}

Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2 X 6.3 Mva, 33/11 Kv Substation On Turnkey Basis At Manikpur Ocp, Korba Area, Secl, manikpur-Chhattisgarh

South Eastern Coalfields Limited-SECL has published Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2 X 6.3 Mva, 33/11 Kv Substation On Turnkey Basis At Manikpur Ocp, Korba Area, Secl. Submission Date for this Tender is 06-04-2023. Substation Tenders in manikpur Chhattisgarh. Bidders can get complete Tender details and download the document.




Tender Notice

36400255
Corrigendum : Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2 X 6.3 Mva, 33/11 Kv Substation On Turnkey Basis At Manikpur Ocp, Korba Area, Secl
Open Tender
Indian
Chhattisgarh
manikpur
06-04-2023

Tender Details

Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2 X 6.3 Mva, 33/11 Kv Substation On Turnkey Basis At Manikpur Ocp, Korba Area, Secl

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 04-Mar-2023 Independent External Monitor Other 06-04-2023

Key Value

Document Fees
Refer document
EMD
INR 1476400.0 /-
Tender Value
INR 11.81 Crore /-

BOQ Items

Name of the Work / Contract No:
Sl. No. Item Description
1DESIGN AND ENGINEERING COST(for2 X 6.3 MVA, 33/11 kV Substation)
2Design and Engg onPLANT & MACHINERY ( P&M - Electrical) to be supplied by bidder inlcusive of Overhead constuction cost, Contigencices, but excluding GST
3Design and Enggon Civil & Structural work
4CIVIL CONSTRUCTION AND STRUCTURAL WORKSfor 2 X 6.3 MVA, 33/11 kV Substation on Turnkey Basis at Manikpur inclusive of Insurance,Contingencie but excluding GST
5Sub-station Building
6Outdoor steel structures
7Foundation of outdoor structures including Transformer foundation
8Cable Trench
9Barbed wire fencing
10Boundary wall
11Gate
12Road
13Surface dressing
14Stone laying
15Anti weed treatment
16Bore well with submersible pump
17Path way
18Security Room
19RCC sump and Pump House
20Shed for DG & oil filter unit
21Drain along boundary wall
22Parking Shed
23Oil Overflow Chamber
24Oil Drain Pipe
25Survey & Soil testing
26SUPPLY OF PLANT & MACHINERY inclusive of Overhead Construction cost, Insurance, Contingencies, but excluding GST forsubstation ( 2 X 6.3 MVA, 33/11 kV Substation )
27Isolators, 33 kV (nominal),3 poles, pole mounted, 800A, suitable fault rating, arrangement for interlocking with 33 kV Vacuum Circuit breaker
28Isolators, 33 kV (nominal), 3 poles, pole mounted,800A, suitable fault rating, arrangement for interlocking with 33 kV Vacuum Circuit breaker withEarthing switch
29Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,suitable fault rating, arrangement for interlocking with 33 kV Vacuum Circuit breaker
30Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,suitable fault rating, arrangement for interlocking with 33 kV Vacuum Circuit breaker withEarthing switch
31Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,suitable fault rating,with D.O. Fuses.
32Lightning Arrestors, station class, 30 kV,10 kA, suitable for 33kV, solidly earthed (each set consists of 3 nos.) with counters/surge monitors
33Single phase current transformer ,outdoor type with required CT ratio for 33 kV system for metering and protection (1 set consists of 3 units for 3 phase supply)
34Potential transformer ,outdoor type 33kV, 100 VA each 33/v 3 kV/ 110/ v 3 Vfor metering and protection each for three phase system
35Vacuum Circuit Breaker, 33kV,630 A/1250A, outdoor type, 25 kAwith remote control panel having IDMTL relay for O/L and E/F protection,ammeter, energymeter
36Power Transformer outdoor type plinth mounted 33/11kV, 6.3 MVA, ONAN cooled, DY-11 conforming to IS:2026 (current) having OFF-LOAD tap changer on HV side and LV neutral effectively earthed through required value of Resistance ( Restricted Neutral System) with all accessories including 33 kV remote control panel for on load tap changer as per IS:3639 (Current) with the rating as given below Rated kVA: 6300 Rated Voltage(primary):33000V Rated Voltage(secondary):11000V Connection and vector group:Dy11
37Neutral Grounding Resistors with Protection
3811 kV switch-board, indoor type, 18 panel, with vacuum circuit breakers 350 MVA symmetrical breaking capacity. The function of eachpanel is as given below: All panels will conform to IS:3427 (Current) and relevant parts to IS:2516 ( current). These will be provided with cable entry boxes. The incoming panels will be provided with restricted earth fault protection. All panels will be provided with IDMTL relays for over current and earth fault protection. The incoming and outgoing panels shall be provided with Trivector meters.
39Station Transformer,outdoor typerated as follows: Rated kVA: 160 Rated Voltage(primary):33000 V Rated Voltage(secondary):433 V, Cu wound , Plinth mounted
40Lighting Transformer,outdoor typerated as follows Rated kVA: 100 Rated Voltage(primary):33000 V Rated Voltage(secondary):230V(L-L) , plinth mounted
41415V switch board, indoor type with 4 nos MCCB having O/L,S/C and E/Lprotection, 25 MVA symmetrical breaking capacity (All out going panels will be provided with ammeter, and incoming panel with ammeter and voltmeter). The function of panels will be as follows : - 1 no, required rating MCCB, required CTR , as controller for incoming feeder. - 3 nos, required rating MCCBs, required rating CTR, as controller for outgoing feeders.
42230 V (L-L) Main Lighting Distribution boards with the following : "--1no. MCCB, 3 pole,req.amps for control of incoming feeder. "-3 nos.,MCBs, 2 pole,req.amps for control of out going feeders. "-3 nos.,MCBs, 2 pole, req.amps for control of out going feeders.
43Capacitor bank, 11 kV indoor type 1440 kVAR including APFC.
44Battery (110 V) lead Acid type, 200 AH and battery charging (with one stand bye battery charging unit) equipment, control panels, wooden racks including DCDB etc.
45Earthing system (Safe Earth Electrode type) including earth pits, required galvanised strips/flats,MS Rod for inter connection etc.
46Lightning protection system consisting of spikes, earth pits, galvanised strips/flats, shield conductors etc.
47Luminaries
48Decorative, LED (Suitable rating) light fittings
49Suitable rating LED Bulbs for indoor lighting
50Tubular steel poles,11m height along with 90 W LED lamps with fittings ( minimum 7 nos.)
51Lighting masts, 16m height (Min) along with required nos. of 200 W LED lamps with fittings.(min. one number)
5290 W LED fitted on substation building(in. 4 nos.)
53Emergency lighting system suitable for operation on 110 V DC supply in substation building.
54Accessories such as sub distribution board, junction boxes,individual control cables, PVC conduits/ casings, back up fuses, switches, sockets, ceiling roses, single core PVC cable with copper conductors, flexible wire etc.
55Cable and accessories
56HT power cable, 11000 V grade, XLPE, FRLS, Copper conductor
57LT Power cable, 1100V grade, PVCSWA, 10 sq. mm.(minimum),3/4 core copper stranded conductors
58Outdoor Lighting cable, 1100V, PVCSWA , 2 cores, 10 sq mm (minimum) stranded Al conductors
59Outdoor Control cables, 1100V grade, PVCSWA, not less than 2.5 sq mm , copper conductors of with required number of cores
60Wires for internal wiring of 1.5 sq mm and 6 sq mm size, PVC insulated copper conductor cable of 1100 V grade.
61Cables for internal control wiring of illumination, ceiling fans, power sockets etc. 2.5 sq mm size, PVC insulated copper conductor of 1100 V grade
62Cable trays, cable racks, binding materials, cable glands/lugs, cablejointing kit, bolts, nuts, washers, termination kit etc.
63Overhead conductors,Insulators,Towers, poles, insulators, string bus, ACSR conductors, steel hardware etc for 33 kV sides in the out door yard. 2 pole structure fitted with gang operated AB switch, lightning arrester etc for out going feeders
64Fire Fighting System
65Fire fighting equipment consisting of fire hydrants hose cabinets, hose reels, valves, pipes,fire detection alarming system, Nitrogen injection fire prevention system for power transformers,diesel pump, electric pump with electricals and cables , jockey pump etc
66Supply of portable fire extinguisher system
67Sand buckets with stand
68Miscellaneous items
69Room air conditioners, min. 1.5 t capacity( 5 star rating inverter compressor type ) including servo stabilizer
70Supply of 63/62.5 kVA Diesel Generator set (silent type) with 3 ph, 50 Hz ,415 V output supply with cable, change over switch and earthing etc
71Exhaust fans, 600 mm sweep.
72BLDC Ceiling fan ,1200 mm sweep along with electronic regulator (5 star rating)
73Water cooler with water purifier
74Vacuum Cleaner Set
75LOTO station system/kit-1 no. , Electrical Layout/Single Line Diagram Board , Electrical shock treatment Chart , Do"s & Don’t Chart , Earth pit connection diagram with retro refractive radium type display , Danger plates , Furniture & fittings and insulating mat etc
76Erection and commissioning of Plant and Machinary for substation to be suplied by bidder as above inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST
77Training of O&M staff
78Store cost for maintenance of P&Mduring Defect Liability Period (DLP) of five years.
79Cost of Maintenace during during Defect Liability Period (DLP) of five years.
80Total impact of GST for the purpose of CTC
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail