Tender For Electrical Work In The Construction Of Phc Building At Basai Jogiyan (Thangagazi) Distt. Alwar, alwar-Rajasthan

Medical Health And Family Welfare has published Tender For Electrical Work In The Construction Of Phc Building At Basai Jogiyan (Thangagazi) Distt. Alwar. Submission Date for this Tender is 03-03-2023. Coats and Jackets Tenders in alwar Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

36432910
Tender For Electrical Work In The Construction Of Phc Building At Basai Jogiyan (Thangagazi) Distt. Alwar
Open Tender
Indian
Rajasthan
alwar
03-03-2023

Tender Details

Tender For Electrical Work In The Construction Of Phc Building At Basai Jogiyan ( Thangagazi ) Distt. Alwar - Wiring Of Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq. Mm Nominal Size Fr Pvc Insulated Unsheathed Flexible Copper Conductor 1.1 Kv Gradeand 1.5 Sq. Mm Nominal Size Fr Pvc Insulated Unsheathed Flexible Copper Earth Conductor 1.1 Kv Grade ( Is:694 ) Inrecessed Isi Marked Mms ( Is:9537 P - Iii ) Virgin Material Pvc Conduit & ItSisi Marked ( Is:3419-1988 ) Accessories, Round Tiles, 1.2 Mm Thickhot Dipped Galvanized Modular Box With Earth Terminal, 10A Modular Switch, Modular Face Plate With Grid Plate, 3 Pin Ceiling Rose / Holder / 3 Way Connector, Screws, Making Connections, Testing Etc. As Required.For Specification Of Copperconductor, Phenolic Laminated SheetS & Electrical / Wiring Accessories Refer Chapter E - 04, E - 05 & E - 07 For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 3 Short Point ( Up To 3 Mtr. ) 4 Medium Point ( Up To 6 Mtr. ) 5 Long Point ( Up To 10 Mtr. ) 6 Wiring Of Twin Control Light Point With 1.5 Sq. Mm Nominal Size Fr Pvc Insulated Unsheathed Flexible Copper Conductor 1.1 Kv Gradeand 1.5 Sq. Mm Nominal Size Fr Pvc Insulated Unsheathed Flexible Copper Earth Conductor 1.1 Kv Grade ( Is:694 ) In Recessed Isi Markedmms ( Is:9537 P - Iii ) Pvc Conduit & ItS Isi Marked ( Is:3419-1988 ) Accessories, Round Tiles, 2 Nos Hot Dipped Galvanized M.S Modularbox Of 1.2 Mm Thickwith Earth Terminal, 2 Nos10 A Two Way Modular Switch, 3 Pin Ceiling Rose / Holder / 3 Way Connector , Modular Face Plate With Grid Plate, Screws, Making Connections, Testing Etc. As Required.For Specification Of Copperconductor, Phenolic Laminated SheetS & Electrical / Wiring Accessories Refer Chapter E - 04, E - 05 & E - 07 For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 7 Medium Point ( Up To 6 Mtr. ) 8 Long Point ( Up To 10 Mtr. ) 9 Wiring Of 3 / 5 Pin 6 Amp. Light Plug Point With 1.5 Sq. Mm Nominal Sizefr Pvc Insulated Unsheathed Flexible Copper Conductor 1.1 Kv Gradeand 1.5 Sq. Mm Nominal Size Fr Pvc Insulated Unsheathed Flexible Copper Earth Conductor 1.1 Kv Grade ( Is:694 ) Inrecessed Isi Marked Mms ( Is:9537 P - Iii ) Pvc Conduit & ItS Isi Marked ( Is:3419-1988 ) Accessories, Hot Dipped Galvanizedmodular Box Of 1.2 Mm Thick With Earth Terminal, 10 A Modularswitch, 3 / 5 Pin 6 A Modular Socket, Modular Face Plate With Grid Plate, Screws, Making Connections, Testing Etc. As Required.For Specification Of Copperconductor, Phenolic Laminated SheetS & Electrical / Wiring Accessories Refer Chapter E - 04, E - 05 & E - 07 For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 10 On Board 11 S&F Following Sizes ( Dia. ) Of Isi Marked Virgin Material Mms ( Is:9537 P - Iii ) Pvc Conduit Along Withisi Marked ( Is:3419-1988 ) Accessories As Requiredinrecessincludingcutting The Wall, Covering Conduit And Making Good The Same As Required. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 12 20 Mm 13 25 Mm 14 32 Mm 15 Supplying And Drawing Fr Pvc Insulated & Unsheathed Flexible Copper Conductor As Per Pwd Specification For Electrical Works With Isi Marked ( Is:694 ) And As Per Is 8130 : 2013 Of 1.1 Kv Grade . Wire Should Be Made From99.90 % Purity Copper, Class 5 Stranding In Acc. To Is:8130 / Iec 60228 Forlower Watt Loss , Oxygen Free For Less Chances Of Oxidization, Insulation Pvc Type A / C / D , Flame Retardant As Per Is 10810-53, Better Amperage Rating As Per Is:3961 Part 5, In Existingsurface Or Recessed Pvc / Ms Conduit / Casing Capping Making Connections With Copper Lugs Of Suitable Size, Ferrules, Testing Etc. As Required. Oem Must Have Its Own In House Nabl Lab Setup For All Testing Facilities For Wires. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 16 1 X 1.5 Sq.Mm 17 3X 1.5 Sq.Mm 18 2 X 2.5 Sq. Mm. + 1X1.5Sqmm 19 2 X 4.0 Sq. Mm. + 1 X 2.5 Sq. Mm. 20 4 X 10.0 Sq.Mm 21 4 X 6.0 Sq.Mm 22 1 X 4.0 Sq.Mm 23 1 X 2.5 Sq.Mm 24 2 X 6.0 Sq. Mm. + 1 X 2.5 Sq. Mm. 25 Supplying And Drawing Pe Insulated & Pvc Sheathed Unarmoured Telephone Cable With 0.5 Mm Dia. Solid Annealed Electrolytic Grade Bare Copper Conductor As Per Is: 8130 / 84 &Confirming To Tec Specification Gr / Wir / 06-03 March 2002In Existingsurface Or Recessed Conduit / Casing Capping. Including Ferruling On Each Pair For Identification Etc. As Required. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 26 2 Pair 27 P & F In Position Frame Made Out Of M.S. Angle ( Riveted Or Welded ) Finished With Two Coats Of Red Oxide And Two Coats Enamel Paint Including Cutting, Welding, Holes Etc.Of Following Sizes As Required.For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 28 40Mm X 40Mm X 5Mm 29 P & F Paper Phenolic Resin Bondedlaminates Confirming To Is : 2036 -1995 For Boxes / Frames Including Making Holes For Switches Etc, With Brass Screws, Washers / Zinc Platednut And Bolts As Required. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 30 6.4 Mm Thick 31 P & F Phenolic Laminated Sheet 2.0 Mm Thick Of Following Size . Including Screws, Cup Washer As Required.For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 32 75 Mm Dia 33 Providing & Fixing Of 240 / 415 V Ac Mcb With Positive Isolation Of 10 Ka Breaking Capacity ( B / C / D Tripping Characteristic As Per Type Of Load Andsite Requirement ) 4 Kv Impulse Withstand Voltage, Isi Marked Is 8828 ( 1996 ) / Conforming To Iec 60898-1 2002, Iec 60947-2, Low Watt Losses, Trip Free Mechanisum , Energy Limiting Ofclass 3 As Per Iec, Minimum Phase Termination Capacity Of 35Sq.Mm. , Conductor Line Load Reversibility , Ip 20 Contact Protection And Fitted Inexisting Distribution Board / Sheets, Minimum Electrical Operation 20, 000 Upto 20 A Rating And 10, 000 Upto 63 A, 5000 For 80 A & Above Ratingincluding Making Connections, Testing Etc. As Required. Oem Shall Have Submitnabl / Cpri / Erda Accrediated Lab Type Test Reports& All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 34 Single Pole Mcb ( With B / C Curve Tripping Characteristics ) 35 6 A To 32 A Rating 36 Double Pole Mcb ( With B / C Curve Tripping Characteristics ) 37 6 A To 32 A Rating 38 Four Pole Mcb ( With B / C Curve Tripping Characteristics ) 39 6 A To 32 A Rating 40 50 / 63 A Rating 41 Providing & Fixing Of Recessed / Surface Mounting Heavy Duty Horizontal Type Double Door ( Metal / Glazed ) Distribution Board With Metal End Box Made Out From Galvanized Steel / Crca Sheet Not Less Then 1.2 Mm Thick Conforming To Is-8623-1 & 3 / Iec 61439- 1 & 3, Powder Painted Complete With Reversible Door ( For Double Door Db Only ) 100 Amp. Insulated Copper Bus Bar / Shorting Link , Copper Neutral Link, Copper Earth Link , Color Coded Interconnecting Wire Set Of Suitable Rating And Din Bar, Masking Sheet, Making Internal Db Terminations With Copper Lugs, Ferrules, Detachable Gland Plate, Including Making Connections, Testing Etc. As Required. Oem Shall Have Submitnabl / Cpri / Erda Accrediated Lab Type Test Reports& All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 42 Metal Door ( Single Phase ) Ik-09 And Ip-43 With Metal End Box 43 16 Way ( 16+2 ) 44 Metal Door ( Three Phase ) Ik-09 And Ip-43With Metal End Box 45 6 Way 46 P&F Metal Clad / Plastic Industrial Plug Top & Socket Unit With Pin And Sleeve Type Contact On Porcelain / Bakelite Base In Recessed / Surface Mounting Heavy Duty Enclosure Made Out From Galvanized Steel / Crca Sheet Not Less Then 1.2 Mm Thick Conforming To Is-8623-1 & 3 / Iec 61439- 1 & 3. Powder Painted ( Without Mcb ) Including Making Connections, Testing Etc.As Required.For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 47 20 Amp, 3 Pin + Scrapping Earth, 4 Module 48 P & F Of Industrial Plug And Socket Conforming To Iec 60309-1 / 2 Made Out Of Self Extinguishing Engineering Polymer / Polyamide, Nickel Plated Brass Sleeve And Pins, Socket With Shutter Including Making Connection Etc As Reqd. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 49 Ip -67 Panel Mounted Socket 50 32 A 3 Pin ( 2P+E ) 51 Providing & Fixing Of Flush Typenon Modular Single Line Telephone Jackmade Out Fromindustrial Grade Polycarbonate Or Fire Resistant Abs Material, Including Making Connection Testing Etc. As Required.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 52 Providing & Fixing Of Ding Dong / Musical Chime Bell As Per Pwd Specification For Electrical Works, Including Making Connection Testing Etc. As Required.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 53 Providing & Fixing Of Modular Type 120 W Step Fan Regulator Duly Isi Marked ( Is 11037:1984 ) With Cm / L No. Printedmade Out Of Unbreakable And Fire Retardant Vergin Poly Carbonate With Brass Terminals And Captive Screws & Silver Alloy Contact Tipwith Ip-20 Rating , Includingall As Per Pre Approved By Engineer In Charge, Making Connections, Testing Etc. As Required.For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 54 5 Step Fan Regulator 2 Module 360 Dgree Rotating 55 Supplying And Fixing Of Power Plug Point With Modular Accessories As Per Pwd Specification For Electrical Works, On Hot Dipped Galvanized Modular Box Of 1.2 Mm Thick With Earthing Terminal / Connector On Surface Or In Recessed With Suitable Size Of Modular Face Place With Grid Plate And Cover Plate Including Cost Ofisi Marked Modular 16 Amp. Switch ( Is :3854 ) And 6 / 16 Amp. Socket Outlet ( Is:1293 ) Making Connection , Testing , Etc. As Required. For Specification Ofwiring Accessories Refer Chaptere - 07Related Item & For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 56 P & F Krone Module With Base Framein The Recess / Surface Made Out Of 1.2 Mm Thicksheet Steel Box, Front Openable, Having Locking Arrangements Duly Powder Painted, Including Dressing, Ferrulingandpunchingof Telephone Cable With Krone Tool Etc. As Required. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 57 10 Pairs 58 Sitc Of Ip-42 And General Construction Confirming To Is:8623 : 1993, Wall / Free Standing Floor Mounted Dust And Vermin Proof Compartmentalisedcubical Panel As Specifications Andother Parameters Requiredas Per Point ( A ) , ( B ) , ( C ) , ( D ) , ( E ) , ( F ) , ( G ) , ( H ) As Below:- 59 ( A ) Thickness Of Crca Sheet Shallbe 2.0 Mm, Cable Alley Compartments Having Concealed Hinged Type Doors With Key Type Lock With / Withoutdetachable Extension Type Structure. Removable 3 Mm. Thick Sheet Steel Gland Plates With Appropriate Size Of Knockouts For Cables Shall Be Provided 60 ( B ) Complete Panel Shall Undergo A Process Of Degreasing, Water Rinsing, Activation, Derusting, Pickling In Acid Bath, Phosphatising & Shall Be Subjected To Nine Tank Process And Then Powder Coated With Approved Shade Of Minimum 70 Microns On Both Side Of Panel.The Panel Having Pe Foam / Neoprene Rubber Gasket Of Not Less Than 3Mm Thickness , Required Hardware , Concealed Hinged Door With Key Type Locking Arrangement For Equipment / Switchgear Earthed With 2.5 Sq.Mm Braided Copper Wire. 61 [ C ) Interconnection Between Bus Bar And Switchgears / Cable Shall Be Rigidly Supported And Made Out By Flexible Copper Wires ( Up To 63 Amp ) And By Solid Bus Bar ( >63 Amp ) . Control Wiring Will Be Carried Out With 1.5 Sq.Mm, Earth Wire With 2.5 Sq.Mm And Ct With 2.5 Sq.Mm Flexible Copper Wire Only.All Joints / Interconnections Of Copper Bus Bar Shall Be Dully Tinned . Clearance Between Main Bus Bar And Risers / Metal Parts Shall Be At Least 10 Mm Additional To Width Of Bus Bar Bus Bar Is Insulated By Heat Shrinkable Sleeves . Earth And Neutral Bus Bar Shall Be Half Of The Size Of Phase Bus Bar. ( Cost Of Bus Bar / Flexible Wire For Interconnection Between Main Busbar And Switchgearis To Be Paid Extra ) 62 ( D ) Wiring Between Components Within Switchgear And Incoming / Outgoing Cableshall Be Done Through The Terminal Block Only. Direct Connection Shall Not Be Permitted. Each Terminal Block Shall Be One Piece Moulded, Barrier Type, 650 Volt Grade, Complete With Washers, Heads, Studs With Two Nuts And Identification Strips And Shall Have Adequate Continuous Current Rating. For Tap-Offs, Adjacent Terminals With Shorting Strips Shall Be Used. 10% Spare Terminal Blocks Shall Be Provided. Wire Identification On Marking Strip Shall Correspond To The Designation Of The Wiring Diagrams. All Wire Terminals On The Equipment Shall Also Be Marked With Designation Corresponding To Those Of The Wiring Diagram. 63 ( E ) All Wiring Shall Be Enclosed In Plastic Channels And Neatly Bunched And Closed In Metering Chamber, Wiring Between Terminals Of Various Devices Shall Be ‘Point To Point’ ( No Wire Splitting Or Tee Connections ) With Wires Neatly Trucked Along The Back Of The Panels, Adequately Supported To Prevent Sagging. 64 ( F ) Floor Mounted Panel Shall Be Mounted On Base Frame Of Ismcchannel Size 100 X 50 X 5 Mm ( To Be Paid Extra ) 65 ( G ) Tests: The Insulation Resistance ( With 1000 V Megger ) And High Voltage Power Frequency Test ( By Applying A Voltage Of 2.5Kv For One Minute ) Shall Be Measured Between Phases, Between Phase And Neutral And Between Phase And Earth. Both Before And After High Voltage Power Frequency Test. The Insulation Resistance Shall Not Be Less Than Three Megaohm. Ct Secondary Current Injection Test Shall Also Be Carried Out. 66 ( H ) Only Outer Surface Area On All Sides Shall Be Measured & Panel To Be Fabricated Only From Cpri Approved Fabricator Only ( Cpri Test Certificates To Be Submitted ) All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 67 Supplying And Fixing Of Aluminium ( Iec 60105 Iso 209-1, 2 ) / Copper ( Iec 60028 ) Bus Bar By Means Of Smc / Dmc Type Insulatorwith Standard Short Circuit Withstand Capacity, High Tensile Nuts And Bolts Spring Washers In Existing Panel Including Bending , Cutting In Required Shape And Size And Colour Coding With Heat Shrinkable Pvc Sleeves. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 68 Electrolytic Grade Aluminium Bus Bar 6010 Grade 69 Providing & Fixing Of Bis Approvedcurrent Transformeras Per Pwd Specification For Electrical Works , Isi Marked As Peris 2705-1992 / Conforming To Iec 60044-1, With Secondary Terminalof Ct Shall Be Brought Out Suitable To A Terminal Block Which Shall Be Easier Accessible For Testing And Terminal Connection , With All Necessary Support In Existing Panel Including Connection Etc. As Requiredcurrent Transformer Ring Type Tape Wound / Resin Cast Wound As Per Is 16227 With, Accuracy Cl, Ct Ratio And Burden As Specified. Isf<=5, Cu Cross Section Of Secondary Wire 1.5Sqmm ( Minimum ) , Including All Necessary Support In Existing Panel Including Connection Etc. As Required . All As Per Pre Approved By Engineer In Charge.All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 70 Ring Type Tape Wound Ct 71 C T Class 1, Ratio 200 / 5 To 300 / 5, Burden 10 Va 72 Providing & Fixing Of110 / 220 V, Unibody Led Indicatinglamp Iec 60947With Integral Circuit, Ip 65 Above Panel &Ip 20 Terminal Block, Approx. Body Dia For Panel Not Less Then 20 Mm, Length Min. 50Mm, Front Led Cover Dia Min.29 Mm, Contact Material Phospher Bronze For Led, Pcb Contacts Shall Be Ofbrass ( Tin Plated ) , Impulsedielectric Tested For 2.5 Kv, Rated Insulation Resistance Shall Be 100 M Ohm At 500Vdcincluding Connection Etc. As Required.All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 73 Red / Yellow / Green Colour 74 Providing & Fixing Of Electricalinsulating Rubber Matts As Per Pwd Specification For Electrical Works, Isi Marked Confirming To Is: 15652 / 2006With One Sideanti Skid Abberation Marks And Pasting The Mat With Synthetic Rubber Adhesive As Required. All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 75 3.3 Kv, Class A 2 Mm Thick With Proof Voltage 10 Kv Ac ( Rms ) And Break Down Voltage 30 Kv Ac ( Rms ) 76 Sitc Of3 / 4Pole Current Limiting Moulded Case Circuit Breaker ( Mccb ) Made Of Flame Retardent & Heat Resistant Materialhaving Following Current Rating, Short Circuitbreaking Capacityat 440 / 415 V, 50 Hz; O / L & S / C Settings , Conforming To Is / Iec 60947 P -2 :2003 With Frontface And Centralised Adjustable, Trip Free Mechanisum, True Contact Position Indicator, Line Load Interchangeability, Designed For Both Horizontal & Vertical Mounting Without Any Adverse Effect On Electrical Performance, Suitable For Operation Upto 55 Degree And Without Derating Upto 40 Degree, Pollution Degree 3, Having Positive Isolation Capability, Push ( Test ) To Trip, Trip Time Less Then 10 Ms Under S / C Condition, Breaking Capacity Ics = 100% Icu. U Imp =8 Kv, Rated Insulation Voltage690 V.Provision For Uvr , Shunt Trip , Earth Fault Trip, Door Interlock, Pad Lock & Rotary Handle , Including Making Connectionsetc. As Required.Oem Shall Have Submitnabl / Cpri / Erda Accrediated Lab Type Test Certificate Before Execution All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 77 4 Pole Mccb With Thermal Magnetic Release 78 125 Amp , 25 Ka, Adjustable O / L & Adjustable S / C Setting, 79 Up To 100 Amp , 25 Ka, Adjustable O / L & Adjustable S / C Setting, 80 Providing & Fixing Of Iso Certified Company Made On Load Change Over Switch, Front Handle Operated, Four Pole 415 V As Per Pwd Specificationfor Electrical Works Conforming To Is / Lec 60947-3 : 1999 Including Connections , Testing Etc. As Required .In The Following Rating.Appropriate Type Test Certificate / Oem Test Report Shall Be Submitted .All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 81 Open Execution Type 82 160 A 83 Providing & Laying P.V.C. / Xlpe Insulated & P.V.C. Sheathed Arrmouredaluminiumcable Confirming To Is:1554 P-I / Is :7098 P - I Of 1.1 Kv Withh4- Grade Electrolyticaluminium Conductor Confirming To Is 8130 Of Purity >99.6 %, Round / Flat Strip Armouring Of Cables, Inner / Outer Sheath Confirming To Is:5831In Existing Rcc / Hume / Stoneware / Pvc Pipe / Open Duct / Cable Trench / Cable Tray ( With Cable Tie ) Includingtesting Etc. As Required Of Following Size. Oem Must Have ItS Own In House Nabl Accrediated Laboratory For Testing Procedure As Per Is:10810.For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 84 10.0 Sq. Mm 85 2 Core 86 35.0 Sq. Mm 87 3.5 Core 88 Supplying And Making One End Termination With Nickel Plated Heavy Duty Brass Single Compression Gland ( As Per Is 12943-1990 ) ) Sibg Type Consisting Of Check Nut, Gland Body, Metal Washer ( 3 Nos. ) , Outer Seal Rubber Ring, Compression Nut, Heavy Duty Aluminium Lugs ( As Per Is 8309 -1993 ) Duly Crimped With Crimping Tool, Pvc Tape As Peris 8337-1976Offollowing Size Ofpvc Insulated & Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1100 Volt Grade As Required.All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 89 3.5 X 35.0 Sq.Mm 90 Supplying And Makingend Termination With Heavy Aluminiumlugs ( Pin / Ring Type ) Confirming To Is 8309 -1993 & Is 8337-1976 Duly Crimped With Crimping Tool, Pvc Tape Etc Of Following Size.All As Per Pre Approved By Engineer In Charge. For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 91 35.0 Sq.Mm 92 Supplyandinstallationofhigh Tensile Low Carbon Steel Rod Molecularly Bonded With 99.9 % Copperthickness ( 250 Microns ) Andconfirming Toul 467, Is / Iec 62561-2Of Following Size And Length And As Per Point Mentioned ( A ) , ( B ) , [ C ) , ( D ) , ( E ) Below :- 93 ( A ) Bore A Hole Of Dia. 100 Mm Of Required Length, Place The Rod In The Centre Of Hole 94 ( B ) Filled With Anti Corrosiveconductivecompounds With The Permanent Sealings At Both The Ends, Cpri / Erdatested With Rms Capacity Of Minimum 30 Ka For Withstanding 1 Second .To Ensure The Moisture Content And Electrical Conductivity, 25 Kg For 2000 Mm & 50 Kgs For 3000Mm Of Resistance Lowering Earth Enhancement Material Shall Be Used As A Backfill Compound. The Compound Shall Be Tested Form Nabl Acredeated Labfor Lowresistivity ( Less Than 0.12 Ohm - Meter ) & High Conductivity In Nature With Carbon As A Major Contentas Per Referance Of Is 3043-1987, Ieee 80-2013 ( Clause 14.5D ) , Ieee 837 & Ier 1956 With Latest Amendemnts 95 © Connect The Rod With Copper Strip / Conductor / Wire With Suitable Clamp Made From Tinned Copper And Ss 304 Bolt 96 ( D ) Place Heavy Duty Weather Proof Poly-Propylene Earth Pit Chamber With Lockable Jam Free Lid Suitable For Safe Working Load 5000 Kg Or More Of Size Top Dia. 225 To 260 Mm, Bottom Dia 300 To 350 Mm. And Height250 To 300 Mm. 97 ( D ) Testing Of Earth Resistance For Value Of 5 Ohms Or Lessas Required & Must Record By Engineer In Charge During Site Visit And Ensure To Enter In Measurment Book. 98 ( E ) Test Certificatesfor Confirming Above Standards From Oem Is Mandatory. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 99 17.2 Mm Thick And 3 Mtr. Long 100 Supply & Laying Following Size Earth Wire In Horizontal Or Vertical Run In Ground / Surface / Recess Including Riveting, Soldering, Saddles, Making Connection With Gi / Cu Purity Purity >95%Thimble Etc. As Required.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 101 8 Swg Copper Wire 102 8 Swg G.I. ( Hot Dipped ) Wire 103 Making Of Hole In Wall ( Brick / Stone ) Of Required And Placing Np-2 Rcc Pipe Ring Of Required Size For Housing Exhaust Fan And Making Good The Same, With Cement Plaster Required Of Following Size. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 104 Up To 457 Mm Size 105 Providing & Fixing Ofbeestar Rated Copper Wounded Double Ball Bearing Capacitor Start, Aluminium Body & Metallicblade Ceilingfanconforming To All The Performance Requirements Laid Down In Is 374:2019 Including All Amendments, As Applicable ; & Carry Bis Licensing ( I.E. Isi Marking ) With Down Rod Up To 80 Cm With Secondary Support Safety Cable ( Steel Rope ) , Cotter Pin With 3 X 1.5 Sq.Mm Pvc Insulated Flexible Copper Conductor Making Connection Testing Etc. As Required. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 106 1200 Mm Sweep Bee 2 Star Rated ( Service Value >=4.5 To < 5 ) 107 1200 Mm Sweep Bee 3 Star Rated ( Service Value >=5.0 To< 5.5 ) 108 P & F 1.2Mm Thickm.S. Recessed Fan Box, Hexagonal / Round Of Size 130 Mm Dia, Depth 75Mm, 12 Mm Dia Rod Fan Hook With 100 Mmlength Extended On Each Side . All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 109 P & F 1.2Mm Thickm.S. Recessed Fan Box, Hexagonal / Round Of Size 130 Mm Dia, Depth 75Mm, 12 Mm Dia Rod Fan Hook With 100 Mmlength Extended On Each Side . All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Product / Work Refer Annexure A Attached With This Bsr 110 Providing & Fixing Ofof Double Ball Bearing, Copper Wounded Capacitor Startsingle Phase Metallicblade Fresh Air Fan, In Existing Opening Including Cost Of Hardware , Flexible 3 Core Copper Conductor , Making Connections, Testing Etc. As Required. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 111 225 Mm Sweep 112 Providing & Fixing Of Heavy Duty Capacitor Start, Copper Wounddouble Ball Bearing900 / 1400 Rpm Single Phaseexhaustfan Conforming To Is:2312 Isi Marked In Existing Opening Including Making Connections Testing Etc. As Required. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 113 300 Mm Sweep ( 900 / 1400 Rpm ) 114 Providing & Fixing Of Wall Mounting / Pedestal Type Heavy Duty Air Circulator , Double Ball Bearing And With Metal Sturdy Mesh Guard; Aluminium Alloy One Piece Blade And Conforming To Is:2997, Including Fixing With Anchor Bolts, Making Connection Testing Etc. As Required. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 115 450 Mm Sweep Wall Mounting And Three Speed Regulator With Minimum Air Delivery 150 Cum. / Minute 116 P & F Of Gravity Louver Shutter Of Superior Quality Made Out Of Frame Of18 Swg M.S. Sheet & Louvers Made From 24 Swg Ms Sheetwith Enamel Paint Including Cost Of Nuts, Bolts, Etc As Reqd.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 117 Up To 380 Mm Size 118 Providing & Fixing Of Vertical ( Bee 5 Star Rated ) / Horizontal ( Bee 3 Star Rated ) Storage Water Heater With Outer Casing Made Of Engineering Plastic Sheet ( Upto 25 Ltr ) / Metal Rust Proof Body ( 35 & 50 Ltr ) , Glass - Line / Titanium Enamel Coated Pressure Pump Compatible 8 Bar Pressure Inner Tank, Glass Line Coated , Mineral Filled Heating Element, Stem Type, Snap Actionadjustable Thermostat , Dual Indicating Lampsinjected Puf Insulation, Multi Function Valve Etc. As Required Held In Position With 2 / 4 No. 10 / 12 Mm Anchor Fastener, Duly Wired With 3 Core 2.5 / 4.0 Sqmm Pvc Insulated & Sheathed Copper Conductor And 16 A / 25A Three Pin Plug Top With Portable Residual Current Device ( Prcd ) , Including Making Inlet, Outlet Flexible Alloyconnection, Testing Etc. As Required. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 119 15 Ltr. 120 Sitc Ofmnre Approved & Confirming To Is:12933 P-1, 2, 3 & 5 Flat Plate Collector Type Solar Hot Water System Havingcollector Withzincalum Sheet Outer Body , Glass - Line / Titanium Enamel Coated Inner Tank With Metal Rust Proof Puf Insulated Body Includingelectrical Back Up, Thermostat, Powder Coated / Hot Dipped Galvanized Ms Standfor Collector & Tank Etc. As Required. Of Following Capacity Complete In All Respect. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 121 200 Litre / Day 122 Providing & Fixing Of Energy Efficient Direct Fit ( Retrofit ) Polycarbonate / Glasshousingsmd Mid Power Led Tube Rod ( With Integral Driver & Alumn. Heat Sink ) , On Existing Fixture.System Lumen Efficacy = 100 Lm / Watt Output, Internal Surge Protection Of 2.5 Kv , Thd < 20% , P.F.=0.95, Cri >80 , Life Time Of Minimum35000 Burning Hours With , 70% Of Intial Lumen Maintaned Till Life Ends, Cct 3000°K / 4000°K / 5700°K / 6000°K / 6500°K ( As Per Ansi Bin ) , Maximum Power Consumption Should Not More Than The Specified Rating And Fixture Shall Be Ofbis Standard Andtrade Mark Certificate ( T.C. ) . Manufactures Word Mark / Name Engraved / Embossing / Screen Printing Onhousing. Oem Must Have Its Own In House Nabl Lab Setup For All Testing Facilities For Led Fixtures. ( Lm79 & Lm80 ) Certificate / Report From Oem Shall Be Submitted.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 123 1200Mm , Min. Lumens Output 2000 Lmled Tube Rod With Polycarbonate Housing 124 Providing & Fixing Of Ip-20 Led Recessed / Surface Mounted, Round / Sqauresmd Mid Power Led Downlight With Power Coated Die-Cast Aluminum Housingwith Uv Stabilized Non Yellowish Diffuser Withbis Complience 2.5 Kv Surge Protected Isolated Driver, With Short & Open Circuit Protection, Having Efficiency > 85% . System Lumen Efficacy Of = 110 Lm / Watt, Thd < 10 % , Pf.=0.95, Cri >80, Life Time Of Minimum50000 Burning Hours With , 70% Of Intial Lumen Maintaned Till Life Ends, Cct 3000°K / 4000°K / 5700°K / 6000°K / 6500°K ( As Per Ansi Bin ) , Maximum Power Consumption Should Not More Than The Specified Rating And Fixture Shall Be Ofbis Standard Andtrade Mark Certificate ( T.C. ) . Manufactures Word Mark / Name Engraved / Embossing / Screen Printing Onhousing. 125 Oem Must Have Its Own In House Nabl Lab Setup For All Testing Facilities For Led Fixtures. ( Lm79 & Lm80 ) Certificate / Report From Oem Shall Be Submitted. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 126 Surface Mounting ( With Extruded Alumn. Housing ) 127 Minimum Lumen Output 1950 Lm 128 Providing & Fixing Of Ip20, 2X2 Led Surface / Recessedmounting Mid Power Smd Type Led Light Fixture Not Less Than 50Mm Housing Depth Made From Crca Sheet Steel Housing, High Purity / Transmisivity Uv Stabilized Non -Yellowish Diffuser For Uniform Light Distribution. High Efficiency With 4 Kv Internal / External Surge Protection Bis Certified Isolated Driver Having Efficiency > 85% , With Short & Open Circuit Protection ( Integral With Light Fixture ) . System Lumen Efficacy Of = 120 Lm / Watt , Thd < 10 % , P.F.=0.95, Cri >80 , Life Time Of Minimum50000 Burning Hours With , 70% Of Intial Lumen Maintaned Till Life Ends, Cct 3000°K / 4000°K / 5700°K / 6000°K / 6500°K ( As Per Ansi Bin ) , Maximum Power Consumption Should Not More Than The Specified Rating And Fixture Shall Be Ofbis Standard Andtrade Mark Certificate ( T.C. ) . Manufactures Word Mark / Name Engraved / Embossing / Screen Printing Onhousing. 129 Oem Must Have Its Own In House Nabl Lab Setup For All Testing Facilities For Led Fixtures. ( Lm79 & Lm80 ) Certificate / Report From Oem Shall Be Submitted.All As Per Pre Approved By Engineer In Charge. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 130 Recessed Mounting 131 Minimum Lumen Output 4200 Lm 132 Providing & Fixing Of Ik08, Ip 66 Protected Led Street Light Luminaire On Existing Bracket / Pole. Fixture Made Of Powder Coated Single Piece Pressure Die Cast Aluminummaterial With Heat Dissipation Fins On Housing With Uv Stabilized Pc ( Uv Stablization Report Submitted For Uv Cover ) / Toughened Glass Coverand Secondary Lens On Each Led & Should Be Smd Type Of 3 To 5 Watt Each . The System Efficacy >=125 Lm / Wt And Potted Driver& Has A Unique Bis R Number Withinput Voltage Ac 120 To 270 V Ac With High Voltage Cutoff @>=300 V Ac And Auto Resetting Safety , Power Factor >0.95 Driverefficiency >85%, Thd ( I ) <10%Humidity 10% To 90% Rh Working Temp -5C To 45C .Driver Current <750Ma. The Luminaireshall Be Bis Certified And Trade Mark Certified. Life Expectancyequal Or More Than 50000 Burning Hrs With Minimum 70% Lumen Maintened , Cri >70 And Cct 5700K +355K. Surge Protection Shall Be Min = 4 Kv Internal And Min 10 Kv External Inside Driver Compartment. Driver Should Be Phase To Phase Protection Of 440 V For 4 Hrs.Manufactures Word Mark / Name Engraved / Embossing On Die Cast Housing To Allow Traceability / Authenticity. Fixture Shall Be As Per Is 10322 Complianced.Oem Must Have Its Own In House Nabl Lab Setup For All Testing Facilities Forled Fixtures. ( Lm79 / Lm80 ) Certificate / Report With Liable Warranty Of Product / Accessories From Oem Shall Be Submitted. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 133 Led Street Light Fixture With Minimum Lumen Output 2450 Lm 134 Providing & Fixing Of Street Light Bracket Made Out From Following Size Of B Class , Medium Class G.I. Pipe Confirming To Is : 1239 P - 1 ( 2004 ) With Heavy Duty Pole Clamp, Saddles Suitable Fastners Etc. As Required. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 135 25 Mm Dia. 136 Supply, Drawing And Testing Of 4 Pair, 23 Awg Solid Bare Copper Wire Insulated With Pvc, Utp ( Unshielded Twisted Pair ) , Category 6, Class E, 100 Ohm Impedance, Indoor Cable As Per Latest Ammendments Of Ansi / Tia / Eia-568 , The Copper Conductors Should Be Balanced Twisted In Pairs, Seperated By A Cross-Member Fluted Pair Divider & Protected Bypvc Jacket. Certified Performance In A 4-Connector Configuration Upto 100 Mtrs Channel Requirements & Transmission Frequencies Up To 250 Mhz. In Existing Ms / Pvc Conduits / Casing Capping Including Making Connections To Information Outlets And Patch Panels With Jack &Ferruling At Both Ends For Identification With Necessary Tools For Punching, Stripping, Crimping And Testing Etc As Required Complete In All Respect. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 137 Supply And Installation Of Unsheilded / 360 Degree Sheilded Information Outlets Made Of High Impact Plastic Body With Abs, Fr Grade Halogen Free Material With Provision For Protection Against Dust In Jack, Suitable For Cat 6 / 6A Application Complying To Latest Ammendments, According. To Cat. 6 / 6A Channel, It Should Support Channel As Well As Components Requirements Of Cat.6 / 6A Standards At Frequencies Of Up To 250 To 500 Mhz. Cat 6 / 6A Unshielded / Shielded Jack Should Be Suitable To Terminate 4 Pair, 23 / 24 Awg Solid / Stranded Wire Diameters, Using 100 Ohm Unshielded / Shielded Balance Twisted Pair Cable, The Jack Should Have Tooless / Impact Termination On Reliable Copper Tin Plated Insulation Displacement Contact, With Easy Lock Mechanism, It Supports Iec 60603-7-4 And Complied With Ansi / Tia / Eia 568 C.2 Standard. Jack Should Be Rj11, Rj12 & Rj45 Compatible. Should Support Ethernet 1.2 Gb / S Atm, Digital Video And Broadband / Baseband Analog Video, Voice Over Internet Protocal ( Voip ) Specifications In Existing Modular / Ms Boxes Along With Necessory Connections As Required.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 138 Cat 6, Un-Sheilded Information Outlet 139 Supply & Fixing Of Square Faceplate For Flush / Surface Mount Information Outlets Single / Dual Or Quad Aperture , Material Should Bepc+Abs Body, Suitable For Rj45 Unshielded / Shielded Connection Modules. Should Match With I. O. Oem. Dimensions Should Be 86Mm X 86Mm As Required Complete In All Respect.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 140 Single Aperture 141 Supply , Installation And Testing Of 4 Pair, 100 Ohm Impedance, Cat 6 / 6A / Class E / Ea Patch Cords Should Be Constructed Of Minimum 23 / 24 Awg, Stranded Bare Copper Cable With Frpvc / Lszh Jacket, With An Enhanced Performance By Factory Moulded Rj45 Connectors With Strain Relief Boots As Per Ansi / Tia / Eia 568-C.2 Suitable For Cat 6 / 6A Application Complying To Latest Ammendments Category 6 / 6A Standards, According. To Tia568c.2, Iso / Iec 11801, En 50173, Iec 60603-7-51, En 60603-7, Ieee 802.3An Minimum Requirement For 1G Base-T To 10G Base-T Performance. Patch Cords Shall Be Straight Thru Cable Compatible With Both T568-A And T568-B Wiring Schemes, Should Support Ieee 802.3Af / Ieee 802.3At For Poe Applications, Minimum 750 To 1000 Mating Cycles In Plug Contacts For Long Durability, Should Support Ethernet 10Gbase-T, 1.2 Gb / S Atm, Token Ring 4 / 16, Digital Video And Broadband / Baseband Analog Video, Voice Over Internet Protocal ( Voip ) .All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 142 Cat 6, U / Utp ( Unscreened / Un-Sheilded Twisted Pair ) Patch Cord 143 1 Mtr 144 Supply, Installation, & Testing Of 19 1U Rack Mounted / Surface Mounted Aluminum / Crca 1.2Mm Powder Coated, Multimode Glass Fiber Optic Cable Patch Panel / Liu Loaded With Flangless / Screwable Adapters For St / E-2000 / Sc / Lc / Mt-Rj / Pc Type, It Should Have Easy Removable Top Plate With Push Buttons, There Should Be A Splice Tray Installed In The Patch Panel / Liu Which Can Handle The Fiber Cores, Splice Tray Should Be Pc+Abs Material, It Should Include Accessories Like Mounting Hardware, Gormetts, Heat Shrink Tubes / Sleevs, Screws, Nuts To Install The Panel For Rack / Wallmount Applications As Per Requirement Complete In All Respect. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 145 Multi Mode Liu 12 Ports 146 Supply & Installation Of Ip-20 & Ik-08 , Ul Listedwall Mounted Double Section Communication Enclosure ( Rack ) Made From Powder Coated ( 60 To 80 Micron ) Crca Sheet, Front Sturdy Sheet Steel Frame Folded From One Piece And Welded With Minimum 5Mm Toughened Glass Door, Vertical Mounting Rail 1.6 Mm With UMarking , With All Round Protective Channel On The Door Aperture, Lock Integrated On Front Door, Top And Bottom Cover With Cable Entry Provision With Gland Plates, Integrated Side Walls, 2 Pair Of 19 Angles With Wall Mounting Provision On Wall. Accessories Like: 1 No Of 19 1U Horizontal Cable Manager, 1 No Of 90 Cfm 230V Ac Fan With 1 Mts Long Cable, Mounting Hardware , 1 No Of 19 1U, Mountable Socket Strips With 5 Nos Of 5A Universal Sockets With 2 Mts Long Power Chord For Supplying Power To Switches, Fans Etc Along With Earth Continuity Kit, Indicator, Moulded Power Supply Cable. Fixing On Wall With Suitable Anchor Fastneretc As Required.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 147 6 U Rack With Width 600 Mm &Depth 400 Mm + 100 Mm 148 Supply , Installation, Testing And Comissioning Ofmanaged Layer-2 Intelligent 10 / 100 Ethernet Switch Providing 24 X 10 / 100 / 1000 Mbps Giga Ethernet Ports / With Min 2 Sfp Giga Ports ( Provision For Fiber Giga Connectivity ) With Related Lan Base Software Including Making Connections Etc As Required.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 149 Sitc Of Single Stage, Water Cooled, High Speed ( 2880 Rpm ) , Horizontal, Centrifugal, Openwell Submersible Pumps Set Pre Filled With Coolent Water And Fitted With Mechanical Seal - T / C Vs T / C, Thrust Bearing Shall Be Ofcarbon + S.S.The Stator Body Of Single Phase Pumpshall Be Of Ss And Rest Of All Shall Be Of Cast Iron. All Casting Parts Should Be Cathod Electro Deposition ( Ced ) Coated And Other Construction Material Should Be Confirming To Is : 14220: 2018 . The Overall Performance Of Pump Shall Confirm To Bee Energy Efficiency Level Of 3 Star. Valid Bee Certificate From Oem Must Be Submitted For The Same. Motor Should Be Ie2 Class As Per Iec 60034-2-1: 2007, Iec 60034-30: 2008, & Is12615:2011, Including Making Connection Etc As Required Complete In All Respect. Oem Shall Have Submitnabl / Cpri / Erda Accrediatedlab Type Test Certificate Before Execution. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 150 1.0 Hp, 1-Ø, ( 7 -12 ) Mtr, ( 405- 240 ) Lpm 151 Sitc Of Monoblock Motor Pump Set Isi Marked ( Is:9079-2002 ) With Tefc Motor, Motor Should Be Ie2 Class As Per Iec 60034-2-1: 2007, Iec 60034-30: 2008, & Is12615:2011. With Stainless Steel Impellor, Stainless Steel Shaft, Mechanical Seal, Single / Three Phase ( 240 - 440 V ) Permanent Split Capacitor Type ( Psc ) , Fitted With Thermal Overload Protection, Including Cost Of Hardware Etc On Existing Platform Complete. Pump Shall Have Following Hp Rating, Phase, Head, Minimum Discharge Respectively Complete In All Respect. Oem Shall Have Submitnabl / Cpri / Erda Accrediatedlab Type Test Certificate Before Execution. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 152 1.0 Hp, 1-Ø, ( 10-120 ) Mtr, ( 30-12 ) Lpm 153 Supply , Installation, Testing And Comissioning Ofinverter Type Air Cooled Hi Wall Split Type Air Conditioners With Latest Star Rating System As Per Bee Amended Upto Date Complete With Indoor Unit ( Idu ) , Out Door Unit ( Odu ) , Surface / Concealed Copper Refrigerant Piping With Insulation ( Closed Cell Elastomeric Nitrile Rubber Tubular Pipe Section ) Upto 3 Mtr ( Idu To Odu ) , Copper Power Cable Upto 3.5 Mtr ( Idu To Odu ) , R-32 / R-410 Green Refrigerant, Wireless Remote Control, Suitable For Working Between 230V + / - 10% With Low & High Voltage Cutoff And50 Hz , Single Phaseacsupply Capable Of Performing Cooling, Dehumidification, Air Circulation Of Following Capacity With Scroll / Rotary Compressor. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 154 1.5 Tr Iseer Not Less Then 3.8 155 Providing & Fixing Of Is : 4985 - 2000 Class -4 ( 10 Kgf / Sqcm ) Upvc Drain Water Piping Withfittings ( Is:7834 & 10Kgf / Sqcm ) Like Elbow, Socket, Tee, Solvent Cement Jointing, Support With Ms Hanger On Ceiling Or Recessed In Wallwith Chasing & Plastering With 6 Mmthickclosedcellelastomeric Nitrile Rubberinsulation Including Leakage Testing Etc. As Required Of Following Nominal Sizes. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 156 25 Mm 157 Supply, Fixing And Testing Of Following Capacity Iso Certified Company Made Wall Mounted Stabilizer Having Output Voltage Variation From 200 V To 250 V ( + / -5% ) With Input Voltage Variation From 170 V To 260 V, Time Delay Facility From 2 To 4 Minute And High Cutoff At 270 V With Providing Of 16 Amp / 20 Amp Industrialplug Top Making Connection Etc Complete In All Respect.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 158 4 Kva 159 Making Hole In Stone Masonary / Rcc Wall / Rcc Slab With Core Cutter For Accomodating Refrigerant Pipe / Drain Pipe / Ms Pipe / Cables Etc Of Following Dia 160 150 Mm Dia Per Running Inch Length 161 Supply & Fixing Ms Powder Coated Stand Suitable For 1.0 / 1.5 / 2.0 Tr Outdoor Type Of Split Ac.All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr . 162 Supply & Fixing Of Dry Powder Agent ( As Per Is 4308:2019 ) , Abc Typefire Extinguisher ( Stored Pressure Type ) Conforming To Is:15683:2018 , Powder Coated Internal & External Surface Deep Drawn Cylinder Body Of Mild Steel Cr2 Grade Conforming To Is: 513, Squeeze Grip Forged Brass Release Valve With Inbuilt Safety Release Device, Diaphragm Type, 0 To 28 Bar Range Pressure Gauge, 450 Mm Long Epdm Discharge Tube, Qr Code For Product Traceability Including Fixing On Wall With Suitable Anchor Fasteners As Required Of Following Capacity. Test Certificates Of All The Parameters Along With Hydro Test & Burst Test ( For Cylinder Body ) Certificatefrom Oem / External Nabl Accrediated Lab Is To Be Submitted. All As Per Pre Approved By Engineer In Charge.For Additional Technical Parameters Of Products / Work, Refer Annexure A Attached With This Bsr .

Key Value

Document Fees
INR 500 /-
EMD
INR 20200.0 /-
Tender Value
INR 10.10 Lakhs /-

BOQ Items

Name of Work: Electrical work in the construction of PHC Building at Basai Jogiyan (Thangagazi) Distt. Alwar
Sl. No. Item Description
1ELECTRIC WORK
2Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)inrecessed ISI marked MMS ( IS:9537 P - III ) virgin material PVC conduit & it"sISI marked (IS:3419-1988) accessories, round tiles, 1.2 mm thickHot Dipped Galvanized Modular Box with earth terminal, 10A Modular switch,Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
3Short point (up to 3 mtr.)
4Medium point (up to 6 mtr.)
5Long point(up to 10 mtr.)
6Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694)in recessed ISI markedMMS ( IS:9537 P - III ) PVC conduit & it"s ISI marked (IS:3419-1988) accessories, round tiles, 2 Nos Hot Dipped Galvanized M.S Modularbox of 1.2 mm thickwith earth terminal,2 Nos10 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate,screws,making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
7Medium point (up to 6 mtr.)
8Long point(up to 10 mtr.)
9Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal sizeFR PVC insulated unsheathed flexible copper conductor 1.1 kV gradeand 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) inrecessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it"s ISI marked (IS:3419-1988)accessories, Hot Dipped GalvanizedModular box of 1.2 mm thick with earth terminal, 10 A modularswitch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.For specification of copperConductor,Phenolic Laminated sheet"s & Electrical/ Wiring accessories refer Chapter E - 04, E - 05 & E - 07 For additional technical parameters of product / work refer Annexure "A" attached with this BSR
10On board
11S&F following sizes (dia.) of ISI marked virgin material MMS ( IS:9537 P - III ) PVC conduit along withISI marked (IS:3419-1988) accessories as requiredinrecessincludingcutting the wall, covering conduit and making good the same as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
1220 mm
1325 mm
1432 mm
15Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor as per PWD specification for electrical Works with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from99.90 % purity copper, class 5 stranding in acc. to IS:8130/IEC 60228 forlower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5,in existingsurface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for wires. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
161 x 1.5 sq.mm
173x 1.5 sq.mm
182 x 2.5 sq. mm. + 1x1.5sqmm
192 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
204 x 10.0 sq.mm
214 x 6.0 sq.mm
221 x 4.0 sq.mm
231 x 2.5 sq.mm
242 x 6.0 sq. mm. + 1 x 2.5 sq. mm.
25Supplying and drawing PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 &confirming to TEC specification GR / WIR/06-03 March 2002in existingsurface or recessed conduit/casing capping. including ferruling on each pair for Identification etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
262 pair
27P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and two coats enamel paint including cutting, welding, holes etc.of following sizes as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
2840mm x 40mm x 5mm
29P & F paper phenolic resin bondedlaminates confirming to IS : 2036 -1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc platednut and bolts as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
306.4 mm thick
31P & F phenolic laminated sheet 2.0 mm thick of following size . Including screws, cup washer as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
3275 mm dia
33Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load andsite requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanisum , energy limiting ofclass 3 as per IEC,minimum phase termination capacity of 35sq.mm. , conductor line load reversibility , IP 20 contact protection and fitted inexisting distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating and 10,000 upto 63 A, 5000 for 80 A & above ratingincluding making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
34Single pole MCB (With B/C curve tripping Characteristics)
356 A to 32 A rating
36Double pole MCB(With B/C curve tripping Characteristics)
376 A to 32 A rating
38Four pole MCB (With B/C curve tripping Characteristics)
396 A to 32 A rating
4050/63 A rating
41Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door ( Metal / Glazed )Distribution board with Metal end box made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3, powder painted complete with reversible door (for double door DB only )100 amp.  insulated copper bus bar/shorting link , copper neutral link, copper earth link , color coded interconnecting wire set  of suitable rating and din bar,masking sheet,  making internal DB  terminations with copper lugs, Ferrules,  detachable gland plate, including making connections, testing etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test reports& All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
42Metal door (single phase) IK-09 and IP-43 with Metal end box
4316 Way (16+2)
44Metal door (Three phase) IK-09 and IP-43with Metal end box
456 Way
46P&F metal clad / Plastic industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet not less then 1.2 mm thick  conforming to IS-8623-1 & 3 /  IEC 61439- 1 & 3. powder painted (without MCB) including making connections, testing etc.as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
4720 amp, 3 pin + scrapping Earth, 4 Module
48P & F of Industrial plug and socket conforming to IEC 60309-1/2 made out of self extinguishing engineering polymer / polyamide, nickel plated brass sleeve and pins, socket with shutter including making connection etc as reqd. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
49IP -67 Panel mounted socket
5032 A 3 pin(2P+E)
51Providing & Fixing of flush typenon modular single line telephone jackmade out fromindustrial grade Polycarbonate or fire resistant ABS material, including making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
52Providing & Fixing of ding dong/musical chime bell as per PWD specification for electrical Works, including making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
53Providing & Fixing of modular type 120 W Step Fan regulator duly ISI marked (IS 11037:1984 ) with CM/L no. printedmade out of unbreakable and fire retardant vergin poly carbonate with brass terminals and captive screws & silver alloy contact tipwith IP-20 rating ,includingall as per pre approved by Engineer in charge,making connections, testing etc. as required.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
545 step fan regulator 2 Module 360 dgree rotating
55Supplying and fixing of power plug point with Modular accessories as per PWD specification for electrical Works, on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost ofISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. For specification ofWiring accessories refer ChapterE - 07related item & For additional technical parameters of product / work refer Annexure "A" attached with this BSR
56P & F Krone module with base framein the recess / surface made out of 1.2 mm thicksheet steel box, front openable, having locking arrangements duly powder painted,including dressing, ferrulingandpunchingof telephone cable with krone tool etc. as required. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
5710 Pairs
58SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel as specifications andOther parameters requiredas per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
59(a)Thickness of CRCA sheet shallbe 2.0 mm,cable alley compartments having concealed hinged type doors with key type lock with / withoutdetachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
60(b)complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting,pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side of panel.The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
61[c)Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar(>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only.All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar/ Flexible wire for Interconnection between Main busbar and Switchgearis to be Paid Extra )
62(d)Wiring between components within switchgear and Incoming / outgoing cableshall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
63(e)All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
64(f)Floor mounted panel shall be mounted on Base frame of ISMCchannel size 100 x 50 x 5 mm( to be paid Extra )
65(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
66(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI Test certificates to be submitted)All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
67Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulatorwith standard short circuit withstand capacity, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
68Electrolytic grade Aluminium bus bar 6010 grade
69Providing & Fixing of BIS approvedCurrent Transformeras per PWD specification for electrical Works ,ISI marked as perIS 2705-1992/ conforming to IEC 60044-1, with secondary terminalof CT shall be brought out suitable to a terminal block which shall be easier accessible for testing and terminal connection , with all necessary support in existing panel including connection etc. as requiredCurrent transformer Ring Type Tape Wound/Resin Cast Wound as per IS 16227 with, Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . All as per pre approved by Engineer in charge.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
70Ring type tape wound CT
71C T Class 1, Ratio 200/5 to 300/5, Burden 10 VA
72Providing & Fixing of110/220 V, unibody LED Indicatinglamp IEC 60947with integral circuit, IP 65 above panel &IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min.29 mm, contact material phospher bronze for Led, PCB contacts shall be ofbrass (tin plated), impulsedielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDCincluding connection etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
73Red/yellow/Green colour
74Providing & Fixing of Electricalinsulating rubber matts as per PWD specification for electrical Works, ISI marked confirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
753.3 KV,class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms)
76SITC of3 /4pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant materialhaving following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with frontface and centralised adjustable, trip free mechanisum, true contact position indicator,line load interchangeability,designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation upto 55 degree and without derating upto 40 degree,pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage690 V.provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle , including making connectionsetc. as required.OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution All as per pre approved by Engineer in charge. For additional technical parameters of product / work refer Annexure "A" attached with this BSR
774 pole MCCB With Thermal Magnetic release
78125 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
79up to 100 Amp , 25 kA, adjustable O/L & adjustable S/C setting,
80Providing & Fixing of ISO certified company made on load change over switch, front handle operated, four pole 415 V as per PWD specificationfor electrical Works conforming to IS/lEC 60947-3 : 1999 including connections , testing etc. as required .in the following rating.Appropriate type test certificate / OEM test report shall be submitted .All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
81Open execution type
82160 A
83Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
8410.0 Sq. mm
852 core
8635.0 Sq. mm
873.5 core
88Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
893.5 x 35.0 sq.mm
90Supplying and makingend termination with heavy aluminiumlugs ( Pin / ring type )confirming to IS 8309 -1993 & IS 8337-1976 duly crimped with crimping tool, PVC tape etc of following size.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
9135.0 Sq.mm
92Supplyandinstallationofhigh tensile low carbon steel rod molecularly bonded with 99.9 % Copperthickness (250 microns) andconfirming toUL 467, IS/IEC 62561-2of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
93(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
94(b)filled with anti corrosiveconductivecompounds with the permanent sealings at both the ends, CPRI/ ERDAtested with RMS capacity of minimum 30 KA for withstanding 1 second .To ensure the moisture content and electrical conductivity, 25 kg for 2000 mm & 50 Kgs for 3000mm of resistance lowering earth enhancement material shall be used as a backfill compound. The compound shall be tested form NABL acredeated labfor lowresistivity ( less than 0.12 Ohm - meter ) & high conductivity in nature with carbon as a major contentas per referance of IS 3043-1987,IEEE 80-2013 (clause 14.5d) , IEEE 837 & IER 1956 with latest amendemnts
95© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
96(d) Place Heavy duty weather proof poly-propylene earth pit chamber with lockable Jam free lid suitable for safe working load 5000 Kg or more of size Top Dia. 225 to 260 mm, Bottom Dia 300 to 350 mm. and Height250 to 300 mm.
97(d)Testing of earth resistance for value of 5 ohms or lessas required & must record by engineer in charge during site visit and ensure to enter in measurment book.
98(e) Test certificatesfor confirming above standards from OEM is mandatory. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
9917.2 mm thick and 3 Mtr. Long
100Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles,making connection with GI/Cu purity purity >95%thimble etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1018 SWG copper Wire
1028 SWG G.I. ( Hot Dipped) Wire
103Making of hole in wall (brick/stone) of required and placing NP-2 RCC pipe ring of required size for housing exhaust fan and making good the same, with cement plaster required of following size. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
104Up to 457 mm size
105Providing & Fixing ofBEEStar rated copper wounded double ball bearing capacitor start, aluminium body & Metallicblade ceilingfanConforming to all the performance requirements laid down in IS 374:2019 including all amendments, as applicable ; & Carry BIS licensing (i.e. ISI marking) with down rod up to 80 cm with secondary support safety cable ( steel rope) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1061200 mm Sweep BEE 2 Star rated (service value >=4.5 to < 5 )
1071200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
108P & F 1.2mm thickM.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm,12 mm dia rod fan hook with 100 mmlength extended on each side . All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
109P & F 1.2mm thickM.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm,12 mm dia rod fan hook with 100 mmlength extended on each side . All as per pre approved by Engineer in charge.For additional technical parameters of product / work refer Annexure "A" attached with this BSR
110Providing & Fixing ofof Double ball bearing, copper wounded capacitor startsingle phase metallicblade fresh air fan, in existing opening including cost of hardware , flexible 3 core copper conductor ,making connections, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
111225 mm sweep
112Providing & Fixing of Heavy duty capacitor start, copper woundDouble ball bearing900/1400 RPM single phaseExhaustfan conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
113300 mm sweep(900/1400 RPM)
114Providing & Fixing of Wall mounting / Pedestal type Heavy duty Air Circulator , Double ball bearing and with metal sturdy mesh guard; Aluminium alloy one piece blade and conforming to IS:2997, including fixing with anchor bolts,making connection testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
115450 mm sweep Wall mounting and three speed regulator with Minimum Air Delivery 150 Cum. / Minute
116P & F of Gravity Louver shutter of superior quality made out of frame of18 swg M.S. sheet & Louvers made from 24 swg MS Sheetwith enamel paint including cost of nuts, bolts, etc as reqd.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
117Up to 380 mm size
118Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap actionadjustable thermostat , Dual indicating lampsInjected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top with Portable Residual Current Device ( PRCD ) , including making inlet, outlet Flexible alloyconnection, testing etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
11915 Ltr.
120SITC ofMNRE approved & confirming to IS:12933 P-1,2,3 & 5 Flat Plate Collector type solar hot water system havingcollector withZincalum sheet outer body ,Glass - line / Titanium Enamel coated Inner tank with Metal rust proof PUF insulated Body includingelectrical back up, Thermostat, Powder coated / Hot dipped galvanized MS standfor Collector & Tank etc. as required. of following capacity complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
121200 litre/ day
122Providing & Fixing of energy efficient direct fit (Retrofit)Polycarbonate/ GlasshousingSMD Mid Power LED tube rod(with integral driver & alumn. heat sink ), on existing fixture.system lumen efficacy = 100 lm/Watt output, internal surge protection of 2.5 KV ,THD < 20% ,p.f.=0.95,CRI >80 , life time of minimum35000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80)certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1231200mm , Min. Lumens output 2000 lmLED Tube rod with Polycarbonate Housing
124Providing & Fixing of IP-20 LED Recessed / Surface Mounted, Round / SqaureSMD Mid Power LED Downlight with power coated die-cast aluminum housingwith UV Stabilized non yellowish Diffuser withBIS complience 2.5 KV surge protected Isolated driver, with Short & Open circuit protection, having efficiency > 85% . System Lumen efficacy of = 110 lm / watt, THD < 10 % , Pf.=0.95, CRI >80,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing.
125OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
126Surface Mounting (with extruded alumn. Housing )
127Minimum lumen output 1950 lm
128Providing & Fixing of IP20, 2"x2" LED Surface/ Recessedmounting Mid power SMD type LED Light fixture not less than 50mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 4 KV internal/external surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection(Integral with light fixture). System lumen efficacy of = 120 lm/Watt ,THD < 10 % , p.f.=0.95,CRI >80 ,life time of minimum50000 Burning Hours with , 70% of intial Lumen maintaned till life ends, CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be ofBIS standard andtrade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing onhousing.
129OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. (LM79 & LM80) certificate / Report from OEM shall be submitted.All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
130Recessed Mounting
131Minimum lumen output 4200 lm
132Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminummaterial with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass coverand secondary lens on each LED & should be SMD type of 3 to 5 watt each . The System efficacy >=125 lm/ wt and potted driver& has a unique BIS R number withInput Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety , Power Factor >0.95 driverEfficiency >85%,THD(I) <10%Humidity 10% to 90% RH Working Temp -5C to 45C .driver current <750mA. The luminaireshall be BIS certified and Trade mark certified. Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min = 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs.Manufactures Word Mark/Name Engraved/Embossing on die cast housing to allow traceability/authenticity. Fixture shall be AS PER IS 10322 Complianced.OEM Must have its own in house NABL lab setup for all testing facilities forLED fixtures.(LM79/LM80) Certificate/ report with liable warranty of product/accessories from OEM shall be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
133LED Street Light fixture with Minimum lumen output 2450 lm
134Providing & Fixing of Street light bracket made out from following size of " B " class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
13525 mm Dia.
136Supply, Drawing and Testing of 4 pair, 23 AWG Solid Bare Copper wire insulated with PVC, UTP (Unshielded Twisted Pair), Category 6, Class E, 100 Ohm Impedance, Indoor Cable as per latest ammendments of ANSI/TIA/EIA-568 , The copper conductors should be balanced twisted in pairs, seperated by a cross-member fluted pair divider & protected byPVC Jacket. Certified performance in a 4-connector configuration upto 100 Mtrs channel requirements & transmission frequencies up to 250 Mhz. in existing MS/PVC Conduits/casing capping including making connections to Information outlets and Patch Panels with jack &ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing etc as required complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
137Supply and Installation of unsheilded/360 degree sheilded Information outlets made of high impact plastic body with ABS, FR Grade halogen free material with provision for protection against dust in jack, suitable for Cat 6/6A application complying to latest ammendments, According. to Cat. 6/6A channel, It should support channel as well as components requirements of Cat.6/6A standards at frequencies of up to 250 to 500 Mhz. Cat 6/6A unshielded/shielded Jack should be suitable to terminate 4 pair, 23/24 AWG solid/stranded wire diameters, using 100 Ohm unshielded/shielded balance twisted pair cable, the jack should have tooless/impact termination on reliable copper tin plated Insulation displacement contact, with easy lock mechanism, It supports IEC 60603-7-4 and complied with ANSI/TIA/EIA 568 C.2 standard. jack should be RJ11,RJ12 & RJ45 compatible. Should support Ethernet 1.2 Gb/s ATM,Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP) Specifications in existing modular/MS Boxes along with necessory connections as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
138Cat 6, Un-sheilded Information Outlet
139Supply & fixing of square Faceplate for Flush / Surface Mount Information Outlets Single/Dual or Quad Aperture ,material should bePC+ABS body, Suitable for RJ45 unshielded/shielded connection modules. Should match with I. O. OEM. Dimensions should be 86mm X 86mm as required complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
140Single Aperture
141Supply , Installation and Testing of 4 pair, 100 Ohm impedance, Cat 6/6A /Class E/Ea patch cords should be constructed of minimum 23/24 AWG, stranded bare Copper cable with FRPVC/LSZH Jacket, with an enhanced performance by factory moulded RJ45 connectors with strain relief boots as per ANSI/TIA/EIA 568-C.2 suitable for Cat 6/6A application complying to latest ammendments Category 6/6A Standards, According. to TIA568C.2, ISO/IEC 11801, EN 50173, IEC 60603-7-51, EN 60603-7, IEEE 802.3an minimum requirement for 1G BASE-T to 10G BASE-T performance. Patch cords shall be straight thru cable compatible with both T568-A and T568-B wiring schemes, should support IEEE 802.3af / IEEE 802.3at for POE applications, Minimum 750 to 1000 mating cycles in plug contacts for long durability, Should support Ethernet 10GBASE-T, 1.2 Gb/s ATM, Token ring 4/16, Digital video and broadband/baseband analog video, Voice over internet protocal (VOIP).All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
142Cat 6, U/UTP (Unscreened/Un-sheilded Twisted Pair) Patch Cord
1431 Mtr
144Supply, Installation, & Testing of 19" 1U Rack Mounted/ surface mounted aluminum/ CRCA 1.2mm powder coated, multimode glass Fiber Optic Cable Patch panel/LIU loaded with flangless/screwable adapters for ST/E-2000/SC/LC/MT-RJ/PC type, It should have easy removable Top plate with push buttons, there should be a splice tray installed in the Patch panel/LIU which can handle the fiber cores, splice tray should be PC+ABS material, it should include accessories like mounting hardware, gormetts, heat shrink tubes/sleevs, screws, nuts to install the panel for rack/wallmount applications as per requirement complete in all respect. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
145Multi Mode LIU 12 Ports
146Supply & Installation of IP-20 & IK-08 , UL ListedWall mounted Double Section Communication enclosure (Rack) made from powder coated (60 to 80 Micron) CRCA sheet, front sturdy sheet steel frame folded from one piece and welded with minimum 5mm toughened glass door,Vertical Mounting Rail 1.6 MM with "U"Marking , with All round protective channel on the door aperture, lock integrated on front door, top and bottom cover with cable entry provision with gland plates, integrated side walls, 2 pair of 19" angles with wall mounting provision on wall. Accessories like: 1 No of 19" 1U Horizontal Cable manager, 1 No of 90 cfm 230V AC Fan with 1 mts long cable, mounting hardware , 1 No of 19" 1U, mountable socket strips with 5 nos of 5A universal sockets with 2 mts long power chord for supplying power to switches, fans etc along with earth continuity kit, indicator, moulded power supply cable. fixing on wall with Suitable Anchor fastneretc as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1476 U Rack with Width 600 mm &Depth 400 mm + 100 mm
148Supply , Installation, Testing and Comissioning ofManaged Layer-2 Intelligent 10/100 Ethernet Switch providing 24 x 10/100/1000 MBPS Giga Ethernet ports / with min 2 SFP Giga Ports (provision for Fiber Giga connectivity) with related LAN Base Software including making connections etc as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
149SITC of Single Stage, water cooled, High Speed (2880 RPM), Horizontal, Centrifugal, Openwell Submersible pumps set pre filled with coolent water and fitted with mechanical seal - T/C Vs T/C, Thrust bearing shall be ofcarbon + S.S.The stator body of single phase pumpshall be of SS and rest of all shall be of cast iron. All casting parts should be cathod electro deposition (CED) coated and other construction material should be confirming to IS : 14220: 2018 . The overall performance of pump shall confirm to BEE energy efficiency level of 3 star. Valid BEE certificate from OEM must be submitted for the same. Motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008,& IS12615:2011, including making connection etc as required complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1501.0 HP, 1-Ø, (7 -12) Mtr, (405- 240) LPM
151SITC of Monoblock motor pump set ISI marked (IS:9079-2002) with TEFC motor, motor should be IE2 class as per IEC 60034-2-1: 2007, IEC 60034-30: 2008,& IS12615:2011. with Stainless steel Impellor, Stainless steel shaft, Mechanical seal, Single/Three phase ( 240 - 440 V ) permanent split capacitor type (PSC), fitted with thermal overload protection, Including cost of hardware etc on existing platform complete. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively complete in all respect. OEM shall have submitNABL / CPRI / ERDA accrediatedlab type test certificate before execution. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1521.0 HP, 1-Ø, (10-120)Mtr, (30-12) LPM
153Supply , Installation, Testing and Comissioning ofInverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and50 hz , single phaseACsupply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1541.5 TR ISEER not less then 3.8
155Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping withfittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing,support with MS hanger on ceiling or recessed in wallwith chasing & plastering with 6 mmthickclosedcellelastomeric nitrile rubberinsulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
15625 mm
157Supply, Fixing and testing of following capacity ISO certified company made wall mounted stabilizer having output voltage variation from 200 V to 250 V(+/-5%) with input voltage variation from 170 V to 260 V, time delay facility from 2 to 4 minute and high cutoff at 270 V with providing of 16 Amp /20 Amp Industrialplug top making connection etc complete in all respect.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1584 kVA
159Making hole in stone masonary/ RCC wall/ RCC slab with core cutter for accomodating refrigerant pipe/ drain pipe/ MS pipe/ cables etc of following dia
160150 mm dia per running inch length
161Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
162Supply & Fixing of Dry Powder Agent (as per IS 4308:2019), ABC typeFire Extinguisher (Stored Pressure type) conforming to IS:15683:2018 , Powder coated Internal & External Surface Deep drawn cylinder body of Mild Steel CR2 grade conforming to IS: 513, Squeeze grip Forged brass release valve with Inbuilt safety release device, Diaphragm Type, 0 to 28 bar range pressure gauge, 450 mm long EPDM discharge tube, QR code for Product Traceability including Fixing on wall with suitable Anchor Fasteners as required of following capacity. Test Certificates of all the Parameters along with Hydro test & Burst test (For Cylinder Body) Certificatefrom OEM / External NABL Accrediated Lab is to be submitted. All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
1634 kg