Tender For Water Supply Reorganisation Scheme Survey Design Supply Of All Material Labour Etc For Construction Of Oht Cwr Pump House Staff Quarter Boundary Wall Site Development Laying Of Rising Main Distribution System Sitc Work Of Tubewell Including Pl, jalaun-Uttar Pradesh

Uttar Pradesh Jal Nigam-UPJN has published Tender For Water Supply Reorganisation Scheme Survey Design Supply Of All Material Labour Etc For Construction Of Oht Cwr Pump House Staff Quarter Boundary Wall Site Development Laying Of Rising Main Distribution System Sitc Work Of Tubewell Including Pl. Submission Date for this Tender is 04-03-2023. Wall Construction Tenders in jalaun Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

36114072
Tender For Water Supply Reorganisation Scheme Survey Design Supply Of All Material Labour Etc For Construction Of Oht Cwr Pump House Staff Quarter Boundary Wall Site Development Laying Of Rising Main Distribution System Sitc Work Of Tubewell Including Pl
Open Tender
Indian
Uttar Pradesh
jalaun
04-03-2023

Tender Details

Water Supply Reorganisation Scheme Survey Design Supply Of All Material Labour Etc For Construction Of Oht Cwr Pump House Staff Quarter Boundary Wall Site Development Laying Of Rising Main Distribution System Sitc Work Of Tubewell Including Plc / Scada Automation Work At Jalaun. -Design And Supply Of All Labour, Material T&P Etc To Construct Rcc Clear Water Resevoir Cum Pump House Of Required Capacity In All Type Of Strata With Ht, Lt And Meter Room, Ms Pipes Railling Consisting Of 3 Rows And Posts On The Roof / Doom Periphery, M.S Ladder From Ground Level To Top Of Tank And Inside The Tank, Locking Device, Ci Cowl Type With Mosquito Mesh Ventilator, Supply And Fixing Water Level Indicator, 25Mm Pcc 1:2:4 Over 80Mm Pcc 1:4:8 In Apron, 150 Mm Semicircular Drain Around The Tank, Two Coats Of Apex Paint Of Approved Make And Testing Of Tank For Water Tightness Etc. And Also Including The Cost Of Supply And Fixing Of All Necessary Pipe Assembly And Valves With By Pass Arrangement Etc All Complete As Per Approved Design And Drawing. ( Detail Specification As Per Tender Document ) 3 500 Kl In Zone 1 4 450 Kl In Zone 2 5 600 Kl In Zone 3 6 Construction Of R.C.C Over Head Tank ( Oht ) Of Various Capacity At Different Sites / Zones 7 Design & Supply Of All Labour Material T&P Etc And Construct Rcc Over Head Tank Of Following Capacity And Staging Including Inlet Outlet Washout & Overflow Arrangements With Rcc Two Column Staircase & 1M Wide Balcony, G.I Pipes Ralling Consisting Of 3 Rows Of 20Mm Dia G.I Pipe And Angle Iron Posts Around Balcony And At The Dome Periphery, M.S. Ladder From Balcony To Top Of Tank And Inside The Tank, Ms Grill Gate Of 2 M Height And Box Type Enclosure At Entrance Of Staircase With Locking Arrangement, Chambers For All Valves, Ventilating Shafts With Steel Frame And Fixing G.I Fly Proof Mesh Of 26 Gauge, Ci Manhole Frame And Covers, Copper Lightening Conductor, Fixing Of Puddle Collars And Bell Mouths, Supply And Fixing M.S. Clamps With Rcc Column, Fixing Of Water Level Indicator, 25Mm Pcc 1:2:4 Over 80Mm Pcc 1:4:8 In Apron, 150Mm Semicircular Drain Around The Tank, Escape Channel Of 20M Length, Two Coats Of Apex Paint Of Approved Make And Testing Of Tank For Water Tightness Etc. And Also Including The Cost Of Supply And Fixing Of All Necessary Pipes Assembly And Valves With Bypass Arrangement Etc All Complete As Per Approved Design And Drawing. ( Detail Specification As Per Tender Document ) 8 1550 / 20 M Stagging In Zone 2 9 1800 / 22 M Stagging In Zone 2 10 2350 / 22 M Stagging In Zone 3 11 Add Or Substract According To The Stagging Height Of Oht If Increased Or Decreased, It Also Includes Variation In Foundation And Staircase Accordingly. 12 Renovation Of Existing Over Hand Tank Of Following Capacity In Zone 1 Including Repairing Of Floor, Drain, Appron, Balcony Walls & Columns With Scracping Of Old Concrete And Cc Grouting With Waterproofing Chemical For Water Tightness Inside And Outside Of Container Wall, Fixing / Reparing Of Railing, Pipes, Valves And Fittings, Chambers, Ventilator Shaft, Fixing Of Manhole Covers, Water Level Indicator And Lightning Conductor, Apex Painting With Two Coats Etc Including All Labour, Material T&P Etc For Proper Completion Of Work. 13 350 Kl / 20 M Stagging 14 Dismantling Of Existing Old Over Head Tank Of Following Capacity At Zone 1 By Mechnical Or Manual Means Including Supply Of All Labour, Material T&P Required For Completion Of Work With Proper Safety Measures To Be Carried Out During Dismantling Of Oht Necessary To Safegaurd The Nearby Structures And Disposal Of Malwa Or Dismantelled Material Upto 8Km Lead As Per Directions. 15 200 Kl / 18 M Stagging 16 Pump House 17 Renovation Of Existing Pumphouse 18 Construction Of Staff Quarter With Pile Foundationas Per Approved Design / Drawing Including With Pile Foundationwith Supply Of All Material, Labour, T&P All Complete With Providing Complete Doors, Windows, Ventilators, Flooring, Painting, Drainage, Electricity, Plumbing And Lighting Facilities As Per Requirement. 19 Type I - 2 Set ( 3 Nos. ) - 40.80 Sqm 20 Type Ii ( 1 Nos. ) - 54 Sqm 21 Type Iii ( 1 Nos. ) - 63 Sqm 22 Demolition / Dismantling Of Abandoned Existing Old Staff Quarters, Pumphouse, Store Etc At Jalsansthan Water Works Campus Including Shifting / Disposal Of Dismantled Malwa / Scrap Upto 8 Km Lead As Per Directions. 23 Construction Of Administrating Building As Per Approved Design / Drawing At Site Demarcated With Pile Foundationfor The Same Including All Labour, Material T&P All Complete As Per Reqiurement Alongwith Making Provision Of Water Supply Testing Lab With Supply And Installation Of All Necessary Apparatus And Euipments To Completely Fufill The Testing Requirement Of Potable Water Supplied To The Consumers 24 Building Work Complete In All Respect 25 Lab Equipments As Per Requirements 26 Construction Of Boundary Wall As Per Approved Design / Drawing Including Supply Of All Labour, Material T&P Etc To Complete The Work. With Pile Foundation Andyshape M.S Angel Iron Including Concertina Coil Fencing. Including Painting Departmental Approved Colour 27 Zonal Water Supply Campus 28 Ms Gate As Per Approved Drawing With Priming Coat And Paint As Per Specifications. 29 Ms Wicket Gate As Per Approved Drawing With Priming Coat And Paint As Per Specifications. 30 Construction Of New Interlocking Tile Road As Per Approved Drawing And Specifications Inside Water Work Campus, Levelling & Plantation For Asthetically Development Of Water Work Campus As Per Directions. 31 Filling Of Good Earth In Lower Portion At Various Zonal Campus Including Levelling And Dressing With Proper Compaction By Mechnical Or Manual Means At Water Work Campus. 32 Design And Construction Of Rwh Chamber With All Necessary Arrangement As Per Approved Design / Drawing For Rain Water Harvesting At Zonal Water Works And Admin Building Etc Including Supply Of All Labour, Material T&P For Proper Completion Of Work. 33 Distribution Network 34 Supply Of Isi Marked Or Its Relevant Code Hdpe Pipes Of Approved Make Of Follwing Sizes ( Dia In Mm ) With Jointing Materials, ( Electric Fusion Coupler ) Specials Of Sizes Required During Constructionas Per Latest I.S.Amendement Upto Site Of Work Including Loading, Unloading, Cartage Insurance, Etc All Completed But Exclusive Of Gst In Various Zone As Per The Drawing And Approval Of Engineer. 35 Hdpe Pipe Grade Pe 100 / Pn 6- 90 Mm 36 Hdpe Pipe Grade Pe 100 / Pn 6- 110 Mm 37 Hdpe Pipe Grade Pe 100 / Pn 6- 140 Mm 38 Hdpe Pipe Grade Pe 100 / Pn 6- 160 Mm 39 Supply Of Isi Marked Or Its Relevant Code Di K-7 Pipes Of Approved Make Of Follwing Sizes ( Dia In Mm ) With Jointing Materials, During Construction As Per Latest I.S Amendements Upto Site Of Work Including Loading Unloading Cartage Insurance, Etc All Completed But Exclusive Of Gst In Various Zone As Per The Drawing And Approval To Engineer.With Sectional Testing 40 D.I. K-7 / 200 Mm 41 D.I. K-7 / 250 Mm 42 D.I. K-7 / 300 Mm 43 D.I. K-7 / 350 Mm 44 D.I. K-7 / 400 Mm 45 Supply Of Following Size Ofsluice Valves / Scour Valves, Fire Hydrants & Air Valves Of Approved Make As Per Relevent I.S Or Its Latest Amandementup To Store / Site Of Work Including Loading, Unloading & Cartage, Taxes Duties Insurance Etc All Complete. As Per Is: 2906-1969. 46 Air Valve As Per As I.S : 14845 47 20 Mm. Dia Di D / Fair Valve 48 D.I. D / F Sluice Valve / Scour Valve 49 100 Mm Dia. 50 200 Mm Dia. 51 250 Mm Dia. 52 300 Mm Dia. 53 350 Mm Dia. 54 400 Mm Dia. 55 Fire Hydrant ( 65 Mm Dia. ) 56 Dismantling Of Following Types Of Roads Including Sorting Out Of Servicable Materials Stacking And Disposal Of Unservicable Matarials With In A Distance Of 50 M. Including Supply Of Labour Specials T&P Etc. Required For Proper Completion Of Work. 57 Interlocking Tile 58 C.C Road 59 Bituminous Road 60 B.O.E Road 61 Excavation For Pipe Line Trenches In All Type Of Soil Requiring Use Of Specialt&P Etc. With Lift Upto 1.5 M Lead Upto 50 Mincluding Filling Back Of Excavated Earth Into Trenches And Watering Ranmming Dressing And Removal Of Surplus Earth Upto 50M Including Supply Of Alllabour T&P Etc Complete And As Per Direction Of Engineer Incharge. 62 Cartage From Local Store To Site Of Work For Following Size ( Dia In Mm ) Hdpe Pipes And Specials Coupling, Fittings, And Lowering The Same Into Trenches And Laying True To Alignment And Gradiant Including Testing Of Pipe Lines Cuttings Of Pipes For Making Up The Length And Making Joints With Electrofusion Couplers, Bends, Tees, Endcap Etc. With Electrofusion Machinery Including All Jointing Materials, Labour, T&P Etc Required For Proper Completion Of Work. & Including Sectional Testing. 63 Hdpe Pipe Grade Pe 100 / Pn 6- 90 Mm 64 Hdpe Pipe Grade Pe 100 / Pn 6- 110 Mm 65 Hdpe Pipe Grade Pe 100 / Pn 6- 140 Mm 66 Hdpe Pipe Grade Pe 100 / Pn 6- 160 Mm 67 Cartage Of Di K-7 Pipes And Specials Of Following Size ( Dia In Mm ) From Store To Site Of Work, Lowering Them Into Trenches And Laying, Jointing True To Alignment And Gradiant Including Testing Of Pipe Line But Excluding Cost Of Trenching Including All Supply Of Labour T&P And All Jointing Material Etc Complete Required For Proper Completion Of Work. 68 D.I. K-7 / 200 Mm 69 D.I. K-7 / 250 Mm 70 D.I. K-7 / 300 Mm 71 D.I. K-7 / 350 Mm 72 D.I. K-7 / 400 Mm 73 Carting Of Following Size Of Sluice Valves / Scour Valves, Fire Hydrants & Air Valves From Store To Site Of Work And Lowering Them Into The Trenches, Fixing In Position And Jointing Them With Pipe Line And Testing Etc Including Supply Of Jointing Materialand Also Including Supply Of All Material And Construction Of Suitable P.C.C Support Below Fittings Etc All Complete. 74 20 Mm Dia Di D / F Air Valve 75 D.I. D / F Sluice Valve / Scour Valve 76 100 Mm Dia. 77 200 Mm Dia. 78 250 Mm Dia. 79 300 Mm Dia. 80 350 Mm Dia. 81 400 Mm Dia. 82 Fire Hydrant ( 65 Mm Dia. ) 83 Design And Construction Of R.C.C. Thrust Block With Cement, Coarse Sand, And 20Mm Gauges Stone Ballast In Propotion Of 1:1.5:3 In Thrust Block Of Pipe Line Including Reinforcement And Its Bending The Same With 0.08 Mm Thick Binding Wire In Position And Necessary Shuttring Including Proper Curing And Supply Of All Materials, Labour And T&P Etc Required For Proper Completion Of Work As Approved By Engineer. 84 For 250 Mm To 400 Mm Dia 85 For 80 Mm To 200 Mm Dia 86 Reinstatement Of Following Types Of Roads Including Sorting Out Of Servicable Materials Stacking And Disposal Of Unservicable Materials With In A Distance Of 50 M. Including Supply Of Required New Matarials & Reinstatement The Same Including Supply Of Labour T&P Etc. Required For Proper Completion Of Work. 87 Interlocking Tile 88 C.C Road 89 Bitumenous Road 90 B.O.E Road 91 Supply Of All Matarial Labour T&P Etc And Constuction Of Following Type Of Chamber As Per Approved Design & Drawing According To Diretion Of Engineer Incharge . 92 Sluice Valve Chamber 93 Scour Valve Chamber 94 Air Valve Chamber 95 Fire Hydrant Chamber 96 Provision For Shifting Of House Connection Which Are Cominginpipe Line Alignment During Excavation Including All Labour, Material T&P Etc All Complete. 97 Upto 110 Mm Dia 98 For 125 Mm To 160 Mm Dia 99 For 180 Mm To 250 Mm Dia 100 Provision For Nala / Culvert Crossing Including All Materials, Labour And T&P Etc. Complete. It Includes Supply Of Di / Hdpe Pipe & Specials Of Required Size For Encasing, Cement Concrete And Brickwork For Pillars And Any Other Job For Proper Completion Of Work. 101 For Crossing Of ( 1.0To 1.5 M Wide ) 102 For Crossing Of ( 1.5To 2.0 M Wide ) 103 Construction Of Single Tap Pillar Type Stand Post Including All Material, Labour T&P Etc Complete 104 Provision For Inter Connection With Existing Pipeline From New Pipe Line Including Bailing Out Of Water, Fixing Of Clamps Etc. Complete For Proper Completion Of Work.Including All Material, Labour T&P Etc Complete Forproper Completion Of Work. 105 250 Mm D.I. 106 200 Mm D.I. 107 160 Mm Hdpe 108 110 Mm Hdpe 109 90 Mm Hdpe 110 Rising Main 111 Supply Of Isi Marked Or Its Relevant Code Di K-7 / K-9 Pipes Of Follwing Sizes ( Dia In Mm ) With Jointing Materials, Specials Of Sizes Required During Construction Included Jointing As Per Latest I.S.Samandement Upto Site Of Work Included Loading Unloading Cartage Insurance, Etc All Completed But Exclusive Of Gst In Various Zone As Per The Drawing And Approval Of Engineer. 112 D.I. K-7 / 150 Mm 113 D.I. K-7 / 200 Mm 114 D.I. K-7 / 250 Mm 115 D.I. K-7 / 300 Mm 116 D.I. K-9 / 350 Mm 117 Supply Of Following Size Ofsluice Valves / Scour Valves, Fire Hydrants & Air Valves As Per Relerelavent I.S.I Or Its Latest Amandement. Up To Store Including Loading, Unloading & Cartage, Taxes Duties Insurance Etc All Complete. As Per Is: 2906-1969. 118 D.I. D / F Sluice Valve / Scour Valve 119 150 Mm Dia. 120 200 Mm Dia. 121 250 Mm Dia. 122 300 Mm Dia. 123 350 Mm Dia. 124 Dismantling Of Following Types Of Roads Including Sorting Out Of Servicable Matarials Stacking And Disposal Of Unservicable Matarials With In A Distance Of 50 M Including Supply Of Labour Specials T&P Etc. Required For Proper Completion Of Work 125 Interlocking Tile 126 C.C Road 127 Bitumenous Road 128 B.O.E Road 129 Excavation For Pipe Line Trenches In Ordinary Soil Use Ofspecialt&P Etc With Lift Upto 1.5 M Lead Upto 50 M Including Filling Back Of Excavated Earth Into Trenches And Watering Ranmming Dressing And Removal Of Surpluas Earth Upto 50M Including Supply Of All Materials Labour T&P Etc Complete And As Per Direction Of Engineer Incharge. 130 Cartage Of Following Size ( Dia In Mm. ) Of Di K-7 / K-9 Pipes And Specials Includingjointingmaterials From Store To Site Of Worklowering The Same Into Excavated Pipe Line Tenches True Toaligment And Gradidient And Jointing The Same Including Testing Of Pipe Line Including Supply Of All Materials Labaour T&P Etc Complete And As Per Direction Of Engineer Incharge 131 D.I. K-7 / 150 Mm 132 D.I. K-7 / 200 Mm 133 D.I. K-7 / 250 Mm 134 D.I. K-7 / 300 Mm 135 D.I. K-9 / 350 Mm 136 Carting Of Following Size Of Sluice Valves / Scour Valves, From Store To Site Of Work And Lowering Them Into The Trenches, Fixing In Position And Jointing Them With Pipe Line And Testing Etc Including Supply Of Jointing Materialand Also Including Supply Of All Material And Construction Of Suitable P.C.C Support Below Fittings Etc. Complete. 137 D.I. D / F Sluice Valve 138 150 Mm Dia. 139 200 Mm Dia. 140 250 Mm Dia. 141 300 Mm Dia. 142 350 Mm Dia. 143 R.C.C. Thrust Block With Cement, Core Sand, And 20Mm Gauges Stone Ballast In Propotion Of 1:1.5:3 In Thrust Block Of Pipe Line Including Reinforcement And Its Bending The Same With 0.08 Mm Thick Binding Wire In Position And Necessary Shuttering Including Proper Curing And Supply Of All Materials, Labour And T&P Etc Required For Proper Completion Of Work. 144 For 250 Mm To 400 Mm Dia 145 For 80 Mm To 200 Mm Dia 146 Supply Of All Material Labour T&P Etc For Constuction Of Following Type Of Chamber As Per Type Design & Drawing According To Diretion Of Engineer-In-Charge . 147 Sluice Valve / Scour Valve Chamber 148 Reinstatement Of Following Types Of Roads Including Sorting Out Of Servicable Matarials Stacking And Disposal Of Unservicable Matarials With In A Distance Of 50 M. Including Supply Of Required New Matarials & Reinstatement The Same Includng Supply Of Labour Specials T&P Etc Required For Proper Completion Of Work. 149 Interlocking Road 150 C.C Road 151 Bitumen Road 152 B.O.E Road 153 Making Water Supply House Connection In New / Existing Pipe Line As Per Approved Drawing And Material Including Supply Of All Labour, Material T&P Required For Proper Completion Of House Connection Work As Per Approved Drawing, 154 In Kachcha Road 155 Upto 110 Mm Dia 156 For 300 Mm Dia 157 For 350 Mm To 500 Mm Dia 158 In Boe Road 159 Upto 110 Mm Dia 160 For 125 Mm To 160 Mm Dia 161 For 180 Mm To 250 Mm Dia 162 In Cement Concrete Road 163 Upto 110 Mm Dia 164 For 125 Mm To 160 Mm Dia 165 For 180 Mm To 250 Mm Dia 166 For 300 Mm Dia 167 For 350 Mm To 500 Mm Dia 168 In Bituminous Road 169 Upto 110 Mm Dia 170 For 125 Mm To 160 Mm Dia 171 For 180 Mm To 250 Mm Dia 172 For 300 Mm Dia 173 In Interlocking Road 174 Upto 110 Mm Dia 175 For 125 Mm To 160 Mm Dia 176 For 180 Mm To 250 Mm Dia 177 Electrical And Mechanical Works ( Supply, Storage, Testing And Comissioning And Trail & Run Of Following As Per Details ) 178 Construction Of ( 9No ) New & ( 2No ) Rebore Tubewells 179 Resistivity Survey Of Tubewell Site 180 Transportation Of Rig Machine Erection, Dismantling And Associated T&P Complete In All Respect Including Required All Material , Labour Etc. 181 Drilling Of Tubewell Bore 182 Drilling Of 550 Mm. Dia Bore From G.L. To 100M. Bgl ( 100Mx11no ) 183 Drilling Of 550 Mm. Dia Bore From 101 Bgl To 120M. Bgl ( 20Mx11no ) 184 Logging Of Bore Hole By Electirc Logger 185 Tubewell Assembly 186 M.S. Tube Well Assembly With All Required Parts Like Plain Pipe, Slotted Pipe Rings, , Well Cap, Bail Plug Clamp, Reducer, Central Guide, Support Structure Etc. As Required And As Per Typed Design Complete In All Respect. 187 300 Mm. Dia 7.1 Mm Thick Mserw Plain Pipe With Ms Ring & Reducer ( 60Mx11no ) 188 200 Mm.Dia 7.1 Mm Thick M.S. Plain Pipe & Slotted Pipe With Ms Ring ( 50Mx11no ) 189 Lowering Of Tubewell Assembly Duly Welded Including Welding Electrode And Shrounding Of Pea Gravel Complete In All Respect. 190 300 Mm. Dia 7.1Mm Thick Mserw Plain / Slotted Pipe 191 200 Mm. Dia Plain / Slotted Pipe 61 M. Bglto 110 M. Bgl 192 Development Of Tubewell 193 Transportation, Erection, Dismantling Of 250 P.S.I. Compressor. 194 Development By 250 P.S.I. Compressor 195 Transportation, Erection, Dismantling Of 2 Cusec O.P. Unit And Yeild Test. 196 Development By 2 Cusec / Suitable Capacity O.P. Unit 197 Chemical And Bacteriological Test Of Water Sample Form Departmentel / Approved Lab. 198 Supply & Shrouding Of Lal Kuan Pea Gravel 1.6 To 4.8 Mm. Size For Tubewell 199 Pumping Plant For New And Rebore Tubwells With Painting Work 200 Supply, Installation, Testing And Commissioning Of Clear Water Submersible Pump ( Is 9236 ) Complete With Electric Motor ( Is 8034 ) Capable To Operate On 380 / 420 Volts 3 Phase 50 C / S A.C. Supply Of 1000 Lpm, 60 Mtr Head Or As Per Design & Hp As Per Design With Margin According To Ceepho Manual 201 Supply, Installation, Testing And Commissioning Of Main Piping & Valves With 24Mtr. Column Pipe, Power Wiring, Earthing, Painting, Wiring Of Pump House ( Internal & External ) And Gauges Complete In All Respect With All Required Material, T&P Labour 100 Mm Dia. Size 202 Supply, Installation, Testing And Commissioning Of 3 Mtr Long Heavy Duty Exta Coloum Pipe 100 Mm Dia. Size ( 8 Nos For Each Tw ) 203 Supply, Installation, Testing And Commissioning Of Electrically Operated Actuater Suitable For 100 Mm Size Sluice Valves ( 1No For Each Tw ) 204 Supply, Installation, Testing And Commissioning Of Submersible Flat Copper Condutor Cable 1X3cx4mm2 Pvc Sheathed Double Run ( 1X2rx30m=60M For Each Tw ) 205 Supply, Installation, Testing And Commissioning Of Pvc Sheathed Aluminium Armoured Cable From Upppcl Pole / Trasformer To Meter And Meter To Pump House 1X3.5Cx25mm2 206 Supply, Installation, Testing And Commissioning Of Scada Compitable 3 Phase Control Panel With Soft Stater Module Incuding Rs 485 Port- 400 V Suitable To Operate Tw Submersible Pumping Plant 207 Supply & Installtion Of 30 Kva Servo Voltagestablizer With 63Amp Changeover Switch 208 Supply, Installation, Testing And Commissioning Ofof 2 Ton 4.5 Mtr Lift Chain Pully Block 209 Supply, Installation, Testing And Commissioning Of Ce / Ul Certified Electromegnatic Flowmeter 100Mm 210 Supply, Installation, Testing And Commissioning Of Auto Phase Reversal Unit With Inbuilt Time Delay & Enclosure ( Conforming To Iec:60947-1 & Iec:60947-B-1 ) Suitable To 25 Hp 211 Supply, Installation, Testing And Commissioning Of Ce / Ul Certified Pressure Transmitter 212 Supply, Installation, Testing And Commissioning Of Ce / Ul Certified Surge Protector For Control Panel 213 Supply, Installation, Testing And Commissioning Of Security Survelliance Ip Camera With Required Accessories 214 Rennovation Work Of Exsisting Works With Painting Work 215 Supply, Installation, Testing And Commissioning Of Clear Water Submersible Pump ( Is 9236 ) Complete With Electric Motor ( Is 8034 ) Capable To Operate On 380 / 420 Volts 3 Phase 50 C / S A.C. Supply Of 1000 Lpm, 60Mtr Head Or As Per Design & Hp As Per Design With Margin According To Ceepho Manual 216 Supply, Installation, Testing And Commissioning Of Main Piping & Valves With 24Mtr. Column Pipe, Power Wiring, Earthing, Painting, Wiring Of Pump House ( Internal & External ) And Gauges Complete In All Respect With All Required Material, T&P Labour 100 Mm Dia. Size 217 Supply, Installation, Testing And Commissioning Of 3 Mtr Long Heavy Duty Exta Coloum Pipe 100 Mm Dia. Size ( 8 Nos For Each Tw ) 218 Supply, Installation, Testing And Commissioning Of Electrically Operated Actuater Suitable For 100 Mm Size Sluice Valves ( 1No For Each Tw ) 219 Supply, Installation, Testing And Commissioning Of Submersible Flat Copper Condutor Cable 1X3cx4mm2 Pvc Sheathed Double Run ( 1X2rx30m=60M For Each Tw ) 220 Supply, Installation, Testing And Commissioning Of Scada Compitable 3 Phase Control Panel With Soft Stater Module Incuding Rs 485 Port- 400 V Suitable To Operate Tw Submersible Pumping Plant 221 Supply & Installtion Of 30 Kva Servo Voltagestablizer With 63Amp Changeover Switch 222 Supply, Installation, Testing And Commissioning Of Ce / Ul Certified Electromegnatic Flowmeter 100Mm 223 Supply, Installation, Testing And Commissioning Of Auto Phase Reversal Unit With Inbuilt Time Delay & Enclosure ( Conforming To Iec:60947-1 & Iec:60947-B-1 ) Suitable To 25 Hp 224 Supply, Installation, Testing And Commissioning Of Ce / Ul Certified Pressure Transmitter 225 Supply, Installation, Testing And Commissioning Of Ce / Ul Certified Surge Protector For Control Panel 226 Supply, Installation, Testing And Commissioning Of Security Survelliance Ip Camera With Required Accessories 227 Pumping Plant At 500 Kl Cwr ( Zone - 1 ) Cwr Feed From 6No TwS ( 3Exsisting+3New ) 228 ( A ) Vt Pumping Plant :- Supply Of 1400 Lpm, Head As Per Actual Design , 1450 Rpm , S.S 410 Impeller & Shaft, Pump Casing 2% Nici, Is:210 Fg: 260 Self Water Lubricated Vt Pump Set Coupled With Squirrel Cage Vhs / Vss Tefc Ip-55 Induction Motor ( Operating Voltage 415 V + 10%, 3 Ph, 50Hz + 5% ) As Per Actual Design Including According To Ceepho Manual With Bowl Assembly Discharge Head, Head Shaft, Strainer And 5 Mts ( Or Suitable Sump Depth ) Column Assembly To Feed 350 Kl Exsisting Oht ( 1W+1S ) 229 ( B ) Vt Pumping Plant :- Supply Of 2400 Lpm, Head As Per Actual Design, 1450 Rpm , S.S 410 Impeller & Shaft, Pump Casing 2% Nici, Is:210 Fg: 260Self Water Lubricatedvt Pump Set Coupled With Squirrel Cage Vhs / Vss Tefc Ip-55 Induction Motor ( Operating Voltage 415 V + 10%, 3 Ph, 50Hz + 5% ) As Per Actual Design Including According To Ceepho Manual With Bowl Assembly Discharge Head, Head Shaft, Strainer And 5 Mts ( Or Suitable Sump Depth ) Column Assembly To Feed 1550 Kl New Oht ( 2W+1S ) 230 Control Pannel :- 231 Supply Of M.S. Fabricated Dust And Vermin Proof, Cubical Type, Floor Mounted, Control Panel Compitable To Scada With Rs485 Port Consisting As Following Incoming :-1 No. M.C.C.B. Motorised & Microprocessor Based250 Amp Capacityoutgoing :- ( I ) 2 Nos. Outgoing Consist Of Scada Compatible Motorised M.C.C.B. Microprocessor Based 80Amp Capacity, Suitable To Operate 25 Hp Induction Motor ( Ii ) 3 Nos. Outgoing Consist Of Scada Compatible Motorised M.C.C.B.Microprocessor Based 100 Amp Capacity, Suitable To Operate 40 Hp Induction Motor ( Iii ) 2 Nos Mccb 63 Amp For Lighting And Fancontrol Panel / Starter :- ( I ) 2 Nos. 25 H.P Soft Starter With Ampere Meter, Power Capacitor, Motor Protections, Indicating Lamps, Toggle Switches And Instrument Fuses Suitable To Scada Operation With Rs485 Port ( Ii ) 3 Nos.40 H.P Soft Starter With Ampere Meter, Power Capacitor, Motor Protections, Indicating Lamps, Toggle Switches And Instrument Fuses Suitable To Scada Opertation With Rs485 Port ( Iii ) Apfc Panal With Scada Compatible Of Suitable Capacityas Per Designnote :- Starter And Mccb Rating May Be Vary As Per Actual Capacity According To Site Situation And No Extra Payment Shall Be Made For This 232 Supply Of Ce / Ul Certified Surge Protector For Control Panel 233 Supply Of 3 Core 35 Sq.Mm Copper Conductor Cable From L.T. Panel To Respective Motors With Lugs Etc. 234 Supply Of Powder Coated Ms Cable Tray 150Mmx50mmx1.6Mm 235 Earthing :-Strip Double Plate Earthing For Complete Electrical Installation In The Pump House ( As Per Ier / Is ) Including Civil Work With All Materials Individual Earthing For Each Equipment Shall Be Carried Out 236 Auto Phase Reversal Unit / Automatic Switch With Inbuilt The Delay & Enclosure ( Confirms To Iec: 60947-1 & Iec: 60947-6-1 ) 315 Amp. 237 Main Piping And Valves :- ( For 1400 Lpm Vt Pumps ) 238 Reflex Valve 150 Mm Size Cidf Pn 1.0 239 Sluice Valve 150 Mm Size Cidf Pn 1.0 ( With Actuater Suitable To Scada Operation ) 240 Sluice Valve 150 Mm Size Cidf Pn 1.0 ( With Actuater Suitable To Scada Operation ) For Common Header 241 Sluice Valve 150 Mm Size Cidf Pn 1.0 ( Manual For Bypass ) 242 Main Pipings1. 150 X 150 X 150 Mm Ms D / F Tee ( 12Mm Thickness ) - 3 No2. 150 Mm Ms D / F Pipe 0.50 Mt. ( 12Mm Thickness ) - 3 No3. 150 Mm Ms D / F Pipe 1.00 Mt. ( 12Mm Thickness ) - 3 No4. 150 Mm Ms D / F Pipe 2.00 Mt. ( 12Mm Thickness ) - 3 No5. 150 Mm Ms D / F ( 12Mm Thickness ) Bend 90O - 3 No6. 150 Mm Blind Flange - 1 No7. Necessary Nut Bolt’S & Rubber Packing - 1 Lotand All Other Specials Required To Complete The Work In Proper Manner 243 Main Piping And Valves :- ( For 2400 Lpm Vt Pumps ) 244 Reflex Valve 150 Mm Size Cidf Pn 1.0 245 Sluice Valve 150 Mm Size Cidf Pn 1.0 ( With Actuater Suitable To Scada Operation ) 246 Sluice Valve 200 Mm Size Cidf Pn 1.0 ( With Actuater Suitable To Scada Operation ) For Common Header 247 Sluice Valve 200 Mm Size Cidf Pn 1.0 ( Manual For Bypass ) - 1 No 248 Main Pipings1. 200 X 150 X 200 Mm Ms D / F Tee ( 12Mm Thickness ) - 3 No2. 150 Mm Ms D / F Pipe 0.50 Mt. ( 12Mm Thickness ) - 3 No3. 150 Mm Ms D / F Pipe 1.00 Mt. ( 12Mm Thickness ) - 3 No4. 200 Mm Ms D / F Pipe 2.00 Mt. ( 12Mm Thickness ) - 3 No5. 200 Mm Ms D / F Bend 90O - 3 No6. 200 Mm Blind Flange - 1 No7. Necessary Nut Bolt’S & Rubber Packing - 1 Lot ( S.S. ) Including All Other Specials Required To Complete The Work In Proper Manner 249 3 Ton Capacity 6.00 Mt Lifting Tackle Manual With Traveling Trolley Chain Pully Block & Double Gurder H Type 250 Tools & Spannerpipe Wrenches - 2Nod / E Spanner 22 / 6 Mm - 6No Adjustable Wrench 300 Mm - 1Noscrew Driver / Tester 250 Mm - 1Noscrew Driver / Tester 200 Mm - 1Noscrew Driver / Tester 150 Mm - 1Nocombination Pliers 200 Mm - 1Nonose Pliers 150 Mm - 1Nohammer With Handle 1 Kg. - 1Noline Tester ( Taparia Make ) - 1No Cripming Tool Of Suitable Size - 1No 251 Co2 / Abc Dry Powder Type Fire Extinguisher 4.5 Kg As Per Is:15683 252 200 Mm Diameter, Ce / Ul Certified Electromagnetic Type Flow Meter Digital Reading 253 150 Mm Diameter, Ce / Ul Certified Electromagnetic Type Flow Meter Digital Reading 254 Internal & External Electrification Of Cwr & Substation With 5 Nos Solar Street Lights 255 Electromegnatic Dozzer Of Suitable Capacity Scada Compatible 256 Ce / Ul Certified Pressure Transmitter For Each Pump 257 Ce / Ul Certified Residual Cholorine Sensor At Oht Outlet 258 Ce / Ul Certified Radar Type Level Sensor With Rtu Communication For Oht 259 Ce / Ul Certified Ultrasonic Level Sensor For Cwr 260 Ce / Ul Certified Electomgnatic Flow Meter At Oht Outlet Of Suitable Size 261 Security Survelliance Ip Camera ( Optional ) 262 1Feet Hight Ms Stand For Lt Panel Made Fromms Angle Iron 263 Testing Of Pumping Plant & Control Panel At Manufacturer Works 264 Installation. Commissioning And Testing Of All Above Equipments As Per Approved Drawings At Cwr Zone -1 Includingpainting Of Pumping Plants. 265 160 Kva Sub Station At Cwr 500 Kl ( Zone-1 ) 266 Indoor Type Floor Mounted Metal Clad, 11 Kv Vcb Ht Panel With 1No. Incoming Vcb & 2Nos Outgoing Vcb Totally Enclosed, Horizontal Drawout, Horizontal / Vertical Isolation Type Breaker As Per Is With All Necessory Protection And Also Should Be Compatible To Scada Operation With Rs485 Port And Multifunction Meter. 267 70 Sq.Mm Size Xlpe Cable From 11 K.V.Uppcl Metering Panel To H.T. Incoming Panel, And H.T. Panel To Transformer. 268 160 Kva, 11 / 0.44 Kv, 3 Phase, 50 Hz, Dyn11, Indoor Onan Type, Copper Wound Transformer With Off Load Tap Changing Arrangement On Hv Side In Steps Of +7.5% & -15%, Lv Side @ 2.5% Each Tapping Complete With All Accessories I / C First Filling Of Filtered Dehydrated Oil And Confirming To Is 1180 ( Revised ) & As Per Specificationcomplete In All Respects As Required At Site. 269 H.T. Cable End Termination Heat Shrink Joint Kit Indore Type 70 Sq.Mm. 270 H.T. Cable End Termination Heat Shrink Joint Kit Outdoor Type 70 Sq.Mm. 271 Earthing System Shall Executed As Per Is : 3043 And I.E. Rules. 272 Sheet Fabricated Factory Wired, Floor Mounting Type L.T. Panel Comprising Of Following. L.T. Panel Comprising Of 2 No Incomer Mccb Of 250 Amp Capacity Panel And 1 No. Outgoing 250 Amp Mccband 1 Nos 250 Amp For Dg Set For Future Planning ( All Are Electrically And Mechanicaly Interlockd ) & 1Nos 63 Amp Mccb For Lighting Complete Panel Of Suitable For Above 160 Kva Transformers. All Mccb Should Be Motorised And Microprocessor Based Compatable For Scada 273 1.1 Kvgrade 120 Sq Mm 3.5 Core Pvcinsulated Armored Aluminum Cable From160 Kva Transformer To L.T. Panel. 274 Rubber Sheet Of Size 1Mx2m And 19 Mm Thick Shock Resistance Sheet 275 Supply , Installation Of Transformer Sub – Station Fencing With Painting Complete. 276 Co2 / Abc Dry Powder Type Fire Extinguisher 4.5 Kg As Per Is:15683 277 Testing Of Ht, Lt Panel & Transformer At Manufactrer Works 278 Installation. Commissioning And Testing Of All Above Equipments As Per Approved Drawings At Cwr Zone -1 Substation. 279 Noc For Substation From Electrical Sefety Department 280 Pumping Plant At 450 Kl Cwr ( Zone - 2 ) Cwr Feed From 6No TwS ( 2Exsisting+3New ) 281 Vt Pumping Plant :- Supply Of2600 Lpm, 40 Mtr Head Or As Per Actual Design , 1450 Rpm , S.S 410 Impeller & Shaft, Pump Casing 2% Nici, Is:210 Fg: 260 Self Water Lubricated Vt Pump Set Coupled With Squirrel Cage Vhs / Vss Tefc Ip-55 Induction Motor ( Operating Voltage 415 V + 10%, 3 Ph, 50Hz + 5% ) 40 Hp Or As Per Actual Design Including Ceepho Margin With Bowl Assembly Discharge Head, Head Shaft, Strainer And 5 Mts Column Assembly To Feed 2150 Kl Oht ( 2W+1S ) 282 L.T Panel With Control Pannel :- 283 Supply Of M.S. Fabricated Dust And Vermin Proof, Cubical Type, Floor Mounted, Lt Panel With Control Panel Compitable To Scada With Rs485 Port Consisting As Following Incoming ( From Transformer ) :-2 No. M.C.C.B. Motorised & Microprocessor Based250 Amp Capacity ( Electrically & Mechanically Interlocked ) & 1 No. M.C.C.B. Motorised & Microprocessor Based250 Amp Capacity & Outgoing 1 No. M.C.C.B. Motorised & Microprocessor Based250 Amp Capacity ( For Dg Set ) Both Are Electrically & Mechanically Interlocked, Volt Meter With Selector Switch, Ampere Meter With Selector Switch, Kwh Smart Meter , Power Factor Meter, Frequency Meter, Indicating Lamps, Toggle Switch, Instrument Fuses And Aluminum Bus Bar. Outgoing :- ( I ) 3 Nos. Outgoing Consist Of Scada Compatible Motorised M.C.C.B. Microprocessor Based 100 Amp Capacity, Suitable To Operate 40 Hp Induction Motor ( Ii ) 2 Nos Mccb 63 Amp For Lighting And Fancontrol Panel / Starter :- ( I ) 3 Nos. 40 H.P Soft Starter With Ampere Meter, Power Capacitor, Motor Protections, Indicating Lamps, Toggle Switches And Instrument Fuses Suitable To Scada Operation With Rs485 Port ( Ii ) Apfc Panel Scada Compatible Of Suitable Capacity As Per Designnote :- Starter And Mccb Rating May Be Vary As Per Actual Capacity According To Site Situation And No Extra Payment Shall Be Made For This 284 Supply Of Ce / Ul Certified Surge Protector For Control Panel 285 Supply Of 3 Core 35 Sq.Mm Copper Conductor Cable From L.T. Panel To Respective Motors With Lugs Etc. 286 Supply & Fixing Of Powder Coated Ms Cable Tray 150Mmx50mmx1.6Mm 287 Earthing :-Strip Double Plate Earthing For Complete Electrical Installation In The Pump House ( As Per Ier / Is ) Including Civil Work With All Materials Individual Earthing For Each Equipment Shall Be Carried Out 288 Auto Phase Reversal Unit / Automatic Switch With Inbuilt The Delay & Enclosure ( Confirms To Iec: 60947-1 & Iec: 60947-6-1 ) 315 Amp. 289 Main Piping And Valves :- ( For 2500 Lpm Vt Pumps ) 290 Reflex Valve 200 Mm Size Cidf Pn 1.0 291 Sluice Valve 200 Mm Size Cidf Pn 1.0 ( With Actuater Suitable To Scada Operation ) 292 Sluice Valve 250 Mm Size Cidf Pn 1.0 ( With Actuater Suitable To Scada Operation ) 293 Sluice Valve 250 Mm Size Cidf Pn 1.0 ( Manual For Bypass ) 294 Main Pipings1. 250 X 200 X 250 Mm Ms D / F Tee ( 12Mm Thickness ) - 3 No2. 200 Mm Ms D / F Pipe 0.50 Mt. ( 12Mm Thickness ) - 3 No3. 200 Mm Ms D / F Pipe 1.00 Mt. ( 12Mm Thickness ) - 3 No4. 250 Mm Ms D / F Pipe 2.00 Mt. ( 12Mm Thickness ) - 3 No5. 250 Mm Ms D / F ( 12Mm Thickness ) Bend 90O - 3 No6. 250 Mm Blind Flange - 1 No7. Necessary Nut Bolt’S & Rubber Packing - 1 Lotincluding All Other Specials Required To Complete The Work In Proper Manner 295 3 Ton Capacity 6.00 Mt Lifting Tackle Manualwith Traveling Trolley Chain Pully Block& Double Gurder H Type 296 Co2 / Abc Dry Powder Type Fire Extinguisher 4.5 Kg As Per Is:15683 297 250Mm Diameter, Ce / Ul Certified Electromagnetic Type Flow Meter Digital Reading 298 Ce / Ul Certified Electomgnatic Flow Meter At Oht Outlet Of Suitable Size 299 Internal & External Electrification Of Cwr & Substation With 5 Nos Solar Street Lights 300 Electromegnatic Dozzer Of Suitable Capacity Scada Compatible 301 Ce / Ul Certified Radar Type Level Sensor With Rtu Communication For Oht 302 Ce / Ul Certified Ultrasonic Level Sensor For Cwr 303 Ce / Ul Certified Pressure Transmitter For Each Pump 304 Ce / Ul Certified Residual Chlorine Sensor At Oht Outlet 305 Security Survelliance Ip Camera With All Required Accessories 306 1Feet Hight Ms Stand For Lt Panel Made Fromms Angle Iron 307 Testing Of Pumping Plant & Control Panel At Manufacturer Works 308 Installation. Commissioning And Testing Of All Above Equipments As Per Approved Drawings At Cwr Zone -2Includingpainting Of Pumping Plants. 309 100 Kva Sub Station At Cwr 450 Kl ( Zone-2 ) 310 Indoor Type Floor Mounted Metal Clad, 11 Kv Vcb Ht Panel With 1No. Incoming Vcb & 2Nos Outgoing Vcb Totally Enclosed & Fully Interlocked, Horizontal Drawout, Horizontal / Vertical Isolation Type Breaker As Per Is With All Necessory Protection And Also Should Be Compatible To Scada Operation With Rs485 Port And Multifunction Meter. 311 70 Sq.Mm Size Xlpe Cable From 11 K.V.Uppcl Metering Panel To H.T. Incoming Panel, And H.T. Panel To Transformer. 312 100 Kva, 11 / 0.44 Kv, 3 Phase, 50 Hz, Dyn 11, Indoor Onan Type, Copper Wound Transformer With Off Load Tap Changing Arrangement On Hv Side In Steps Of +7.5% & -15%, Lv Side @ 2.5% Stapping Complete With All Accessories I / C First Filling Of Filtered Dehydrated Oil And Confirming To Is 1180 ( Revised ) & As Per Specificationcomplete In All Respects As Required At Site. 313 H.T. Cable End Termination Heat Shrink Joint Kit Indoortype 70Sq.Mm. 314 H.T. Cable End Termination Heat Shrink Joint Kit Outdoor Type 70Sq.Mm. 315 Earthing System Shall Executed As Per Is : 3043 And I.E. Rules. 316 1.1 Kvgrade 120 Sq Mm 3.5 Core Pvcinsulated Armored Aluminum Cable Fromtransformer To L.T. Panel. 317 Rubber Sheet Of Size 1Mx2m And 19 Mm Thick Shock Resistance Sheet 318 Supply , Installation Of Transformer Sub – Station Fencing With Painting Complete. 319 Co2 Dry Powder Type Fire Extinguisher 4.5 Kg As Per Is:15683 320 Testing Of Ht Panel & Transformer At Manufactrer Works 321 Installation. Commissioning And Testing Of All Above Equipments As Per Approved Drawings At Cwr Zone -2 Substation. 322 Noc For Substation From Electrical Sefety Department 323 Pumping Plant At 600 Kl Cwr ( Zone - 3 ) Cwr Feed From 7No TwS ( 4Exsisting+3New ) 324 Vt Pumping Plant :- Supply Of3650 Lpm, 40 Mtr Head Or As Per Actual Design , 1450 Rpm , S.S 410 Impeller & Shaft, Pump Casing 2% Nici, Is:210 Fg: 260 Selfwater Lubricated Vt Pump Set Coupled With Squirrel Cage Vhs / Vss Tefc Ip-55 Induction Motor ( Operating Voltage 415 V + 10%, 3 Ph, 50Hz + 5% ) 50 Hp Or As Per Actual Design Including According To Ceepho Manual With Bowl Assembly Discharge Head, Head Shaft, Strainer And 4.5 Mts Column ( Or Suitable Sump Depth ) Assembly To Feed 2350 Kl Oht ( 2W+1S ) 325 L.T Panel With Control Pannel :- 326 Supply Of M.S. Fabricated Dust And Vermin Proof, Cubical Type, Floor Mounted, Lt Panel With Control Panel Compitable To Scada With Rs485 Port Consisting As Following Incoming ( From Transformer ) :-2 No. M.C.C.B. Motorised & Microprocessor Based320 Amp Capacity ( Electrically & Mechanically Interlocked ) & 1 No. M.C.C.B. Motorised & Microprocessor Based320 Amp Capacity & Outgoing 1 No. M.C.C.B. Motorised & Microprocessor Based320 Amp Capacity ( For Dg Set ) Both Are Electrically & Mechanically Interlocked, Volt Meter With Selector Switch, Ampere Meter With Selector Switch, Kwh Smart Meter , Power Factor Meter, Frequency Meter, Indicating Lamps, Toggle Switch, Instrument Fuses And Aluminum Bus Bar. Outgoing :- ( I ) 3 Nos. Outgoing Consist Of Scada Compatible Motorised M.C.C.B. Microprocessor Based 125Amp Capacity, Suitable To Operate 50 Hp Induction Motor ( Ii ) 2 Nos Mccb 63 Amp For Lighting And Fancontrol Panel / Starter :- ( I ) 3 Nos. 50 H.P Soft Starter With Ampere Meter, Power Capacitor, Motor Protections, Indicating Lamps, Toggle Switches And Instrument Fuses Suitable To Scada Operation With Rs485 Port ( Iii ) Apfc Panel Scada Compatible Of Suitable Capacity As Per Design Note :- Starter And Mccb Rating May Be Vary As Per Actual Capacity According To Site Situation And No Extra Payment Shall Be Made For This 327 Ce / Ul Certified Surge Protector For Control Panel 328 Supply Of 3 Core 35 Sq.Mm Copper Conductor Cable From L.T. Panel To Respective Motors With Lugs Etc. 329 Supply & Fixing Of Powder Coated Ms Cable Tray 150Mmx50mmx1.6Mm 330 Earthing :-Strip Double Plate Earthing For Complete Electrical Installation In The Pump House ( As Per Ier / Is ) Including Civil Work With All Materials Individual Earthing For Each Equipment Shall Be Carried Out 331 Auto Phase Reversal Unit / Automatic Switch With Inbuilt The Delay & Enclosure ( Confirms To Iec: 60947-1 & Iec: 60947-6-1 ) 315 Amp. 332 Main Piping And Valves :- ( For 3500 Lpm Vt Pumps ) 333 Reflex Valve 200 Mm Size Cidf Pn 1.0 334 Sluice Valve 200 Mm Size Cidf Pn 1.0 ( With Actuater Suitable To Scada Operation ) 335 Sluice Valve 250 Mm Size Cidf Pn 1.0 ( With Actuater Suitable To Scada Operation ) 336 Sluice Valve 250 Mm Size Cidf Pn 1.0 ( Manual For Bypass ) 337 Main Pipings1. 250 X 200 X 250 Mm Ms D / F Tee ( 12Mm Thickness ) - 3 No2. 200 Mm Ms D / F Pipe 0.50 Mt. ( 12Mm Thickness ) - 3 No3. 200 Mm Ms D / F Pipe 1.00 Mt. ( 12Mm Thickness ) - 3 No4. 250 Mm Ms D / F Pipe 2.00 Mt. ( 12Mm Thickness ) - 3 No5. 250 Mm Ms D / F ( 12Mm Thickness ) Bend 90O - 3 No6. 250 Mm Blind Flange - 1 No7. Necessary Nut Bolt’S & Rubber Packing - 1 Lotincluding All Other Specials Required To Complete The Work In Proper Manner 338 3 Ton Capacity 6.00 Mt Lifting Tackle Manual With Traveling Trolley Chain Pully Block& Double Gurder H Type 339 Co2 / Abc Dry Powder Type Fire Extinguisher 4.5 Kg As Per Is:15683 340 250 Mm Diameter, Ce / Ul Certified Electromagnetic Type Flow Meter Digital Reading 341 Ce / Ul Certified Electomgnatic Flow Meter At Oht Outlet Of Suitable Size 342 Internal & External Electrification Of Cwr & Substation With 5 Nos Solar Street Lights 343 Electromegnatic Dozzer Of Suitable Capacity Scada Compatible 344 Ce / Ul Certified Radar Type Level Sensor With Rtu Communication For Oht 345 Ce / Ul Certified Ultrasonic Level Sensor For Cwr 346 Ce / Ul Certified Pressure Transmitter For Each Pump 347 Ce / Ul Certified Residual Cholorine Sensor 348 Security Survelliance Ip Camera With Required Accessories 349 Testing Of Pumping Plant & Control Panel At Manufacturer Works 350 1Feet Hight Ms Stand For Lt Panel Made Fromms Angle Iron 351 Installation. Commissioning And Testing Of All Above Equipments As Per Approved Drawings At Cwr Zone -3 Includingpainting Of Pumping Plants. 352 160 Kva Sub Station At Cwr 600 Kl ( Zone-3 ) 353 Indoor Type Floor Mounted Metal Clad, 11 Kv Vcb Ht Panel With 1No. Incoming Vcb & 2Nos Outgoing Vcb Totally Enclosed & Fully Interlocked, Horizontal Drawout, Horizontal / Vertical Isolation Type Breaker As Per Is With All Necessory Protection And Also Should Be Compatible To Scada Operation With Rs485 Port And Multifunction Meter. 354 70 Sq.Mm Size Xlpe Cable From 11 K.V.Uppcl Metering Panel To H.T. Incoming Panel, And H.T. Panel To Transformer. 355 160 Kva, 11 / 0.44 Kv, 3 Phase, 50 Hz, Dyn 11, Indoor Onan Type, Copper Wound Transformer With Off Load Tap Changing Arrangement On Hv Side In Steps Of +7.5% & -15%, Lv Side @2.5% Stapping Complete With All Accessories I / C First Filling Of Filtered Dehydrated Oil And Confirming To Is 1180 ( Revised ) & As Per Specificationcomplete In All Respects As Required At Site. 356 H.T. Cable End Termination Heat Shrink Joint Kit Indore Type 70 Sq.Mm. 357 H.T. Cable End Termination Heat Shrink Joint Kit Out Door Type 70 Sq.Mm. 358 Earthing System Shall Executed As Per Is : 3043 And I.E. Rules. 359 1.1 Kvgrade 120 Sq Mm 3.5 Core Pvcinsulated Armored Aluminum Cable From160 Kva Transformer To L.T. Panel. 360 Rubber Sheet Of Size 1Mx2m And 19 Mm Thick Shock Resistance Sheet 361 Supply , Installation Of Transformer Sub – Station Fencing With Painting Complete. 362 Co2 / Abc Dry Powder Type Fire Extinguisher 4.5 Kg As Per Is:15683 363 Testing Of Ht Panel & Transformer At Manufactrer Works 364 Installation. Commissioning And Testing Of All Above Equipments As Per Approved Drawings At Cwr Zone -3 Substation 365 Noc For Substation From Electrical Sefety Department 366 Scada Works Of Tubewells ( 18 No ) 367 Supply, Storage, Installation, Testing And Comissioning Of Ce & Ul Certified Plc / Rtu In Ip 54 Enclosure Suitable To Communicate With Intelligent Gsm Based Modem Unit With Cpu And Power Supply With Analog And Digital Parameter And Features As Specified. One Each For Each Tubewell To Store And Transmit Data On Gsm Backbone, Rtu Designed With Logic To Tansfer Data At Multiple Stations And Also Compatible For Satellite Communication Along With Control Panel For All Equipment And 24V Power Supply 368 Supply, Storage, Installation, Testing And Comissioning Of Gsm / Gprs Based Wireless Communication With 4G Modem For Rtu / Plc Capable To Transfer And Gather Data From Remote Sites To Control Stations All Accessories Included With Signal Enhancer, Antenna Made For Pumping Plant With Sim And Recharge Till Handed Over 369 Supply, Storage, Installation, Testing And Comissioning Of Ce & Ul Certified 7 Hmi Touch Screen Suitable To Communication With Plc / Rtu For Local Display & Control Of Process Parameters 370 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified Intelligent Energy Meters With Communication Port 371 Scada Works Of 500 Kl Cwr To 350 Kl Oht & 1550 Kl Oht ( Zone-1 ) ( Having 5 Nos Pumps ) 372 Supply, Storage, Installation, Testing And Comissioning Of Ce & Ul Certified Plc / Rtu In Ip 54 Enclosure Suitable To Communicate With Intelligent Gsm Based Modem Unit With Cpu And Power Supply With Analog And Digital Parameter And Features As Specified For Each For Each Zps / Oht To Store And Transmit Data On Gsm Backbone, Rtu Designed With Logic To Tansfer Data At Multiple Stations And Also Compatible For Satellite Communicationalong With Control Panel For All Equipment And 24V Power Supply 373 Supply, Storage, Installation, Testing And Comissioning Of Gsm / Gprs Based Wireless Communication With 4G Modem For Rtu / Plc Capable To Transfer And Gather Data From Remote Sites To Control Stations All Accessories Included With Signal Enhancer, Antenna Made For Pumping Plantwith Sim Andrecharge Till Handed Over 374 Supply, Storage, Installation, Testing And Comissioning Of Ce & Ul Certified 7 Hmi Touch Screen Suitable To Communication With Plc / Rtu For Local Display & Control Of Process Parameters 375 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified Intelligent Energy Meters 376 Complete Cabling For Cwr & Oht ( Above 3 Pumps ) 377 Scada Works Of 450 Kl Cwr To 2150 Kl Oht ( Zone-2 ) ( For 3 Pumps ) 378 Supply, Storage, Installation, Testing And Comissioning Of Ce & Ul Certified Plc / Rtu In Ip 54 Enclosure Suitable To Communicate With Intelligent Gsm Based Modem Unit With Cpu And Power Supply With Analog And Digital Parameter And Features As Specified For Each For Each Zps / Oht To Store And Transmit Data On Gsm Backbone, Rtu Designed With Logic To Tansfer Data At Multiple Stations And Also Compatible For Satellite Communication Along With Control Panel For All Equipment And 24V Power Supply 379 Supply, Storage, Installation, Testing And Comissioning Of Gsm / Gprs Based Wireless Communication With 4G Modem For Rtu / Plc Capable To Transfer And Gather Data From Remote Sites To Control Stations All Accessories Included With Signal Enhancer, Antenna Made For Pumping Plantwith Sim Andrecharge Till Handed Over 380 Supply, Storage, Installation, Testing And Comissioning Of Ce & Ul Certified 7 Hmi Touch Screen Suitable To Communication With Plc / Rtu For Local Display & Control Of Process Parameters 381 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified Intelligent Energy Meters 382 Complete Cabling For Cwr & Oht ( Upto 3Pumps ) For Scada 383 Scada Works Of 600 Kl Cwr To 2350 Kl Oht ( Zone-3 ) ( For 3 Pumps ) 384 Supply, Storage, Installation, Testing And Comissioning Of Ce & Ul Certified Plc / Rtu In Ip 54 Enclosure Suitable To Communicate With Intelligent Gsm Based Modem Unit With Cpu And Power Supply With Analog And Digital Parameter And Features As Specified For Each For Each Zps / Oht To Store And Transmit Data On Gsm Backbone, Rtu Designed With Logic To Tansfer Data At Multiple Stations And Also Compatible For Satellite Communicationalong With Control Panel For All Equipment And 24V Power Supply 385 Supply, Storage, Installation, Testing And Comissioning Of Gsm / Gprs Based Wireless Communication With 4G Modem For Rtu / Plc Capable To Transfer And Gather Data From Remote Sites To Control Stations All Accessories Included With Signal Enhancer, Antenna Made For Pumping Plantwith Sim Andrecharge Till Handed Over 386 Supply, Storage, Installation, Testing And Comissioning Of Ce & Ul Certified 7 Hmi Touch Screen Suitable To Communication With Plc / Rtu For Local Display & Control Of Process Parameters 387 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified Intelligent Energy Meters 388 Complete Cabling For Cwr & Oht ( Upto 3Pumps ) For Scada 389 Local Control Station ( Lcs ) For TwS And CwrS 390 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul & Bis Certified Industrial Grade Led Monitor With Latest Configuration As Per Specification 65 ( Upto 50 Tubewells ) 391 Supply, Storage, Installation, Testing And Comissioning Of Full Development Version Of Tags Scada Software With Costomization Of Software For Mcs For Unlimited Digital And Analog Input / Output Features As Per Requirements 392 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified Local Control Room Plc With Redundant Cpu & Power Supply At Mcs In Ip-54 Enclosure As Per Site Requirement And Specification Required To Complete In All Respect 393 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified Field Gateway Agent For Transfering Data From Mcs To Central Control Room 394 Supply, Storage, Installation, Testing And Comissioning Of Gsm / Gprs Based Wireless / Broadband / Equivelent Communication System For Plc Capable To Transfer And Receive Data & Gather Data From Remote Sites To Control Stations All Accessories Included With Signal Enhancer, Antenna Along With Running Expences Till Dlp 395 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified Firewall For Network Protection 396 Supply, Storage, Installation, Testing And Comissioning Of Surge Protector For Ethernet Communication Protection 397 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified Industrial Grade Ethernet Switch 398 Supply, Storage, Installation, Testing And Comissioning Of Ce / Ul Certified 3 Kva Ups With Batterieswith 02 Hrs Backup Required For Mentioned Work 399 Supply, Storage, Installation, Testing And Comissioning Of Hp Or Equivalent 600 Dpi Ink Jet Colour Printer 400 Supply, Storage, Installation, Testing And Comissioning Of Hp Or Equivalent Laser Printer 1018 Or Equivalent. 401 Core I5 10Th Gen Desktop With 8 Gb Ram And 1Tb Ssd 402 Core I5 10Th Gen 15.6 Inch Laptop With 8 Gb Ram And 1Tb Ssd For Scada Presentation And Record Work 403 Supply, Storage, Installation, Testing And Comissioning Of Security Survelliance Ip Camera With Recorder 404 Installation. Commissioning And Testing With Required Furniture 405 Trial & Run For 3 Months For Electrical - Mechanical & Scada Work With Operators, Technician And Scada Operators 406 Sodium Hypochloride For 3 Months Trial & Run

Key Value

Document Fees
INR 23600 /-
EMD
INR 5080000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Jalaun Nagar Palika Parishad W/s Scheme Under Amrut 2.0
Sl. No. Item Description
1Construction OF R.C.C Clear Water Reservoir (C.W.R) cum Pump House of Various Zonal Sites
2Design and supply of all labour,material T&P etc to construct RCC Clear Water Resevoir cum pump house of required capacity in all type of strata with HT, LT and meter room, MS pipes railling consisting of 3 rows and posts on the roof/doom periphery, M.S ladder from ground level to top of tank and inside the tank, locking device, CI cowl type with mosquito mesh ventilator, supply and fixing water level indicator, 25mm PCC 1:2:4 over 80mm PCC 1:4:8 in apron, 150 mm semicircular drain around the tank, two coats of apex paint of approved make and testing of tank for water tightness etc. and also including the cost of supply and fixing of all necessary pipe assembly and valves with by pass arrangement etc all complete as per approved design and drawing. (detail specification as per tender document)
3500 KL in Zone 1
4450 KL in Zone 2
5600 KL in Zone 3
6Construction of R.C.C Over Head Tank (OHT) of various capacity at different sites/zones
7Design & supply of all labour material T&P etc and construct RCC over head Tank of following capacity and staging including inlet outlet washout & overflow arrangements with RCC two column staircase & 1m wide balcony,G.I pipes ralling consisting of 3 rows of 20mm dia G.I pipe and angle iron posts around balcony and at the dome periphery, M.S. ladder from balcony to top of tank and inside the tank, MS grill gate of 2 m height and box type enclosure at entrance of staircase with locking arrangement, chambers for all valves, ventilating shafts with steel frame and fixing G.I fly proof mesh of 26 gauge, CI manhole frame and covers, copper lightening conductor, fixing of puddle collars and bell mouths, supply and fixing M.S. clamps with RCC column, fixing of water level indicator, 25mm PCC 1:2:4 over 80mm PCC 1:4:8 in apron, 150mm semicircular drain around the tank, escape channel of 20m length, two coats of apex paint of approved make and testing of tank for water tightness etc. and also including the cost of supply and fixing of all necessary pipes assembly and valves with bypass arrangement etc all complete as per approved design and drawing. (detail specification as per tender document)
81550 / 20 m stagging in Zone 2
91800 / 22 m stagging in Zone 2
102350 / 22 m stagging in Zone 3
11Add or substract according to the stagging height of OHT if increased or decreased, it also includes variation in foundation and staircase accordingly.
12Renovation of Existing Over Hand Tank of following capacity in Zone 1 including repairing of floor, drain, appron, balcony walls & columns with scracping of old concrete and CC grouting with waterproofing chemical for water tightness inside and outside of container wall, fixing/reparing of railing, pipes, valves and fittings, chambers, ventilator shaft, fixing of manhole covers, water level indicator and lightning conductor, apex painting with two coats etc including all labour, material t&p etc for proper completion of work.
13350 KL/ 20 m stagging
14Dismantling of Existing Old Over Head Tank of following Capacity at Zone 1 by mechnical or manual means including supply of all labour, material t&p required for completion of work with proper safety measures to be carried out during dismantling of OHT necessary to safegaurd the nearby structures and disposal of malwa or dismantelled material upto 8km lead as per directions.
15200 KL/18 m stagging
16Pump House
17Renovation of existing pumphouse
18construction of staff quarter with pile foundationas per approved design/drawing including with pile foundationwith supply of all material, labour, t&p all complete with providing complete doors, windows, ventilators, flooring, painting, drainage, electricity, plumbing and lighting facilities as per requirement.
19Type I - 2 set (3 Nos.) - 40.80 sqm
20Type II (1 Nos.) - 54 sqm
21Type III (1 Nos.)- 63 sqm
22Demolition/dismantling of abandoned existing old staff quarters, pumphouse, store etc at Jalsansthan water works campus including shifting/disposal of dismantled malwa/scrap upto 8 km lead as per directions.
23construction of Administrating building as per approved design/drawing at site demarcated with pile foundationfor the same including all labour, material t&p all complete as per reqiurement alongwith making provision of water supply testing lab with supply and installation of all necessary apparatus and euipments to completely fufill the testing requirement of potable water supplied to the consumers
24Building work complete in all respect
25Lab Equipments as per requirements
26Construction of Boundary wall as per approved design/drawing including supply of all labour, material T&P etc to complete the work. With pile foundation andYShape M.S Angel Iron including concertina coil fencing. Including Painting departmental approved colour
27Zonal water supply campus
28MS Gate as per approved drawing with priming coat and paint as per specifications.
29MS wicket gate as per approved drawing with priming coat and paint as per specifications.
30Construction of new interlocking tile road as per approved drawing and specifications inside water work campus, levelling & plantation for asthetically development of water work campus as per directions.
31Filling of good earth in lower portion at various zonal campus including levelling and dressing with proper compaction by mechnical or manual means at water work campus.
32Design and construction of RWH chamber with all necessary arrangement as per approved design/drawing for Rain Water Harvesting at zonal water works and admin building etc including supply of all labour, material t&p for proper completion of work.
33Distribution network
34Supply of ISI Marked or its relevant code HDPE Pipes of approved make of follwing sizes (Dia in mm) with jointing materials, (Electric Fusion Coupler)specials of sizes required during constructionas per latest I.S.amendement upto site of work including loading, unloading, cartage insurance, etc all completed but exclusive of GST in various zone as per the drawing and approval of Engineer.
35HDPE PIPE GRADE PE 100/ PN 6- 90 mm
36HDPE PIPE GRADE PE 100/ PN 6- 110 mm
37HDPE PIPE GRADE PE 100/ PN 6- 140 mm
38HDPE PIPE GRADE PE 100/ PN 6- 160 mm
39Supply of ISI Marked or its relevant code DI K-7 Pipes of approved make of follwing sizes (Dia in mm) with jointing materials, during construction as per latest I.S amendements upto site of work including loading unloading cartage insurance, etc all completed but exclusive of GST in various zone as per the drawing and approval to Engineer.with sectional testing
40D.I. K-7/ 200 mm
41D.I. K-7/ 250 mm
42D.I. K-7/ 300 mm
43D.I. K-7/ 350 mm
44D.I. K-7/ 400 mm
45Supply of following size ofSluice Valves/ Scour Valves, Fire hydrants & Air Valves of approved make as per relevent I.S or its latest amandementup to store/site of work including loading, unloading & cartage, taxes duties insurance etc all complete. As per IS: 2906-1969.
46Air Valve as per as I.S : 14845
4720 mm. dia DI D/FAir Valve
48D.I. D/F Sluice valve/ Scour valve
49100 mm dia.
50200 mm dia.
51250 mm dia.
52300 mm dia.
53350 mm dia.
54400 mm dia.
55Fire hydrant (65 mm dia.)
56Dismantling of following types of roads including sorting out of servicable materials stacking and disposal of unservicable matarials with in a distance of 50 m. including supply of labour specials T&P etc. required for proper completion of work.
57Interlocking tile
58C.C Road
59Bituminous Road
60B.O.E Road
61Excavation for pipe line trenches in all type of soil requiring use of specialT&P etc. with lift upto 1.5 m lead upto 50 mincluding filling back of excavated earth into trenches and watering ranmming dressing and removal of surplus earth upto 50m including supply of alllabour T&P etc complete and as per direction of engineer incharge.
62Cartage from local store to site of work for following size (dia in mm)HDPE pipes and specials coupling, fittings, and lowering the same into trenches and laying true to alignment and gradiant including testing of pipe lines cuttings of pipes for making up the length and making joints with electrofusion couplers, bends, tees, endcap etc. with electrofusion machinery including all jointing materials, labour, T&P etc required for proper completion of work. & including sectional testing.
63HDPE PIPE GRADE PE 100/ PN 6- 90 mm
64HDPE PIPE GRADE PE 100/ PN 6- 110 mm
65HDPE PIPE GRADE PE 100/ PN 6- 140 mm
66HDPE PIPE GRADE PE 100/ PN 6- 160 mm
67Cartage of DI K-7 pipes and specials of following size (dia in mm)from store to site of work, lowering them into trenches and laying, jointing true to alignment and gradiant including testing of pipe line but excluding cost of trenching including all supply of Labour T&P and all jointing material etc complete required for proper completion of work.
68D.I. K-7/ 200 mm
69D.I. K-7/ 250 mm
70D.I. K-7/ 300 mm
71D.I. K-7/ 350 mm
72D.I. K-7/ 400 mm
73Carting of following size of Sluice Valves/ Scour Valves, Fire hydrants & Air Valves from store to site of work and lowering them into the trenches, fixing in position and jointing them with Pipe line and testing etc including supply of jointing materialand also including supply of all material and construction of suitable P.C.C support below fittings etc all complete.
7420 mm dia DI D/F Air Valve
75D.I. D/F Sluice valve/ Scour valve
76100 mm dia.
77200 mm dia.
78250 mm dia.
79300 mm dia.
80350 mm dia.
81400 mm dia.
82Fire hydrant (65 mm dia.)
83Design and construction of R.C.C. Thrust block with cement, coarse sand, and 20mm gauges stone ballast in propotion of 1:1.5:3 in thrust block of pipe line including reinforcement and its bending the same with 0.08 mm thick binding wire in position and necessary shuttring including proper curing and supply of all materials, labour and T&P etc required for proper completion of work as approved by Engineer.
84For 250 mm to 400 mm dia
85For 80 mm to 200 mm dia
86Reinstatement of following types of roads including sorting out of servicable materials stacking and disposal of unservicable materials with in a distance of 50 m. including supply of required new matarials & reinstatement the same including supply of labour T&P etc. required for proper completion of work.
87Interlocking tile
88C.C Road
89Bitumenous Road
90B.O.E Road
91Supply of all matarial labour T&P etc and constuction of following type of chamber as per approved design & drawing according to diretion of engineer incharge .
92Sluice valve chamber
93Scour Valve Chamber
94Air Valve chamber
95Fire hydrant chamber
96Provision for shifting of house connection which are cominginpipe line alignment during excavation including all labour, material t&p etc all complete.
97Upto 110 mm dia
98For 125 mm to 160 mm dia
99For 180 mm to 250 mm dia
100Provision for Nala/Culvert crossing including all materials, labour and T&P etc. complete. It includes supply of DI/HDPE pipe & specials of required size for encasing, cement concrete and Brickwork for pillars and any other job for proper completion of work.
101For crossing of (1.0to 1.5 m wide)
102For crossing of (1.5to 2.0 m wide)
103Construction of Single Tap pillar type Stand post including all material, labour T&P etc complete
104Provision for Inter Connection with existing pipeline from new pipe line including bailing out of water, fixing of clamps etc. complete for proper completion of work.including all material, labour T&P etc complete forproper completion of work.
105250 mm D.I.
106200 mm D.I.
107160 mm HDPE
108110 mm HDPE
10990 mm HDPE
110Rising Main
111Supply of ISI Marked or its relevant code DI K-7/K-9 Pipes of follwing sizes (Dia in mm) with jointing materials, specials of sizes required during construction included jointing as per latest I.S.Samandement upto site of work included loading unloading cartage insurance, etc all completed but exclusive of GST in various zone as per the drawing and approval of Engineer.
112D.I. K-7/ 150 mm
113D.I. K-7/ 200 mm
114D.I. K-7/ 250 mm
115D.I. K-7/ 300 mm
116D.I. K-9/ 350 mm
117Supply of following size ofSluice Valves/ Scour Valves, Fire hydrants & Air Valves as per relerelavent I.S.I or its latest amandement. Up to store Including loading, unloading & cartage, taxes duties insurance etc all complete. As per IS: 2906-1969.
118D.I. D/F Sluice valve/ Scour valve
119150 mm dia.
120200 mm dia.
121250 mm dia.
122300 mm dia.
123350 mm dia.
124Dismantling of following types of roads including sorting out of servicable matarials stacking and disposal of unservicable matarials with in a distance of 50 m including supply of labour specials T&P etc. required for proper completion of work
125Interlocking tile
126C.C Road
127Bitumenous Road
128B.O.E Road
129Excavation for pipe line trenches in ordinary soil use ofspecialT&P etc with lift upto 1.5 m lead upto 50 m including filling back of excavated earth into trenches and watering ranmming dressing and removal of surpluas earth upto 50m including supply of all materials labour T&P etc complete and as per direction of engineer incharge.
130Cartage of following size (dia in mm.) of DI K-7/K-9 pipes and specials includingjointingmaterials from store to site of worklowering the same into excavated pipe line tenches true toaligment and gradidient and jointing the same including testing of pipe line including supply of all materials labaour T&P etc complete and as per direction of engineer incharge
131D.I. K-7/ 150 mm
132D.I. K-7/ 200 mm
133D.I. K-7/ 250 mm
134D.I. K-7/ 300 mm
135D.I. K-9/ 350 mm
136Carting of following size of Sluice Valves/ Scour Valves, from store to site of work and lowering them into the trenches, fixing in position and jointing them with Pipe line and testing etc including supply of jointing materialand also including supply of all material and construction of suitable P.C.C Support below fittings etc. complete.
137D.I. D/F Sluice valve
138150 mm dia.
139200 mm dia.
140250 mm dia.
141300 mm dia.
142350 mm dia.
143R.C.C. Thrust block with cement, core sand, and 20mm gauges stone ballast in propotion of 1:1.5:3 in thrust block of pipe line including reinforcement and its bending the same with 0.08 mm thick binding wire in position and necessary shuttering including proper curing and supply of all materials, labour and T&P etc required for proper completion of work.
144For 250 mm to 400 mm dia
145For 80 mm to 200 mm dia
146Supply of all material labour T&P etc for constuction of following type of chamber as per type design & drawing according to diretion of engineer-in-charge .
147Sluice valve/Scour Valve chamber
148Reinstatement of following types of roads including sorting out of servicable matarials stacking and disposal of unservicable matarials with in a distance of 50 m. including supply of required new matarials & reinstatement the same includng supply of labour specials T&P etc required for proper completion of work.
149Interlocking Road
150C.C Road
151Bitumen Road
152B.O.E Road
153Making water supply house connection in New/Existing pipe line as per approved drawing and material including supply of all labour, material T&P required for proper completion of house connection work as per approved drawing,
154In Kachcha Road
155Upto 110 mm dia
156For 300 mm dia
157For 350 mm to 500 mm dia
158In BOE Road
159Upto 110 mm dia
160For 125 mm to 160 mm dia
161For 180 mm to 250 mm dia
162In Cement Concrete Road
163Upto 110 mm dia
164For 125 mm to 160 mm dia
165For 180 mm to 250 mm dia
166For 300 mm dia
167For 350 mm to 500 mm dia
168In Bituminous Road
169Upto 110 mm dia
170For 125 mm to 160 mm dia
171For 180 mm to 250 mm dia
172For 300 mm dia
173In Interlocking Road
174Upto 110 mm dia
175For 125 mm to 160 mm dia
176For 180 mm to 250 mm dia
177ELECTRICAL AND MECHANICAL WORKS (Supply, storage,testing and comissioning and Trail & Run of Following as per details)
178CONSTRUCTION OF (9No)NEW & (2No)REBORE TUBEWELLS
179Resistivity Survey of Tubewell Site
180Transportation of rig machine erection, dismantling and associated T&P Complete in all respect including required all material , labour etc.
181DRILLING OF TUBEWELL BORE
182Drilling of 550 mm. dia bore from G.L. to 100M. BGL (100mx11No)
183Drilling of 550 mm. dia bore from 101 BGL to 120M. BGL (20mx11No)
184Logging of bore hole by electirc logger
185TUBEWELL ASSEMBLY
186M.S. tube well assembly with all required parts like plain pipe, slotted pipe rings,, well cap, bail plug clamp, reducer, central guide, support structure etc. as required and as per typed design complete in all respect.
187300 mm. dia 7.1 mm thick MSERW Plain Pipe with MS ring & reducer(60mx11No)
188200 mm.dia 7.1 mm thick M.S. Plain pipe & Slotted pipe with MS ring(50mx11No)
189Lowering of tubewell assembly duly welded including welding electrode and shrounding of pea Gravel complete in all respect.
190300 mm. dia 7.1mm thick MSERW Plain/Slotted Pipe
191200 mm. dia Plain/Slotted Pipe 61 M. BGLto 110 M. BGL
192DEVELOPMENT OF TUBEWELL
193Transportation, Erection, Dismantling of 250 P.S.I. Compressor.
194Development by 250 P.S.I. Compressor
195Transportation, Erection, Dismantling of 2 Cusec O.P. Unit and yeild Test.
196Development by 2 Cusec/Suitable capacity O.P. Unit
197Chemical and Bacteriological test of water sample form departmentel / approved lab.
198Supply & Shrouding of Lal Kuan Pea Gravel 1.6 to 4.8 mm. size for Tubewell
199PUMPING PLANT FOR NEW AND REBORE TUBWELLS WITH PAINTING WORK
200Supply, installation,testing and commissioning of Clear water submersible pump (IS 9236) complete with electric motor (IS 8034) capable to operate on 380/420 volts 3 phase 50 c/s A.C. supply of 1000 Lpm, 60 mtr Head or as per design & HP as per Design with margin according to CEEPHO manual
201Supply, installation,testing and commissioning of Main Piping & Valves with 24Mtr. Column pipe, power wiring, earthing, painting, wiring of pump house (Internal & External)and gauges complete in all respect with all required material, T&P labour 100 mm Dia. size
202Supply, installation,testing and commissioning of 3 Mtr Long Heavy duty exta Coloum pipe 100 mm Dia. Size (8 Nos for each TW)
203Supply, installation,testing and commissioning of Electrically Operated Actuater suitable for 100 mm Size sluice valves (1No for Each TW)
204Supply, installation,testing and commissioning of Submersible flat copper condutor cable 1x3Cx4mm2 PVC Sheathed double run (1x2Rx30m=60m for each TW)
205Supply, installation,testing and commissioning of PVC Sheathed Aluminium armoured cable from UPPPCL Pole/Trasformer to Meter and Meter to Pump house 1x3.5Cx25mm2
206Supply, installation,testing and commissioning of SCADA compitable 3 Phase Control Panel with Soft stater module incuding RS 485 Port- 400 V suitable to operate TW submersible pumping plant
207Supply & Installtion of 30 KVA Servo VoltageStablizer with 63Amp changeover switch
208Supply, installation,testing and commissioning ofof 2 Ton 4.5 mtr lift chain pully block
209Supply, installation,testing and commissioning of CE/UL Certified Electromegnatic flowmeter 100mm
210Supply, installation,testing and commissioning of Auto phase reversal unit with inbuilt time delay & enclosure (conforming to IEC:60947-1 & IEC:60947-b-1) suitable to 25 HP
211Supply, installation,testing and commissioning of CE/UL Certified Pressure transmitter
212Supply, installation,testing and commissioning of CE/UL Certified Surge protector for control panel
213Supply, installation,testing and commissioning of Security Survelliance IP Camera with required accessories
214RENNOVATION WORK OF EXSISTING WORKS WITH PAINTING WORK
215Supply, installation,testing and commissioning of Clear water submersible pump (IS 9236) complete with electric motor (IS 8034) capable to operate on 380/420 volts 3 phase 50 c/s A.C. supply of 1000 Lpm, 60mtr Head or as per design & HP as per Design with margin according to CEEPHO manual
216Supply, installation,testing and commissioning of Main Piping & Valves with 24Mtr. Column pipe, power wiring, earthing, painting, wiring of pump house (Internal & External)and gauges complete in all respect with all required material, T&P labour 100 mm Dia. size
217Supply, installation,testing and commissioning of 3 Mtr Long Heavy duty exta Coloum pipe 100 mm Dia. Size (8 Nos for each TW)
218Supply, installation,testing and commissioning of Electrically Operated Actuater suitable for 100 mm Size sluice valves (1No for Each TW)
219Supply, installation,testing and commissioning of Submersible flat copper condutor cable 1x3Cx4mm2 PVC Sheathed double run (1x2Rx30m=60m for each TW)
220Supply, installation,testing and commissioning of SCADA compitable 3 Phase Control Panel with Soft stater module incuding RS 485 Port- 400 V suitable to operate TW submersible pumping plant
221Supply & Installtion of 30 KVA Servo VoltageStablizer with 63Amp changeover switch
222Supply, installation,testing and commissioning of CE/UL Certified Electromegnatic flowmeter 100mm
223Supply, installation,testing and commissioning of Auto phase reversal unit with inbuilt time delay & enclosure (conforming to IEC:60947-1 & IEC:60947-b-1) suitable to 25 HP
224Supply, installation,testing and commissioning of CE/UL Certified Pressure transmitter
225Supply, installation,testing and commissioning of CE/UL Certified Surge protector for control panel
226Supply, installation,testing and commissioning of Security Survelliance IP Camera with required accessories
227PUMPING PLANT AT 500 KL CWR (ZONE - 1) CWR feed from 6No TW"s (3exsisting+3new)
228(A) VT Pumping Plant :- Supply of 1400 LPM,Head as per actual design , 1450 RPM , S.S 410 impeller & shaft,Pump Casing 2% NiCi,IS:210 FG: 260 Self Water Lubricated VT Pump set coupled with squirrel cage VHS/VSS TEFC IP-55 induction motor (Operating Voltage 415 V + 10%, 3 ph, 50Hz + 5%) as per actual design including according to CEEPHO manual with Bowl Assembly Discharge Head, Head Shaft, Strainer and 5 mts (or suitable sump depth) Column Assembly to feed 350 KL Exsisting OHT (1w+1s)
229(B) VT Pumping Plant :- Supply of 2400 LPM,Head as per actual design, 1450 RPM , S.S 410 impeller & shaft,Pump Casing 2% NiCi,IS:210 FG: 260Self Water LubricatedVT Pump set coupled with squirrel cage VHS/VSS TEFC IP-55 induction motor (Operating Voltage 415 V + 10%, 3 ph, 50Hz + 5%) as per actual design including according to CEEPHO manual with Bowl Assembly Discharge Head, Head Shaft, Strainer and 5 mts (or suitable sump depth) Column Assembly to feed 1550 KL New OHT (2w+1s)
230CONTROL PANNEL :-
231Supply of M.S. Fabricated Dust and Vermin Proof, Cubical Type, Floor Mounted, Control Panel compitable to SCADA with RS485 Port consisting as following INCOMING :-1 No. M.C.C.B. motorised & microprocessor based250 Amp capacity OUTGOING :- (i) 2 Nos. Outgoing Consist of SCADA Compatible Motorised M.C.C.B. microprocessor based 80Amp Capacity, suitable to operate 25 HP induction motor (ii) 3 Nos. Outgoing Consist of SCADA Compatible Motorised M.C.C.B.microprocessor based 100 Amp Capacity, suitable to operate 40 HP induction motor (iii) 2 Nos MCCB 63 Amp for lighting and fan Control Panel / Starter :- (i) 2 Nos. 25 H.P Soft starter with Ampere Meter, Power Capacitor, Motor protections, Indicating Lamps, Toggle Switches and Instrument Fuses suitable to SCADA operation with RS485 Port (ii) 3 Nos.40 H.P Soft Starter with Ampere Meter, Power Capacitor, Motor protections, Indicating Lamps, Toggle Switches and Instrument Fuses suitable to SCADA opertation with RS485 Port (iii) APFC Panal with SCADA compatible of suitable capacityas per design Note :- Starter and MCCB rating may be vary as per actual capacity according to site situation and no extra payment shall be made for this
232supply of CE/UL Certified Surge protector for control panel
233Supply of 3 Core 35 sq.mm Copper Conductor Cable from L.T. Panel to respective Motors with lugs etc.
234Supply of Powder coated MS Cable Tray 150mmx50mmx1.6mm
235EARTHING :-Strip Double Plate Earthing for Complete Electrical Installation in the Pump House (As per IER/IS) including civil work with all materials Individual Earthing for each equipment shall be carried out
236Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1) 315 Amp.
237MAIN PIPING AND VALVES :-( for 1400 LPM VT Pumps)
238Reflex Valve 150 mm size CIDF PN 1.0
239Sluice Valve 150 mm Size CIDF PN 1.0 ( with actuater suitable to SCADA operation)
240Sluice Valve 150 mm Size CIDF PN 1.0 ( with actuater suitable to SCADA operation) for common header
241Sluice Valve 150 mm Size CIDF PN 1.0 (Manual for Bypass)
242Main Pipings 1. 150 x 150 x 150 mm MS D/F Tee (12mm thickness) - 3 No 2. 150 mm MS D/F Pipe 0.50 mt. (12mm thickness) - 3 No 3. 150 mm MS D/F Pipe 1.00 mt.(12mm thickness) - 3 No 4. 150 mm MS D/F Pipe 2.00 mt. (12mm thickness) - 3 No 5. 150 mm MS D/F (12mm thickness) Bend 90o - 3 No 6. 150 mm Blind Flange - 1 No 7. Necessary Nut Bolt’s & Rubber Packing - 1 Lot And all other specials required to complete the work in proper manner
243MAIN PIPING AND VALVES :-( for 2400 LPM VT Pumps)
244Reflex Valve 150 mm size CIDF PN 1.0
245Sluice Valve 150 mm Size CIDF PN 1.0 ( with actuater suitable to SCADA operation)
246Sluice Valve 200 mm Size CIDF PN 1.0 ( with actuater suitable to SCADA operation) for common header
247Sluice Valve 200 mm Size CIDF PN 1.0 (Manual for Bypass)- 1 No
248Main Pipings 1. 200 x 150 x 200 mm MS D/F Tee (12mm thickness) - 3 No 2. 150 mm MS D/F Pipe 0.50 mt. (12mm thickness) - 3 No 3. 150 mm MS D/F Pipe 1.00 mt. (12mm thickness) - 3 No 4. 200 mm MS D/F Pipe 2.00 mt. (12mm thickness) - 3 No 5. 200 mm MS D/F Bend 90o - 3 No 6. 200 mm Blind Flange - 1 No 7. Necessary Nut Bolt’s & Rubber Packing - 1 Lot (S.S.) Including all other specials required to complete the work in proper manner
2493 Ton Capacity 6.00 mt Lifting Tackle Manual with traveling trolley chain pully block & double gurder H type
250Tools & Spanner Pipe wrenches - 2No D/E Spanner 22/6 mm - 6No Adjustable wrench 300 mm - 1No Screw driver/Tester 250 mm - 1No Screw driver/Tester 200 mm - 1No Screw driver/Tester 150 mm - 1No Combination pliers 200 mm - 1No Nose pliers 150 mm - 1No Hammer with handle 1 kg. - 1No Line tester (Taparia make) - 1No Cripming tool of suitable size - 1No
251CO2/ABC Dry Powder type Fire Extinguisher 4.5 kg as per IS:15683
252200 mm diameter, CE/UL Certified Electromagnetic type flow meter digital reading
253150 mm diameter, CE/UL Certified Electromagnetic type flow meter digital reading
254Internal & External electrification of CWR & Substation with 5 nos solar street lights
255Electromegnatic dozzer of suitable capacity SCADA compatible
256CE/UL Certified Pressure transmitter for each pump
257CE/UL Certified Residual cholorine sensor at OHT outlet
258CE/UL Certified Radar type Level sensor with RTU communication for OHT
259CE/UL Certified Ultrasonic Level sensor for CWR
260CE/UL Certified Electomgnatic flow meter at OHT outlet of suitable size
261Security Survelliance IP Camera (optional)
2621feet hight MS stand for LT Panel made fromMS angle iron
263Testing of Pumping Plant & Control Panel at Manufacturer Works
264Installation. Commissioning and testing of all above equipments as per approved drawings at CWR zone -1 includingpainting of pumping plants.
265160 KVA SUB STATION AT CWR 500 KL (Zone-1)
266Indoor type floor mounted metal clad, 11 KV VCB HT panel with 1No. incoming VCB & 2Nos outgoing VCB totally enclosed, horizontal drawout, horizontal/ vertical isolation type breaker as per IS with all necessory protection and also should be compatible to SCADA operation with RS485 port and multifunction meter.
26770 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to H.T. incoming Panel, and H.T. panel to Transformer.
268160 KVA, 11/0.44 KV, 3 Phase, 50 Hz, Dyn11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +7.5% & -15%,LV side @ 2.5% each tapping complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 (Revised) & as per specificationcomplete in all respects as required at site.
269H.T. Cable end termination heat shrink joint kit Indore Type 70 sq.mm.
270H.T. Cable end termination heat shrink joint kit Outdoor Type 70 sq.mm.
271Earthing system shall executed as per IS : 3043 and I.E. rules.
272Sheet fabricated factory wired, floor mounting type L.T. panel comprising of following. L.T. panel comprising of 2 no incomer MCCB of 250 Amp capacity panel and 1 no. outgoing 250 Amp MCCBand 1 nos 250 Amp for DG set for future planning (all are electrically and mechanicaly interlockd) & 1Nos 63 Amp MCCB for lighting complete panel of suitable for above 160 KVA transformers. All MCCB should be motorised and microprocessor based compatable for SCADA
2731.1 KVgrade 120 sq mm 3.5 core PVCinsulated Armored Aluminum cable from160 KVA Transformer to L.T. Panel.
274Rubber Sheet of size 1mX2m and 19 mm thick shock resistance sheet
275Supply , Installation of transformer Sub – station Fencing with painting complete.
276CO2/ABC Dry Powder type Fire Extinguisher 4.5 kg as per IS:15683
277Testing of HT,LT Panel & Transformer at Manufactrer works
278Installation. Commissioning and testing of all above equipments as per approved drawings at CWR zone -1 substation.
279NOC for substation from electrical sefety department
280PUMPING PLANT AT 450 KL CWR (ZONE - 2) CWR feed from 6No TW"s (2exsisting+3new)
281VT Pumping Plant :- Supply of2600 LPM, 40 mtr Head or as per actual design , 1450 RPM , S.S 410 impeller & shaft,Pump Casing 2% NiCi,IS:210 FG: 260 Self Water Lubricated VT Pump set coupled with squirrel cage VHS/VSS TEFC IP-55 induction motor (Operating Voltage 415 V + 10%, 3 ph, 50Hz + 5%) 40 HP or as per actual design including CEEPHO margin with Bowl Assembly Discharge Head, Head Shaft, Strainer and 5 mts Column Assembly to feed 2150 KL OHT (2w+1s)
282L.T PANEL WITH CONTROL PANNEL :-
283Supply of M.S. Fabricated Dust and Vermin Proof, Cubical Type, Floor Mounted, LT Panel with Control Panel compitable to SCADA with RS485 Port consisting as following INCOMING (from Transformer) :-2 No. M.C.C.B. motorised & microprocessor based250 Amp capacity (electrically & mechanically interlocked) & 1 No. M.C.C.B. motorised & microprocessor based250 Amp capacity & Outgoing 1 No. M.C.C.B. motorised & microprocessor based250 Amp capacity (for DG set ) both are electrically & mechanically interlocked,Volt Meter with Selector Switch, Ampere meter with selector switch, KWH smart meter ,Power Factor meter, Frequency Meter, Indicating lamps, Toggle switch, Instrument fuses and Aluminum Bus Bar. OUTGOING :- (i) 3 Nos. Outgoing Consist of SCADA Compatible Motorised M.C.C.B. microprocessor based 100 Amp Capacity, suitable to operate 40 HP induction motor (ii) 2 Nos MCCB 63 Amp for lighting and fan Control Panel / Starter :- (i) 3 Nos. 40 H.P Soft starter with Ampere Meter, Power Capacitor, Motor protections, Indicating Lamps, Toggle Switches and Instrument Fuses suitable to SCADA operation with RS485 Port (ii) APFC Panel SCADA Compatible of suitable capacity as per design Note :- Starter and MCCB rating may be vary as per actual capacity according to site situation and no extra payment shall be made for this
284supply of CE/UL Certified Surge protector for control panel
285Supply of 3 Core 35 sq.mm Copper Conductor Cable from L.T. Panel to respective Motors with lugs etc.
286Supply & Fixing of Powder coated MS Cable Tray 150mmx50mmx1.6mm
287EARTHING :-Strip Double Plate Earthing for Complete Electrical Installation in the Pump House (As per IER/IS) including civil work with all materials Individual Earthing for each equipment shall be carried out
288Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1) 315 Amp.
289MAIN PIPING AND VALVES :-( for 2500 LPM VT Pumps)
290Reflex Valve 200 mm size CIDF PN 1.0
291Sluice Valve 200 mm Size CIDF PN 1.0 ( with actuater suitable to SCADA operation)
292Sluice Valve 250 mm Size CIDF PN 1.0 ( with actuater suitable to SCADA operation)
293Sluice Valve 250 mm Size CIDF PN 1.0(Manual for Bypass)
294Main Pipings 1. 250 x 200 x 250 mm MS D/F Tee (12mm thickness) - 3 No 2. 200 mm MS D/F Pipe 0.50 mt.(12mm thickness) - 3 No 3. 200 mm MS D/F Pipe 1.00 mt. (12mm thickness) - 3 No 4. 250 mm MS D/F Pipe 2.00 mt.(12mm thickness) - 3 No 5. 250 mm MS D/F (12mm thickness) Bend 90o - 3 No 6. 250 mm Blind Flange - 1 No 7. Necessary Nut Bolt’s & Rubber Packing - 1 Lot Including all other specials required to complete the work in proper manner
2953 Ton Capacity 6.00 mt Lifting Tackle Manualwith traveling trolley chain pully block& double gurder H type
296CO2/ABC Dry Powder type Fire Extinguisher 4.5 kg as per IS:15683
297250mm diameter, CE/UL Certified Electromagnetic type flow meter digital reading
298CE/UL Certified Electomgnatic flow meter at OHT outlet of suitable size
299Internal & External electrification of CWR & Substation with 5 nos solar street lights
300Electromegnatic dozzer of suitable capacity SCADA compatible
301CE/UL Certified Radar type Level sensor with RTU communication for OHT
302CE/UL Certified Ultrasonic Level sensor for CWR
303CE/UL Certified Pressure transmitter for each pump
304CE/UL Certified Residual chlorine sensor at OHT outlet
305Security Survelliance IP Camera with all required accessories
3061feet hight MS stand for LT Panel made fromMS angle iron
307Testing of Pumping Plant & Control Panel at Manufacturer Works
308Installation. Commissioning and testing of all above equipments as per approved drawings at CWR zone -2includingpainting of pumping plants.
309100 KVA SUB STATION AT CWR 450 KL (Zone-2)
310Indoor type floor mounted metal clad, 11 KV VCB HT panel with 1No. incoming VCB & 2Nos outgoing VCB totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS with all necessory protection and also should be compatible to SCADA operation with RS485 port and multifunction meter.
31170 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to H.T. incoming Panel, and H.T. panel to Transformer.
312100 KVA, 11/0.44 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +7.5% & -15%, LV side @ 2.5% stapping complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 (Revised) & as per specificationcomplete in all respects as required at site.
313H.T. Cable end termination heat shrink joint kit indoortype 70sq.mm.
314H.T. Cable end termination heat shrink joint kit outdoor type 70sq.mm.
315Earthing system shall executed as per IS : 3043 and I.E. rules.
3161.1 KVgrade 120 sq mm 3.5 core PVCinsulated Armored Aluminum cable fromTransformer to L.T. Panel.
317Rubber Sheet of size 1mX2m and 19 mm thick shock resistance sheet
318Supply , Installation of transformer Sub – station Fencing with painting complete.
319CO2 Dry Powder type Fire Extinguisher 4.5 kg as per IS:15683
320Testing of HT Panel & Transformer at Manufactrer works
321Installation. Commissioning and testing of all above equipments as per approved drawings at CWR zone -2 substation.
322NOC for substation from electrical sefety department
323PUMPING PLANT AT 600 KL CWR (ZONE - 3) CWR feed from 7No TW"s (4exsisting+3new)
324VT Pumping Plant :- Supply of3650 LPM, 40 mtr Head or as per actual design , 1450 RPM , S.S 410 impeller & shaft,Pump Casing 2% NiCi,IS:210 FG: 260 SelfWater Lubricated VT Pump set coupled with squirrel cage VHS/VSS TEFC IP-55 induction motor (Operating Voltage 415 V + 10%, 3 ph, 50Hz + 5%) 50 HP or as per actual design including according to CEEPHO manual with Bowl Assembly Discharge Head, Head Shaft, Strainer and 4.5 mts Column (or suitable sump depth) Assembly to feed 2350 KL OHT (2w+1s)
325L.T PANEL WITH CONTROL PANNEL :-
326Supply of M.S. Fabricated Dust and Vermin Proof, Cubical Type, Floor Mounted, LT Panel with Control Panel compitable to SCADA with RS485 Port consisting as following INCOMING (from Transformer) :-2 No. M.C.C.B. motorised & microprocessor based320 Amp capacity (electrically & mechanically interlocked) & 1 No. M.C.C.B. motorised & microprocessor based320 Amp capacity & Outgoing 1 No. M.C.C.B. motorised & microprocessor based320 Amp capacity (for DG set ) both are electrically & mechanically interlocked,Volt Meter with Selector Switch, Ampere meter with selector switch, KWH smart meter ,Power Factor meter, Frequency Meter, Indicating lamps, Toggle switch, Instrument fuses and Aluminum Bus Bar. OUTGOING :- (i) 3 Nos. Outgoing Consist of SCADA Compatible motorised M.C.C.B. microprocessor based 125Amp Capacity, suitable to operate 50 HP induction motor (ii) 2 Nos MCCB 63 Amp for lighting and fan Control Panel / Starter :- (i) 3 Nos. 50 H.P Soft starter with Ampere Meter, Power Capacitor, Motor protections, Indicating Lamps, Toggle Switches and Instrument Fuses suitable to SCADA operation with RS485 Port (iii) APFC Panel SCADA Compatible of suitable capacity as per design Note :- Starter and MCCB rating may be vary as per actual capacity according to site situation and no extra payment shall be made for this
327CE/UL Certified Surge protector for control panel
328Supply of 3 Core 35 sq.mm Copper Conductor Cable from L.T. Panel to respective Motors with lugs etc.
329Supply & Fixing of Powder coated MS Cable Tray 150mmx50mmx1.6mm
330EARTHING :-Strip Double Plate Earthing for Complete Electrical Installation in the Pump House (As per IER/IS) including civil work with all materials Individual Earthing for each equipment shall be carried out
331Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1) 315 Amp.
332MAIN PIPING AND VALVES :-( for 3500 LPM VT Pumps)
333Reflex Valve 200 mm size CIDF PN 1.0
334Sluice Valve 200 mm Size CIDF PN 1.0 ( with actuater suitable to SCADA operation)
335Sluice Valve 250 mm Size CIDF PN 1.0 ( with actuater suitable to SCADA operation)
336Sluice Valve 250 mm Size CIDF PN 1.0 (Manual for Bypass)
337Main Pipings 1. 250 x 200 x 250 mm MS D/F Tee (12mm thickness) - 3 No 2. 200 mm MS D/F Pipe 0.50 mt.(12mm thickness) - 3 No 3. 200 mm MS D/F Pipe 1.00 mt.(12mm thickness) - 3 No 4. 250 mm MS D/F Pipe 2.00 mt.(12mm thickness) - 3 No 5. 250 mm MS D/F (12mm thickness) Bend 90o - 3 No 6. 250 mm Blind Flange - 1 No 7. Necessary Nut Bolt’s & Rubber Packing - 1 Lot Including all other specials required to complete the work in proper manner
3383 Ton Capacity 6.00 mt Lifting Tackle Manual with traveling trolley chain pully block& double gurder H type
339CO2/ABC Dry Powder type Fire Extinguisher 4.5 kg as per IS:15683
340250 mm diameter,CE/UL Certified Electromagnetic type flow meter digital reading
341CE/UL Certified Electomgnatic flow meter at OHT outlet of suitable size
342Internal & External electrification of CWR & Substation with 5 Nos solar street lights
343Electromegnatic dozzer of suitable capacity SCADA compatible
344CE/UL Certified Radar type Level sensor with RTU communication for OHT
345CE/UL Certified Ultrasonic Level sensor for CWR
346CE/UL Certified Pressure transmitter for each pump
347CE/UL Certified Residual cholorine sensor
348Security Survelliance IP Camera with required accessories
349Testing of Pumping Plant & Control Panel at Manufacturer Works
3501feet hight MS stand for LT Panel made fromMS angle iron
351Installation. Commissioning and testing of all above equipments as per approved drawings at CWR zone -3 includingpainting of pumping plants.
352160 KVA SUB STATION AT CWR 600 KL (Zone-3)
353Indoor type floor mounted metal clad, 11 KV VCB HT panel with 1No. incoming VCB & 2Nos outgoing VCB totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS with all necessory protection and also should be compatible to SCADA operation with Rs485 port and multifunction meter.
35470 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to H.T. incoming Panel, and H.T. panel to Transformer.
355160 KVA, 11/0.44 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +7.5% & -15%, LV side @2.5% stapping complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 (Revised) & as per specificationcomplete in all respects as required at site.
356H.T. Cable end termination heat shrink joint kit indore type 70 sq.mm.
357H.T. Cable end termination heat shrink joint kit out door type 70 sq.mm.
358Earthing system shall executed as per IS : 3043 and I.E. rules.
3591.1 KVgrade 120 sq mm 3.5 core PVCinsulated Armored Aluminum cable from160 KVA Transformer to L.T. Panel.
360Rubber Sheet of size 1mX2m and 19 mm thick shock resistance sheet
361Supply , Installation of transformer Sub – station Fencing with painting complete.
362CO2/ABC Dry Powder type Fire Extinguisher 4.5 kg as per IS:15683
363Testing of HT Panel & Transformer at Manufactrer works
364Installation. Commissioning and testing of all above equipments as per approved drawings at CWR zone -3 substation
365NOC for substation from electrical sefety department
366SCADA WORKS OF TUBEWELLS(18 No)
367Supply, storage, installation, testing and comissioning of CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with intelligent GSM Based modem unit with CPU and Power Supply with analog and Digital Parameter and features as specified. One each for each tubewell to store and transmit data on GSM backbone, RTU designed with logic to tansfer data at multiple stations and also compatible for satellite communication along with control panel for all equipment and 24V power supply
368Supply, storage, installation, testing and comissioning of GSM/GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer, antenna made for pumping plant with SIM and recharge till Handed over
369Supply, storage, installation, testing and comissioning of CE & UL Certified 7" HMI touch screen suitable to communication with PLC/RTU for local display & control of process parameters
370Supply, storage, installation, testing and comissioning of CE/UL Certified Intelligent energy meters with communication port
371SCADA WORKS OF 500 KL CWR to 350 KL OHT & 1550 KL OHT (Zone-1) (Having 5 Nos Pumps)
372Supply, storage, installation, testing and comissioning of CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with intelligent GSM Based modem unit with CPU and Power Supply with analog and Digital Parameter and features as specified for each for each ZPS/OHT to store and transmit data on GSM backbone, RTU designed with logic to tansfer data at multiple stations and also compatible for satellite communicationalong with control panel for all equipment and 24V power supply
373Supply, storage, installation, testing and comissioning of GSM/GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer, antenna made for pumping plantwith SIM andrecharge till Handed over
374Supply, storage, installation, testing and comissioning of CE & UL Certified 7" HMI touch screen suitable to communication with PLC/RTU for local display & control of process parameters
375Supply, storage, installation, testing and comissioning of CE/UL Certified Intelligent energy meters
376Complete cabling for CWR & OHT (above 3 pumps)
377SCADA WORKS OF 450 KL CWR to 2150 KL OHT(Zone-2) (for 3 pumps)
378Supply, storage, installation, testing and comissioning of CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with intelligent GSM Based modem unit with CPU and Power Supply with analog and Digital Parameter and features as specified for each for each ZPS/OHT to store and transmit data on GSM backbone, RTU designed with logic to tansfer data at multiple stations and also compatible for satellite communication along with control panel for all equipment and 24V power supply
379Supply, storage, installation, testing and comissioning of GSM/GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer, antenna made for pumping plantwith SIM andrecharge till Handed over
380Supply, storage, installation, testing and comissioning of CE & UL Certified 7" HMI touch screen suitable to communication with PLC/RTU for local display & control of process parameters
381Supply, storage, installation, testing and comissioning of CE/UL Certified Intelligent energy meters
382Complete cabling for CWR & OHT (upto 3pumps) for scada
383SCADA WORKS OF 600 KL CWR to 2350 KL OHT (Zone-3) (for 3 pumps)
384Supply, storage, installation, testing and comissioning of CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with intelligent GSM Based modem unit with CPU and Power Supply with analog and Digital Parameter and features as specified for each for each ZPS/OHT to store and transmit data on GSM backbone, RTU designed with logic to tansfer data at multiple stations and also compatible for satellite communicationalong with control panel for all equipment and 24V power supply
385Supply, storage, installation, testing and comissioning of GSM/GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer, antenna made for pumping plantwith SIM andrecharge till Handed over
386Supply, storage, installation, testing and comissioning of CE & UL Certified 7" HMI touch screen suitable to communication with PLC/RTU for local display & control of process parameters
387Supply, storage, installation, testing and comissioning of CE/UL Certified Intelligent energy meters
388Complete cabling for CWR & OHT (upto 3pumps) for SCADA
389LOCAL CONTROL STATION (LCS) FOR TW"s AND CWR"s
390Supply, storage, installation, testing and comissioning of CE/UL & BIS Certified industrial grade LED MONITOR with latest configuration as per specification 65" (upto 50 Tubewells)
391Supply, storage, installation, testing and comissioning of Full Development version of TAGS SCADA software with costomization of software for MCS for unlimited digital and analog Input / output features as per requirements
392Supply, storage, installation, testing and comissioning of CE/UL certified Local control room PLC with redundant CPU & power supply at MCS in IP-54 enclosure as per site requirement and specification required to complete in all respect
393Supply, storage, installation, testing and comissioning of CE/UL certified Field gateway agent for transfering data from MCS to central control room
394Supply, storage, installation, testing and comissioning of GSM/GPRS based wireless/Broadband/equivelent communication system for PLC Capable to transfer and receive data & gather data from remote sites to control stations all accessories included with signal enhancer, antenna along with running expences till DLP
395Supply, storage, installation, testing and comissioning of CE/UL certified Firewall for network protection
396Supply, storage, installation, testing and comissioning of Surge protector for Ethernet communication protection
397Supply, storage, installation, testing and comissioning of CE/UL Certified industrial grade Ethernet switch
398Supply, storage, installation, testing and comissioning of CE/UL Certified 3 KVA UPS with Batterieswith 02 hrs backup required for mentioned work
399Supply, storage, installation, testing and comissioning of HP or equivalent 600 DPI ink jet colour printer
400Supply, storage, installation, testing and comissioning of HP or equivalent Laser Printer 1018 or equivalent.
401Core i5 10th gen Desktop with 8 gb ram and 1TB SSD
402Core i5 10th gen 15.6 inch laptop with 8 gb ram and 1TB SSD for SCADA presentation and record work
403Supply, storage, installation, testing and comissioning of Security Survelliance IP Camera with recorder
404Installation. Commissioning and testing with required furniture
405Trial & Run for 3 months for electrical - mechanical & SCADA work with Operators,Technician and SCADA Operators
406Sodium Hypochloride for 3 months trial & run
Disclaimer :