Tender For Provision Of Additional Facilities For Jetties/Dry Dock Near Sbw At Naval Dockyard Mumbai, mumbai-Maharashtra

Military Engineer Services-MES has published Tender For Provision Of Additional Facilities For Jetties/Dry Dock Near Sbw At Naval Dockyard Mumbai. Submission Date for this Tender is 09-06-2023. Civil Work Tenders in mumbai Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

36047831
Corrigendum : Tender For Provision Of Additional Facilities For Jetties/Dry Dock Near Sbw At Naval Dockyard Mumbai
Open Tender
Indian
Maharashtra
mumbai
09-06-2023

Tender Details

Provision Of Additional Facilities For Jetties / Dry Dock Near Sbw At Naval Dockyard Mumbai

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 24-Feb-2023 DATE CORRIGENDUM 8538 DT 24 FEB 2023 Date 11-04-2023
2 24-Mar-2023 DATE CORRIGENDUM 8538122 DT 24 MAR 2023 Date 28-04-2023
3 12-Apr-2023 DATE CORRIGENDUM 8538 125 dated 12 APR 2023 Date 13-05-2023
4 03-May-2023 DATE CORRIGENDUM 8538 DT 03 May 2023 Date 30-05-2023
5 18-May-2023 Amendment to tender documents8538 18 May 23 BOQ 30-05-2023
6 18-May-2023 DATE CORRIGENDUM 8538 DT 18 May 2023 Date 06-06-2023
7 23-May-2023 DATE CORRIGENDUM 853835 dated 23 May 2023 Date 09-06-2023

Key Value

Document Fees
INR 3000 /-
EMD
INR 1250000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work:PROVISION OF ADDITIONAL FACILITIES FOR JETTIES/DRY DOCK NEAR SBW AT NAVAL DOCKYARD MUMBAI
Sl. No. Item Description
1LIST OF WORKS (Schedule A Part I to Part XVI)
2Total amount of Sch "A" Part-I (Building Works) brought forwarded from sl page No 29
3Total amount of Sch "A" Part-II (Pile Foundation) brought forwarded from sl page No 30
4Total amount of Sch "A" Part-III (Earth Work and Site Clearance) brought forwarded from sl page No 32
5Total amount of Sch "A" Part-IV (Internal Water Supply ) brought forwarded from sl page No 35
6Total amount of Sch "A" Part-V (Internal Electrification) brought forwarded from sl page No 55
7Total amount of Sch "A" Part-VI (Lightening Protection )brought forwarded from sl page No 57
8Total amount of Sch "A" Part-VII (Fire alarm & Fighting fightingsystem ) brought forwarded from sl page No 87
9Total amount ofSch "A" part- VIII (External WaterSupply) brought forwarded from sl page No 93
10Total amount ofSch "A" part- IX (External Electric Supply ) brought forwarded from sl page No 111
11Total amount ofSch "A" part- X ( Sewage Disposal) brought forwarded from sl page No 112
12Total amount ofSch "A" part- XI( Internal Roads)brought forwarded from sl page No 115
13Total amount ofSch "A" part- XII( Sewage Disposal)brought forwarded from sl page No .117
14Total amount ofSch "A" part- XIII( Area Drainage) brought forwarded from sl page No 119
15Total amount ofSch "A" part- XIV( Platform for transformer & Bldg for RMU ) brought forwarded from sl page No 126
16Total amount ofSch "A" part- XV ( EOT Crane ) brought forwarded from sl page No 128
17Sch "A" Part- XIV(MISCELLANEOUS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
18Plates ( plain or chequered ) channels sqaure cut or notched ( ordinary and counter sunk ) forimg holes, wihtout any attachment in Fe410-W ( gde E-250) quality -B ) Providing 6mm thick MS Plate with stiffners and drains the same to a depth of rock touch level for piles all as directed and specified ( The rates shall include for cutting of MS liner at cutt off level as directed )
19Providing and fixing 300mm dia RCC NP3 Half round gutter pointing in CM 1:2 with proper slope etc, complete, all as specified & directed.
20Preaparing new surface of steel of any description, over 10cm in width or girth,not otherwise described and applying two coats of anticorrosive paint over coat of primer, complete, all as specified & directed.
21Angle stop cock with wall flange make- Jaquar QQP-7053PM or equivalentfor 15mm bore pipe complete, all as specified & directed.
22Pillar Cock ( straight line mode) including auto closing system with elbow operated extended lever for 15mm bore pipe etc, complete, all as specified & directed. make- Jaquar PRS-001MED
23Bib Cock with wall flange etc, for 15mm bore pipecomplete, all as specified & directed. Make -Jaquar QQP-7073PM
24Two way Bib Cock with wall flange etc, for 15mm bore pipecomplete, all as specified & directed. Make -Jaquar QQP-7041PM
25Hand Shower ( health Faucet ) with 8mm dia and 1.20 long flexible tube including wall hook etc, complete, all as specified & directed. Make - Jaquar ALD-563
26Ball brass valves high pressure with polythene float and flynut complete screwded for iron pipe or brass ferrule and fixed to 40mm dia pipe etc, complete, all as specified and directed.
27Pile Foundation
28Boring for bore cast in situ pile 1000mm dia through any type of soil, clay, soft disintergrated rock, boulders & like etc and getting out & disposal of spoil to any distance outside of MoD land , using bored piling rotary rig method, complete, all as specified & directed.
29Boring for bore cast in situ pile 800mm dia through any type of soil, clay, soft disintergrated rock, boulders & like etc and getting out & disposal of spoil to any distance outside of MoD land, using bored piling rotary rig method, complete, all as specified & directed.
30Boring for bored cast in situ pile 1000mm dia through hard rock and getting out & disposal of spoil to any distnace outside of MoD land , using bored piling rortary rig method, complete, all as specified and directed,
31Boring for bored cast in situ pile 800mm dia through hard rock and getting out & disposal of spoil to any distnace outside of MoD land , using bored piling rortary rig method, complete, all as specified and directed,
32Intila load testing Dynamic testing ( High Starin Dynamic ) on piles 1000mm dia all as per Is-2911 Part IV and all specified and directed including bring on site all equipment required and removal from the site aftertesting is completed, all as specified & directed.
33Intila load testing Dynamic testing ( High Starin Dynamic ) on piles 800mm dia all as per Is-2911 Part IV and all specified and directed including bring on site all equipment required and removal from the site aftyer testing is completed, all as specified & directed.
34Routine load testing ( High Starin Dynamic) on piles 1000mm dia all as per IS-2911 Part-IV and all as specified and directed including bring on site all equipment required and removal the site after testing is complete, all as specified & directed.
35Routinr load tseting ( High Starin Dynamic) on piles 800mm dia all as per IS-2911 Part-IV and all as specified and directed including bring on site all equipment required and removal the site after testing is complete, all as specified & directed..
36Non destructive intergrity testing on 1000mm dia piles to be carried out as per IS-14893 of 2001, complete, all as specified & directed.
37Non destructive intergrity testing on 800mm dia piles to be carried out as per IS-14893 of 2001, complte, all as specified & directed.
38INTERNAL ELECTRIFICATION
39Sheet Metal Enlosure for 4P MCCB, Generous space for cable termination, in-built neutral Link for TPN sysstem, IKO8 and IP30 protection, Mounting holes for easy wall mounting, Louvers for better heat dissipation, size 1 suitable up to 125A MCCBs, 36KA, complete all as specified & directed.
40Double door VTPN MCB DB with provision for FP MCB / isolator / RCCB / RCBO as bincomer and SP/TP MCB"s as outgoing made of steelsheet phosphatised powder painted, 440Volt with bus bar erated 100Amp, neutral link, Earth bar and Din Rail and havinh IP 42 Proyecyion for size 4 way, incomer 4 pole MCB of 63/100 Amp rating 10KA breaking capacity, all as specified & directed.
41Double door VTPN MCB DB with provision for FP MCB / isolator / RCCB / RCBO as bincomer and SP/TP MCB"s as outgoing made of steelsheet phosphatised powder painted, 440Volt with bus bar erated 100Amp, neutral link, Earth bar and Din Rail and havinh IP 42 Proyecyion for size 4 way, incomer 4 pole MCB of 63/100 Amp rating 10KA breaking capacity, all as specified & directed.
42Blanking Plate of plastic ( Suitable for distribution board)
43Air circulator heavy duty wallmounting 450mm sweep, 240volts, single phase ISI marked with built in selector switch including making connection by using PVC sheathed twin core copper cable cable from ceiling rose to air circulator, complete, all as specified & directed.NOTE :- The air circultaor is to be fixed on wall with all necessary T&P and other accessories required shall be deemed to be included in the above item no extra payment shall be admissible on this account.
44LED lamp 1x5 watt with holder complete suitable for fixation on wall / roof body robust, corrosion resistant, superior finish and without any cracks of through holes. The system wattage of fitting should not be more than 5 watt + 10% surge protection of minium 2KV power factor should be more than 0.90 cool white colour, total harmonic distortion (THD) shouldd not be morte than 15% lumen output should not be less than 351 limens, total input voltage range 140-280V AC colour rendering index should be less than 80, correltaedd colour should be minium 6000 degree kelvin, complete, all as specified v& directed.
45High bay Beam LED light fitting of 56watt including Led lamps specifically designed heat sink for long life vertical high bay / medium LED luminaries complte with body robust, corrosion resistant, superior finish and without any cracks of fixing on wall / roof with help of suitable GI clamps, nuts, bolts and washers etc complete all as directed. The luminaries shall be monolithic construction totally enclosed dust and water proof with minium IP-65 protection as per IS-10322-1982 ( part-I) with latest amendments and input voltage range 140-360V, AC, frequency 5060 Hz, P,F should be more than 0.9 with Total Harmonic distortion THD (I) less tahn 15%, cool white colour and lamp starting time should not be more than 10 second. Fitting should be provided with 10KV surge protection. Driver should also have high voltage withstanding capacity upto 300V, AC driver should also have double phase protection, no load, open circuit and sgort circuit protection, LED light fitting should be suitable for ambient temperture from -10 degree centrigrade to 50 degree toughened glass to ensure IP 65 degree protection. Cover should not degrade due to heating and ageing. The effiueceincy of LED luminaries system shall be more than 90 lumens per watt and must be certified by the LM-79 test report, complete, all as specified & directed.
46LED street / Security light fittings of 45 watt including LED lamps complete with body robust, corrosion resistnt, superior finish and without any cracks of through holes, made in asingle piece by high pressure die cast aluminium alloy including fixing on wall with 1.2mtr long GI pipe 32mm dia , medium grade bracket at 120 degree angle with help of suitable GI clamps, nuts, bolts and washers etc complete all as directed. The luminaries shall be monoliyjic construction totally enclosed dust and water proof with minium IP 65 protection as per IS-10322-1982 with latest amendments and input voltagevoltage range 140-300V, AC, frequency 50-60Hz, PF should be more than 0.9 with Total Harmonic distortion THD (I) less than 15% cool, white colour and lamp starting time should not more than da10 second. Fitting should be provided with 10KV surge protection. Driver should be constant current voltage driver. Driver should have high volatge with standing capcity upto 300V, AC Driver should also ahve phase protection, no ambient temperture from (-) 10 degree centigrade 50 degree centigrade and humidity level 10% to 90% RH. Covers should be polycarbonate / toughened glass to ensure IP 65 degree protection. Cover should degrade due to heating and ageing. The efficiency of LED luminaries system shall be more than 90 lumens per awtt and must be certified by the LM-79 test report, complete, all as specified & directed.
47Supply installing, commissioning and testing LT panel board ( Indoor type) cubicaltype made out of CRCA sheet 2mm thick dust and vermin proof and angle iron of size 25mm x25mm x6mm, pedestal frame grouted in PCC ( 1:2:4) type B-1 20mm graded crushed stone aggregates, thimble and cable entry boxes with cable glands, Panel should covered from all sides with front and back lockable door and hinges complete with aluminium bus bar of capacity 500Amps, TPN, three phase 04 wire ( In separate chambers) including paitning with two coats synthectic enamelled paint over a coat of red oxide primer and consisting of the following ( Ground Floor Panel )
48(a) Incoming MCCB 4 pole 325 Amps 36 KA with fixed type and extension link- 01 No
49(b) Out going MCCB 4 pole 100 Amps 25 KA with fixed type and extension links- 02 Nos
50(c) Out going MCCB 4 pole 63 Amps 25 KA with fixed type and extension links- 07 Nos
51(d) Out going MCB SPN 10 Amps -01 No
52(e) Digital voltmeter with built in selector switch 0-500 Volts - 1 No
53(f) Digital Ammeter with built in selector switch 0-30Amps with suitable CTs-1 No
54(g) LED indicated Lamp ( R Y B ) one set - 01
55Supply, installing, commissioning and testing LT panel board ( indoor type ) cubical type made out of CRCA sheet 2mm thick dust and vermin proof and angle tron of size 25mm x25mmx 6mm, pedestal frame grouted in PCC 1:2:4 type B-1( 20mm graded stone aggregates ) , thimble and cable entry boxes with cable glands, Panel should covered from all sides with front and back lockable door and hinges complete with aluminium bus bar of capacity 300 Amps, TPN, three phase, 04 wire ( in separate chamber ) including painting with two coats of synthetic enamelled paint over coat of red oxide primer and consisting of the following ( Second Floor panel)
56(a) Incoming MCCB 4 pole 200 Amps 25 KA with fixed type and extension link- 01 No
57(b) Out goingMCCB 4 pole 125 Amps 25 KA with fixed type and extension link- 01 No
58(c) Out goingMCCB 4 pole 63 Amps 25 KA with fixed type and extension link- 01 No
59(d) Out goingMCCB 4 pole 40 Amps 25 KA with fixed type and extension link- 01 No
60(e)Out going MCB SPN 40 Amps - 1 No.
61(f) Digital voltmeter with built in selector switch 0-500 Volts - 1 No
62(g ) Digital Ammeter with built in selector switch 0-30Amps with suitable CTs-1 No
63(h) LED indicated Lamp ( R Y B ) one set - 01
64Supply, installing, commissioning and testing LT panel board ( indoor type ) cubical type made out of CRCA sheet 2mm thick dust and vermin proof and angle tron of size 25mm x25mmx 6mm, pedestal frame grouted in PCC 1:2:4 type B-1( 20mm graded stone aggregates ) , thimble and cable entry boxes with cable glands, Panel should covered from all sides with front and back lockable door and hinges complete with aluminium bus bar of capacity 500 Amps, TPN, three phase, 04 wire ( in separate chamber ) including painting with two coats of synthetic enamelled paint over coat of red oxide primer and consisting of the following (Third Floor Panel)
65(a) Incoming MCCB 4 pole 325 Amps 36 KA with fixed type and extension link- 01 No
66(b) Out goingMCCB 4 pole 125 Amps 25 KA with fixed type and extension link- 01 No
67(c) Out goingMCCB 4 pole 100 Amps 25 KA with fixed type and extension link- 01 No
68(d) Out goingMCCB 4 pole 63 Amps 25 KA with fixed type and extension link- 04 No
69(e)Out going MCB SPN 40 Amps - 1 No.
70(f) Digital voltmeter with built in selector switch 0-500 Volts - 1 No
71(g ) Digital Ammeter with built in selector switch 0-30Amps with suitable CTs-1 No
72(h) LED indicated Lamp ( R Y B ) one set - 01
73Supply, installing, commissioning and testing LT panel board ( indoor type ) cubical type made out of CRCA sheet 2mm thick dust and vermin proof and angle tron of size 25mm x25mmx 6mm, pedestal frame grouted in PCC 1:2:4 type B-1( 20mm graded stone aggregates ) , thimble and cable entry boxes with cable glands, Panel should covered from all sides with front and back lockable door and hinges complete with aluminium bus bar of capacity 200 Amps, TPN, three phase, 04 wire ( in separate chamber ) including painting with two coats of synthetic enamelled paint over coat of red oxide primer and consisting of the following (FifthFloor Panel)
74(a) Incoming MCCB 4 pole 125 Amps 25 KA with fixed type and extension link- 01 No
75(b) Out goingMCCB 4 pole 63 Amps 25 KA with fixed type and extension link- 01 No
76(c) Out goingMCCB 4 pole 100 Amps 25 KA with fixed type and extension link- 01 No
77(d) Out goingMCCB 4 TP 63 Amps 25 KA with fixed type and extension link- 04 No
78(e)Out going MCB SPN 40 Amps - 1 No.
79(f) Digital voltmeter with built in selector switch 0-500 Volts - 1 No
80(g ) Digital Ammeter with built in selector switch 0-30Amps with suitable CTs-1 No
81(h) LED indicated Lamp ( R Y B ) one set - 01
82Supply, installing, commissioning and testing LT panel board ( indoor type ) cubical type made out of CRCA sheet 2mm thick dust and vermin proof and angle tron of size 25mm x25mmx 6mm, pedestal frame grouted in PCC 1:2:4 type B-1( 20mm graded stone aggregates ) , thimble and cable entry boxes with cable glands, Panel should covered from all sides with front and back lockable door and hinges complete with aluminium bus bar of capacity 200 Amps, TPN, three phase, 04 wire ( in separate chamber ) including painting with two coats of synthetic enamelled paint over coat of red oxide primer and consisting of the following (TerraceFloor Panel)
83(a) Incoming MCCB 4 pole 100 Amps 25 KA with fixed type and extension link- 01 No
84(b) Out goingMCB TPN63 Amps 10 KA -01 No
85(c) Out goingMCB TPN 16 Amps 10 KA - 02 No
86(d) Out goingMCB SP 16 Amps- 01 No
87(e) Digital voltmeter with built in selector switch 0-500 Volts - 1 No
88(f) Digital Ammeter with built in selector switch 0-30Amps with suitable CTs-1 No
89(g ) LED indicated Lamp ( R Y B ) one set - 01
90LIFT
91Design, supply, install, testing & commissioning goods llift 2 Ton capacity, speed 0.5 metre /sec with single speed motor, 415 volts, 3 phase AC 50Hz supply, conforming to IS-14665 and as amended suitable to serve G+05 floors with AC variable voltage and Variable Frequency Drive ( VVVFDrive ) complete with all standard accessories, simplex automatic & manual dual controlled operation with / without attendent, centre opening doors with door drive ( electric motor drive mechanism ), sliding stainless steel doors, automatic rescue device (ARD ) system , 3D infra red sensor in full height of door & built in announcing system without hand set ( 03 Nos, one in car, Machine room & Ground floor landing door ) complete, all as specifed & directed.
92AIR-CONDITIONING
93Supply and install hi wall split units indoor/ outdoor complete with cordless remote control remote control unit and with in built air ioniser and plasma filter for better indoor air quality with minimum 5 star rating, inventer type and EER 3.2 of capacity 2TR , complete, all as specified & directed.
94Suipply and install Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type wall mounted & designed for input variation between 170 V to 250V with out put voltage stabilized at 230V with accuracy of + 2.5% and of capacity 5 KVA including time delay control, Voltmeter, indication lamps etc, complete, all as specified & directed.
95EOT CRANE
96Indoor type double girder EOT crane, 10 Ton safe working capacity, Long travel-33 metre for span 5.3 meter and mainm Hoist lift height 5.5 meter speed 2.25 mtr/ min, cross Travel speed 12 mtr/min and long travel speed 12 mtr / min with operation through radio remote control pendent push button type ( RRC PB ) design standard -IS : 3177-1999, IS-807, 2006 other relevant standards, duty of crane : Class III M7, shrouded / MS angle type Down shop lead (DSL), Civil / grouting work, cable tray, isolator switch, power supply : 415 V AC 50 Hz, complete, all as specified & directed.
97Note :- MS rail shall be measured and paid separately under respective item of Sch "A" Part I
98NOTE ;-
99(i) Contractor is required to measure necessary dimensions, span, long travel, height of lift, clearance between rail centre to the existing column at site before starting of the crane design / manufacturing
100(ii) Any items / additional accessories required for safely operation of the crane shall be deemed to be included in the quoted rate.
101EXTERNAL WATER SUPPLY
102Making connections by cutting existing CI main 300mm dia under ground pipe including inserting tee 300x300x200mm and CI collar including necessary earth work jointing materials complete, all as specified & directed.NOTE :- CI Fitting shall measured and paid separately in respective items
103Making connections by cutting existing CI main 150mm dia under ground pipe including inserting tee 150x150x80mm and CI collar including necessary earth work jointing materials complete, all as specified & directed.NOTE :- CI Fitting shall measured and paid separately in respective items
104Supply, laying, jointing, commissioning and testing Ductile iron pipe with flanged ends centifugally cast class K-9 conforming to iS 8329-2000 in any length complete of size 200mm bore complete, all as specified & directed. NOTE :- Excavation and earth work shall be measured & paid seprately.
105CI foot valve with strainer at bottom conforming to IS 4038 of size 100mm dia including joints and jointing materils i.e. nuts bolts, washers, rubber insertion sheet etc, complete, all as specified & directed.
106CI foot valve with strainer at bottom conforming to IS 4038 of size 50mm dia including joints and jointing materils i.e. nuts bolts, washers, rubber insertion sheet etc, complete, all as specified & directed.
107Supply installing, commissioning and testingof centrifugal pump set horizontal split casing pump with bronze impeller stainless steel shaft mountedon common base frame foundation with nuts bolts, coupled directlythrough set of flexible coupling with three phase induction motor totally enclosed fan cooled t suitable capacity of operation on 415 volts, 50 Hz, AC class "B" insulation complete with pumping capacity 31.5 LPS at 40 mtr head including comprising of the following :-(a) Pressure guage with brass cock-01 No. (b) Standard foundation as per manufactures instructions
108Supply, installing, commissioning and testingof centifugal mono block pump coupled with electric driven motor 5 HP capacity, with supply voltage 415 volts, 3 phase, 50 Hzsuiatble for operation with operating head 36 mtrs and having capacity to discharge of size 65 x50mm bore including duly mounted on MS frame on foundation / PCC platform grouted with MS bolts, nuts of required size properly connected with suction and delievery water line complete all as specified & directed.
109Construction of valve chamber of size 1350mm x 1000mm x1200mm internal size suitable for housing 200 / 250mm dia sluice valve etc, with PCC M-20 for foundation, solid blck masonry using PCC 1:3:6 type C-1, blocks set in CM 1:4, PCC sheet cover 3mm thick double door type fixed to MS angle iron frame 50 x50x6mm embedded in concrete with suitable hinges and locking arrangments, including two coats of synthetic enamelled paint over a coat of red oxide primer, with all necessary excavation and earth work, complete, all as specified and directed.
110Construction of valvepitof size 90 cm x 90cm x 90cmof block masonry from top of surface including cover of MS sheeet 3.15mm thick and angle iron 40mm x40mmx 6mm with hinges, handle and locking arrangement including painting with two coats of synthetic enmaelled paint over a coat of red oxide primer and grouting to PCC 1:2:4 plastering in cement mortar 1:3, foundation concrete 1:3:6 including necessary earth work, complete, all as specified & directed.
111Excavation in trenches upto 1.5mtr depth and getting out in any type of soil for laying of CI pipe of dia 200mm and fill excavated earth upto 400mm from the bottom of trench and hardcore of n. exc 63mm gauge deposited, spread and levelled n. exc 15cm thick watered and rammed to a true surface over filling excavation soil & PCC 1:3:6 type C2 ( using 40mm graded stone aggregates )150mm thick layingover hardcore with rough finish, complete, all as specified & directed.
112FIRE FIGHTING SYSTEM
113Low smoke zero halogen ( LSOH) fire survival control cable with circuit integrity, conforming to BS 7846 and rated for 600V, having plain annealed stranded copper conductor with fire resistant mica tapes covered by extruded layers of cross-linked polyethylene, extruded layer of thermoplastic low smoke zero halogen ( LSOH) compound sheath, suitable for operating temperature range-40 degree celceius to +90 degree celceius and minimum bending radius being 12 times the overall cable diameter, including laying, clamping, termination and ferruling complete, all as specified & directed.
1142 Core 2.5 Sqmm ( for instrumentation )
1153 Core 2.5 sqmm ( for auto start / stop panel )
11612 Core 2.5 Sqmm ( for diesel engine pump )
1171.1 KV graded copper conductor , XLPE insulated armoured cable conforming to IS 7098-1: 1988, having stranded aluminium compact shaped conductors as per CI.2of IS 8130 : 1984, PVC inner sheath, single armouring of galvanised steel strip / wire and OVC type ST-2 outer sheath conforming to IS 5831 : 1984, including necessary clamping / dressing with cable ties and termination complete, all as specified & directed
1183 Core 35 sqmm ( for electric motor driven main fire pump)
1193 Core 6 Sqmm ( for jockey pump )
120PN 1.6 rated 150mm NB polypropelene vortex inhibitor suction lift conforming to BS 4504 with stainless wire mesh, bolts, nuts and washers etc complete, all as specified & directed. Make :- Associated Enterprises, Enduramax, Balmoral Tanks
121CL#150 rated two-piece design 25mm NB cast iron ( CI) straight pattern ball valve, conforming to IS 9890:981 and tested as peeBS 6755-1, having cast iron body, stainless steel AISI 304 ball, renewable PTFE seat & gland packing , CS fastners & lever having screwed / socket welded end connection with accessories complete, all as specified & directed.
122Orificeplate made out of 6mm thick SS304 with orifice of required size to be fitted between flange and landing valve of extrenal and internal hydrants to reduce pressure at outlet to the level of 3.5 Kg/ SQCM, complete, all as specified & directed. Make :- Newage, AAAG, Minimax
123FM approved and Ullisted PN 1.6 rated lever operaated, 80mm NB wafer type CI butterfly valve,conforming to IS 13095: 1991 fitted with visual indicator & temper switch, having csat iron (CI) body with ductilr iron EPDM coated disc, SS431 stub shaft, PTFE bushing, flange drilling standard end connection conforming to IS : 1538-1993 along with necessary accessories complete as specified & directed( For Zone control valve assembly) Make :- Grinell-Tyco, Nibbco, Bk Valve, Kartar Valve
124FM approved and UL listed 25mm NB compact 3 position ball valve with drain office ( Test and drain Valve) to test and darin water flow through sprinkler systems having OFF-TEST-DRAIN position, integral sight glass, rated pressure 300 psi, orifice size 15mm and K factor 5.6, conforming to NFPA13, along with necessary accessories complete, all as specified & directed. Make :-Tyco, HD, Viking
125RAIN HARVESTING Providing & fixing Prcast 1.20mtr dia RCC ring of 35mm thick to 40mm thick ( approx) of height 250mm ring each etc. in recharge pit,all complete as per dierction of Consultant / Engineer-in-Charge.
126EXTERNAL ELECTRIC SUPPLY
127Boring of holes under main road pavment , hard standing by trenchless technology using ultra sound tecnique and necessary machine for accomodet 100mm / 80mm / 50mm / 40mm bore GI tube ( light grade ) in the drilled holes, returning, filling in the end working space including removal of surplus soil and making good the surface. NOTE :- GI pipe light grade shall be measured and paid separately
128Supply, installation, testing and commissioning of outdoor type 3 Ph, 630A, 11/6.6 KV with system voltage 12 kV, 50 Hz dead front, floor -standing , fully compartmentalized metal clad dust, damp and vermin-proof HT Panel (SF6 insualted 2 LBS + 01 VCB RMU variant) conforming to IEC 62271-200, having 21 KA short time withstand current (for 3 sec) & internal arc tested for 21 kA )1 sec) with provision of bolting to the floor, suitable for severe tropical climate conditions conforming to IEC 60068-2-30, having separately earthed IP 67 rated HV and busbar compartments and IP2X rated LV compartment made of 2.0 mm thick CRCA sheet steel, outdoor type motor operated spring closing vaccume circuit breaker (VCB) & Load Break Switch (LBS), conforming to IEC 62271-100 having SCADA compatible facilities and complete with all accessories, short-circuit and earth fault protection for rupturing capacity of 350 MVAcomplete as specified and directed by the Engineer - in Charge. Make: Schneider, ABB,Siemens,L&T (i) The RMU shall be inside a hermatically sealed stainless steel tank, with SF6 gas , with a service life of 30 yrs for the main circuit without maintainance. (ii) Self - powdered microprocessor-based IDMT, O/C E/F numerical relays, conforming to IS 3231:1986, with high set for botgh phase & earth shall be provided. The relay shall store ffault data, site selectable CT secondary relay currents i.e 5 A or 1A, LED/LCD display for Nos , functions element of a realy to enable identification of the type of fault condition, composite relay unit having O/C, E/F, O/V, U/V, etc. features shall be preferred. The numerical relays shall be of communicable type and shall communicate on Modbus protoclo.
129The use of communication protocol converter is unaccepatable. RS485 port for communication in Modbus protocol shall be provided. (iii) Digital type multi-function meter displaying A, V, PF, Hz, kW, kVA, kVAr,kWh, kVArh, etc.) of class 0.5 accuuracy with RS485 port for communication in Modbus prottocol shall be provided. (iv) Ammeter and voltmeter selector switches shall be of four position type and have make before break feature to prevent open circuiting of CT secondary. The selector switch shall be suitable for semi-flush mounting with only switch fornt plate and operating ga bdle projection out (v) CTs shall be double core window / bar primary and the CT ratio shall be 100-150/1A. Maximum VA burden shall vbe 15 VA and rated ffor full short circuit current for 1 s . CTs shall be of a minimum accuracy of class 0.5/ accuracyof class 0.5/5P 10 and CT Secondary rating shall be 1 A unless otherwise specified. (vi) PT shall be 3-phase , 3-limb type with 50 VA per phase of class 0.5/3P accuracy and shall be mountex on incomer breaker truck. The same shall be mounted in a separate withdrawable truck in a separate verticle panel for bus connected PT. (vii) Control supply for closing and tripping shall be 110/220 V DC through an external battery source. 230V, 50Hz 1Ph AC supply shall be also beavailable for the operation of spring charging motor andcubical space heater. Wattage rating of closing and tripping coils shall be within 250 W. (viii) All other secondary wiring in the panel shall have high quality PVC insulation and the same shall have conductor size of not less than 1.5sqm copper.
130NOTE for Item No. 60.00 (I) The RMU shall be purchased from the original equipment manufacturer (OEM) / OEM authorised channel only. (ii) The bidder shall furnish dimensional drawsings of the items offered, indicating all the fittings, dimesional tolerances, typical GADs, etc. for approval of the Enigineer-in-Charge. (iii) Pre dispatch factory inspection to be carried out by Rep of Accepting Officer and the same shall be deemed to be included in the quoted rate.
131Supply , laying &testing PVC insulated, PVC sheathed, industrial cable with stranded copper conductor of size 10 sq mm, 3 core, 1100 Volts grade. (for 2 X 30 HP pumps).
132Supply , laying &testing PVC insulated, PVC sheathed, industrial cable with stranded copper conductor of size 4 sq mm, 3 core, 1100 Volts grade. (for 4 X 5 HP pumps).
133Supply, fixing, testing and commissioning of junction box of size 200 x 160 x 98 mm with provn of one SP MCB 6 Amp and suitable connection for incoming cable and outgoing cable thimble enclosed in thermoplastic enclosure, shockproof IP-65 weather proof, rust proof, dust and water proof internally embedded gasket with provn of cable entry through gland wih MS clamps as reqd complete all as specified and directed.
134Supply, installing, commissioning and testing LT panel board (indoor type) cubical type made out of CRCA sheet 2mm thick dust and vermin proof and angle iron of size 50mm x 50mm x 6mm, pedestal frame grouted in PCC (1:2:4) type B-1 20mm graded crushed stone aggregates, thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete with aluminum bus bar of capacity 1200 Amps, TPN, three phase, 04 wire (In separate chamber) including painting with two coats synthetic enameled paint over a coat of red oxide primer and consisting of the following :-(LT Main panel) (a) Incoming ACB 4Pole 800 Amp, microprocessor based tripping 40-100 % adjustable with extension links, Digital Ammeter 0-630 Amps, volt meter 0-500 Volts, Indicating lamp for RYB phases. 01 No. (b) Out going MCCB 4 pole 630 Amps 50 KA. With Adjustable type and extension links.– 01 No. (c) Out going MCCB 4 pole 400 Amps 50 KA. With Adjustable type and extension links.– 03 Nos. (d) Out going MCCB 4 pole 250 Amps 50 KA. With Adjustable type and extension links.– 01 Nos. (e) Out going MCCB 4 pole 125 Amps 25 KA With Fixed type and extension links.– 02Nos. (f)Out going MCCB 4 pole 100 Amps 25 KA With Fixed type and extension links.– 01No. (f)Out going MCCB 4 pole 63 Amps 25 KA With Fixed type and extension links.– 01No. (Spare) (g) Digital Voltmeter with built in selector switch 0-500 Volts -1No. (h) Digital Ammeter with built in selector switch 0-1500 Amps with suitable CTs -1No. (j) LED Indicated Lamp (R,Y,B) one Set-01
135Supply, installing, commissioning and testing LT panel board (indoor type) cubical type made out of CRCA sheet 2mm thick dust and vermin proof and angle iron of size 25mm x 25mm x 6mm, pedestal frame grouted in PCC (1:2:4) type B-1 20mm graded crushed stone aggregates , thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete with aluminum bus bar of capacity 200 Amps, TPN, three phase, 04 wire (In separate chamber) including painting with two coats synthetic enameled paint over a coat of red oxide primer and consisting of the following :-(Pump House Panel 2X5 Hp Pump at service Complex) (a) Incoming MCCB 4 pole 63 Amps 25 KA With fixed type and extension links – 01 No. (b) Out going MCB 4 pole 25 Amps 10 KA With fixed type and extension links – 02 Nos. (c)Fully automatic DOL starter , suitable for the 5 HP centrifugal pum complete with contactors, pushbutton, LED type indicators, autp/manua selector switch, overload protection, current sensing type sinle phase preventer complete with all accessories and wiring etc. 02 Nos. (For Pump House ) (d) Single phase preventor for 5 HP pump Set -02 Nos (e) Digital Voltmeter with built in selector switch 0-500Volts -1No (f) Digital Ammeter with built in selector switch 0-30 Amps with suitable CTs -1No (f) LED Indicated Lamp (R,Y,B) one Set-01
136Supply, installing, commissioning and testing LT panel board (outdoor type) cubical type made out of CRCA sheet 3.15mm thick dust and vermin proof and angle iron of size 50 x 50 x 6mm, pedestal frame grouted in PCC (1:2:4) type B-1 20mm graded crushed stone aggregated thimble and cable entry boxes with cable glands. Panel should covered from all sides with front and back lockable door and hinges complete with aluminum bush bar of capacity 200 Amps, TPN, three phase, 04 wire (In separate chamber) including painting with two coats synthetic enameled paint over a coat of red oxide primer and consisting of the following :-(Pump House 2X30 HP Motor) (a)In coming MCCB 4 pole 125 Amps 36 KA . With fixed type and extension links.– 01 No. (b) Out going MCCB 3 pole 63 Amps 16 KA . With fixed type and extension links.– 03 Nos. (c) Out going MCCB 4 pole 40 Amps 16 KA . With fixed type and extension links.– 01 No. (d) Out going Isolator DP 20 Amps – 1 No. (e) Star delta starter fully automatic suitable for capacity30 HP pump set-02 No. including suitable copper wiring from starter to pumpset-02 Nos (f)DOL Starter suitable for capacity5 HP pump set-01 No. including suitable copper wiring from starter to pumpset-02 Nos (g) Single phase preventer suitable for 30 HP pump set-01 No. (h) Digital Voltmeter with built in selector switch 0-500Volts -1No. (j) Digital Ammeter with built in selector switch 0-200 Amps with suitable CTs -1No. (k)LED Indicated Lamp (R,Y,B) one Set-01
137FIRE ALARM SYSTEM
138Supply, installation, testing and commissioning of FM approved and UL listed microprocessor- based, true peer-to-peer networkable, 1 loop (extendable up to 10 loops) addressable Fire Alarm Control Panel (FCAP)with its own microcontroller memory, communication module, fire device loop interface cards for intelligent initiating and indicating devices and peer-to-peer networkable with other addressable fire alarm panels. conforming to UL 2572 mass notification systems & NFPA 72, with required accessories complete all as specified and directed by the engineer-in-charge.
139The FACP shall meet following specifications / functional requirements.
140[i] The FACP shall have one to ten isolated intelligentSignalling Line Circuits (SLCs) capable of connecting up to 159 detectors and 159 modules per SLC or 318 devices per loop.
141[ii] The FACP shall have a degrade mode and the loops shall work in degrade mode in case of the CPU failure.
142[iii] The FACP shall have640 character LCD backlit display/ Touch Screen display, full QWETRY program keypad, LED indicators viz. power; fire alarm; supervisory; system trouble; other event; signals silenced; point disabled; CPU failure; controls active; etc. membrane switch controls viz. acknowledge; signal silence; drill; system reset; lamp test; etc
143[iv] The FACP shall have four access levels, flash EPROM,240 VAC power supply, automatic battery charger, 24 V sealed lead acid batteries, sufficient for 24 hrs normal working and 30 min in alarm condition.
144[v] The FACP shall havemanual sensitivity adjustment up to nine levels, built-in alarm; trouble; security and supervisory relays, history file with 4000-event capacity in non-volatile memory plus separate 1000-event alarm-only file, keypad operation, LCD unit to indicate fire / fault signal of individual unit, in built printer to log all incoming data, etc.
145[vi] The FACP shall have integrated 8 channel digital voice evacuation system controller capable of broadcasting evacuation messages on the same peer-to-peer network, fire fighter"s telephone two-way communication system capable of supervising all the speaker circuits with adequate zone control and accessories etc.
146NOTES:
147[i] The FACP shall be servicable by any system integrator & shall not have dependency on specific system integrator.
148[ii] The FACP shall have feature to "ADD", "EDIT" & "DELETE" field devices like detectors & modules without dependency on PC / Software / Special tool / dongle.
149Make: Notifier NFS23030 + DVC or equivalent model of JC, Esser
150Supply, installation, testing and commissioning of FM approved & UL listed remote power supply conforming to UL 864 & 1481 and NFPA 72 with integral battery charger capable of charging up to 18 Ah batteries to provide regulated and filtered 24 VDC power to notification appliance circuits, having power-supervision relay, fully regulated and filtered power output, AC trouble report selectable for immediate 2-hour delay, selectable earth fault detection, etc. complete all as specified and directed by the engineer-in-charge. Make: Notifier HPF24S6E or equivalent model of JC, Esser
151Supply, installation, testing and commissioning of FM approved and UL listed Network Control Display (NCD) / Repeater Panel capable of full supervision of all inputs and network integrity, having10"high definition 1024 X 600 colour touchscreen display, environmental adjustment controls to maximize LCD legibility, LED status indicators (for power supply and off normal condition), network connection, three USB connections, trouble relay, tamper and trouble inputs, etc. and features viz. network-wide acknowledge silence, reset, lamp test, fully programmable node-mapping subsystem, colour coded icon based event notification, event vectoring, etc. along with UL listed non-resettable 24 VDC power source complete all as specified and directed by the engineer-in-charge.
152M & L for low smoke zero halogen (LS0H) flame retardant fire alarm cable, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, drawn through concealed PVC conduit and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 °C to +70 °C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed by the engineer-in-charge. Make: RR Kabel, Polycab, Havells
1532 Core 1.5 Sqmm
1542 Core 2.5 Sqmm ( Supply to hooter / strobe)
155Supply, installation, testing and commissioning ofUL listed (fire fighter"s) addressable Telephone Jack mounted to a single-gang electrical back box with suitable interface module for two way communication with the Central Fire Fighter Telephone Console complete all as specified and directed by engineer-in-charge.Make: Notifier FPJ + FCM-1 or equivalent model of JC, Esser
156Supply, installation, testing and commissioning of UL listed Fire Fighter"s Telephone Handset for two way communication with the Central Fire Fighter Telephone Console complete all as specified and directed by engineer-in-charge.Make: Notifier FHS or equivalent model of JC, Esser
157Supply, installation, testing and commissioning of UL listed all purpose 2 W Ceiling Speaker having crush and rust resistant design and fully ABS plastic & ABS grille with tap-setting range between 1/4 W and 2 W, rated (RMS) voltage 70.7 V, sound pressure level at 1 W (1 m & 1 kHz) 80 ± 4 dB, frequency response 125 Hz- 16 kHz, (-10 dB with reference to 1 kHz), complete all as specified and directed by engineer-in-charge. Make: Notifier NF-SP100CI/UL or equivalent model of JC, Esser
158FIRE EXTINGUISHER
159S & F of 4.5 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the engineer-in-charge. Make: Kanex, Minimax, Aim-EX, Safeguard, coffco, Variex
160[i] Test Pressure: 250 kgf / Sq. cm
161[ii] Operating temperature :-300C to + 550C
162[iii] Locking pin and wire seal should be provided to indicate that the extinguisher has not been use.
163[iv]Every Extinguisher should be supplied with an operating manual.
164S & F 6 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed by the engineer-in-charge. Make: Kanex, Minimax, Aim-EX, Safeguard, coffco, Variex
165S & F 2 kg capacity Clean Agent (Hexafluropropane or Heptafluropropane) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union,discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed by the engineer-in-charge. Make: Kanex, Minimax, Aim-EX, Safeguard, coffco, Variex
166[i] Test Pressure: 35 kgf / Sq. cm
167[ii] Operating temperature :-200C to + 550C
168[iii] Locking pin and wire seal should be provided to indicate that the extinguisher has not been use.
169[iv]Every Extinguisher should be supplied with an operating manual.
170SIGNAGE
171S & F of Signage having size 300 mm X 150 mm reading "EXIT" in 12.5 mm block letters in Green and white background, self illuminated properly spaced to provide good legibility located directly in corridor near to each staircase and squarely attached to the wall or partition in a way that the top of the sign is not above 2 m from the finished floor level.These lights shall emit the maximum light required even during the electricity supply or in Black out period with high energy efficiency manufactured using superior quality Alluminium Extrusion body raw material Make: Variex, Mr safe, Matrix sign lab
172Product Material: Alluminium ALLOY Extrusion
173Product Finish:- Matt Black / Snow white finish after phosphochromate treatment
174Wattage:- 5 Watt
175Mounting: Surface/ Hanging
176S & F of Signage having size of 500 mm X 500 mm, indicating the "Floor Number" in bold type and at 75 mm high numerals in red and white background, made out of 3 mm thick opaque PVC foam boaed with computer cut, PVC non-reflective self adhesive vinyle painted foam board, posted and maintained within each stair enclosure on every floor, securely attached to the stair side of the door in a way that the bottom of the sign is not above 1.5 m from the finished floor level Make: Variex, Mr safe, Matrix sign lab
177S & F of Signage having size of 450 MM X 150 MM reading "FIRE EXTINGUISHER" in 12.5 mm block letters in White and Red background, made out of 3 mm thick opaque PVC foam boaed with computer cut, PVC non-reflective self adhesive vinyle painted foam board,properly spaced to provide good legibility located directly in corridor near to each Manual call point/Fire Extinguisher and squarely attached to the wall or partition in a way that the top of the sign is not above 2 m from the finished floor level Make: Variex, Mr safe, Matrix sign lab
178LIGHTNING POROTECTION
179S & F of Signage having size of 150 mm X 600 mm, posted and maintained at each lift landing and on the side of the stairway door from which egress is to be made on every floor, indicating the "STAIRCASE" by an alphabetical letter in bold type and at 75 mm high letters in red and white background, made out of 3 mm thick opaque PVC foam boaed with computer cut, PVC non-reflective self adhesive vinyle painted foam board,securely attached to the side of the stairway door from which egress is to be made in a way that the bottom of the sign is not above 1.5 m from the finished floor level Make: Variex, Mr safe, Matrix sign lab
1808. Speaker (Guest Lounge & Green Room ) : Frequency range (-10dB) : 80Hz-20kHz , Nominal coverage : H (90) x V (90) , Components :6.5”(160mm) cone driver , 1” (25mm) balanced dome tweeter , Power rating : PGM 50W , Nominal impedance : 8O/15W, 7.5W, 3.8W SPL : 110dB SPL (100W) Yamaha VS6/panasinic/Bose/Ahuja.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail