Tender For Supply, Installation, Testing And Commissioning Of Diesel Generator Set Of 160 Kva Along With Amf Panel At Fci Ro Bhopal, bhopal-Madhya Pradesh

Food Corporation Of India-FCI has published Tender For Supply, Installation, Testing And Commissioning Of Diesel Generator Set Of 160 Kva Along With Amf Panel At Fci Ro Bhopal. Submission Date for this Tender is 09-03-2023. Diesel Generators Tenders in bhopal Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

36377225
Tender For Supply, Installation, Testing And Commissioning Of Diesel Generator Set Of 160 Kva Along With Amf Panel At Fci Ro Bhopal
Open Tender
Indian
Madhya Pradesh
bhopal
09-03-2023

Tender Details

Supply, Installation, Testing And Commissioning Of Diesel Generator Set Of 160 Kva Along With Amf Panel At Fci Ro Bhopal As Per Attached Tender Documents

Key Value

Document Fees
Refer document
EMD
INR 30000.0 /-
Tender Value
INR 14.94 Lakhs /-

BOQ Items

Name of Work: Supply, installation, testing and commissioning of Diesel Generator Set of 160 kVA along with AMF Panel at FCI RO Bhopal
Sl. No. Item Description
1Sub Head "A" Equipment
2Supply, Installation, testing andcommissioning of 160 kVA Silent type Liquidcooleddieseldrivengenerating set conforming to CPCB 2 / latestnormscomprisingofradiator,4strokemulti cylinder engine of suitable BHP to deliverratedkVAatprevailingsite conditions equipped with flywheel, residential type silencer, fuel governor, fuelpump,builtinfueltank,electric startingequipmentwithrequirednos of suitable AH sealed maintenance free batteriesetc.,directlycoupledto160 kVA0.8PF,alternatorsuitablefor3 phase, 4 wire 50Hz AC supply system with the entire system mounted on common base frame etc. on an existing foundation, exhaust piping with thermal insulation, control wiring from Alternatortocontrolpanel,acoustic enclosure, etc.as specified and consisting of the followings and AMF panel as per specification given below etc. as required.. (including rate of AMF panel as mentioned at Sr. no. 2)
3Diesel Engine: One number Diesel Engine multi-cylinder,four stroke, liquid cooled, electric start, turbo charged typeengine suitable for developingtherequiredBHPat1500 rpm, suitable for above output of alternatorat40ºC,50%RHandat 1000MetreMSLandconformingto BS 5514, BS 649, IS:10000, ISO 8528 Part I with upto date amendments/ norms, capable of taking 10%overloadingfor onehour after 12 hours of continuous operation completewith common baseframe, Anti vibration mountings, radiator, starting equipment,batteries, residential type silencer and other accessories etc. as required and as specifiedinthedetailedspecification enclosed. Governing Class (As per ISO 8528 part-V); Noise Level < 75 dBA/ CPCB NORMS ; Fuel Consumption-(in Litres/Hr) ; At 75% Load-25 to 32; Fuel Tank Capacity-200 to 300 L ; Weight of Gen Set with Canopy-Wet-2500-2800 Kgs (or as per Manufacturer standards) ;Electrical Battery Starting Voltage-12 V DC Engine Specifications- Rated Output (Prime continuous Rating as per ISO 8528-1)-147 kW/197 HP ; No of Cylinders-6;Rated Speed at 1500 RPM Aspiration - Turbo Aspiration ;Lube Oil Sump Capacity-14-18 L; Coolant Capacity-21-26 L Alternator: Insulation-Class H ; Efficiency at (100% Load)-0.8 pf (As per Standards IS 4722, IEC 34-1)-92.5% ;Max time to build Rated Voltage at Rated RPM-Voltage Recovery TIme-6 sec
4Engine mounted instrument panel fitted with and having digital display for the following: Start- stop switch with Key, Water/ liquid temperature indication, lubrication oil presuure indication, Lubrication oil temperature indication, Battery charging Indication, RPM indication, Over Speed indication, Low lubrication oil trip indication, engine Hours indication.
5Alternator: One number synchronous alternator ratedat160kVA,415 voltsat1500 rpm, 3phase,50Hz.ACsupply with 0.8 lagging power factor at 40ºC, 50% RH and at 1000 Metre MSL. The alternatorshallbehavingSPDP enclosure,brushless,continuousduty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class F/H insulation
6Base Frame & Foundation: Both the engine and alternator shall be mountedonsuitablebaseframemade ofMSchanneldwithnecessary reinforcementwhichshallbeinstalled on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.(Price of foundation needs to be quoted seperately at sr. no. 12 of this BOQ)
7Fuel tank: Inbuiltdailyservicefueltankaspe manufactures specification complete withallstndardaccessoriesandfuel pipingbetweenfueltankanddiesel engine,completewithvalves, levelindicator and accessories as required as per specification attached.
8Exhaust system:Dry exhaust mainfold with hospital exhaust silencerandcatalytic convertor
9Starting System: 12V/24V DC starting system comprisingofstartermotor,voltage regulatorandarrangementforinitial excitation, complete with required nos of suitable batteries as required and as per specification.
10Acoustic Enclosure: Acousticandweatherproofenclosure witharrangementforfreshairintake forcoolingoftheengineand alternator,extraction,discharginghot airintotheatmosphereasper specification attached.
11AMF Panel: Supplying, installation, testing and commissioning of automatic mains failure control including auto By pass panel of 16SWG CRCA sheet with suitable rating of copper bus bar, suitable for 160KVA silent type DG site complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH & provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF Panelto diesel Engine and else where if required all complete and inter locking includingthe following (Rates to be include in Item Sr. no. 1)
12300Amps. (minimum) FourpoleMCCB,withrotaryoperating mechanism with phase barriers - 2 nos. L&T Model (For mains and alternator)
13300Amps (minimum) ,FPpowercontactor(L&T model MNX- 300/ or suitable model of L&T) - 2 sets (For mains and alternator) with interlocking arrangement.
14Microprocessorbasedautomatic mains failure function unit for emergency and stand by power supply system having under voltage, over voltageandsinglephasingprotection and other standard features - 1 no.
15Micro processor based IDMT relay for three phase over current + earth fault - 1 set.
16Energyanalyserunittoindicate, current,voltage,frequency,power factor and kWh
17Phase indication lamps for DISCOM and Generator - 1 Set
18Emergencytripswitch, Auto/Manual/Offselectorswitch, trickle/boost charger switch and SMPS battery charger unit complete with transformer, rectifier, DC Voltmeter and ammeter, off and boost and current adjustment etc. - 1 Set
19BakeliteHRCfuses/ MCBandcontrol wiring for the entire system - 1 Set
20Indicating lamps for load on mains and load on set - 1 Set
21Fuse for instruments - 1 Set
22Sub Head "B" Earthing
23Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required.
24Supplying and laying 25 mm X 5 mm G.l strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.l. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.l. nut bolt & spring washer spaced at 50mm)
25Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/coke and salt as required.
26Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
27Laying of one no. PVC Insulated PVC sheathed XLPE power cable of 1.1 KV gradein existing RCC HUME/ METAL PIPE as reqd. a)up to 35 sq. mm.
28Laying of one no. PVC insulated, PVC Sheathed XLPE/ power cable of 1.1 KV grade on wall Surface etc. as reqd. a)up to 35 sq. mm. ( Clamped with 1mm thick saddle)
29Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC sheathed XLPE aluminium conductor cable of 1.1 KV grade as reqd. a) 3.5 X 185sq. mm.(57 mm)
30Providing laying& fixing of Gl pipe medium in ground complete with GI fitting including trenching (75 cm deep) & refilling etc. as required a) 65 mm dia
31Supply of PVC insulated and PVC sheathed power cable of 1.1 KV grade armoured aluminium conductor cable confirming to IS 1554 Part I 1988 with up to date amendment of follwing size etc. as required ofmake of reputed brand under MII confirming to IS and IEC codes a) 3.5 X 185 Sq mm
32Sub Head "C" Miscellaneous Items
33Providing foundation and platform with CC of M15/M20/M25/ as per OEM standard for the 160 kVA Silent type DG set so as to place the above mentioned DGSet conforming to clause 2.5.1of General specifications for Electrical Works Part - VII DG Sets 2013 including dismantling of exisitng paver block for preparation of foundation.