Military Engineer Services-MES has published Tender For Necessary Repair Action May Please Be Taken To Carry Out The Under Mentioned Job Work For Smooth Functioning Of Bucholz Relay Apfc Capacitors And Connected Accessories At 66 Kv Grid Station Under Ge(N) Patiala Urgent Basis To Provide Unin. Submission Date for this Tender is 27-02-2023. Power Factor Panel Tenders in patiala Punjab. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 20-Feb-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 27-02-2023 |
Sl. No. | Item Description |
1 | Replacement of capacitor having capacity of 137.3KVAr, 6.99KV 1 Ph, 2 Bushing, CRCA container, BIL-28/75 KV peak. |
2 | Supply and replacement of Tap position Indicator. |
3 | Supply and replacement of Amp meter on RCP panel. |
4 | Supply and errection of AVR relay in power transformer-1 (having capacity of 10.5/12 MVA"s) RTCC panel. |
5 | Supply and fixing of 50 Nos ring type 2.5 sqmm cu thimble, supply and fixing 50 Nos "C" channel type connectors in RTCC panel of Power transformer - 1 (having capacity of 10.5/12 MVA"s) to run the OLTC in auto mode. |
6 | Supply and fixing of 50 Nos ring type 2.5 sqmm cu thimble, supply and fixing 50 Nos "C" channel type connectors in RTCC panel of Power transformer - 2 (having capacity of 6.3/8 MVA"s) to run the OLTC in auto mode. |
7 | Calibration to Trouble shooting in OLTC of transformer No.1 (having capacity of 10.5/12 MVA"s)to run the OLTC in motorized mode. |
8 | Supply, laying and termination of 7 core 2.5 sqmm 60 mtr cu cables from source to RTCC panel transformer No- 1 (having capacity of 10.5/12 MVA"s) for point supply. |
9 | Supply, laying and termination of 7 core 2.5 sqmm 60 mtr cu cables from source to RTCC panel transformer No- 2 (having capacity of 6.3/8 MVA"s) for point supply. |
10 | Supply and erection of DC DB 110 VDC 50 Ampincluding switch gear |
11 | Supply, laying and termination of 75 mtr, 4 core 2.5 sqmm cu cables from DCDB to RTCC panels including 50 Nos 2.5 sqmm pin type cu thimbles. |
12 | Supply and erection of one NumberOTI and one number WTI meters and including wiring of the OTI and WTI meterwith testing complete. |
13 | Supply and fixing the HRC fuse capacity of 11 KV 26 Amp for capacitor bank of capacity 1680 KVAR mounted on outdoor gantry in 66 KV Grid station including testing complete. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy