Defence Statutory Bodies & Commissions/Committees Closing in 0 days TDR #36068402

Tender For Provision Of Otm And Mess For Radar Units At Nellore Afs Suryalanka Phase I

Issued by Statutory Bodies & Commissions/Committees · suryalanka, Andhra Pradesh
Tender Value
9.69 Crore
Estimated cost
Bid Submission
19 Apr 2023
0 days left
EMD
13.84 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
suryalanka → Andhra Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Provision Of Otm And Mess For Radar Units At Nellore Afs Suryalanka Phase I

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 09-Mar-2023 Amendment No 1 Date 27-Mar-2023
2 18-Mar-2023 DATE2 Date 03-Apr-2023
3 23-Mar-2023 Amendment No 3 Date 14-Apr-2023
4 01-Apr-2023 BOQ WITH CORRIGENDUM BOQ 14-Apr-2023
5 05-Apr-2023 Amendment No 6 Date 19-Apr-2023
6 05-Apr-2023 Amendment No 5 BOQ 19-Apr-2023

BOQ

Name of Work: PROVISION OF OTM AND MESS FOR RADAR UNITS AT NELLORE AFS SURYALANKA (PHASE I)
Sl. No. Item Description
1BOQ Dated 03 Feb 2023
2GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to X are prepriced by MES under Ser No. 1 to 10. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
3Lumpsum price worked out by the contractor for “Building or works” as listed in Schedule ‘A’ Part–I
4Lumpsum price worked out by the contractor for “Internal Water Supply” as listed in Schedule ‘A’ Part - II
5Lumpsum price worked out by the contractor for “Internal Electric Supply\" as listed in Schedule ‘A’ Part–III
6Lumpsum price worked out by the contractor for “Road / Path” as listed in Schedule ‘A’ Part – IV.
7Lumpsum price worked out by the contractor for “Sewage Disposal” as listed in Schedule ‘A’ Part – V.
8Lumpsum price worked out by the contractor for \"Area Drainage\" as listed in Schedule ‘A’ Part - VI.
9Lumpsum price worked out by the contractor for \"External Water Supply\" as listed in Schedule ‘A’ Part - VII.
10Lumpsum price worked out by the contractor for “External Electric Supply” as listed in Schedule ‘A’ Part – VIII.
11Lumpsum price worked out by the contractor for \"Lightning Protection\" as listed in Schedule ‘A’ Part - IX.
12Lumpsum price worked out by the contractor for “Air Conditioning & Refrigeration” as listed in Schedule ‘A’ Part – X.
13Sch \"A\" Part - XI : Fittings / Fixtures & Misc items. INTERNAL WATER SUPPLYSupply and fix 15mm bore angle cock, cast copper alloy chromium plated fancy type, screwed for iron pipe or brass ferrule and fixed complete all as specified and as directed.
14Supply and fix 15mm bore two way bib tap cum health faucet with 1.25m long tube and wall hook, cast copper alloy chromium plated with crutch or butterfly handle, screwed down, screwed for pipe complete all as specified and as directed
15Supply and fix 15mm bore push cock cast copper alloy chromium plated for urinals complete all as specified and as directed.
16SEWAGE DISPOSALSupply and fix and connecting up LLDPE Septic Tank 10 users designed to carry sewage and sullage water including excavation in any type of Soil, PCC 1:4:8 below foundation, vent shaft, connection etc., complete all as directed.
17Supply and fix and connecting up LLDPE Septic Tank 25 users designed to carry sewage and sullage water including excavation in any type of Soil, PCC 1:4:8 below foundation, vent shaft, connection etc., complete all as directed.
18INTERNAL ELECTRIC SUPPLYSupply and fix and connecting up BEE 5 star rated ceiling fan of size 1200mm sweep including 3 core of size 0.5sqmm copper cable from ceiling rose to fan and writing MES No 2cm height with synthetic enamel paint complete all as specified and as directed.
19Supply and fix exhaust fan 300mm sweep heavy duty 900rpm single phase 240 volts AC 50 Hz with frame and louversincluding 3 core of size 0.5sqmm copper cable from ceiling rose to fan complete all as specified and as directed.
20Supply and fix exhaust fan 450mm sweep heavy duty 1200rpm single phase 240 volts AC 50 Hz with frame and louvers including 3 core of size 0.5sqmm copper cable from ceiling rose to fan complete all as specified and as directed.
21Supply and fix Telephone socket, PVC / polycarbonate type with back plate suitable for fittings complete all as specified and as directed.
22Material and labour for sub main wiring complete with two runs of 6.0 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistrandedcopper conductor cable with one run of6.0sqmm single core PVC insulated FRLS cable 1100 volts grade, multistrandedcopper conductor cable as earth continuity conductor, drawn through and including 25 mm dia rigid nonmetallicPVC conduit and conduit accessories (Concealed in walls / roofs) all as specified and as directed.Note :-Two runs of 6 sqmm cable and one run of earth continuity conductor and one run of PVC Conduit shall be measured as one unit length / running meter.
23Material and labour for sub main wiring complete with two runs of 10.0 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistrandedcopper conductor cable with one run of10.0sqmm single core PVC insulated FRLS cable 1100 volts grade, multistrandedcopper conductor cable as earth continuity conductor, drawn through and including 32 mm dia rigid nonmetallicPVC conduit and conduit accessories(Concealed in walls / roofs) all as specified and as directed. Note :-Two runs of 10 sqmm cable and one run of earth continuity conductor and one run of PVC Conduit shall be measured as one unit length / running meter.
24Supply and fixing of LED light fitting 4 feet, 1 x 20 Watt, 220Volt AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
25Supply and fixing of LED light fitting mirror type with high out put diffuser 2 feet, 1 x 10 Watt, 220Volt AC decorative type with driver, and LED lamp including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
26Supply and fixing of LED light fitting mirror type with high out put diffuser 2 feet, 1 x 5 Watt, 220Volt AC decorative type with driver, and LED lamp including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
27Supply and Fix 35W High efficient LED Building Security light fitting around the building, Aluminium pressure Die cast housingwith pure polyester powder coated for long life, High purity lenses for superior performance, IP66 protection, Suitable for external pipe dia Up to 50 mm, with Luminiare efficacy >100lm/W, driver Voltage range 150-270V AC, temperature range- 0 to 50DegC, Driver efficiency > 85%, Power factor > 0.95, THD<10%, CRI >70, Colour Temperature- 6500K, with Luminiare efficacy >100lm/W,Surge protection from overvoltage- 3.5KV in CM, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, 50000 burning hours as per L70 Criteria, including provision of 40mm dia GI light grade pipe1.5 mtr length bend to shape and necessary clamps etc for fixing the light fittings on wall/pole fixed complete as specified and as directed.
28Material and labour for Earthing complete with galvanized iron earth plate electrode of size 600mmx600mm x 6.3 mm thick buried directly under ground vertically to depth not less than 2.25 meter below ground level with top edge of plate at a depth not less than 1.5 m below ground level connected to and including GI wire 4mm dia and GI protection pipe 15mm dia and light grade connectedto and including by means of bolts nuts check nuts and washers made of copper as shown plate no 3 of SSR part 1 to the extent applicable to this item including necessary excavation earth work, PCC 1:3:6 chamber RCC 1:2:4 cover 50mm tick with 6mm TMT bar 100mm center to center watering pipe medium grade 20mm bore funnel wire mesh etc. and testing on completion all as specified and as directed.
29Supply and fix PVC conduit 20mm dia medium grade for telesocket and TV socket all as specified and as directed.
30EXTERNAL WATER SUPPLYMaterial and labour for Drilling 01 No of pilot/trail bore by DTH method through any kind of soil, kankar, boulder or soft or hard rock down up to the 250 RM depth below ground level by using 6 1/2 inch dia drilling bit including the cost of mud pit channels etc and disposal of soil obtained to a distance not exc. 1 km away complete all as directed.Note: (i) The drilling shall be continued up to specified depth and in case non availability of water, the location will be changed and fresh drilling shall be carried out as per direction of Engr-in-charge. (ii) After completion of pilot/ trail bore, the contractor shall have to arrange for electro logging of each bore (water logging test with electro logging equipment shall be measured and paid as separate item). Without electro logging of bore, remaining work should not be started in any case. (iii) Rig plant along with necessary T&P for drilling bore shall be arranged including its transportation charges by contractor under his own arrangement/cost. Note : The depth is for two Nos of bore well and all connected items are considered for two No borewell
31Material and labour for Development of trial/pilot bore holes-01 No into tube well to the dia upto 9 inch in alluvial strata complete by DTH method down to the depth upto 60 Mtrs depth incl removal of soil obtained up to a distance not exceeding 1 Km and site clearance complete from ground level complete all as specified and as directed.
32Material and labour for Development of trial/pilot bore holes-01 No into tube well to the dia upto 9 inch in alluvial strata complete by DTH method down to the depth60 Mtrs to 120 Mtrs depth incl removal of soil obtained up to a distance not exceeding 1 Km and site clearance complete from ground level complete all as specified and as directed
33Supply and lowering and fixing in position 9 inch dia bore (Nominal bore), PVC casing pipe, threaded type, not less than 12 mm wall thickness suitable for depth up to 150 meter, socketed trapezoidal threads jointing, confirming to IS – 12818 / DIN 4925 complete all as specified and as directed. Make: SUPREME/APPOLO/SKIPPER/BANSAL
34Supply and lowering and fixing in position 7 inch dia bore (Nominal bore), PVC casing pipe, threaded type, not less than 12 mm wall thickness suitable for depth up to 150 meter, socketed trapezoidal threads jointing, confirming to IS – 12818 / DIN 4925 complete all as specified and as directed. Make: SUPREME/APPOLO/SKIPPER/BANSAL
35Supply, Lowering and fixing in position Casing pipe of 7 inch dia bore PVC ribbed screen/strainer slotted pipe, not less than 12 mm wall thickness, horizontal slotting done by CNC Machines, slot width right from 0.2mm to 3.00mm, slot numbers designate width of openings in thousand part of an inch, suitable for depth up to 150 meter depth, socketed, trapezoidal threads conforming to IS:12818 / DIN 4925 including necessary jointing complete all as specified and as directed. Make: SUPREME/APPOLO/SKIPPER/BANSAL
36Developing tube well with Air compressor for minimum 08 hours of suitable capacity with adjustable length of pipe for pumping muddy water till sand free potable water upto 10 PPM is obtained complete all as specified and as directed.Note: The primary source to running air compressor like fuel/ electric supply and other connected resources is deemed to be included in the above quoted rate.
37Material and labour for testing the tube/ bore well for Two consecutive days each of 8 hours after development is completed and determining the yield by continuously pumping for 16 hours to determine safe pumping yield complete all as specified and as directed.Note: The primary source to running motor pump set like fuel/ electric supply and other connected resources is deemed to be included in the above quoted rate.
38Supply, install, testing & commissioning of Submersible borewell pump (CED coated pump casing), electric driven 415V, 50Hz suitable for 7 inch dia tube well, Head 140 meter at 100 LPM discharge for column pipe of size 50 mm bore, Bronze Impeller, Stainless steel motor casing, stainless steel pump shaft, stainless steel motor shaft, no.of stages shall be met the required head, SS body motor including electric connection with pump starter all as specified and as directed by Engr-In-Charge. (Note :2 X for bore well and 01 for stand by)
39Material and labour for PVC well cap made of 8 mm thick PVC sheet suitable upto 300 mm bore housing pipe incl necessary washer/gasket etc complete all as specified and as directed by Engr-in-Charge.Make:SUPREME/ APPOLO / SKIPPER/ BANSAL
40Material and labour water logging test with electro logging equipment & required machinery for ascertaining / logging aquifers encountered in bore well and arranging and defining the water availability test giving test report of Geohydrologist from Govt. approved laboratory recommending water bearing zones, TDS of water etc. complete as specified and as directed. Note : The contractor shall submit electro-logging result with recommended bore assembly details in duplicate for approval of AGE (I).
41Material and labour for strata sample collection (at every change of strata) one set in suitable wooden box made up of 12 mm thick and with sliding/ openable glass cover of 3mm thick, each sample strata should be produced and submitted to department including borewell assembly coloured chart in A4 size - 03 Nos for each bore well duly laminated and framed suitable for hanging on wall with following information furnished by the contractor on completion of the tube well:(i)Total depth of tube well drilled, type & size of pipe at levels.(ii)Strata chart of the tube well indicating different type of soil formations met with at different depths and indicating the depth of each type of soil formation,(iii) Marking of Strata at levels(iv) Position of every joint in well assembly,(v) Method used for development,(vi) Total hours of development done,(vii) Developed discharge in L.P.S.,(viii) Discharge is totally sand free or presence of sand particles is there,(ix) P.P.M. and turbidity after development,(x) Pumping water level at developed discharge,(xi) Static water level.
42Material and labour for carrying Chemical analysis of Borewell water sample in any Govt / SPCB approved / NABL accredited lab & submission of Test Report. Tests to be carried out on physical chemical and bacteriological parameters in accordance with IS-10500 and confirm the portability of water complete all as specified and as directed. Note: Quoted rate shall be deemed to be included collection of water sample from site.
43Material and labour for sanitary sealing of tube well with PCC (1:2:4) type B1(not more than 20mm graded stone aggregate) upto and a depth of 1mtr below ground level and 0.45 mtr above ground level (square type external dimension 600mm x 600mm) around tube well casing, platform of external dimension 1000mmx1000x150mm at ground level with PCC 1:4:8 type D2 foundation (using 40mm stone aggregate) including necessary form work complete all as specified and as directed.
44Supply and fix Submersible motor starter for 3 Phase suitable upto 7.5 HP Fully automatic Heavy Duty star delta starter with over load, under voltage, dry run protection, single phase preventer, Angle iron frame work to fix the starter on 3 mm thick CRCA sheet, Suitable incomer MCB, near borewell with necessary GI Sheet cover for outdoor installation, PCC foundation height of starter bottom 1 mtr above the ground level with associated items complete all as specified and as directed.Note: The Starter Panel Diagram shall be approved by Engr-in-charge before installation.
45Supply and fix/Laying PVC insulated 3 core 6 sq mm Copper multi stranded PVC sheathed flexible, flat, submersible cable ISI marked and conforming to IS 694 and connecting to submersible pump and upto LT panel / starter complete all as specified and as directed.
46Supply, install, testing & commissioning of Granular chlorination dosing pump, high pressure, single head, gear motored adjustable dosing pump having output of 2 U>S GPD to 40 U.S GPD and adjustable high pressure of up to 100 PSI with accessories including lead, tubing connection nuts, injection check valve, clay weight and ferrules and 100 liters FRP tank with lid & Level gauge along with Agitator and shaft & blade in plastic mounted on tank.The agitator motor must possess following specification :Voltage input 230 V, Single Phase 50 Hz, 900 RPM of suitable capacity.The accessories in the dosing system must consist of the following :(a) Preparation tank (300 Ltr)(i)Water inlet line of PPR pipe of suitable size and valves from main water line upto tank.(ii) Outlet pipe of PPR with strainer from preparation tank to main tank.(iii)Drain pipe of suitable size from preparation tank to outside where directed.(iv) Overflow(v) Conical bottom for sludge disposal(vi)Port whole with cover(vii)Level gauge(viii)Aigtator 120 Watt, 900 RPM, Single phase flange mounted motor with plastic shaft & impeller.
47(b) Service tank (100 Ltrs)(i) Water inlet(ii)Dosing pump mounting provision of lid/Wall(iii) Drain(iv) Overflow(v)Level gauge(vi)Inspection port(vii)Agitator motor fixed on wall/lid.Note : The quoted rate inclusive of following :-(i)All necessary electric connection required to run the agitator motor and dosing motor i.e. single phase 15 Amp socket 3 Nos including necessary wiring with 2.5 Sqmm copper wire.(ii) All necessary suitable size of valves required to take water for preparation tank and dosing etc complete.(iii) Preparation of suitable base as instructed by manufacturer for preparation tank and service tank.
48Supply and laying of DI pipespigot and socket type Class “K-9” ,100 mm (4”) dia suitable for tyton ring joint complete all as specified and as directed.
49Construction of Masonry valve chamber 1500mm x 1500mm x 750mmincluding excavation and earth work in any type of soil and 100 mm thick PCC 1:4:8 type D2 foundation, brick work in CM (1:6), plastering internal surface in 15 mm thick in CM (1:4), PCC (1:3:6) type C1 coping 50mm x50mm x6 mm angle iron, 6 mm thick MS plate cover complete with locking arrangement painting steel and iron surface with two coats of synthetic enamel paint over a coat of zinc chrome primer all as specified and as directed.
50EXTERNAL ELECTRIC SUPPLYSupply, installation and commissioning of HT 11 KV, 3 phase 50 cycles, outdoor type, totally enclosed metal clad switchgear complete with Vacuum circuit breaker having rupturing capacity upto 250 MVA, overload and earth fault protection, ammeter, voltmeter and of rating upto 400 Amp complete along with 4 Nos SF6 switch for inter connection including extension of bus bar of suitable capacity and size for the transformer load not more than 500 KVA and foundation complete all as specified and as directed.
51Supply and Installation of 11 KV, 630 Amp Load break switch panel with 16 Amp DO set (for I/C and O/G) and earth switch consist of three nos I/C-01, O/G 1 for transformer and 01 Nos for ring maint complete and including necessary foundation for fixing of panel complete all as specified and as directed (Three No switch consist of one panel)
52Supply, install, testing and commissioning of transformer of 100 KVA, level 3, step down Outdoor type complete with standard fittings, HT 11 KV 3 phase LT 433 volts, 3 phase 4 wire corrugated off circuit tape links of rating + 7.5 to -7.5 % @ 2.5% by means of hand operated off load tap changing gear, transformer copper wound, double wound, oil immersed naturally cooled with external cooling tubes, core type delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector symbol Dyn11 vector group with neutral brought on secondary side (LV side) and the maximum temperature rises should not exceed 45 degree centigrade in oil and 55 degree centigrade in HV / LV winding ring measured by resistance after continuous full load run in ambient temp as per IS-11171 per transformer, IS-3639 for fitting & accessories,IS-2099 for high voltage porcelain bushings and the transformer shall be comprised with the following standard fitting with off load tappings on HT side to vary secondary voltage within limit all as per IS-1180 of capacity up to of following:-
53(i) Pressure release valve(ii) Thermometer pocket on tank over with Thermometer(iii) Oil temperature indicator with 2 contacts alarm & trip(iv) Rating plate with terminal marking(v) Two earthing terminals on tank and cover to facilitate fixing of GI earth strip(vi) Oil level guage(vii) Oil drain filter valve(viii) HT/LT Cable terminal boxesNote: The transformer will have its initial oil filling to appropriate level (cost of oil including testing with desired dielectric strength deemed to be included in quoted rate)
54All as per item no 49 here-in-before but capacity 200 KVA, level 3
55Supply, install, testing and commissioning of Sound Proof DG set 62.5 KVA, 3 phase 4 wire, 415 volts,1500 RPM, 50 Hz power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integral acoustic enclosure having silent features such as modular bolted construction with fabrication on imported CNC torret punch machines, nine tank treatment process with pure polyster based powder coating to ensure long life in all weather conditions and for out door application/ installation, integrated design thereby facilitating /easy handling installation & shifting of the equipment at site. The design of integral acoustic enclosure should be any type approved by national Physical laboratory as per Central Pollution Control Board (CPCB-II) latest norms/regulation with fuel tank, battery and standard accessories and PCC foundation for (acoustic enclosure also 45 CM above ground level) as recommended by manufacturer, vibration pad, sand cushioning around PCC foundation, tools and spares, as provided by manufacturer all as specified and as directed with the following specifications
56(A) ENGINE :- Water cooled diesel engine of suitable capacity to match the 62.5 KVA alternator under NTP conditions with provision of 10% over load for 1 hour in every 12 hours running confirming to BS-5514 / ISO 3046 Standards. The engine shall consist of following :-(i) Fly wheel (ii) Radiator, Air-to-Air After cooler, pusher fan & fan drive arrangement (iii) Dry type Air cleaner with restriction indicator(iv) Fuel injection system (v) Radiator fan (blower type) with guard(vi) Precision governor (mechanical type) Class A1(vii) Gear Driven Water Pump(viii) Fuel Filter(ix) Spin-on Lubricating oil filters (x) 12 V DC electrical starting system consisting of starter motor, charging alternator. (xi) Exhaust silencer heavy duty residential type(xii) First Fill of Lubricating oil (API CF4 grade, Make Greaves Maxtherm Lube or its equivalent stranded)(xiii) Sensors for Oil pressure, Coolant Temperature & level.(xiv) Exhaust piping as per manufacturer design
57(B) Control Panel : The Control Panel is manufactured with 16 guage sheet steel fabricated, dust & vermin proof with complete internal wiring and microprocessor based DG Set controller for both engine and alternator parameter in one console. The Control Panel consists of the following parts:(a) DSE4510 Auto Start Control Module and the DSE 4520 Auto mains failure control module or latest model.(b) MCCB of Adequate rating(c) Indicating Lamps for DG ON, Main On, Load on DG, Load on Mains, etc(d) Key switch (e) Set of current transformers and control fuses and MCBs(f) Controller shall monitor and display the engine speed, oil pressure, coolant temperature, frequency, voltage, current, power factor and fuel level, Battery voltage and modules for comprehensive engine and alternator protection. (g) Controller shall also display the array of warning, electrical trip and shutdown alarms. Provide a record of most recent fault conditions. Fault history stored in the control non volatile memory.(h) Control includes provision for service adjustment and calibration of DG control functions - Voltage, frequency selection-Configurable input and output set up-Meter calibration(j) Controller provide configurable time delay of 0-300 sec to start after remote start signal and time delay of 0-600 secs prior to shutdown after stop signal.(k) Emergency stop: Annunciated whenever an emergency stop signal is received by the control.
58(C) BRUSHLESS ALTERNATOR:-(i) Alternator coupled to engine through a flexible coupling to an indigenous alternator mounted on strong steel fabricated base frame suitable for mounting on a permanent foundation. Self Excited, self regulated Brush less Single bearing alternator shall be confirming to BS- 5000 or relevant of IS-4722 Make: Crompton/ Stamford(ii) Type: self excited self regulated with automatic voltage regulator (iii) Rating: 62.5 KVA at 0.8 PF lagging (iv) Speed- 1500 RPM (v) System -415 V +/- 2.5% AC 3 phase 4 wire 50 Hz.(vi) Connection - 4 wire star connected (vii) Enclosure -Screen projected drip proof (viii) Ventilation - self ventilated(ix) Insulation: class H , IP-23(D) Sub base Fuel tank 14 SWG MS sheet and capacity to hold diesel sufficient for running 08 hours at full load including (i) Level indicator on fuel tank.(ii) Drain plug(iii) Piping for fuel tank as per manufacturer design(iv) Fuel strainer. (vi) Battery : 01 Nos 12 V not less than 88 AH with mounting frame.
59(E) AMF PANEL OUTDOOR TYPE:TheAMF Panel Outdoor type suitable for 62.5 KVA DG Set factory made out of CRCA Steel 3 mm thick Sheet floor mounted type and front operated type, totally enclosed dust, damp and vermin proof, all doors and joints will be suitable gasketed to form dust and vermin proof. The panel would be powder coated minimum thickness of 50 microns, stove enameled paint finished after elaborate pretreatment to form a long lasting characteristic. The control panel will be complete in all respect with fuses, wiring and labels etc, the following will be incorporated in the AMF Panel :- (a) HRC Fuse with fuse base, Din type 35A-06 No(b) Current transfrmer,CL-1, 5 VA, 200 /5A-04 No. (c) Four pole Contactor, 240 V AC, 2 NO +2 NC, of Suitable Current, AC3-02 Nos for (DG Set & Commercial) & MCCB 4 Pole, 25 KA, 100 A - 02 Nos. (d) Indicating Lights R ,Y, LED type, 240V AC -04 No.(e) Indicating Lights B,LED type, 240V AC -02 No. (f) Illu Push Button with elements, LED type -NO/NC-01 No.(g) Mushroom head push button, Press to lock, Turn to release-01 No. (h) KW/PF/KWH meter 96 x 96 sqmm, 3 Phase Digital type 415 V AC-01 No. (j) DC Ammeter 96 x 96 Sqmm, Digital type 0-20 A -01 No. (k) 12 V, 10 A DC Automatic Battery Charger with inbuilt trickle / boost facality-01 No(l) 4 Point Alarm Annuciator with inbuilt Hooter,Test,Accept & Reset Push button. (m) Solid state single element earth fault relay with 2 c/o contact, CTR-250/5A , Aux supply 230V AC - 1 No. (n) AMF Controller,12 V DC - 01 No. (o) Aux relay,Coil voltage, 24V DC, 4C/O, 14 PIN-24V DC-06 Nos(p) Thermal O/L Relay with inbuilt SPP Feature.
60Supply and fix LED street light fitting with and including individual high power not less than 60 watt LED new generation energy saving and environmental friendly long life LED street light made up of pressure die cast alu with secondary optics, suitable for outdoor use IP 66, connected withconnecting cable of suitable size of 3 core copper from Jn box to light fittings complete all as specified and as directed
61Supply and fix LED Flood light of 100 Watt Symmetrical illumination, along with Driver assembly as per OEM Specifications, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP66 flood light, necessary arrangement for fixing of light fitting on pole/wall by using necessary Angle Iron/clamp, nuts and bolts etcand connecting copper cable of suitable size complete all as specified and as directed.
62Supply and installation of 12.5 Mtr High galvanized high mast light with 8 lantern of 100 Watt LED Flood light fittings symmetrically fitted along with their control gear and having two point suspension system with stainless steel wire rope of 6 mm dia 97/19 guage and double drum winch with luminaire mounting arm, pulley assembly, aviation obstruction light, active lightning arrester spike including RCC foundationincluding necessary panel suitable for out door made out 3.15 mm thick CRCA Sheet of suitable size consist of starter for operation of wench up/down for repair/replacement of light fittings, MCB\"s/control contacts, timers and suitable copper cable from panel to light fittings etcfor operation of high mast lights with timer complete all as specified and directed.Note :The contractor should submit the drawing of High mast light with foundation suitable for wind pressure 120 Km/Hours and panel board for approval.
63Supply, installation, commissioning and testing of LT Feeder Pillar Box Indoor, double door type made out of CRCA Sheet of 2.0 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 300 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel as required, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following (for Transformer 1):
64(A) Main Incoming(i) MCCB conforming to IS:13947 (Part-II), adjustable IEC-947, TPN (4 pole), 160 Amps, 415 volts, 50 Hz, rupturing capacity 36 KA - 01 No.(ii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iii)LED indicating lamps with colour Red, Yellow, Blue (03 Lights) - 01 Set(iv) 6 Step APFC Relay with ultra heavy duty capacitor of rating 20 kVAR-01 No., 05 kVAR-03 Nos along with necessary harmonic filters, Duty Contactors, control switch gears etc - 1 Set(B) Main Outgoing(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 01 No. (PH )(ii) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 40 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 04 No. (Single living, MES, Mess& Spare -4)(iii) MCB TPN 6-32 Amps, 10 kA, C Curve - 03 Nos (High Mast light, MES complex & street light)
65Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCB mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 300 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following (for Transformer 2):
66(A) Main Incoming(i) MCCB conforming to IS:13947 (Part-II) adjustable, IEC-947, TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 01 No.(iii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iv)LED indicating lamps with colour Red, Yellow, Blue, Mains On, Standby On (05 Lights) - 01 Set(B) Main Outgoing(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 16 KA - 01 No. (AF Net, BCR & Spare)(ii) MCCB FP 32 Amps, 16 kA, C Curve - 02 Nos (Armoury & spare)(iii) MCB TPN 6-32 Amps, 10 kA, C Curve - 02 Nos (Street Light & Spare)
67Supply, installation, commissioning and testing of LT Feeder Pillar Box out door, double door type made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size for fixing the I/C & O/G MCCBs mentioned below made out of angle iron 45 x 45 x 6 mm and four numbers of 150 Amps aluminum strips / bars duly insulated on insulators - 4 Nos / suitable size Bakelite sheet, free space between MCCBs / busbar and other connection items should be provided, the space between ground to panel should be 60 cm with PCC foundation for LT Panel, LT panel should be provided with necessary locking arrangement, danger notice sticker, cable glands, internal wiring with FRLS copper wires of suitable size and comprising and including the following (AF Net):-
68(A) Main Incoming(i) MCCB conforming to IS:13947 (Part-II) adjustable, IEC-947, TPN (4 pole), 100 Amps, 415 volts, 50 Hz, rupturing capacity 25 KA - 01 No.(iii) LED Multifunctional Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (iv)LED indicating lamps with colour Red, Yellow, Blue, Mains On, Standby On (05 Lights) - 01 Set(B) Main Outgoing(i) MCCB conforming to IS:13947 (Part-II), IEC-947, TPN (4 pole), 63 Amps, 415 volts, 50 Hz, rupturing capacity 16 KA - 01 No. (AF Net, BCR & Spare)(ii) MCCB FP 32 Amps, 16 kA, C Curve - 02 Nos (Armoury & spare)(iii) MCB TPN 6-32 Amps, 10 kA, C Curve - 02 Nos (Street Light & Spare)
69Material and labour for Earthing complete with earth galvanized steel plate electrode 600x600x6mm buried directly in ground earth pit not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level, surrounded from all sides with mixture of charcoal and common salt and electrode connected with galvanized earth lead GI strip 32X6 by means of bolts, check nut and washers of GI or steel, GI pipe medium grade of 40 mm bore as protection pipe, GI strip of length not more than 7.5 mtr and connected to test point. GI pipe 20mm dia medium grade for watering, funnel with wire mesh, PCC pit and RCC (1:2:4) type B-1 for cover with 8 mm dia bar reinforcement both ways @ 140 c/c including excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr as shown on electrical plate No 3 of SSR 2009 complete all as specified and as directed.
70Material and labour for Earthing complete with earth galvanized steel plate electrode 600x600x6mm buried directly in ground earth pit not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level, surrounded from all sides with mixture of charcoal and common salt and electrode connected with galvanized earth lead 4 mm GI wire by means of bolts, check nut and washers of GI or steel, GI pipe medium grade of 40 mm bore as protection pipe, GI strip of length not more than 7.5 mtr and connected to test point. GI pipe 20mm dia medium grade for watering, funnel with wire mesh, PCC pit and RCC (1:2:4) type B-1 for cover with 8 mm dia bar reinforcement both ways @ 140 c/c including excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr as shown on electrical plate No 3 of SSR 2009 complete all as specified and as directed.
71Supply and fix Solar LED 24 W light with inbuilt SCC, all in one street light with Solar PV Module 100 wp, MPPT, 2400 lumens, including 5 mtr GI Tube Pole, earthwork, PCC in foundation and coping, complete all as specified and as directed.
72Returning and filling of trenches in two parts(i) using riddled soil obtained fromexcavated soil upto depth of 30cm (8cm below cable and remaining above cable) for cushioning of cable and(ii)refilling the trench of remaining depthwith normal excavated soil all as specified and directed.Note :- (i) Excavatedsoil shall be riddled by using sieve to separate composite particles etc as per IS 1255-1983 and refilling in trenches as in cable cushioning.
73Supply and fix street light brackets made of 25 mm dia G.I. Pipe light grade in shape and including suitable size of reducer to fix the LED street light of capacity 45W and angle as directed not exceeding 1.5 mtrs in length fixed to pole with suitable size of M.S. flat iron clamps, 2 Nos, M.S nut & bolt with cup washers complete all as specified and as directed.
74Supply and fix loop in-out junction box with non metallic FRP junction box suitable of size (Appx 350 x 250 x 150) with connector 4 way and including one MCB SP 6 A, 230V alongwith 2 Nos \"C\" Clamps and back clamp made up of 20x3 flat iron and fixing on pole with necessary nuts bolts, washers, 2 Nos PVC cable glands of size not exceeding 4 core 25 sqmm, Cable lugs as required complete all as specified and as directed.
75Supply and fix Automatic Street Light Control panel out door made out of CRCA Sheet of 3.15 mm thick with powder coated painting frame suitable size and the space between ground to street light control panel should be 60 cm with PCC foundation for street light control Panel, control panel should be provided with necessary locking arrangement, danger notice sticker, provn of cable entry and exit arrangement for Al cable size upto 120 Sqmm and glands, thimbling for connection of cable to MCBs/MCCBs/bus bar etc internal wiring with FRLS copper wires of suitable size and three indicator lights, LED Multifunctional Panel meter to measure voltage, current frequency, power factor, kWH, etc with all connected CTs, suitable size of bus bar and control accessories i.e. Three Phase, 5 kW using Infrared Sensor based NATURE SWITCH for automatic switching of Street Lights, 3 nos. Contactors, 3 nos. Incoming MCBs & 3 nos. Outgoing MCBs of 16-20 Amps each & Circuit wiring (Copper) of suitable size. Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is = 30 Lux and for Switching OFF = 10 Lux. The Sensor should also have part night operation facility of min. 4 hrs. to max. 12 hrs.
76The Sensor along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Enclosure conforming to IP54. The circuit should also have provision for Manual Operation (i.e. Sensor By-Pass option) with necessary clamps, and connecting to existing XLPE Cables by providing proper size of glands and thimbles (lugs) complete all as specified and as directed. with following :-a)I/C MCCB4 Pole 63 Amps 25 KA -01(b) O/G MCB 4Pole 32 Amps 10 KA - 02 NosNote :a) Nature Switch - Kakatiya Energy Systems/BAJAJ/Healerb) MCB\"s & Contactors - BCH/L&T/Schneiderc)Enclosure - Sintex or equivalent Model: Swadeep-02EC-5kW3P or as approved by Accepting officer
77LIGHTNING PROTECTIONMaterial and labour for Earthing complete with copper earth plateelectrode 600x600x3.15mm buried directly in ground earth pit not less than 2.25 mtr below ground level with top edge of the plate not less than 1.5 mtr below ground level, surrounded from all sides with mixture of charcoal and common salt and electrode connected with galvanized earth lead copper strip 20x3 by means of bolts, check nut and washers of copper/brass, GI pipe medium grade of 40 mm bore as protection pipe, copper of length not more than 7.5 mtr and connected to test point. GI pipe 20mm dia light grade for watering, funnel with wire mesh, PCC pit and RCC (1:2:4) type B-1 for cover with 8 mm dia bar reinforcement both ways @ 140 c/c including excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr as shown on electrical plate No 3 of SSR 2009 complete all as specified and as directed.
78AIR CONDITIONING & REFRIGERATIONSupply and fix Voltage stabilizer of capacity 4.0 KVA for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% complete all as directed.
79Supply and fix Voltage stabilizer of capacity 5.0 KVA for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% complete all as directed.
80Supply and fix refrigerator, electric driven (single phase), capacity more than 195 Litres BEE 5 star rated complete all as specified and directed
81Supply and fix Voltage stabilizer of capacity 2.0 KVA for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% complete all as specified and as directed.
82Material and labour for submain wiring with two runs of FRLS single core cable PVC insulated unsheathed cable, 1100 volts grade 4 Sqmm copper multistranded conductor including and drawing into 20mm dia rigid non metallic Concealed PVC conduit, fixed on wall, ceiling including one run of 4 sqmm FRLS PVC insulated unsheathed multistranded for earth wire connected to earth and making good, complete all as specified and as directed. Note :-Two runs of 4 sqmm cable and one run of earth continuity conductor and one run of PVC Conduit shall be measured as one unit length / running metre.

AI Tender Summary

OUR REF NO 36068402
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 9.69 Crore
LAST DATE 19-04-2023
Authority
Authority Name Military Engineer Services
Work Description Provision Of Otm And Mess For Radar Units At Nellore Afs Suryalanka Phase I
Basic Detail
Tender No 801512/E8
Bidding Type Tender
Location
City suryalanka
State Andhra Pradesh
Key Dates
Publish Date 05 Apr 2023
Submission Date 19 Apr 2023
Open Date 26 Apr 2023
Finance
Tender Value 9.69 Crore
Tender Fee 3000
EMD 13.84 Lakhs
Exemption Not Available
Document List
8d16902a-44e1-448a-bad2-a24520148282.html
801512.pdf
BOQ_648580.xls
TDdrawings.pdf
Tenderdrawings.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Apr 05, 2023
11:30 IST

Tender Published

Tender notice published.

Completed
Mar 27, 2023
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Apr 03, 2023
18:00 IST

Corrigendum-2 Issued

Clarifications on tender conditions and amendments issued.

Completed
Apr 14, 2023
18:00 IST

Corrigendum-3 Issued

Clarifications on tender conditions and amendments issued.

Completed
Apr 14, 2023
18:00 IST

Corrigendum-4 Issued

Clarifications on tender conditions and amendments issued.

Completed
Apr 19, 2023
18:00 IST

Corrigendum-5 Issued

Clarifications on tender conditions and amendments issued.

Completed
Apr 19, 2023
18:00 IST

Corrigendum-6 Issued

Clarifications on tender conditions and amendments issued.

Completed
Apr 19, 2023
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Apr 26, 2023

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

8d16902a-44e1-448a-bad2-a24520148282.html

pdf

801512.pdf

xls

BOQ_648580.xls

pdf

TDdrawings.pdf

pdf

Tenderdrawings.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail