Delhi Jal Board-DJB has published Renovation Of Standard Capacitors Make Apfc Panel Installed At Sector-9 Sps (Re-Invite). Submission Date for this Tender is 25-02-2023. Power Factor Panel Tenders in rithala Delhi. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Dismantling of defective capacitor banks from fixed units of HT motors including dismantling of termination, bus bar links and rusted hardware etc. from the existing banksof motors and transporting the same to the storeand allied works etc. as required at site. |
2 | Supply of 250 KVAr 6.6 KV, 3 ph. HT Fixed Capacitor banks for motors , complete with terminal cover, mounting frame of angle iron, post insulators, aluminum bus bar links for fixing protective fuses and cable end box for cable termination-make standard |
3 | Supply of 100A , 6.6 kV HT HRC fuses for replacement of blown fuses in fixed capacitor banks of motors -make Eswari/Anand/ standard/Phoenix |
4 | Supply of 145 kvar 6.6 kv, 3 ph. HT Fixed Capacitor banks for motors , complete with terminal cover, mounting frame of angle iron, post insulators, aluminum bus bar links for fixing protective fuses and cable end box for cable termination-make standard |
5 | Installation of 250 kVAr & 145 KVAr 6.6 kV HT fixed capacitor banks of motors with angle iron frame work , necessary hardware and civil workif any andtouching of rusted parts etc. including earthingof capacitor banks with GI wire/strip as required at site |
6 | Testing & commissioning of HT Capacitor banks andfixed capacitor banks as per required parameters including following: i. Continuity and earth testii. Meggering of all equipment for phase to phase, and phase to earth.iii. Charging of capacitors banks and monitoring of power factor of motors after commissioning of capacitor banks |
7 | Static Capacitors Bank for TransformerSupply of 100 kvar 6.6 kv, 3 ph. HT Fixed Capacitor banks for transformer , complete with terminal cover, mounting frame of angle iron, post insulators, aluminum bus bar links for fixing protective fuses and cable end box for cable termination-make standard |
8 | Installation of 100 KVAr 6.6 kV HT fixed capacitor banks of transformer with angle iron frame work , necessary hardware and civil workif any andtouching of rusted parts etc. including earthingof capacitor banks with GI wire/strip as required at site |
9 | Testing & commissioning of HT Capacitor banks and fixed capacitor banks as per required parameters including following:i. Continuity and earth testii. Meggering of all equipment for phase to phase, and phase to earth.iii. Charging of capacitors banks and monitoring of power factor of motors after commissioning of capacitor banks. |
10 | Renovation of APFC Panel 150 KVAr- 2 Nos Dismantling of defective component of APFC panels such ascapacitors , relays, lights , contactors including dismantling of incoming and outgoing connection etc. as required at site. |
11 | Supply of Super Heavy duty Round type capacitors of various capacities rated at 440V, 50 Hz, 3 phase AC , complete with terminal cover and discharge device -make standard |
12 | Banking of capacitor units to form banks of suitable capacity by electrical interconnection with multistrand copper wires/Al. bus bars using necessary mountings andhardware , etc. as requiredat site. |
13 | Supply of microprocessor based APFC relay with digital display ofpower factor and other parameters for sensing power factor and giving phased impulses to contactor coils for switchingON-OFF required no. of capacitors on receiving signals from Control CT in the main line- make Standard |
14 | Supply of MNX-50 triple pole capacitor duty contactors to replace defective contactors in APFC panel. , makeL&T/Schneider/Havells |
15 | Supply of MNX-32 triple pole capacitor duty contactors to replace defective contactors in APFC panel. , makeL&T/Schneider/Havells |
16 | Supply of MNX-12 triple pole capacitor duty contactors to replace defective contactors in APFC panel. , makeL&T/Schneider/Havells |
17 | Supply oftriple pole MCB up to 63A to replace defective MCB in the capacitor panel- make L&T/Schneider/Havells |
18 | Supply oftriple pole MCB up to 32A to replace defective MCB in the capacitor panel- make L&T/Schneider/Havells |
19 | Supply of LEDindication light of various colors to replace defectives lights in various stagesof capacitor panel-Make : FTC/standard |
20 | Supply of 0-500A Ammeter complete with selector switch and set of 3 nos. CTs for monitoring health of APFC panel. Make : AE/HPL/Havell"s Eqv. |
21 | Supply of digital ammeter 0-500A to replacement defective ammeter in the capacitor panel. Make : AE/L&T/Havells |
22 | Servicing of panels including complete dusting of all components, cleaning of contact point with CTC solution, decarbonizing of various joints, tightening of all nut bolts, sleevingof live partsalignmentof doors to prevent ingress of moisture and vermin’s and touchingof rusted partsof the panels etc.as required at site. |
23 | Installation of all above components in the existing capacitor banks with suitable fabrication work to accommodate new items in the existing enclosure / structure for alignment of components and easeof termination complete with hardware on the mounting structureandtermination of existing cables with lugs, tapes etc. completewith earthingof the capacitor banks,touching the rusted partsof the structure withpaint for protection from moistureetc. as required at site. |
24 | Testing & commissioning of APFC panels bank asper required parameters including following : i. Meggering of all equipment’s for phase to phase, Phaseto neutral and phase to earth.ii. Programming of APFC relays for targetpower factoriii. All function testsiv. Monitoringof power factor |