noida metro rail corporation limited has published Tender For Supply, Installation, Testing And Commissioning Of 500 Kva Servo Controlled Voltage Stabilizer, Phase Reversal Panel, Bus Duct, Cable And Other Associated Work At Nmrc Head Office, Sector-29, Noida.. Submission Date for this Tender is 07-03-2023. Voltage Stabiliser Tenders in noida Uttar Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 24-Feb-2023 | Prebid reply | Other | 07-03-2023 |
Sl. No. | Item Description |
1 | Servo controlled Automatic Voltage Stabilizer |
2 | Design, manufacturing, Supply, installation, testing and commissioning of outdoor type 500 KVA servo controlled Automatic Voltage Stabilizer,self-lubricating Carbon Roller Assemblies suitable for unbalancedload with digital micro controlled with Copper Winding, oil cooled type with bye pass arrangement of power drawing and It also includes testing of Transformer oil and subsequent filtering of oil at site before commissioning rest as per technical specification sheet.Note: Minimum 3 years manufactering warranty |
3 | Unloading,Shifting to foundation,Unpacking,400 kVA servo controlled Automatic Voltage Stabilizer complete in all respect with all accessories. |
4 | LT CABLES |
5 | Supply, Laying, testing & commissioning of the following sizes of LT XLPE cables on existing cable trays or on walls / ceiling or in existing ducts including providing & fixing saddles clamps, nuts & bolts as required. |
6 | 3.5cx240 sq. mm cable |
7 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
8 | 3.5cx240 sq. mm cable |
9 | Bus bar |
10 | Supply and erection of 800 Amp. TPN Rising Mains complete with top end cover plate etc. On angle iron wall brackets complete in all respect. |
11 | Supply and erection of incoming adopter box for mounting 800 Amp. TPN CFS unit including connectors of required capacity on to the rising Mains complete in all respect. |
12 | Supply and Fixing 800 Amp TPN Sandwich alumininum bus bar trunking complete shutable for IP 54 protection with top end cover plate of 1.6mm thik G.I. Sheet with sutaible arrangement for fixing etc complete in all respec |
13 | Supply and Fixing of pluging point 400 Amp to 1000 Amp TPN Sandwich alumininum bus bar trunking complete in all respect. |
14 | Supply and Fixing of Bend for 800 Amp sandwich Al bus bar trunking complete in all respect. |
15 | Supply and Fixing of Flange End for 800 Amp sandwich Al bus bar trunking complete in all respect. |
16 | Supply and Fixing of End Cover for 800 Amp sandwich Al bus bar trunking complete in all respect. |
17 | "Phase reversal Panel |
18 | EARTHING |
19 | Supply and burring of Safe Earthing Electrode T-39 (Hot-Dip Galvanized), Length up to 3000mm, outer pipe 76mm inner Dia 38mm terminal Dia 12 mm ,outer GI pipe of 16 SWG and inner GI pipe of 12 SWG with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30cm square C.I. frame with hinged cover & masonary housing. (From electrode terminal to switch board, cost of 25 X 3 GI. Strip will be extra) Make: As approved in U.P. P.W.D., & C.P.R.I. Certified. |
20 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
21 | CIVIL WORK |
22 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works upto plinth level |
23 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Cold twisted bars |
24 | Disposal of moorum/building rubbish/ malba/ similar unserviceable, dismantled or waste material by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. Note - item to be applicable in urban areas having directions for restricted hours for movement/ plying of load carrying motor vehicle of 3.5 cum or more. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy