3 KVA Off-Line UPSINPUT 1 Voltage Range 230v 20% Frequency Range 50 Hz/60 Hz 4% OUTPUT 1 Voltage 230v Frequency Range 50 Hz/60 Hz 4% Power Factor 0.8 lag to unity Tolerance/Regulation Static Condition 2% Dynamic Condition 4% For 100% Step Load Frequency 50 Hz Admissible Crest factor 3 :1 Waveform Sinusoidal (Pure Sine wave) THD 10 % for linear loads Overload 110% for 1 Min. Peak Efficiency 85 % Inverter Topology Control Section Micro controller / DSP based Inverter Topology Power Section MOSFET Based MPWM with instantaneous Waveform Correction Nominal Float Voltage 48 V Battery Type Tubular C10 rated Preferred makes Exide/Amara raja/Prime VAH 4800 VAH Back Up Time 120 Minutes Rectifier Input High/low voltage protection, Output Output short circuit, over Load protection Over voltage, Battery Low, Over charge Display Parameters (LCD/LED) Displays Input voltage, Output Voltage, Battery Voltage Environment Ambient Temperature 0C to 50C Relative Humidity 5% to 95% condensed Maximum Altitude 3300 ft / 1000m Sound Level @ 1m <6 0Dba, Cooling Forced Air Quality certificates ISO 9001,14001,45001
2
Supply & Installation of Suitable Battery Rack & Accessories
3
Transportation & Installation Charges
4
Supplying & Installation of wiring for input & output with Power Socket
5
Supply & Installation of 12 V 150AH, Exide/Amararaja make VRLA SMF Batteries for 2 hours Back up Time.