| 1 | Material and labour for maint and servicing of HT, 11 KV, VCB panel, relays including calibration of IDMTL relays through primary and secondary injection method and testing complete including re-setting the timer & according to source/out going feeders.Where required and ensuring proper functioing of earth fault and overcurrent relays.Removing carbon deposits in the contact points, greasing and tightening all fixed and moving contacts for smooth functioning including opening and taking down UNSV parts/accessories meggering the value of CT and other accessories etc complete all as specified and as directed. Servicing shall be carried out from OEM complete all as specified and as directed.NOTE : The store reqd for repair shall be measured and paid as supply only under relavant items and fixing of the same is deemed to be inclusive in this Item. |
| 2 | Material and labour for maint and servicing of EHV, 33 KV, SF6, 630 Amps capacity, 3 pole, 750 MVA, outdoor type by drawing out from panel, removing carbon deposits from contact points by spraying CRC spray and tightening of fixed and moving contacts including adjusting of parts as reqd for smooth functioning including opening and taking down of old unsv parts and accessories all as specified and directed. Servicing shall be carried out from OEM including testing/refilling of Gas pressure complete all as specified and as directed. NOTE : The store reqd for repair shall be measured and paid as supply only under relavant items and fixing of the same is deemed to be inclusive in this Item. |
| 3 | Supply only of set of isolating contact assy 630Acomplete all as specified and as directed. |
| 4 | Supply only of UPPER SUPPORT - 450025001complete all as specified and as directed. |
| 5 | Supply only of LOWER SUPPORT complete all as specified and as directed. |
| 6 | Supply only of SPOUT BUSHING UP TO 1250A (1 SET-6 NOS) - 450088057 complete all as specified and as directed. |
| 7 | Supply only of SET OF 3 Nos. SPOUT BUSHING WITH CC PARTS (Contact Plug) UPPER 630/800 AMPcomplete all as specified and as directed. |
| 8 | Supply only of SET OF 3 Nos. SPOUT BUSHING WITH CC PARTS (Contact Plug) LOWER 630/800AMPcomplete all as specified and as directed. |
| 9 | Supply only of SPOUT BUSHING WITH CC PART FOR \"R\" ,\"Y\" & \"B\" PHASE LOWER 630A/800Acomplete all as specified and as directed. |
| 10 | Supply only of SPOUT BUSHING WITH CC PARTS UPPER 1600 AMP - UNIVAC- (SET OF 3 Nos) 450088032 + 450V5512Q complete all as specified and as directed. |
| 11 | Supply only of Emergency Push to Trip assembly for PANEL (Ref.- W.O. V6921) - TRIP CABLE complete all as specified and as directed. |
| 12 | Supply only of VI (3\" Dia) Type WL 34599 M3+complete all as specified and as directed. |
| 13 | Supply only of VI (4\"Dia) Type VL 33379 -109 complete all as specified and as directed. |
| 14 | Supply only of MOTOR & GEAR ASLY 110V AC/DC UMG 14 TYPE (DELCO MAKE PMR-5) complete all as specified and as directed. |
| 15 | Supply only of HOLDING CATCH ASSEMBLY complete all as specified and as directed. |
| 16 | Supply only of PUSH BUTTON BRACKET ASSEMBLY complete all as specified and as directed. |
| 17 | Supply only of CHARGED/DISCHARGED INDICATOR ASSEMBLY complete all as specified and as directed. |
| 18 | Supply only of BIG & SMALL GEAR ASLY WITH MOTOR SHAFT complete all as specified and as directed. |
| 19 | Supply only of MOTOR CHARGED MECHANISM ASLY UMG-14 WITH MOTOR & OPERATING COILS (Single Trip)-- UPTO 26.3KAcomplete all as specified and as directed. |
| 20 | Supply only of MOTOR CHARGED MECHANISM ASLY WITH DELCO MOTOR & OPERATING COILS { SUITABLE FOR 40KA NEW VCB\"s- BENCHMARK MECHANISM} complete all as specified and as directed. |
| 21 | Supply only of SPRING CHARGING HANDLE FOR HAND OPERATING complete all as specified and as directed. |
| 22 | Supply only of CLOSING SPRING ASSEMBLYcomplete all as specified and as directed. |
| 23 | Supply only of TRIPPING SPRING ASSEMBLY-450171005 (1SET-2NOS) complete all as specified and as directed. |
| 24 | Supply only of BREAKER POSITIONING LEVER WITH VCB FREE TO CLOSE/TRIP KNOB (ROLLER CAM SWITCH WITH RED KNOB 2 N/O)complete all as specified and as directed. |
| 25 | Supply only of Motor Bracket for Hand charge complete all as specified and as directed. |
| 26 | Supply only of Upper Terminal Plate Square (12mm Thick) complete all as specified and as directed. |
| 27 | Supply only of Lower Terminal Plate Square (12mm Thick) complete all as specified and as directed. |
| 28 | Supply only of POWER PACK (INPUT-230 VAC - OUTPUT-24 VDC) complete all as specified and as directed. |
| 29 | Supply only of 11kV INDOOR PT PRIMARY FUSE (3.15A) complete all as specified and as directed. |
| 30 | Supply only of BUTTERFLY SWITCH FOR MOTOR CUT-OFF complete all as specified and as directed. |
| 31 | Supply only of TIMER FOR MOTOR complete all as specified and as directed. |
| 32 | Supply only of TEST SERVICE LIMIT SWITCHcomplete all as specified and as directed. |
| 33 | Supply only of LED LAMP-RED, of SAP Code : 460232452D complete all as specified and as directed. |
| 34 | Supply only of LED LAMP-GREEN of SAP Code 460232453D complete all as specified and as directed. |
| 35 | Supply only of LED LAMP-BLUE of SAP code 460232456D complete all as specified and as directed. |
| 36 | Supply only 11 KV Current Transformer IS-2705, current ratio 100/5+5 Amp, rated frequency 50 Hz, STC 18.4 KA for 1 Sec, indoor type complete all as specified and as directed. |
| 37 | Supply only of LED LAMP-AMBER of SAP Code 460232454D complete all as specified and as directed. |
| 38 | Supply only of LED LAMP-WHITE of SAP Code 460232457D complete all as specified and as directed. |
| 39 | Supply only of LED LAMP-YELLOW of SAP Code 460232460D complete all as specified and as directed. |
| 40 | Supply, install, testing of lightening arrestor metal oxide type suitable for 36 KV system discharge current 10 KA station class III, complete with all fitings, transmission class, discharge capacity 65 KA suitable for working voltage of33000 Volts including all necessary fittings, including taking down of existing unserviceable lightening arrestor complete all as specified and as directed. |
| 41 | Material and labour for maint and servicing of APFC pannels of capicity 640 KVAR 11 KV online and their components, cleaning complete with blower and removing of deposited carbon particals from the terminals, adjusting relays and other parts up to certain limit as required and calibrated complete all as specified and as directed. |
| 42 | Supply and fix in repairs high voltage HRC fuse of 100 Amps for capacitor bank complete all as specified and as directed. |
| 43 | Supply and fix in repairs high voltage HRC of 200 Amps fuse for capacitor bank complete all as specified and as directed. |
| 44 | Supply and fix as in repair danger notice plate of 25x20cm size and 1.6mm thick mild steel sheet, vitreous enamelled white, with letters(Local & Hindi language), figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT pole complete all as specified and as directed. |
| 45 | Materials and labour for earthing complete with copper plate 600 x 600 x 3.15mm thick electrode and 20×3mm copper strip as earthing lead, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with copper strip 20x3mmby means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set complete all as specified and as directed.Note:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. |
| 46 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised strip of 32 x 6mm sizeby means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate) with CI cover 10mm thick plate fixedto angle iron frame work including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking out unserviceable earthing plate and accessoriesall as specified and as directed. (Note: Earth strip upto a length of 7.50 m from earthplate shall be deemed to be included in quoted rate.) |
| 47 | Materials and labour for Copper strip 20 x 3.15mm with saddles and fixing screws etc.for roof conductors and down conductors above ground complete all as specified and as directed. |
| 48 | Material and labourfor HT 11 KV (Earthed) grade heat shrinkable end termination jointing kit outdoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and as directed. |
| 49 | Material and labourfor HT 11 KV (Earthed) grade heat shrinkable straight through jointing kit complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 sqmm complete all as specified and as directed. |
| 50 | M & L for painting the outer surface of the transformer ofcapacity ranging from 2000 KVA to 6000 KVA with one coat of corrosion resistant paint after preparing the surface dust and oil free and cleaning the bushes, name plate etc paint free after painting including writing the MES/SM No with white enamelled paint complete all as specified and as directed. |
| 51 | M & L for painting the outer surface of the transformer of capacity ranging from 100-350 KVA with one coat of corrosion resistant paint after preparing the surface dust and oil free and cleaning the bushes, name plate etc paint free after painting including writing the MES/SM No with white enamelled paint complete all as specified and as directed. |
| 52 | Material & Labour preparation of old painted surfaces by scraping out old paint by emmery paper, caustic soda complete of Four poles structure / cross arms, GOD pipe,clamps etc., and applying one coat of silver aluminium paint including painting of red & white alternate strips of 30cm each externally from ground level upto 1.2m with synthetic enamel paint, numbering of poles complete all as specified and directed.Note : All angles and channels will also be painted under the quoted rate. |
| 53 | Material & Labour for preparation of old painted surfaces by scraping out old paint by emmery paper, caustic soda complete ofTwo poles Structure/ cross arms, GOD pipe,clamps etc., and applying one coat of silver aluminium paint including painting of red & white alternate strips of 30cm each externally from ground level upto 1.2m with synthetic enamel paint, numbering of poles complete all as specified and directed.Note : All angles and channels will also be painted under the quoted rate. |
| 54 | Material & Labour for preparation of old painted surfaces by scraping out old paint by emmery paper, caustic soda complete ofSteel poles / cross arms, GOD pipe,clamps etc., and applying one coat of silver aluminium paint including painting of red & white alternate strips of 30cm each externally from ground level upto 1.2m with synthetic enamel paint, numbering of poles complete all as specified and directed.Note : All angles and channels will also be painted under the quoted rate. |
| 55 | Material & Labour for spreading and levelling of coarse graded stone aggregate (broken stone or boulders) of size 40 mm in sub - station yard to cover the complete area complete all as specified and as directed. |
| 56 | Removal of unwanted grass, plants and vegetations from E/M installations on Monthly basis for entire contract period including surface dressing and removal of grass ,plants and vegetations from site not less than 50mtr from starting point complete all as specified and directed (Note- (i) Removal of unwanted grass and vegetation will be repeated once a month(ii) Measurement shall be taken monthwise.) |
| 57 | S & F in repairs incl testing of swing out explusion fuse isolated assembly with fuse carrier out door type 11 KV supply 200 Amp( DO Fuse ) incl mounting bracket & post insulator complete all as specified and as directed. |