| 1 | Supplying all labour T&P for earth work in excavation of foundation & plinth with 50m. Initial lead and 1.50m lift in all kinds of soil including rough dressing and breaking the clods to maximum 5 cm. to 7 cm. and laying inlayers not exceeding of 0.30m.depth as per instruction of E.I.C. |
| 2 | Pipe Laying:-Supplying all materials, labour and T&P for Layingin trenches Centrifugally Cast (Spun) Ductile Iron pressure, socket and spigot pipes Class K9 without cement mortar lining conforming to IS:8329 - 2000 of the following nominal diameter as per specification complete. (Earthwork in trenches, jointing of pipes, specials and fittings to be measured and paid for separately) (including cost of pipe) |
| 3 | 150 mm dia K-9 D I pipe forRising main |
| 4 | 400 mm dia K-9 D I pipe forRising main |
| 5 | Supplying all materials labour T & P for Providing Push-on-Joints confirming to IS: 3114 to centrifugally (Spun)cast Iron Pipes or Ductlle Iron pipes using rubber gasket conforming to IS:5382 of Styrene Butadene Rubber (S.B.R) quality, testing of joints, etc, a complete as per specification and direction of Engineer-in-Charge including supplying of all labour, material, tools & plants required to perform the work. (Excluding cost of Rubber ring) |
| 6 | 150 mm dia |
| 7 | 400 mm dia |
| 8 | Supplying all labour and T&P for providing and laying MS pipe and specials confirming to IS 3589/99 of quality grade FE 410/ GI Pipe (Medium ) confirming to specificationof following nominal dia and including transportation of pipes and fitting to site etc all complete as per the direction of E.I.C.& direction of EIC. |
| 9 | 150 mm dia MS pipe line |
| 10 | 400 mm dia MS pipe line |
| 11 | Supplying & Fixing of cast ironDI Resilient Seated Glandless Gate Valve of RATING PN - 1.60(IS 14846/2000) with double flanged ends (with wheel)for water works purpose for the following rating & nominal diameters but (including cost of Sluice Valves) of reputed make (Vag/ Tallis/ AVK). |
| 12 | 150 mm dia Sluice valve |
| 13 | 400 mm dia Sluice valve |
| 14 | Supplying & Fixing of cast ironDI Resilient Seated Glandless Gate Valve of RATING PN - 1.60(IS 14846/2000) with double flanged ends (with wheel)for water works purpose for the following rating & nominal diameters but (including cost of Sluice Valves) of reputed make (Vag/ Tallis/ AVK).150mm dia non return valve |
| 15 | Supplying all materials Labour& T & Pfor Fixing of Tamper proof Air Valvefor water works purposes conforming to IS specification for the followingnominal diameters as per specificationcomplete including cost of Air valve .(Vag/ Tallis/ AVK/ Bermad/Dorot make )Rating,PN-1.0(150 mm dia Air valve) |
| 16 | Supplying all materials labour T&P for fitting fixing ofwater meter (Bulky type) for water work purpose of following rating& nominal diameter as per specification & direction of E I C including transportation of all materials to site all complete including cost of water meter ,nut, bolt & rubber insertion etc Confirming to IS: 2373-1981(.(Brass/GM Horizontal check/ Non return valve (ISI Mark (a)150 mm diawater meter |
| 17 | Supplying all materials labour T & P for Providing C.I./D.I specials conforming to I.S.-9523:2000 of the rrquired diameter as per P.H. specifications including carriage of materials from store to work site etc complete.(excluding earth work in excavation,jointing and including cost of specials) |
| 18 | 150 mm dia |
| 19 | 400 mm dia |
| 20 | Supplying all materials labour T&P for cutting bituminous / asphalt road for taking pipe line across the road& road crossing including mending good the damages as per specification & direction of E I C. |
| 21 | Supplying all materials labour T&P formending good the damages of BT road with provision of earth work excavation, sand filling, C C(1:4:8) with 40 mm size CBHG metal, CC (1:2:4) with 12 mm size CBHG chips incuding watering curing refilling the earth all complete as per direction of EIC. |
| 22 | Supplying all materials labour T&P for construction of Sluice valve/N R valve/Water meter chamber of inside size 0.90x 0.90x1.20mtr with provision of earth work excavation, sand filling, C C(1:4:8) with 40 mm size CBHGmetal, B W with fly ash brick in CM(1:4),CC (1:2:4) with 12 mm size CBHG chips for roof slab,12 mm thick CP(1:4)including watering curing refilling the earth all complete as per direction of EIC. a)Chamber in side size 0.90x0.90x1.20mtr |
| 23 | Labour charges for refilling the excavated trenches with excavated earth after laying ofPVC pipe including watering and ramming etc.complete |
| 24 | Design,construction,Testing & commissioning of following capacity RCC Under Ground Clear water storage reservoir with provision of Suction and delivery piping arrangement with over flow, washout,Water level indicator etc all complete as per direction of EIC. |
| 25 | Design,Construction of RCC frame structure pump house with RCC roof ( inside size 4.00mx5.00mtr)for installation of Centrifugal pump sets and control panel all complete as per specification &direction of EIC. |
| 26 | Supplying all materials labour T&P providing Earth work excavation in all kinds of soil within1.50mtr initial lift and50mtrs initial lead and including levelling dressingetc all complete as per direction of Engr-In-Charge. |
| 27 | Supplying all materials, labour and T&P for filling approved SAND of specified quality under floors, in foundations, plinths, etc. for all depths and heights including cost of sand,royalties, transportation to site for all leads and lifts,including loading, unloading, spreading in layers of loose thickness not exceeding 150mm, watering,ramming, compacting with mechanical compactors and/or other equipment to the specified levels to achive 85% relative density as per IS:2720 Part XIV,including preparation of subgrade to the required slope,providing testing apparatus and testing the degree of compaction all complete as per drawings, specifications and direction of Engineer-incharge.The rates shall be inclusive of the cost of all labour,material,equipments etc. |
| 28 | Supplying all labour, material, tools & plants for Providing and laying PLAIN CEMENT CONCRETE of following mix proportion with course aggregate (crusher broken hard Granite metal), size as specified, for all works from 3.5m above ground level to 1.5m below ground levelin any shape, position, thickness, finishing the top surface rough or smooth, tamping, ramming, vibrating, curing etc. all complete,including cost of all materials, taxes,labour, lead,transportation of concrete,T & P , but excluding cost of shuttering work, all completeas per specification and direction by Engineer In-Charge for 1:3:6 (1 Cement : 3 coarse sand : 6 crusher broken granite Metal40mmsize). |
| 29 | Cement concrete (1:1.5:3) for R.C.C. works with 12mm size hard granite chips including hoisting and laying with centering and shuttering etc. complete as per direction of Engineer in charge. |
| 30 | RCC F&P,footings ,bases of column & mass concrete |
| 31 | RCC wall |
| 32 | RCCgrade beam Plinth bend |
| 33 | RCC lintels |
| 34 | RCC Roof & Chajja |
| 35 | Supplying all labour, materials and T&P for providing Fly ashwork in C.M (1:6) in superstructure using Fly ash bricksof size 25x12x8cm having C.S not less than 75kg/cm2 including all complete as per direction of Engineer in charge. |
| 36 | M.S. Reinforcement for R.C.C. works including cutting,bending, binding and tying grills and placing in position including cost of M.S.Rods,binding wire 18 to 20 gauge. |
| 37 | Supplying all materials labour & T & P for 12mm. thick cement plaster (1:4)with punning & bitumen painting over top of walla) |
| 38 | Supplying all materials labour & T & P for 16mm. thick cement plaster in cement mortar (1:6) for brick workincluding curing scafolding etc. complete. |
| 39 | Fixing Tiles in floors or steps & landing on 25mm. thick bed of cement mortar (1:1) jointed with neat cement slurry mixed with pigment to match the shades of the tiles all complete |
| 40 | Fixing Tiles to dados skirting & risers of steps on 12mm. thick C.P (1:3) jointed with neat cement slurry mixed with pigments to match the shade of tiles all complete with & without cost of precast tiles. |
| 41 | Supplying all materials labour T&P for providing fitting& fixing of M.S door & window with framegrill with all hinges & cleats including all cost carriage taxes complete. |
| 42 | Supplying all labour, materials, T & P & painting two coats with approved enamel paint and one coat primer on iron work including cost of paint etc. all complete as per direction of Engineer-in-charge. |
| 43 | Finishing walls with 2 coat weather coatpaints on outer plastered surface over a coat of primerof approved shade on newworkto give an even shade including cost of the paint primer etc. complete . |
| 44 | Supplying all materials, labor, T&P for Painting two coats with weather painting of exteriors made of Asian Paint of approved shade including all cost, carriage, taxes etc. complete. |
| 45 | Filling in foundation and plinth with the excavated materials and earth including watering, ramming all complete. |
| 46 | Supply installation testing & commissioning of centrifugal pump sets having discharge of 23lps at a head of 50mtr including stand bye with suction & delivery piping arrangement valves & excluding electrical control paneletc all complete as per specification & direction of EIC. |
| 47 | Supply & installation testing & commissioning of electric driven pumpstarter with 03position selection (with auto switch) automatic panel board (star delta) of any reputedmake suitable for running 20HP three phase pump set with provision of contactor, over load rely,single phase preventer, short circuit preventerwith internal wiring all complete as per specification & direction of EIC. |
| 48 | Recessed / Surface wiring to light point / fan point /Exhaust fan point /call bell point with 1.5 sqmm FR PVC insulated single core multi strand copper conductor of ISI marked with 20 mm dia non-m , MS box with 1.5 sqmm FR PVC insulated single core multistrand copper conductor as earth wire including all accessories and connection (Make of wire -Finolex/L&T/Anchor/Havells/V-Guard) |
| 49 | Short Point - |
| 50 | Medium Point - |
| 51 | Recessed /Surface extra lead submain wiring along earth wire with the following sizes of PVC insulated single core multistrand copper conductor ISI marked confirming to IS-694 /1990 in 20mm dia non metalic heavy duty flexible conduit 1.6 mm in surface / recessed PVC conduit as required (Make of wire -Finolex/L&T/Anchor/Havells/V-Guard) |
| 52 | 2 x1.50 sqmm + 1 x 1.5 sqmm - |
| 53 | 2 x2.50 sqmm + 1 x 1.5 sqmm - |
| 54 | Recessed / Surface wiring to 5 A /6 Amp socket outlet with 2 x 1.50 sqmm FR PVC insulated single core multistrand copper conductor of ISI marked in recess 20 mm dia non metalic PVC flexible MS box and earthing point with 1x 1.50 sqmm FR PVC insulated single core multistrand copper conductor for loop earthing etc. as required . (Make of wire -Finolex/L&T/Anchor/Havells/V-Guard) Separate. |
| 55 | Supply and fixing of 5 Amp plug with switch on existing board(Piano Type) |
| 56 | Separate |
| 57 | Supply and fixing of metal box of 180mm x 100mm x 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing of 6 pin 5/6 & 15/16 Amp socket outlet and 15/16 Amp piano type switches connection painting etc. as required (Make - anchor /Cona) |
| 58 | Supply and fixing of following way single pole and neutral, sheet steel, MCB distribution board consumer unit, 240 V on surface / recess, complete with tinned copper bus bar, neutral bus bar,earth bar, din bar, hinged front acrylic covr for the MCB knobs detachable gland plate,interconnections, phosphatized and powder painted including earthing etc. as required ( But with out MCB / RCCB / Isolator) |
| 59 | 2 + 4 WAY |
| 60 | Supply ,fitting & fixing of 32 amp MCB (HPL / L&T /C &S / SEIMENS / RK /ANCHOR / HAVELS) |
| 61 | Supply ,fitting and fixing of the following fixtures on existing board / cover and connection as required.(Make - Anchor /Cona ) |
| 62 | Angle Holder - |
| 63 | Ceiling Rose - |
| 64 | Supplying fitting and fixing of Bulk head fittings and making connection as required .(Make - Bajaj / Philps ) |
| 65 | Supply and fixing of fan (make - Usha/Orient/V-guard/Khaitan/Havells/Crompton/Almonard) |
| 66 | AC Ceiling Fan 48\" |
| 67 | Supply and fixing of electronic Fan Regulators ((make - Bajaj/Philips/Crompton/PAC) |
| 68 | Supply and fixing of different type of fittings with lamp. |
| 69 | 27 Watt CFL Bulb(Integrated lamp )Tarnado Philps(Bajaj/Philips/Crompton/PAC) |
| 70 | Supplying fitting & fixing of Electric 200mm Exhaust Fan (Havells Ventilair DX) |
| 71 | Supplying installation testing & Commissioning of copper earthing pit complete with 2 mtrs 50m dia G.I.Perfarated earth electrode with G.I.Flange complete with inspection chmber and cover with painting and back filling with salt,charcoal and good quality soil includingCopper Flat earth connection of Pit and Pump house with comlete welded joint apply sink reach point over welded surface and copper termination with 3 nos earth lead along the cable as per site condition and specificaton etc complete as per direction of EIC. |
| 72 | Supply and fixing of 20 watt LEDstreet light fitting with necessaryG.I Brakets . |
| 73 | Supplying fitting fixing PVC insulated 35mm2x31/2 armored Cable of any reputed make tested up to 1100 volt. |
| 74 | Supplying all materials labour T&P for external electrification to pump house for three phase electrification for smooth running of three phase centrifugal pump set with required LT line & structure as per electrical & design specification all complete. |
| 75 | Design, engineering, procurement of materials and bought out components, manufacturing, assembly at shop, inspection, testing and painting at manufacturer’s works, packing, supply, unloading /transportation/ handling/storage at site, assembly at site, installation including touch-up painting, hook-up, pre-commissioning, commissioning, inspection and testing of the complete of the following capacity(Prime Power) DG sets along with AMF Panels, Acoustic enclosure, supply of all erection & commissioning spares, special tools and tackles (as required),instrumentation, allAuxiliaries, Exhaust system& silencer, Fuel Tank, Fuel piping , cable of required size , 4 nos earthingfor DG set, required foundation, good quality(L& T or equivalent) , change over,meetering panel, with CT Meter, all complete etc. with inspection certificate from electrical inspector and as as per site condition & direction of Engineer in charge.of 35KVA three phase Generator of reputed make i,e Kirloske/Cummins/other if any including all materials labour with construction of shed & testing all complete as per direction of EIC. |