Tender For Jal Jeevan Mission (Jjm)-Wss To Kuzhalmannam, Thenkurissi And Kannadi Panchayaths-Optimization Of Water Treatment Plant, Improving Capacity Of 9.5 Wtp At Kannadi Replacing Existing Rapid Sand Filter Media With Dual Media Filter Using Anthracit, Palakkad-Kerala

Kerala Water Authority-KWA has published Tender For Jal Jeevan Mission (Jjm)-Wss To Kuzhalmannam, Thenkurissi And Kannadi Panchayaths-Optimization Of Water Treatment Plant, Improving Capacity Of 9.5 Wtp At Kannadi Replacing Existing Rapid Sand Filter Media With Dual Media Filter Using Anthracit. Submission Date for this Tender is 22-02-2023. Water Pipe Line Tenders in Palakkad Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

36084317
Corrigendum : Tender For Jal Jeevan Mission (Jjm)-Wss To Kuzhalmannam, Thenkurissi And Kannadi Panchayaths-Optimization Of Water Treatment Plant, Improving Capacity Of 9.5 Wtp At Kannadi Replacing Existing Rapid Sand Filter Media With Dual Media Filter Using Anthracit
Open Tender
Indian
Kerala
Palakkad
22-02-2023

Tender Details

Jal Jeevan Mission ( Jjm ) -Wss To Kuzhalmannam, Thenkurissi And Kannadi Panchayaths-Optimization Of Water Treatment Plant, Improving Capacity Of 9.5 Wtp At Kannadi Replacing Existing Rapid Sand Filter Media With Dual Media Filter Using Anthracite And Construction Of 5.50Ll Ohsr At Vellappara Iti Compound At Kuzhalmannam, Supplying And Laying Balance Distribution Lines And Providing Fhtcs In Kuzhalmannam Grama Panchayath-Pipeline Work

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 20-Feb-2023 DATE Date 22-02-2023

Key Value

Document Fees
INR 16540 /-
EMD
INR 500000.0 /-
Tender Value
INR 10.78 Crore /-

BOQ Items

Work Name:Jal Jeevan Mission (JJM)-WSS to Kuzhalmannam, Thenkurissi and Kannadi Panchayaths-Optimization of Water Treatment Plant, Improving capacity of 9.5 WTP at Kannadi Replacing existing Rapid sand filter media with Dual media filter using Anthracite and Construction of 5.50LL OHSR at Vellappara ITI compound at Kuzhalmannam, Supplying and Laying balance distribution lines and providing FHTCs in Kuzhalmannam Grama Panchayath-Pipeline Work
Sl. No. Item Description
1APPENDIX - I - OPTIMIZATION OF WTP BY REPLACING EXISTING FILTER MEDIA WITH DUAL MEDIA (ANTHRACITE)
2OD180661/2022-2023: Designing of dual media filter including under drainage system and air scouring system so that uniform backwashing and uniform air scouring is obtained through uniform distribution of back wash water and compressed air,without any loss of the dual layer filter media and to attain the maximum efficient back wash and air scouring (The dual media fliter bed has to be designed considering the various parameters lie raw water characteristics,desired rate of filtration,required flitrate quality etc.The design shall include calculation of depth of different of the media ,considering the parameters like effective size and uniformity coefficient of the media,settling velocities of the media etc.The underdrain system and air scouring system shall be designed to avoid interface chocking caused by mixing up of different layers at the interface in dual media filter beds.
3OD180665/2022-2023:Modification /Alteration of the existing backwashing system comprising of compressed air /blower and clear water providing new air scouring system ,providing new pressure regulating valves or such other machanisms and fixtures required according to the design of dual layer filter media backwashing operations complete.
4OD180667/2022-2023:Supplying Anchracite with Effective Size d10 of 1.0mm to 1.6mm,specific gravity of 1.45 to 1.55 ,Uniformity coefficient of 1.7 or lower, Hardness greater than 2.7 (Mohs scale ),Acid solubility less than 5% and with Carbon content ,not less than 90% including conveyance to the site and stacking .(The Anchracite filter sand shall be tested in regional research laboratory /CPRI Labs of Government of India for its suitability)
5OD180668/2022-2023:Supplying 2mm to 3.5mm grit (grit shall be hard,clean ,free from clay ,dust and other impurities),stacking in standard heaps for measurement including cost, conveyance upto 5km and labour charges for stacking,spreading,testing and as per the directions of the department officers etc., complete as per CPHEEO specification.
6100.55.4:Supplying and stacking for measurement of filter sand having effective size 0.45 to 0.70 mm and uniformity coefficient 1.30 to 1.7, of specific gravity in the range of 2.55 - 2.65 and hard and clean, free from clay, dust and other impurities including cost of materials, labour charges and conveyance of materials up to 5 km and as per the directions of the department officers etc. complete and as per CPHEEO specification.
7100.55.5:Removing filter media from the filter beds without making any damages to the existing structures and back manifolds and stacking at a safe and convenient place for segregation process and as per the directions of the department officers etc. complete.
8OD180725/2022-2023:Repair / alteration of the underdrain system by replacing all damaged pipes with suitable arrangements and providing all additional mechanisms and fixtures required according to the design of dual-layer filtering system complete.
9OD180734/2022-2023:Washing and cleaning the fiter chamber and rectifying damages of filter walls including glazed tiles and floor.of the filter bed by concreating wherever necessary, prepairing entire chamber suitable for dual media filter refurbishment
104.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
11OD180744/2022-2023:Refurbishing the filter beds using dual layer filter media as per the design separately laying each grade of supporting gravel manually so that each pebble is placed in close contact with each other leaving maximum void space between arid the smaller gravels above. The filter sand media and anthracite are placed above separately Click To Open/Hide Specification
12OD180746/2022-2023:Trial run of all the filter beds for a period up to 30 days and providing required training to the <br>operators and KWA persional for trouble free functioning and maitanance of the filter beds and filter
13OD180748/2022-2023:Supplying & Fixing Suitable filter valves in the filter chamber. Additional valves may be provided. If the existing valve is not functioning, the same may be removed and new vlaves fixed in their place.
14100.55.6:Cleaning, drying and seiving the removed filter media and stacking the dismantled pebbles for reuse and spreading in the filter box in layers as per specifications and as per directions of the department officers.
15100.55.3:Supplying of 20 to 40 mm pebble (pebbles shall be hard, clean, free from clay, dust and other impurities), stacking in standard heaps for measurement including cost, conveyance up to 5 km and labour charges for stacking, spreading, testing and as per directions of the department officers etc. complete and as per CPHEEO specification.
16OD180763/2022-2023:Laying Anthracite / Sand / 2 to 3.5mm grit in the filter box carefully over higher size pebble layer (43cm thick) already laid so that the dual media interface is properly formed for maximum filter efficiency and longer life of filter media, each layer should be laid without disturbing the lower layer already laid, and ensuring uniform thickness for each layer and each media, and as per the directions of the departmental officers.
17OD180767/2022-2023:Additional labor for segregating pebbles (30mm, 20mm, 15-12mm & 6mm) for using as supporting grade for dual media filter
18APPENDIX - II - SUPPLY AND ERECTION OF MOTOR PUMPSETS (RAW WATER AND CLEAR WATER)
19OD180772/2022-2023:Supply and erection of 95HP Vertical turbine pump set including delivery pipe, wiring from starter to motor, earthing and erection as per BEE standards with following specifications. Total head- 28m, Discharge- 180LPS, 70% efficinecy, synchronous speed 960-1500rpm, impeller Bronze LT B2, shaft SS 316, casing-Cast Iron, Neck ring Bronze LT B2, sleeve SS 410, incluiiding pump, motor, panel board, starter 10m cable capacitor, m suction pipe, foot valve, non return valve, sluice valve, pipe connection to valve, earthing , erection, trial running , commissioning and two year maintenance etc, complete. Pumpset is to be installed after dismantling the existing motor pumpset and foundation. New foundation is be designed and constructed as per capacity of newly supplied motor pumpset. The work shall be arranged with minimum interruption of the existing pumping.
20OD180775/2022-2023:Supplying and Erection of 160HP Centrifugal Motor pump set having Head 85m and Discharge 85LPS for Pumping Clear water from WTP to Thenkurissi OHSR- ( 1Nos +1No) - 2Nos - One stand by (for intermediate stage) best quality I S I mark KWA approved make ,960-3000 rpm, Panel board -2Nos with all accessories as per I E rules, Main switch, Fuse carriers , required capacity Ameter, voltmeter ,fixing pipes, specials and valves provide suitable earthing works as per I E rules, Phase indicator lamp, Dry run preventer, ELCB, wiring of Panel board ,Cable of required capacity ,erection, testing ,trial running,commissioning and maintenance for 2 years after commissioning of work etc complete with the following specification 1.Pump Supply, erection, testing and commissioning of KWA pre-qualified reputed make Centrifugal pump sets with Bronze/SS impeller, SS shaft and CI pump casing with suitable type base plate with coupling, coupling guard foundation bolts & nuts etc. complete suitable for coupling the foundation including cost of cement sand and metal etc. complete. Cumulative Discharge - 85LPS, Head - 85m 2. Motor, Supply, erection, testing and commissioning of KWA pre-Qualified reputed make horizontal solid shaft, foot mounted TEFC squirrel cage induction motor suitable for the above pump working 3 phase 50 Hz AC, supply, working voltage 415 V. The motor shall confirm to EEFI/IS 325 including providing suitable concrete foundation including cost of cement sand and metal etc. complete. Digital motor protection relay shall be included in starter as present IE rules. Flexible coupling shall be used for coupling of pumps and motors. 3. Starter Supply, erection, testing and commissioning of suitable rating fully automatic starters suitable for the above motor with over voltage and under voltage protection, single phase preventer, overload relay with motor protection relay with main contactor and bye pass contactor as per IE rules and code of practice etc complete, 4 Panel board (Suitable for operating two pump sets but one pump at a time using castle key iterlock) cubical type floor mounted MS fabricated dust and verm in proof common control panel board ) Supply, erection, testing and commissioning of one number suitable capacity MCCB as incomer and two numbers of suitable capacity MCCB as out going ( Two MCCBs are interlocking with each other, only one will be on at atime) providing suitable size aluminium bus/ interconnect the above MCCBs and fitted with three numbers of indicator lamps, 1No. volt meter with selector switch, 1 No: Ammeter with selector switch etc. complete and provided with a common earth bus for the entire panel and interconnect with the MCCBs as per IE rules and code of practice. The panel shall be fitted on a common base frame on suitable foundation. 5. Cabling work Supply, laying, testing and commissioning of suitable size XLPE cables for the above pump set from panel board to starter and from starter to motor. Considering energy conservation. 6. Earthing Supply of all materials and providing suitable earthing by using suitable size pipe/ plate earthling GI/Copper strip buried in ground and giving double earthing to motor, starter, panel board etc. as per IE standards . 7. Capacitor Supply, erection, testing and commissioning of heavy duty APP capacitor for the motor to get a power factor above 0.95. The capacitor shall confirm to IS 2834. 8. Valves Supply of suitable size best quality heavy duty PN 1.6 ISI marked DI Double flanged sluice valve and non return valve with suitable pressure rating. Fitting of valve shall include proper RCC support specially for non return valves. The pumpset is of positive suction pump set sluice valve should be in suction as well as delivery sides for easy repair works. 9. Suction and delivery pipe connections. Supply and fitting of suitable size best quality pipe for a Length of 10m. The delivery of the individual 2 Nos of pumpsets to be interconnected with the common MS pipe etc. complete. MS fabrication works as per the direction of departmental officers. Pumpset is to be installed after dismantling the existing motor pumpset and foundation. New foundation is be designed and constructed as per capacity of newly supplied motor pumpset. The work shall be arranged with minimum interruption of the existing pumping.
21OD180776/2022-2023:Supplying and Erection of 30HP Centrifugal Motor pump set having Head 35m and Discharge 32LPS for Pumping Clear water from WTP to Kuzhalmannam OHSR- 1Nos - best quality I S I mark KWA approved make ,960-3000 rpm, Panel board -1Nos with all accessories as per I E rules, Main switch, Fuse carriers , required capacity Ameter, voltmeter ,fixing pipes, specials and valves provide suitable earthing works as per I E rules, Phase indicator lamp, Dry run preventer, ELCB, wiring of Panel board ,Cable of required capacity ,erection, testing ,trial running,commissioning and maintenance for 2 years after commissioning of work etc complete with the following specification 1.Pump Supply, erection, testing and commissioning of KWA pre-qualified reputed make Centrifugal pump sets with Bronze/SS impeller, SS shaft and CI pump casing with suitable type base plate with coupling, coupling guard foundation bolts & nuts etc. complete suitable for coupling the foundation including cost of cement sand and metal etc. complete. Cumulative Discharge - 32LPS, Head - 35m 2. Motor, Supply, erection, testing and commissioning of KWA pre-Qualified reputed make horizontal solid shaft, foot mounted TEFC squirrel cage induction motor suitable for the above pump working 3 phase 50 Hz AC, supply, working voltage 415 V. The motor shall confirm to EEFI/IS 325 including providing suitable concrete foundation including cost of cement sand and metal etc. complete. Digital motor protection relay shall be included in starter as present IE rules. Flexible coupling shall be used for coupling of pumps and motors. 3. Starter Supply, erection, testing and commissioning of suitable rating fully automatic starters suitable for the above motor with over voltage and under voltage protection, single phase preventer, overload relay with motor protection relay with main contactor and bye pass contactor as per IE rules and code of practice etc complete, 4 Panel board (Suitable for operating two pump sets but one pump at a time using castle key iterlock) cubical type floor mounted MS fabricated dust and verm in proof common control panel board ) Supply, erection, testing and commissioning of one number suitable capacity MCCB as incomer and one number of suitable capacity MCCB as out going providing suitable size aluminium bus/ interconnect the above MCCBs and fitted with three numbers of indicator lamps, 1No. volt meter with selector switch, 1 No: Ammeter with selector switch etc. complete and provided with a common earth bus for the entire panel and interconnect with the MCCBs as per IE rules and code of practice. The panel shall be fitted on a common base frame on suitable foundation. 5. Cabling work Supply, laying, testing and commissioning of suitable size XLPE cables for the above pump set from panel board to starter and from starter to motor. Considering energy conservation. 6. Earthing Supply of all materials and providing suitable earthing by using suitable size pipe/ plate earthling GI/Copper strip buried in ground and giving double earthing to motor, starter, panel board etc. as per IE standards . 7. Capacitor Supply, erection, testing and commissioning of heavy duty APP capacitor for the motor to get a power factor above 0.95. The capacitor shall confirm to IS 2834. 8. Valves Supply of suitable size best quality heavy duty PN 1.6 ISI marked DI Double flanged sluice valve and non return valve with suitable pressure rating. Fitting of valve shall include proper RCC support specially for non return valves. The pumpset is of positive suction pump set sluice valve should be in suction as well as delivery sides for easy repair works. 9. Suction and delivery pipe connections. Supply and fitting of suitable size best quality pipe for a Length of 10m. The delivery of the pumpsets to be interconnected with the common MS pipe etc. complete. MS fabrication works as per the direction of departmental officers. Pumpset is to be installed after dismantling the existing motor pumpset and foundation. New foundation is be designed and constructed as per capacity of newly supplied motor pumpset. The work shall be arranged with minimum interruption of the existing pumping.
22OD180780/2022-2023:Supplying and Erection of 70HP Centrifugal Motor pump set having Head 56m and Discharge 55LPS for Pumping Clear water from WTP to Kannadi OHSR- 1Nos - best quality I S I mark KWA approved make ,960-3000 rpm, Panel board -1Nos with all accessories as per I E rules, Main switch, Fuse carriers , required capacity Ameter, voltmeter ,fixing pipes, specials and valves provide suitable earthing works as per I E rules, Phase indicator lamp, Dry run preventer, ELCB, wiring of Panel board ,Cable of required capacity ,erection, testing ,trial running,commissioning and maintenance for 2 years after commissioning of work etc complete with the following specification 1.Pump Supply, erection, testing and commissioning of KWA pre-qualified reputed make Centrifugal pump sets with Bronze/SS impeller, SS shaft and CI pump casing with suitable type base plate with coupling, coupling guard foundation bolts & nuts etc. complete suitable for coupling the foundation including cost of cement sand and metal etc. complete. Cumulative Discharge - 55LPS, Head - 56m 2. Motor, Supply, erection, testing and commissioning of KWA pre-Qualified reputed make horizontal solid shaft, foot mounted TEFC squirrel cage induction motor suitable for the above pump working 3 phase 50 Hz AC, supply, working voltage 415 V. The motor shall confirm to EEFI/IS 325 including providing suitable concrete foundation including cost of cement sand and metal etc. complete. Digital motor protection relay shall be included in starter as present IE rules. Flexible coupling shall be used for coupling of pumps and motors. 3. Starter Supply, erection, testing and commissioning of suitable rating fully automatic starters suitable for the above motor with over voltage and under voltage protection, single phase preventer, overload relay with motor protection relay with main contactor and bye pass contactor as per IE rules and code of practice etc complete, 4 Panel board (Suitable for operating two pump sets but one pump at a time using castle key iterlock) cubical type floor mounted MS fabricated dust and verm in proof common control panel board ) Supply, erection, testing and commissioning of one number suitable capacity MCCB as incomer and one number of suitable capacity MCCB as out going providing suitable size aluminium bus/ interconnect the above MCCBs and fitted with three numbers of indicator lamps, 1No. volt meter with selector switch, 1 No: Ammeter with selector switch etc. complete and provided with a common earth bus for the entire panel and interconnect with the MCCBs as per IE rules and code of practice. The panel shall be fitted on a common base frame on suitable foundation. 5. Cabling work Supply, laying, testing and commissioning of suitable size XLPE cables for the above pump set from panel board to starter and from starter to motor. Considering energy conservation. 6. Earthing Supply of all materials and providing suitable earthing by using suitable size pipe/ plate earthling GI/Copper strip buried in ground and giving double earthing to motor, starter, panel board etc. as per IE standards . 7. Capacitor Supply, erection, testing and commissioning of heavy duty APP capacitor for the motor to get a power factor above 0.95. The capacitor shall confirm to IS 2834. 8. Valves Supply of suitable size best quality heavy duty PN 1.6 ISI marked DI Double flanged sluice valve and non return valve with suitable pressure rating. Fitting of valve shall include proper RCC support specially for non return valves. The pumpset is of positive suction pump set sluice valve should be in suction as well as delivery sides for easy repair works. 9. Suction and delivery pipe connections. Supply and fitting of suitable size best quality pipe for a Length of 10m. The delivery of the pumpsets to be interconnected with the common MS pipe etc. complete. MS fabrication works as per the direction of departmental officers. Pumpset is to be installed after dismantling the existing motor pumpset and foundation. New foundation is be designed and constructed as per capacity of newly supplied motor pumpset. The work shall be arranged with minimum interruption of the existing pumping.
23OD180782/2022-2023:THE COST FOR ALL THE PUMPSETS (existing pumps have to be dismantled and removed and new pumps of higher capacity have to be erected and connected to the existing suction and delivery lines) installedTO INCLUDE THE COST OF PANEL BOARDS, suitable Starters [to keep the starting current within 2.5 to 3.5 times FLC] (FCMA above 100 hp), SUITABLE CABLES, CAPACITORS to make the pf above 0.95 AND OTHER ACCESSORIES as REQUIRED AS PER IEI STANDARDS.
24OD180783/2022-2023:Removing existing compressor.Lifting the unit from its foundation.Dismantling its MS pipe connection, Supplying and fixing Blower and Motor as per following specifications Fluid to be handled-Air, Considered inlet temperature-40degree C, Considered inlet pressure - Atmospheric, Specific gravity-1, Capacity-1200m3/hr, Discharge pressure-0.35kg/cm2, Type of cooling-Air cooled, Lubrication-Gear side:oil & pully side:Grease, Quantity-02Nos, Blower speed-1375 RPM, Blower power(BHP)-15.67HP, Motor / Frame Size - 30HP/1500RPM/ND180L Motor details(415V, 4 pole with starter switch,3 phase,50Hz)-IE 2 Efficient foot Mounted,IP 55,Class F insulation with Class B Temp., Type of drive-V-Belt, Flow Orientation-Vertical,Inlet/Outlet size(m.m)-100NB, Sound level(1m Distance)-89-94 dB The work includes all the wiring required to connect the unit to the existing electrical network. The work also includes construction of required foundations using Reinforced cement concrete suitable for the blower foundation using required quantity of reinforcement
25APPENDIX - III - SUPPLY AND ERECTION OF 200KVA TRANSFORMER NEAR RAW WATER INTAKE SITE
26OD180786/2022-2023:Supply and erection of 200KVA Transformer at Well Site including construction of Transformer yard and all other structures
27APPENDIX - IV - RAILWAY CROSSING WORKS ACROSS POLLACHI- PALAKKAD TRACK BETWEEN CHAINAGE 36/9 AND 37 USING HDD METHOD AND DEPOSIT TO RAILWAY AUTHORITY
28OD180787/2022-2023:Towards the charges for conveying Horizontal Drilling Devices after loading in to container truck from Kozhikode/Ernakulam (the nearest place where the devices are available at present) to work site at Kannadi, unloading the device using moving crane with out making any damage to the machine as well as to any structures or establishment belonging to Railway, making necessary temporary road at site for conveying and placing the device at exact location for drilling as directed by Railway authorities<br>, levelling site properly for setting the machine, conveying the pushing pulling device to the other side of road setting the pushing pulling device at the other end of the track up to which the casing pipe of MS 300mm diameter pipe (or as per the design approved by railway authority) having 20mm thick is to be pulled, starting the horizontal drilling work across the Palakkad - Pollachi Railway track chainage 36/9 to 37, 37/8 to 37/9 and 31/9 to 32 after informing the railway authorities and doing the work in their presence so that no interruption in road traffic will occur during the course of work, including cost of casing pipe
29100.37.11.1:In situ fabrication of M.S. pipes of size 400mm (I.D.) using 8mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete.
30100.37.11.2:Fabricating M.S. flanges of diameter 400mm using 12mm thick M.S. plate including cost and conveyance charges of M.S. plate, all fabrication charges, charges of painting the steel work with two or more coat deluxe multi surface paint to give an even shade over an under-coat of primer etc., complete: For pipes fabricated with 8mm thick M.S. plates.
31100.37.11.3:Cutting 400mm (I.D.) M.S. pipes for making bends and other specials by gas cutting including cost of gas, all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates.
32100.37.11.4:Welding 400mm (I.D.) M.S. pipes for making bends and other specials by gas/electric welding machine including cost of gas and welding rods, all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates.
33100.37.11.5:Grinding cut and weld edges of 400mm (I.D.) M.S. pipes during fabrication work including all labour and hire charges of tools etc., complete: For pipes fabricated with 8mm thick M.S. plates.
34OD182404/2022-2023:Construction of valve chamber for 500mm,450mm and 400mm size sluice valve having internal dimension of 1.300x1.300 and depth 1.60 meter in RCC 1:11/ 2:3 base slab thickness 0.10 meter and side wall thickness - 0.15 meter and cover slab thickness 0.20 meter
35APPENDIX- V - CONSTRUCTION OF 5.5 LL CAPACITY OHSR AT VELLAPPARA
362.31:Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared
372.1.1:Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5m in width as well as 10 sqm on plan including disposal of excavated earth up to 50 m and lift up to 1.5 m, disposed soil to be levelled and neatly dressed:All Kinds of soil
382.6.1:Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
392.7.1:Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Ordinary rock
402.7.3:Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Hard rock (blasting prohibited)
41OD180580/2022-2023:Drilling hole 25mm,1.20m for providing dowel bars and conveyance of 25mm bar and locking inside the holes and fixing with cement slurry etc complete with cost of materials
424.1.3:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 (cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
435.33.1:Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to siteof laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level
445.33.2:Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to siteof laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work above plinth level upto floor V level
455.34.1:Extra for providing richer mixes at all floor levels. Note:- Excess/less cement over the specified cement content used is payable/ recoverable separately.Providing M-30 grade concrete instead of M-25 grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum).
465.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
475.9.2:Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
485.9.3:Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
495.9.5:Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
505.9.6:Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
515.9.7:Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases)
525.9.16.1:Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide
535.9.19:Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges
545.11.1:Extra additional height in centering, shuttering where ever required with adequate bracing, propping etc. including cost of de-shuttering and decentering at all levels, over a height of 3.5m, for every additional height of 1 metre or part thereof (Plan area to be measured).Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
555.38:Extra for R.C.C. /B.M.C/R.M.C. work above floor V level for each four floors or part thereof.
565.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
5722.4.1:Providing and Placing in position suitable PVC water stops conforming to IS : 12200 for construction / expansion joints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete etc. complete:Serrated with central bulb ( 225 mm wide, 8-11 mm thick)
5850.6.1.8:Solid block masonry using pre cast solid blocks (Factory made) of size 40x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure up to floor two level with thickness 15cm in: CM 1:6 ( 1 cement : 6 coarse sand etc complete
5913.1.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
6013.7.1:12 mm cement plaster finished with a floating coat of neat cement of mix:1:3 ( 1 cement : 3 fine sand)
6113.18:Neat cement punning
6213.22:Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
632.25:Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
6450.2.26.1:Filling with contractor own earth (excluding rock) in open areas in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge.
6513.43.1:Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
6613.48.1:Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
6710.4:Providing and fixing 1 mm thick M.S. sheet sliding- shutters, with frame and diagonal braces of 40x40x6 mm angle iron, 3 mm M.S. gusset plates at the junction and corners, 25 mm dia pulley, 40x40x6 mm angle and T-iron guide at the top and bottom respectively, including applying a priming coat of approved steel primer.
689.48.2:Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings/ wooden frames with rawl plugs screws etc
6910.26.3:Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approves steel primer.G.I. pipes
7050.18.9.22.8:Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia Vent cowl
7113.61.1:Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work
72100.36.1:Filling water with 5000 litre tankers fited in lorry and conveying water from a distance of 5 km (average) to the reservoir site and pumping the water into the reservoir of height not less than 3 m using 5 HP diesel engine pump set , hire for tanker lorry, tools and other appliences and cost of water etc. complete.
7310.28:Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
7418.73.4:Providing and laying Double Flanged ( Screwed / Welded ) Centrifugally (Spun) Ductile Iron Pipes of Class K - 9 conforming to IS: 8329 :250 mm dia Ductile Iron Double Flanged
7518.30.6:Providing flanged joints to double flanged C.I./ D.I pipes and specials, including testing of joints:250 mm diameter pipe
76100.31.2.6:Conveying and fixing C.I. sluice valves (with cap) by providing bolts, nuts, rubber insertions etc., complete, but excluding the cost of the valve (tail pieces, if required, will be paid separately): 250mm diameter, Class II.
77100.98.217:Supply of PVC Pipe, 6kg/cm2, 200mm Dia.
78100.98.486:Supply of CI Double Flanged Sluice Valve Conforming to IS 14846 - 2000, Sluice Valve with Hand Wheel PN 1.6, Size 250mm.
79100.41.33:Supplying and fixing 500mm dia C.I. manhole cover with frame (medium duty) charges including all cost, labour charges etc., complete.
807.1.1:Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand)
8118.68.1:Providing and laying D.I specials of class K - 12 suitable for push - on jointing as per IS : 9523 :Upt 600 mm dia
82100.1.1:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in all kinds of soil.
83100.9.13:Laying uPVC pipes of class 2 to class 6 and specials, lowering to the trenches already made, placing in position aligning the pipeline to the lines and levels and jointing the pipes and specials with solvent cement and testing the pipeline with water to the required test pressure (excluding cost of pipes and specials): 200 mm nominal outside diameter pipes.
84OD180581/2022-2023:Supplying and fixing Lightning Arrester including lightning conductor of GI 7/10” SWG (10mm) diameter standard wire with lightning rod of 25mm diameter, 0.9 meters long mounted on suitable fixture with 600x600x3mm copper plate earthing, 25mm diameter, 2.75 meters long GI pipe from ground level connecting 50mm diameter, 1.40 meters long perforated GI pipe including fixing of clamps as per IS:2309. fixing all accessories etc complete. (As per vet estimate No. PRJ(PKD)-10/21/02.12.2021 by Special officer electrical. estimate attached)
85OD180582/2022-2023:Supplying fabricating conveying and fixing water level indicator made in GI sheet of 3 mm ( or nearest thickness) , of 20 cm minimum width and required height in full water level, painted , lettering done by using superior quality paint after applying primer, in suitable colour as per directions, fixing at a level to avoid any damages, fixing nylon rope, pully arrangement, standard quality float, etc. as per direction of Engineer at site.
86OD180583/2022-2023:Supplying and installing a electro-magnetic flow meter conforming to protection level of IP-68 for flow sensor and IP-67 for transmeter and having an accuracy level of 0.5% with LED/LCD display unit suitable to measure the discharge of transmission main of 250mm dia. The flow meter should have the housing (flow sensor) to be made of ss304/carbon steel with anti corrosive protection and inside liner to be made up of hard rubber/neoprene all confirming to drinking water standards. The flow meter should be coupled with HART for data acquisition and transfer with provision for wireless transfer through GSM. The manufacturers should have the calibration standards as per ISO 17025 and the product shall have sufficient warranty provisions. Product should be tested and calibrated at FCRI, Palakkad and test certificate should be produced. Flow meter should be calibrated with physical measurement at site after installation. A battery back up of min. 24 hrs should be provided.
8713.71:Lettering with black Japan pint of approved brand and manufacture
88100.47.2.1:Leak rectification work in 90mm uPVC (Class 2 to 6) pipeline including detecting and locating leak, earth work excavation in all kinds of soil for exposing leak portion of the pipe including tar cutting / concrete cutting, cutting the pipe diametrically perpendicular to the axis of pipeline without causing any damages to the balance portion, dismantling and lifting the pipe from trenches, smoothening the cut ends, conveying the new pipe, cutting and lowering new pipe into the trenches, placing in position, aligning the pipe to line and level and jointing the new pipe with the existing pipe with solvent cement or repairable joint and testing the pipeline by operating the valves concerned, and rectifying the defects if noticed and refilling the trenches in layers not exceeding 20cm depth including consolidating each layers by ramming, watering, charges for removing surplus soil from work site, without causing any damages to the existing utilities, including hire for tools and plant, conveyance of tools and materials, bailing out water, providing caution boards, lighting, ribbon fencing, watching, traffic control etc., complete as per the direction of Departmental officers, including the cost of pipe & specials but excluding the cost of C.I.R. Joints; uPVC Pipes and specials shall be of good quality and conforming to relevant standards: Socket & C.I.R. Jointing.
89100.47.2.4:Leak rectification work in 160mm uPVC (Class 2 to 6) pipeline including detecting and locating leak, earth work excavation in all kinds of soil for exposing leak portion of the pipe including tar cutting / concrete cutting, cutting the pipe diametrically perpendicular to the axis of pipeline without causing any damages to the balance portion, dismantling and lifting the pipe from trenches, smoothening the cut ends, conveying the new pipe, cutting and lowering new pipe into the trenches, placing in position, aligning the pipe to line and level and jointing the new pipe with the existing pipe with solvent cement or repairable joint and testing the pipeline by operating the valves concerned, and rectifying the defects if noticed and refilling the trenches in layers not exceeding 20cm depth including consolidating each layers by ramming, watering, charges for removing surplus soil from work site, without causing any damages to the existing utilities, including hire for tools and plant, conveyance of tools and materials, bailing out water, providing caution boards, lighting, ribbon fencing, watching, traffic control etc., complete as per the direction of Departmental officers, including the cost of pipe & specials but excluding the cost of C.I.R. Joints; uPVC Pipes and specials shall be of good quality and conforming to relevant standards: Socket & C.I.R. Jointing.
90100.47.2.6:Leak rectification work in 200mm uPVC (Class 2 to 6) pipeline including detecting and locating leak, earth work excavation in all kinds of soil for exposing leak portion of the pipe including tar cutting / concrete cutting, cutting the pipe diametrically perpendicular to the axis of pipeline without causing any damages to the balance portion, dismantling and lifting the pipe from trenches, smoothening the cut ends, conveying the new pipe, cutting and lowering new pipe into the trenches, placing in position, aligning the pipe to line and level and jointing the new pipe with the existing pipe with solvent cement or repairable joint and testing the pipeline by operating the valves concerned, and rectifying the defects if noticed and refilling the trenches in layers not exceeding 20cm depth including consolidating each layers by ramming, watering, charges for removing surplus soil from work site, without causing any damages to the existing utilities, including hire for tools and plant, conveyance of tools and materials, bailing out water, providing caution boards, lighting, ribbon fencing, watching, traffic control etc., complete as per the direction of Departmental officers, including the cost of pipe & specials but excluding the cost of C.I.R. Joints; uPVC Pipes and specials shall be of good quality and conforming to relevant standards: Socket & C.I.R. Jointing.
91100.48.1.5:Rectification of leakages in 200mm C.I. Pipe of all classes by replacing a length up to 1.5m including earthwork excavation in all kinds of soil for exposing leak portion of the pipe including tar cutting / concrete cutting, cutting and removing and stacking the damaged portion from the existing line without causing any damages to the remaining portion and specials and conveying and replacing with the C.I. pipe and conveying and jointing with C.I.D. joint / suitable mechanical joint of suitable size or any other available size suitable joints after cleaning the ends, grinding if necessary, centering the pipe, inserting the joints, tightening to make a water tight joint, charging and testing to the required pressure, rectifying any defects noticed and refilling the trenches using excavated earth in layers not exceeding 20cm depth including consolidating each layers by ramming, watering, removing the surplus soil from the work site, without causing any damages to any other utilities, including the charges of conveyance and hire for tools and plant, bailing out water, lighting, watching, ribbon fencing, providing caution boards, traffic diversion but excluding cost of materials and as per the direction of departmental officers etc., complete.
92OD180584/2022-2023:Supplying, providing and fixing solar power street light 50w capacity of reputed make including cost of solar panels, battery, bulb & necessary GI post for fixing solar light including cost conveyace and all labour charges etc. complete
93APPENDIX -VI - (A) - COST OF MATERIALS - SUPPLYING AND LAYING DISTRIBUTION LINES IN KUZHALMANNAM
94100.98.117:Supply of DI K9 Pipe Conforming to IS 8329/2000, 200mm Dia.
95100.98.118:Supply of DI K9 Pipe Conforming to IS 8329/2000, 250mm Dia.
96100.98.216:Supply of PVC Pipe, 6kg/cm2, 160mm Dia.
97100.98.214:Supply of PVC Pipe, 6kg/cm2, 110mm Dia.
98100.98.213:Supply of PVC Pipe, 6kg/cm2, 90mm Dia.
99OD180592/2022-2023:Supplying 150mm GI Pipe
100OD180593/2022-2023:Supplying 100mm GI Pipe
10118.12.8:Providing and fixing G.I. pipes complete with G.I fittings including trenching and refilling etc. External work80 mm dia nominal bore
102100.98.448:Supply of CI Air Valve with Flanges, Conforming to IS 14845 - 2000, Kinetic Air Valve Type DS1, Size 40mm
103100.98.457:Supply of CI Double Flanged Sluice Valve Conforming to IS 14846 - 2000, Sluice Valve with Cap PN 1.6, Size 80mm.
104100.98.458:Supply of CI Double Flanged Sluice Valve Conforming to IS 14846 - 2000, Sluice Valve with Cap PN 1.6, Size 100mm.
105100.98.460:Supply of CI Double Flanged Sluice Valve Conforming to IS 14846 - 2000, Sluice Valve with Cap PN 1.6, Size 150mm.
106100.98.462:Supply of CI Double Flanged Sluice Valve Conforming to IS 14846 - 2000, Sluice Valve with Cap PN 1.6, Size 250mm.
107OD180594/2022-2023:Supply of GI Specials
108OD180595/2022-2023:Supply of PVC Specials
10918.17.3:Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :40 mm nominal bore
110APPENDIX -VI- (B) - WORKING CHARGES - PIPE LAYING
111100.1.1:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in all kinds of soil.
112100.1.5:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50 m, in Ordinary Rock.
113100.1.13:Excavating trenches of required width for pipes, cables, etc., including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5m, including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20cm in depth, including consolidating each deposited layer by ramming, watering, etc., and disposing of surplus excavated soil as directed, within a lead of 50m, in Hard Rock where Blasting is Prohibited.
114100.59.1:Cutting the bituminous / concrete roads with cutting machine for a minimum depth of 200mm along the sides of proposed alignment of the pipe to be laid without causing any damage to other utilities, including the charges for hire and conveyance of tools and plant, cost of consumables and charges for lighting, watching, ribbon fencing, caution boards, traffic diversion, and as per the direction of departmental officers etc. complete, before carrying out the demolition of bituminous / concrete road by mechanical means and carrying out the excavation.
115100.8.1:Fencing one side of trenches, 1.50m height with two rows of 10cm plastic caution tape in vertical casuarina pole (girth 15cm to 24cm) fixed at 2m intervals.
116100.9.11:Laying uPVC pipes of class 2 to class 6 and specials, lowering to the trenches already made, placing in position aligning the pipeline to the lines and levels and jointing the pipes and specials with solvent cement and testing the pipeline with water to the required test pressure (excluding cost of pipes and specials): 160 mm nominal outside diameter pipes.
117100.9.9:Laying uPVC pipes of class 2 to class 6 and specials, lowering to the trenches already made, placing in position aligning the pipeline to the lines and levels and jointing the pipes and specials with solvent cement and testing the pipeline with water to the required test pressure (excluding cost of pipes and specials): 110 mm nominal outside diameter pipes.
118100.9.8:Laying uPVC pipes of class 2 to class 6 and specials, lowering to the trenches already made, placing in position aligning the pipeline to the lines and levels and jointing the pipes and specials with solvent cement and testing the pipeline with water to the required test pressure (excluding cost of pipes and specials): 90 mm nominal outside diameter pipes.
119100.14.3:Conveying and laying S&S Centrifugally Cast (Spun) / Ductile Iron Pipes conforming to IS: 8329 excluding cost of pipes and specials: 200mm diameter Ductile Iron Class K-9 Pipes.
120100.14.4:Conveying and laying S&S Centrifugally Cast (Spun) / Ductile Iron Pipes conforming to IS: 8329 excluding cost of pipes and specials: 250mm diameter Ductile Iron Class K-9 Pipes.
12118.30.5:Providing flanged joints to double flanged C.I./ D.I pipes and specials, including testing of joints:200 mm diameter pipe
12218.30.6:Providing flanged joints to double flanged C.I./ D.I pipes and specials, including testing of joints:250 mm diameter pipe
12318.70.3:Providing push - on-joints to Centrifugally (Spun) Cast Iron Pipes or Ductile Iron Pipes including testing of joints and including the cost of rubber gasket:200 mm dia pipes
12418.70.4:Providing push - on-joints to Centrifugally (Spun) Cast Iron Pipes or Ductile Iron Pipes including testing of joints and including the cost of rubber gasket:250 mm dia pipes
12518.68.1:Providing and laying D.I specials of class K - 12 suitable for push - on jointing as per IS : 9523 :Upt 600 mm dia
126100.12.9:Conveying and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc., but excluding cost of pipes and fittings for External work: 100mm diameter nominal bore.
127100.12.11:Conveying and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc., but excluding cost of pipes and fittings for External work: 150mm diameter nominal bore.
128100.31.2.1:Conveying and fixing C.I. sluice valves (with cap) by providing bolts, nuts, rubber insertions etc., complete, but excluding the cost of the valve (tail pieces, if required, will be paid separately): 80mm diameter, Class II.
129100.31.2.2:Conveying and fixing C.I. sluice valves (with cap) by providing bolts, nuts, rubber insertions etc., complete, but excluding the cost of the valve (tail pieces, if required, will be paid separately): 100mm diameter, Class II.
130100.31.2.4:Conveying and fixing C.I. sluice valves (with cap) by providing bolts, nuts, rubber insertions etc., complete, but excluding the cost of the valve (tail pieces, if required, will be paid separately): 150mm diameter, Class II.
131100.31.2.6:Conveying and fixing C.I. sluice valves (with cap) by providing bolts, nuts, rubber insertions etc., complete, but excluding the cost of the valve (tail pieces, if required, will be paid separately): 250mm diameter, Class II.
132100.32.2:Conveying and fixing C. I. Single Acting Air Valve of approved quality with bolts, nuts, rubber insertions etc., complete, but excluding the cost of air valve (tail pieces, if required, will be paid separately): 40mm Single Acting Air Valve.
133100.35.3:Testing 200mm DI/CI pipeline with potable water to the required test pressure 200 mm dia Observed Data derived from item no.1020 of PHED DATA
134100.35.4:Testing 250mm DI/CI pipeline with potable water to the required test pressure . 250 mm dia Observed Data derived from item no.1022 of PHED DATA
1352.6.1:Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
1364.1.6:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size)
1375.1.2:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size
1385.9.2:Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
1395.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
14013.1.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
141100.41.33:Supplying and fixing 500mm dia C.I. manhole cover with frame (medium duty) charges including all cost, labour charges etc., complete.
142100.41.39:Supply, stacking, spreading and consolidating of Quarry Muck in the trench of pipe line, including carriage, loading, unloading & stacking up to any lead.
14310.2:Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
144OD180585/2022-2023:Labour for cutting D.I. pipe with steel saw. 250 mm diameter D.I. pipe
145OD180586/2022-2023:Labour for cutting D.I. pipe with steel saw. 200 mm diameter D.I. pipe
146OD180587/2022-2023:Providing and fixing 200mm dia or nearest size protection tube/AC pipe bit or PVC pipe bit for a length of 1.50m long for protection tube to the below 150mm valve and Air valve in the pipe line /distribution system
147OD180588/2022-2023:Construction of Identification block(size 75cm X 25cm X 10cm) with RCC m20 mix including providing reinforcement and over plastering with CM 1:4 ,12mm thick one coat and printing letters with mould and fixing the block in the pipe line including cost of all materials etc complete
148APPENDIX- VII - RCC STRUCTURE FOR PIPE CARRYING BRIDGE
1492.6.1:Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
150OD187255/2022-2023:Drilling holes for MS dowel bars of size 25mm dia of 2.00m long(1m in rock and 1m in concrete) including drilling holes of 30mm dia and filling the gap with cement grout(0.5Kg/each) etc complete.
1514.1.5:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
1525.1.2:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size
1535.2.2:Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up tot floor five level excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)
1545.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
1555.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
1565.9.5:Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
1575.9.6:Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
1585.9.3:Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
15913.7.1:12 mm cement plaster finished with a floating coat of neat cement of mix:1:3 ( 1 cement : 3 fine sand)
16010.26.3:Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approves steel primer.G.I. pipes
16110.2:Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
162APPENDIX - VIII - PROVIDING FHTCs
163100.60.13.1.2:Providing 15mm (1/2 inch) house connection with 15mm water meter from existing PVC / HDPE mains up to 110 mm dia., up to a length of 5m using 20mm ( 1/2 inch ) PE Pipe, PE80, PN16, Conforming to IS 4984: 2016 or later edition and PP PN 16 Compression / GM / Brass specials viz. brass ferrule, brass hexagonal nipple, GM full way wheel valve, bend, MTA, FTA, couplers, PVC Service Saddle of suitable size etc. and connecting with the mains, testing the joints etc. complete including trenching and refilling in all kinds of soil up to a depth of 1.50m for main line tracing and trench of average cross section 0.3m x 0.75m for laying connection pipe and service pipe, fixing water meter, lighting, watching, providing caution boards, traffic control etc. complete including cost of materials, hire for tools, cost of consumables and labour charges, including the cost of tested Class B Multijet water meter with ISI mark and weather resistant PP / PE meter box of minimum size 300mm x 200mm x 150mm, but excluding charges for cutting the concrete / tarred / bituminous roads etc, and as per the direction of the departmental officers.
164100.60.14.1.2:Providing 15mm (1/2 inch) house connection with 15mm water meter from existing PVC / HDPE mains from 140mm to 200mm dia., up to a length of 5 m using 20mm ( 1/2 inch ) PE Pipe, PE80, PN16, Conforming to IS 4984: 2016 or later edition and PP PN 16 Compression / GM / Brass specials viz. brass ferrule, brass hexagonal nipple, GM full way wheel valve, bend, MTA, FTA, couplers, PVC Service Saddle of suitable size etc. and connecting with the mains, testing the joints etc. complete including trenching and refilling in all kinds of soil up to a depth of 1.50m for main line tracing and trench of average cross section 0.3m x 0.75m for laying connection pipe and service pipe, fixing water meter, lighting, watching, providing caution boards, traffic control etc. complete including cost of materials, hire for tools, cost of consumables and labour charges, including the cost of tested Class B Multijet water meter with ISI mark and weather resistant PP / PE meter box of minimum size 300mm x 200mm x 150mm, but excluding charges for cutting the concrete / tarred / bituminous roads etc, and as per the direction of the departmental officers.
165100.60.15.1.1:Providing additional length of house connection pipe using 20 mm (1/2 inch) PE Pipe, PE80, PN16, Conforming to IS 4984: 2016 or later edition and PN16 specials and testing the joints etc., by trenching and refilling in all kinds of soil with trench of average cross section 0.3m x 0.75m for laying of connection pipe and service pipe, lighting, watching, providing caution boards, traffic control etc., including cost of materials, hire for tools, cost of consumables and labour charges etc. complete, but excluding the cost of cutting of concrete / tarred / bituminous roads etc., and as per the directions of the department officers.
166100.60.21.1.1:Providing 15mm ( 1/2 inch ) GM Air Valve in the water meter assembly for 15mm water connection, using 20mm ( 1/2 inch ) PE Pipe, PE80, PN16, Conforming to IS 4984: 2016 or later edition and PP PN 16 Compression specials including cost of materials, consumables, hire for tools and labour charges etc. complete and as per the directions of the department officers.
167OD180589/2022-2023:Providing Vertical Stand post using 63 mm 6kg PVC pipe for FHTC's including necessary earthwork and fixing in concrete in position etc complete as per the direction of deptl officers.
168100.60.12.3.1:Providing 15mm PVC Tap in the water meter assembly for 15mm connection, using 20mm Indian Standard Class 6 uPVC pipes and specials including cost of materials, consumables, hire charges for tools and labour charges etc. complete and as per the direction of departmental officers.
1694.1.3:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 (cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
170OD180590/2022-2023:Cost of Geotagging Connections
171100.41.39:Supply, stacking, spreading and consolidating of Quarry Muck in the trench of pipe line, including carriage, loading, unloading & stacking up to any lead.
172APPENDIX - IX - PWD ROADRESTORATION CHARGES
1734.2.A.1:Construction of granular sub-base by providing graded material, spreading in uniform layers with a motor grader on a prepared surface, mixing by mix in-place method with rotavator at OMC, and compacting with a vibratory roller to achieve the desired density, complete as per clause 401. Grading-III -For lower sub-base - Mix in Place Method
1744.12:Providing, laying, spreading and compacting graded stone aggregate to Wet Mix Macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density.
1755.1.a:Providing and applying primer coat with bitumen emulsion ( SS) on prepared surface of granular Base including clearing of road surface and spraying primer at the rate of 0.70 - 1.0 kg/sqm using mechanical means.
1765.2.b:Providing and applying tack coat with bitumen emulsion (RS) using emulsion pressure distributor at the rate of 0.25 - 0.30 kg per sqm on the prepared Granular Surface cleaned with mechanical broom.
1775.3.2.a:Providing and laying bituminous macadam with 80-100 TPH hot mix plant producing an average output of 75 tonnes per hour using crushed aggregates of specified grading premixed with a bituminous binder (VG 30), transported to the site, laid over a previously prepared surface with paver finisher to the required grade, level, and alignment and rolled as per clauses 501.6 and 501.7 to achieve the desired compaction For Grading II - (19 mm nominal size)
1785.2.a:Providing and applying tack coat with bitumen emulsion( RS) using emulsion pressure distributor at the rate of 0.20 - 0.30 kg per sqm on the prepared bituminous surface cleaned with mechanical broom.
1795.6.2.a:Providing and laying bituminous concrete with 80-100 TPH hot mix plant producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with a bituminous binder( NRMB) @ 5.4 percent of mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level, and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MORTH specification clause No. 507 complete in all respects For Grading - II (13.2 mm Nominal Size)
1803.6:Excavation for roadwork in soil with hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tippers, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections, and transporting to the embankment location within all lifts and lead upto 1000m
1819.1:Plain cement concrete 1:3:6 mix with crushed stone aggregate 40 mm nominal size mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days
182OD180591/2022-2023:Supply,stacking, spreading and consolidating of Quarry Muck in the trench of pipe line,including carriage, loading , unloading and stacking upto any lead
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail