 3x300, 3X185 sq.mm. XLPE
15M.S. Channel 125x65 , 7X75X6 mm(for Structures)
16ST Pole 11Mtr
17M.S.Angle iron 65x65x6 bracing 2700 mm
1811 KV Top channel 100X50X2240 mm
1911 KV disc insulator T&C type
2011 KV Polymer pin insulator
21Stay wire 7/10
2211 KV disc insulator T&C type
23R.S. Joist 150X150 mm
246 SWGWire
25Plinth of 5MVA, 33/11 KV T/Fs Construction of Plinth of size 3.46x3.46 Mtr for5 MVA T/F having 0.4 Mtr above ground level. The work includes Excavation of foundation, Base concreting in C.C. 1:6:12 ratio ( cement,fine sand and Brick ballast) 1ST Class bricks work in cement mortar of ratio 1:4 foundation, C.C. in 1:4:8 ratio( cement, fine sand and brick ballast) and RCC working ratio 1:2:4 ( cement, coarse sand and stone grit of 20 mm gauge) using MS Bars of 10 mm Dia (Tor) in reinforcement including its cutting, bending and binding in required shape. The work also includes laying of 2 Nos. 3.46 mts long each rail pieces complete with cutting, welding and proper fitting etc. The plinth will be made as per Drawing and shall be plastered/ finished on Top and Side of the plinth. (All the material will be supplied by the Contractor except rail Piece)
26Bus Isolator Structure Fabrication of isolator structures 3.5mtr in height as per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.9 x0.3 Mtr providing stone pad at the bottom of the pit and grouting pad at the bottom of the pit and grouting of two legs of the isolator structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 mtX 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with runner of isolator in proper allingment level and plumb. Plinths of the Isolator structure shall be properly finished with champering of edges.
27Lightening Arrestor/ Post Insulator Fabrication of 2 No Lightening Arrestor structure& 1 set of Post Insulatorstructure per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x0.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr X 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure"s in properallingment level and plumb. Plinths of all the structure shall be properly finished with champering of edges etc.
28Fabricatin Of CTStructure Fabrication of CT Structure as per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x0.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr X 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure"s in properallignment level and plumb. Plinths of all the structure shall be properly finished with champering of edges etc. (All the material will be supplied by the contractor except Steel Section)
29Plinth for 33KV VCB Construction of plinth of size 2.0x1.5x0.9 (Mtr) suitable for erection of super structure for 33 KvVCB including grouting of Anchor bolts in proper allingment and level. Scope of work includes excavation of foundation base concreting in CC 1:6:12( cement, fine sand and brick ballast) 1st class brick work in cement mortor of ratio 1:4 CC in Ratio 1:4:8 and RCC work in ratio 1:2:4 ( Cement, coarse sand and stone grit of 20 mm gauge) as per Drawing
30H.T. Cable Laying Laying & dressing of 11 KV, 3x300 and 3X185 Sq.mm XLPE cable underground from 5 MVA T/F to 11 KV incoming switchgear in the trench 450mm wide, 900mm deep, providing 150mm fine sand cushion bench and 150mm fine sand cushion above the cable. The cable shall be duly protected by 1st class bricks two either side and third on top of the cables, laid in series one after the other, the work includes supplying offine sand and bricks, refillingand rammingof the left out soil, closing the trench and leveling. Spare cable shall be left and buried in the trench in the safe of rings at both ends. Cable laying work includes unrolling, cutting, meggering and sealing both end of the cable.(All the material will be supplied by the contractor)
31Bus Bar Gantry Digging of 1 Nos Pits of size 2.2mt x1.4mt x 0.75Mtr providing stone pad at the bottom of the trench and grouting of the 1 legs of the Bus Bar Gantry in CC ( cement, Coarse sand and stone grit of 20mm gauge) in the ratio 1:3:6 including supply of all T&P shuttering etc. in a block of size 2.2 mtx1.4 mtx0.75 mt. The work consists of dragging , shifting up to 40 mtr raising and erecting the two pre fabricated legs of Bus Gantry in proper allingment level and plumb. The plinths of the termainal gantry shall be properly finished with champeringof edges. The work includes extension fabrication of Bus Bar Gantry 6.23 MtrLong as per RESPO drawing no.38
32Erection and Installation of 33/11 KV 5 MVA Transformer Dragging of 33/11KV 5MVA T/F from Dump site to road site and shifting of the T/F from road site to new constructed plinth distance about 150mtr ,along with loading, unloading and carriage, fixing and fitting of all the accessiories and filling of T/F oil to the desired level and insuring that there is no leakage. Erection and installation of 33/11 Kv, 5 MVA Transformer in a leveled position on the plinth.
33Installation of Post Insulator Installation ofpost insulator on the post insulator structure . The work includes fabrication for proper fixing if required.
34Installation of Bus Isolators Assembling and installation of Bus isolator on the Isolator structure , adjusting of opening mechanism in proper alignment so as to ensured smooth operation of the same. In case of line Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
35Installation of 33 KV VCB Installation of 33 KV 750 MVA 800 Amp VCB on 33 KV VCB structure along with earthing by G.I. strip 50x6 mm size with main earthmat of Switchyards complete in all respect including commissioning.
36Installation Of CT Installation of 3 Nos CTs of ratio 200/100/1Aon the CTs structure. The work includes fabrication for proper fixing if required.(All the material will be supplied by the contractor except Steel Section)
37Installation of Lightening Arrestors Assembling and installation/ mounting of three Nos.Lightening Arrestors on the L.A. structure/ complete with making earth connection ( Separate ) and line connections. The work includes fabrication for proper fixing if required.
3833KV Bus Bar & Stringing. Stringing of 33Kv Bus Bar by using and laying of ACSR Dog Conductor including fixing of Disc Insulator. Strings and tension fitting complete with sagging of Bus Bar etc. and making Vertical/Horizontal jumperconnection through PG clamps and connecting all the equipments with each other through connecting clamps.
3933KV Bay Bus Bar & Stringing. Stringing of 33KV Bay Bus Bar by using and laying of ACSR Dog Conductor including making Vertical/Horizontal (Y-shape) jumperconnection through PG clamps and connecting all the equipments ( Bus isolator, P.I. , C.T. , VCB, L.A & T/F) with each other through connecting clamps.(All the material will be supplied by the contractor)
40Shifting carefully and installation ofSingle/double Transformer Control pannel in control roomand its proper connection.
41Installation of Switchgears in Control room Shifting carefully and safely 11 Kv incomingSwitchgear, 11 KV outgoing Switchgear and 11 KV Bus Coupler from out side of the switch gear room, as per direction of Engineer Incharge, Placing and fixing of switchgear on foundation providing nuts & bolt of proper size in proper position and alignment and mountting of P.T. on incoming S/G.
42Installation of Heat Shrinkable Type cable jointing kits in door and O/D end TerminationJoint suitable for 11KV XLPE cable confirming to IS ESI-09-13-IS-13573 of 1992 amendment I&II VDE-0278 of latest version there of if any.
43Construction of 11 KV Double pole Erection & Grouting of 2 Nos 11Mtr STP support for making DP structure Including fabrication, Fixing of MS Channel, M.S. angle,Disc Insulators/ Pin Insulators etc. The work Includes suply and fixing of necessary clamp with nut, bolts and washers. complete in all respect.(All the material will be supplied by the contracto rexcept steel section)
44Grouting of following structure by digging of pit 1.83 Mtr deep for 11 Mtr STP,with 1:4:8 Ratio cement, sand & first class brickballast0.285 cu mtr for 11 mtr STP, plinthing 0.3 Mtr above G/L and proper plastering.
45Providing and fixing of earth rod for earthing of support by G.I. Wire 6 SWG as per norms. (All materialwill be arranged by the contractorLike earth rod and 6 swg wire)
46Painting of Structure Painting of 11 Mtr ST Pole with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect.
47Nozeling and grouting of stay set. (All the civil material and stay set will be arranged by the contractor excluding Stay wire)
48Cable stand-Fabrication and erection of cable support made of two pieces of M.S. Strip 65x65x6 mm, 3.0 Mtr long joined to each other by means of 5 Nos M.S. Flat 50x6 mm pieces of size 150 mm long each by welding at equal intervals as per drawing and grouting in a block of size300x300x700 mm complete with one coat of ready mixed primer and two coats of Al. paint. This includes providing of four Nos. M.S.clamp made of M.S. flat for holding the cable including nuts and Bolts and fixing of XLPE cable.
49Nutral Stand- Fabrication and grouting of M.S. channel 100x50x6 mm in L shape & in proper size and allignment to provide support for the two separate earthing strips for power transformer neutral including supply & fixing of two Nos. Flexible Copper bonds for neutral earthing.
50Pipe Earthing- Special Earthing by way of boring and lowering of "B" class G.I. pipe 50 mm Dia 20mtr longfrom ground upto the water level andit will be connected to the G.S. strip 50X6 mm ( Providing & laying of G.S. strip including cutting, welding, bending etc.) for equipments(L.A,T/F,C.T., VCB.etc). The earth strip will be welded to the G.I. Pipe. The work also includes Cap & Clamps for pouring water, the cost of all material with all labour & T&P etc. Complete in all respect. (All the material will be supplied by the contractor)
51Providing 4 No. of 3 mtr 32mmround bar drive in to earth at mimi 3 mtr distence and connecting it by 50X6 mm MS Flat and connectig to all indor or out door equpment/structure as per instruction of site in charge.( All tha material will be supplied by the contrector.)
52Hosting of 11 KV Cable on existing/erected support with provision of MS Pipe 150 mm dia 3 mtr long suitable for 3x185 sq mm cable fixing of proper support and its clamping , providing long barral lugs 6 nos and P.G. Clamps & "Y" shapejumpering properly and 02 nos. supporting angle 65X65X6, 2800 mm as per RESSPO Norms. (All material will be supplied by the contractor like MS Pipe , P.G. Clamps, Al. Lug And Supporting Angle 65X65X6, 2800 mm).
53Supply & Laying of 6x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contracto)
54Supply & Laying of 4x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contracto)
55Supply & Laying of 2x2.5 sq.mm. Sq. control cable from power T/F to controle board in the ground as per RESPO Norm with proper connection VCB, CT & Control Pannel with T/F to battery and battrey charger, Bucholz Relay, low higher and winding temperture protection alarm etc with including all the civil material. (All the material will be supplied by the contracto)
56Commissioning of 5 MVA T/F and its eqipments installed in switchyards and 11 KV Incoming and Outgoing Pannels complete in all respect upto energising
57providing of Hand gloves
58Providing of Rubber matting one side chequered and other side plane size
59Digging and lockting the earth mate and outdoor Structures earthing by M.S. G.I Flat. 50X6 mm the job include cutting, bending. (All the material will be supplied by the contractor.)
60Supply, fixing & erection 24 Volt Battery bank & Battery charger with cabinet.
61Painting ofSub Station Structures (Old+New) with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect.
62Breaking the concrete fencing/ Boundary wall in the switchyard of sub. Station for moving 5 MVA Transformer in switchyard after complition the work covered and restore the wall
63Fixing and making Bus Bar connection in between I/C and O/Gswitchgears after cleaning and tapping with H.T. tape, Empire tape and PVC tape properly providing and fixing of 6mm thick bakelite seperators and plugging of all opening and holes with plastic compound. complete work including cost of all materialStrictly to the satisfaction of site incharge.
64High Pressure testing of 11 KV 3x185 and 3X300 sq mm XLPE cable. (Required Testing equipmennts will be arranged by the contractor)