Tender For Supply Installation Testing Commissioning Of Mgps Work In 100 Bedded Ward Field Hospital At Parbatsar, Distt. Nagaur., nagaur-Rajasthan

Medical Health And Family Welfare has published Tender For Supply Installation Testing Commissioning Of Mgps Work In 100 Bedded Ward Field Hospital At Parbatsar, Distt. Nagaur.. Submission Date for this Tender is 08-03-2023. Coats and Jackets Tenders in nagaur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

36435336
Tender For Supply Installation Testing Commissioning Of Mgps Work In 100 Bedded Ward Field Hospital At Parbatsar, Distt. Nagaur.
Open Tender
Indian
Rajasthan
nagaur
08-03-2023

Tender Details

Supply Installation Testing Commissioning Of Mgps Work In 100 Bedded Ward Field Hospital At Parbatsar, Distt. Nagaur. - Sitc Of Mgps Pipe Of Medically Grade As Per Bsen-13348 With Third Party Certification From Lloyds / Tuv Degreased ( Ie Free From Oil, Grease And Particulate Matters ) Seamless Copper Pipe Confirming To Astm B88 And All Copper Joining Done By Brazing With Awsa5.8, Classification Bcup-5 Or Bs 1845 Following Procedure In Accordance With Astm B828 After Purging With Nitrogen. All Pipe Cutting Shall Be Carried Out With A Radial Pipe Cutter And Copper Pipe FittingS Shall Comply With B4 Alloy Designation. Adequate Support Shall Be Provided While Laying Pipeline Testing Shall Be Done At 17 Bar And After Testing Pipe Shall Be Painted With Two Coat Of Enamel Paint As Per Colour Codification As Per Iso 7396-Part-I 2016. Third Party Test Report Shall Be Submitted. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With P.W.D. Electrical Bsr 2021 2 Sitc Of Non Lubricated Ball Type Nickel Coated Isolation Valve With Adapter & Ptfe Seat Having Quarter Turn / Butterfly Handle Opening Of Following Sizes Suitable For Flow Capacity Of Required Lpm As Per The Size Of Valve At 4.7 Bar With Maximum Allowable Pressure Of 30 Bar And Suitable For Working Temperature Ranging - 20°C To 130°C. Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submitted. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021 3 For 12 Mm Od Pipe 4 For 15 Mm Od Pipe 5 For 22 Mm Od Pipe 6 For 28 Mm Od Pipe 7 For 42 Mm Od Pipe 8 Sitc Of Gas Outlet Points Oxy, N2o, ( Ar-4 ) , ( Ar-7 ) And Vaccum ( 8.7 Psig ) For Dispensing Medical Gases ( Oxygen / Air / Vaccum ) At Point Of Use Confirming To Bsen Iso 9170-1:2008. The Gas Outlet Are Quick Connect Type , It Should Have Color Coding For Different Gas Source And Should Accept Only Repective Adapters As Required.Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submitted. The Product Should Be Ce Certified / Ce Marked. All As Per Pre Approved By Engineer In Charge. For Additional Echnical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021 9 Sitc Of Bpc ( Back Pressure Compensated ) Flow Meter With Humidifer Made Of Nickel Plated Body, Double Jacketed With Flow Gradations Ce Marked On It. Desired Flow Will Be Setteled Through Rotary Knob. Flow Range Should Be Between 0 To 15 Lpm & Work Should Be Executed As Per Direction Of Engineer In Charge. Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submitted. The Product Should Be Ce Certified / Ce Marked. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021. 10 Sitc Of Ward Suction Unit ( Suction Controller And Collectionjar-600 Ml Capacity ) With Posibility To Configure Required Capacity Collection Jar And Should Meets The Requirements As Per Bsen Iso 10079-3:2009. The Unit Must Designed To Operate With The Vaccum Line Of Mgps. The Collection Jar Must Accumpained With Vaccum Regulator Suitable For 0-14.7 Psig With Flow Rate 0-55 Lmp ( Min ) For Operating Temperature- 18°C To 50°C With On / Off Facility. The Collection Jar Should Be Transparent, Made Of High Quality Polycarbonate That Can Be Autoclaved At 121°C For 20 Minutes For Reuse And Provided With Auto Stop To Avoid Over Spill And Contaminatin Of The Suction Source When The Jar Collection Reached Optimized Level. The Complete Unit Supplied With Filter To Protect The Source And Pipe Line From Bacterial Contamination. Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submitted. The Product Should Be Ce Ertified / Ce Marked. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021. 11 Sitc Of Valve Box Made Of Crca Sheet Duly Powder Coated With Transparent Window Which Is Installed In The Mgps For Oxygen And Vaccum Line And Should Comply With Bsen Iso5211:2001 Complete With Ball Type Valves And Gauges As Required For Oxygen Compressed Air And Vaccum Line. Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submited. The Product Should Be Ce Ertified / Ce Marked. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021. 12 Three Gas Service 13 Sitc Of Microprocessor Based Auto Alarm ( Digital Type ) Suitable For Medical Gas Service Provided With Audible And Visual Alarm For Mgps Zoning. It Should Monitors The Current Status Of Oxygen / Compresssed Air Pressure In Distribution Pipeline Of Central Medical Supply System And Trigger The Alarm To Alert. The System Should Comply Bsen Iso:7396-I:2007 Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submitted. The Product Should Be Ce Ertified / Ce Marked. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021. 14 Three Gas Service 15 Sitc Of Bed Head Panel Of 900-1500 Mm Long Made Out From High Strength Extruded Aluminium With Powder Coating With At Least 4 Nos 6 / 16 Amp Switch Socket And Provision For Required Number Of Gas Outlet Points As Suggested By The Client. Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submitted. The Product Should Be Ce Ertified / Ce Marked. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021. 16 Sitc Of Emergency Oxygen / Nitrous Oxide Manifold System ( 2+2 ) With Tail Pipes Nrv And One Dgss Regulator Of Minimum 600 Lpm Capacity- Manifold System Comprise Of Bank Of 2+2 Cylinders ( Bulk Cylinder Of D Type ) Capacity Manifold High Pressure Copper Pipe Of Size 1 / 2Idx14 Swg ( Approx. 2.0320 Mm ) & High Pressure Fitting Made Of High Tensile Strength Brass Be Used To Connect The Cylinders To The Header Assemblies With 4 NoS Non Return Valves & 4 NoS High Pressure Flexible Tail Pipe Is Made Of Copper Pipe Of 1 / 3X16 Swg ( Approx. 1.6256 Mm ) The Manifold Is Hydraulically Tested At 225 Kg / Cm2 Pressure It Is Also Degreased And Is To Be Offered Duly Wrapped In A Polythene Bag Make Ce Approved / Ce Certified. Note: Providing Of Cylinders Is In The Scope Of Hospital / End Client. Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submitted. The Product Should Be Ce Ertified / Ce Marked. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021. 17 Sitc Of Automatic Gas Control Panel / Change Over Panel For Oxygen / Nitrous Oxide Control Panel Cover Made For M.S Duly Powder Coated. Compact And Fully Automatic Manifold Control System For Oxygen Services Easy To Maintain And Use Designed With Both Safety And Continuity Of Flow Supply At A Constant Pressure Via Two Banks Of Bottled Gas Cylinders With Following Status Monitoring A- Bank In Use ( Green Indication ) B- Empty Bank ( Red Indication ) Control Panel Should Have Built In Led Display To Indicate Normal, High & Low Line Pressure. It Should Have Facility To Test All Above Indicators Working Perfectly. The Control Panel Should Include Pressure Gauge To Indicate The Gas Pressure Of Each Header And Pipe Line Distribution Pressure. Capable To Provide A Distribution Flow Rate In Excess Of 1200 Lpm. The Control Panel Should Incorporate Manual Bypass System In Case Of Failure Of Shifting Mechanism. Appropriate Test Certificate / Report Of Product / Accessories From Oem Shall Be Submitted. The Product Should Be Ce Ertified / Ce Marked. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With Pwd Electrical Bsr 2021.

Key Value

Document Fees
INR 500 /-
EMD
INR 55600.0 /-
Tender Value
INR 27.80 Lakhs /-

BOQ Items

Name of Work :SITC of MGPS work in 100 bedded ward Field Hospital at Parbatsar, Distt. Nagaur.
Sl. No. Item Description
1SITC of MGPS pipe of medically grade as per BSEN-13348 with third party certification from Lloyds/TUV degreased (ie free from oil, grease and particulate matters) seamless copper pipe confirming to ASTM B88 and all copper joining done by brazing with AWSA5.8, classification BCuP-5 or BS 1845 following procedure in accordance with ASTM B828 after purging with nitrogen. All pipe cutting shall be carried out with a radial pipe cutter and copper pipe fitting"s shall comply with B4 alloy designation. Adequate support shall be provided while laying pipeline testing shall be done at 17 Bar and after testing pipe shall be painted with two coat of enamel paint as per colour codification as per ISO 7396-Part-I 2016. Third party test report shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with P.W.D. Electrical BSR 2021
2SITC of non lubricated ball type Nickel Coated Isolation Valve with adapter & PTFE Seat having quarter turn/Butterfly handle opening of following sizes suitable for flow capacity of required LPM as per the size of valve at 4.7 bar with maximum allowable pressure of 30 bar and suitable for working temperature ranging - 20°C to 130°C. Appropriate Test certificate/report of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021
3For 12 MM OD Pipe
4FOR 15 MM OD Pipe
5FOR 22 MM OD Pipe
6FOR 28 MM OD Pipe
7FOR 42 MM OD Pipe
8SITC of Gas outlet points Oxy, N2O, (AR-4), (AR-7) and Vaccum (8.7 psig) for dispensing medical gases (oxygen/air/vaccum) at point of use confirming to BSEN ISO 9170-1:2008. The gas outlet are quick connect type , it should have color coding for different gas source and should accept only repective adapters as required.Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE Marked. All as per pre approved by Engineer in charge. For additional echnical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021
9SITC of BPC (back pressure compensated) flow meter with humidifer made of nickel plated body, double jacketed with flow gradations CE Marked on it. Desired flow will be setteled through rotary knob. Flow range should be between 0 to 15 lpm & work should be executed as per direction of engineer in charge. Appropriate Test Certificate/report of product/accessories from OEM shall be submitted. The product should be CE Certified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
10SITC of ward suction unit (Suction controller and collectionJar-600 ml capacity) with posibility to configure required capacity collection jar and should meets the requirements as per BSEN ISO 10079-3:2009. The unit must designed to operate with the vaccum line of MGPS. The collection jar must accumpained with Vaccum regulator suitable for 0-14.7 psig with flow rate 0-55 Lmp (min) for operating temperature- 18°C to 50°C with ON/OFF facility. The collection jar should be transparent, made of high quality polycarbonate that can be autoclaved at 121°C for 20 minutes for reuse and provided with auto stop to avoid over spill and contaminatin of the suction source when the jar collection reached optimized level. The complete unit supplied with filter to protect the source and pipe line from bacterial contamination. Appropriate Test certificate/report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
11SITC of valve box made of CRCA sheet duly powder coated with transparent window which is installed in the MGPS for oxygen and vaccum line and should comply with BSEN ISO5211:2001 complete with ball type valves and gauges as required for oxygen compressed air and vaccum line. Appropriate Test certificate/report of product/accessories from OEM shall be submited. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
12Three Gas Service
13SITC of microprocessor based auto alarm (digital type) suitable for medical gas service provided with audible and visual alarm for MGPS zoning. It should monitors the current status of oxygen / compresssed air pressure in distribution pipeline of central medical supply system and trigger the alarm to alert. The system should comply BSEN ISO:7396-I:2007 Appropriate Test certificate/report of product /accessories from OEM Shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
14Three Gas Service
15SITC of Bed Head Panel of 900-1500 MM long made out from high strength extruded aluminium with powder coating with at least 4 Nos 6/16 Amp switch socket and provision for required number of gas outlet points as suggested by the client. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
16SITC of Emergency Oxygen / Nitrous Oxide Manifold System (2+2) with tail pipes NRV and One DGSS Regulator of Minimum 600 LPM capacity- manifold system comprise of bank of 2+2 cylinders (Bulk cylinder of D type ) capacity manifold high pressure copper pipe of size 1/2"IDx14 swg (approx. 2.0320 mm) & high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 4 no"s non return valves & 4 no"s high pressure flexible tail pipe is made of copper pipe of 1/3"x16 swg (approx. 1.6256 mm) the manifold is hydraulically tested at 225 Kg/cm2 pressure it is also degreased and is to be offered duly wrapped in a polythene bag make CE approved /CE certified. Note: Providing of cylinders is in the scope of Hospital/End client. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.
17SITC of automatic gas control panel/Change over Panel for oxygen/nitrous oxide control panel cover made for M.S duly powder coated. Compact and fully automatic manifold control system for oxygen services easy to maintain and use Designed with both safety and continuity of flow supply at a constant pressure via two banks of bottled gas cylinders with following status monitoring A- Bank in use (Green Indication) B- Empty bank (Red Indication) Control Panel should have built in LED display to indicate Normal, High & Low line pressure. It should have facility to test all above indicators working perfectly. The control Panel should include pressure gauge to indicate the gas pressure of each header and pipe line distribution pressure. Capable to provide a distribution flow rate in excess of 1200 LPM. The control panel should incorporate manual bypass system in case of failure of shifting mechanism. Appropriate Test Certificate/Report of product/accessories from OEM shall be submitted. The product should be CE ertified/CE marked. All as per pre approved by Engineer in charge. For additional technical parameters of products/work, refer Annexure "A" attached with PWD Electrical BSR 2021.