Indian Institute Of Technology-IITB has published Tender For Providing And Laying Of Cables To Main Distribution Panel And Fixing Of Three Phase Points, Power Points In Various Labs At A7, A8 And Stable Complex Block, South Campus Of Iit Mandi.. Submission Date for this Tender is 23-02-2023. Cable Laying Tenders in mandi Himachal Pradesh. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Wiring for light point/ fan point/ exhaust fan point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required (Group B) as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
2 | Wiring for circuit/ submain wiring alongwith earth wire with the2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
3 | Supplying and drawing 3x4 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit/Casing/Wall Trunk asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
4 | Supplying and drawing 3x6 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit/ Casing/Wall Trunk asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
5 | Supplying and drawing 5x6 sq mm of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit/ Casing/Wall Trunk asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
6 | Supplying and fixing of 32 sq mm of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
7 | Supplying and fixing 5/6 A switch modular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
8 | Supplying and fixing 15/16 A switch modular switchon the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
9 | Supplying and fixing 3 pin 5/6 Asocket outlet modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
10 | Supplying and fixing 6 pin 15/16 Asocket outlet modular socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
11 | Supplying and fixing 3 Module Modular base & cover plate on existing modular metal boxes etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
12 | Supplying and fixing 6 Module Modular base & cover plate on existing modular metal boxes etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
13 | Supplying and fixing 8 Module Modular base & cover plate on existing modular metal boxes etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
14 | Providing and fixing 100 A,30KA,FPMCCB rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
15 | Providing and fixing 125 A,36KA,FPMCCB rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
16 | Providing and fixing 200 A,36KA,FPMCCB rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
17 | Supplying and fixing 12 way Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
18 | Supplying and fixing 16 way Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
19 | Supplying and fixing 8 Way (4+ 24) Double Door, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
20 | Supplying and fixing of 4 way (4 + 12), Double doorsurface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) asrequired as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
21 | Supplying and fixing of 8 way (4 + 24), Double doorsurface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) asrequired as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
22 | Supplying and fixing of 12 way (4 + 36), Double door ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) |
23 | Supplying and fixing Single pole 5 to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of Single pole, in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
24 | Supplying and fixing Triple pole32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of Triple pole, in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
25 | Supplying and fixing 63A rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as requiredas per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
26 | Supplying and fixing 63 A rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
27 | Supplying and fixing 25 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 25 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
28 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 95 sq. mm and upto 185 sq. mm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
29 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 95 sq. mm and upto 185 sq. mm direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
30 | Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 150 sq. mm (50mm) size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
31 | Supplying and fixing 3 Module PVC box in open surface/wall asrequired as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
32 | Supplying and fixing 6 Module PVC box in open surface/wall asrequired as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
33 | Supplying and fixing 8 Module PVC box in open surface/wall asrequired as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
34 | Supplying and drawing 3x10 sq mm of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
35 | Supplying and drawing 3x16 sq mm of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
36 | Supplying and drawing 5x16 sq mm of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
37 | Supplying and drawing 5x25 sq mm of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
38 | Supplying and drawing 5x35 sq mm of FR PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit asper entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
39 | Supplying and fixing of 32 mm size of Heavy Duty PVC Casing Caping Double lockalong with accessories in surface as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
40 | Supplying and fixing of 32 mm size of medium class PVC Flexible Pipe along with accessories in surface as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
41 | Supplying and fixing 100/125 A,30KA,FP MCCB enclosure Double door suitable to accommodate up to 50 sq. mm 4.0 core cable , powder painted including earthing etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
42 | Supplying and fixing 200 A,30KA,FP MCCB enclosure Double door suitable to accommodate up to 120 sq. mm 4.0 core cable , powder painted including earthing etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
43 | Supplying, Installation, testing and commissioning of pre-wired, 4 Feet Long 18/20 W (6500K) directly on wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc.as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
44 | Supplying of 300 mm sweep metal body exhaust fanas per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
45 | Supplying, installing , testing and commissioning of 200 amps (S.C. rating for 1 sec - 15 KA) 6 way,Copper Bus Bar Chamber as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
46 | Supplying, Installation, testing and commissioning of pre-wired, Square Recess Down Lighter(595x595 mm) of Wattage 24 W (6500K) directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc.as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
47 | Supplying and fixing 25 A, MCB DBOXXMCB procted Socket modular type with plug top, on surface or in recess, for the socket out let and complete with connections, testing and commissioning etc. as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
48 | Supply, installation, testing & commissioning of Wall Mounted Fan 300 mm sweep complete with required mounting bracket, of required size, connecting wires etc. as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
49 | Supplying of 3.5 Core x 120 Sq. mm of 1.1 KVAluminium conductor XLPE Insulated,PVC extruded inner-sheathed, round wired armoured, overall PVC outer-sheathed (as per IS 7098 Part 1) with latest amendments as required as per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
50 | Supplying and fixing 63A rating, four pole, 415 V, MCB in the existing TPN Box complete with connections, testing and commissioning etc. as requiredas per entire satisfaction and direction of Engineer-in-charge including carriage of material in all leads and lifts. |
51 | Supplying ,Installtion, testing, and Commissioning of Main Power Panel (Indoor) of suitable size with 800 A TP+N Aluminium Bus Bar to accommodate the following MCCb"s/MCB"S and made out of minimum 2 mm thick CRCA sheet powder coated complete with MCCB"s,MCB"s with Rotary Handle ,Multifuntion meter, LED indicators, interconnections,internal wiring,earthing etc. as required with hinged door mounted from front and back open able with locking arrangement having bottom cable entry duly fixed 90 cms above G/L with mounting legs made out of 50 mm X 50 mm X 6 mm angle iron & Top hood for rain protection, brick masonryconcreting, i/cconnections / inter connections and fixing of following accessories etc. complete as required with following Comonents-250 A ,36 ka TPN MCCB - Incomer - 2 Outgoings -100 A, 26 ka TPN MCCB- 3 63 A, 10 KA TPN MCCB - 463A, 10 KA TPN MCB - 6 |