Athavanad Grama Panchayath - Project No 240 / 19 - Kattilangadi Glps ( New Block ) Electrification-Electrical Work.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 10-Feb-2023 | TIME EXTENSION | Date | 10-Feb-2023 |
BOQ
| Sl. No. | Item Description |
| 1 | 90.2.1.1Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming toIS3419-1988,fixingtheconduitusingmetalsaddlesspacingnotexceeding50cmor concealedsuitably andwith1.00sqmmFRLSPVCinsulatedstrandedsinglecorecopper conductorcable650V grade, includingprovidingswitchboardmainandcontinuousearthing withNo.14SWGbarecopper,requiredquantityofcopperearthsocket,brassboltandnut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Single Control light point with 6A, plate ceiling rose - Short point |
| 2 | 90.2.1.4Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming toIS3419-1988,fixingtheconduitusingmetalsaddlesspacingnotexceeding50cmor concealedsuitably andwith1.00sqmmFRLSPVCinsulatedstrandedsinglecorecopper conductorcable650V grade, includingprovidingswitchboardmainandcontinuousearthing withNo.14SWGbarecopper,requiredquantityofcopperearthsocket,brassboltandnut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point |
| 3 | 90.2.1.5Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming toIS3419-1988,fixingtheconduitusingmetalsaddlesspacingnotexceeding50cmor concealedsuitably andwith1.00sqmmFRLSPVCinsulatedstrandedsinglecorecopper conductorcable650V grade, includingprovidingswitchboardmainandcontinuousearthing withNo.14SWGbarecopper,requiredquantityofcopperearthsocket,brassboltandnut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Call bell point with 6 A bell push at one end and 6 A, 3 plate ceiling rose at other end - Short point |
| 4 | 90.2.1.6Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming toIS3419-1988,fixingtheconduitusingmetalsaddlesspacingnotexceeding50cmor concealedsuitably andwith1.00sqmmFRLSPVCinsulatedstrandedsinglecorecopper conductorcable650V grade, includingprovidingswitchboardmainandcontinuousearthing withNo.14SWGbarecopper,requiredquantityofcopperearthsocket,brassboltandnut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points |
| 5 | 90.2.1.7Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming toIS3419-1988,fixingtheconduitusingmetalsaddlesspacingnotexceeding50cmor concealedsuitably andwith1.00sqmmFRLSPVCinsulatedstrandedsinglecorecopper conductorcable650V grade, includingprovidingswitchboardmainandcontinuousearthing withNo.14SWGbarecopper,requiredquantityofcopperearthsocket,brassboltandnut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB\"s shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Independent plug - Short point |
| 6 | 90.3.20.3Supply & installation of light fittings on TW round block Supply, conveyanceinstallationtestingandcommissioningthelight fittingsof followingtypes made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required. 1200 mm 1X20W LED Lamp with box type fixture |
| 7 | ODSupply Conveyance, installation, testing and commissioning of 40W LED Flood light with IP 65 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance |
| 8 | 90.5.1.8Supply and fixing the following typesof superior quality 250V A.C call bell on existing M.S. box andgivingconnectionswithrequiredlengthof3core,16/0.20mm650/1100V gradePVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Gong bell 150mm-without MS box |
| 9 | odSupply Installation, testing and commissioning of 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Airelivery minimum 210(cubic meter/minute), 300mm down rod , 2 number canopies, shackele kit, Copper winding, 3 number blades and all remaining accessories including safety pin, nut bolts, washers suitable for 230V/240V single phase AC supply etc. complete as required |
| 10 | 1.27.1Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 1 or 2 Module (75mmX75mm) |
| 11 | 1.27.2Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 12 | 1.27.4Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) |
| 13 | 90.10.3.15Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant ) 32A DP switch with indicator |
| 14 | 1.24.3Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 amp switch |
| 15 | 1.23.5Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.6 pin 15/16 amp socket outlet |
| 16 | 1.24.1Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 17 | 1.24.4Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 18 | 90.6.10.1SupplyandfixingoffollowingsizesoflightgaugePVCconduitalongwithaccessoriesin surface/recessincludingcuttingthewallandmakinggoodthesameincaseofrecessed conduit as required20 mm |
| 19 | 1.17.2Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 1.5 sq. mm |
| 20 | 1.17.4Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm |
| 21 | 1.17.6Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm |
| 22 | 1.17.11Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm |
| 23 | 1.17.20Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required. 2 x 4 sq. mm |
| 24 | 90.11.1.14Supplyandinstallationofsheetsteel,phosphatisedandpainted,dustandverminproof enclosureofMCBDBincludingcopper/brassbusbar,neutrallink,earthbusandDINrail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor boltsor fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43) |
| 25 | 2.3.2Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator.8 way, Double door |
| 26 | 2.3.3Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator.12 way, Double door |
| 27 | 2.13.1Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps |
| 28 | 2.12.1Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 29 | 2.15.2Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 30 | 2.14.2Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 31 | 2.10.4Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole |
| 32 | 2.10.1Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 33 | 2.10.3Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole |
| 34 | 90.12.7.40Supply, layingandclampingof 1no. PVCinsulatedandPVCsheathedarmouredaluminium powercable, 1.1KV gradeof thefollowingsizesusingclampsnotedalongwiththecables, spacing of clampsnot exceeding 60cms, making good the damages, colour washing etc. as required.4 core 10 sq mm with factory made clamp |
| 35 | 90.12.7.3Supply, layingandclampingof 1no. PVCinsulatedandPVCsheathedarmouredaluminium powercable, 1.1KV gradeof thefollowingsizesusingclampsnotedalongwiththecables, spacing of clampsnot exceeding 60cms, making good the damages, colour washing etc. as required.2 core 10 sq mm with factory made clamp |
| 36 | 90.12.5.3Supply & laying of one number PVC insulated and PVC sheathed armoured aluminiumpower cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 10 sq mm |
| 37 | 90.12.10.2Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation 50/38 mm or nearest size |
| 38 | 9.1.32Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm) |
| 39 | 9.1.2Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm) |
| 40 | 5.4Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 41 | ODSupplying and Providing and fixing 25 mm X 3 mm G.I. strip earth lead from the test joint to the earth plate |
| 42 | ODSupply, providing and fixing 2 X 25 mm X 3 mm G.I. strip test joint for earthing system |
| 43 | 90.14.1.2Fabrication,supply,conveyance,installation testing and commissioning offloor or wall mounting,dustandverminproof,cubicletypeMV panelboardcomprisingofthefollowing components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4ofIS8623(withlatestamendments)usingCRCAsheetasperapproveddesignand requirement, with front and rear accessfacility, busbar chambers, hinged doorsfor all switch gearcompartments, earthingthedoorsusing4sqmmbraidedcopperconductor, providing necessary cut-outsfor mounting meters, relays, indication lamps, busbar interconnection etc, detachablecoversforbusbarchamberandcablealley,powdercoatingtheassembly after subjectingto7tank processetc asrequired. CRCA sheet alonebeusedfor thefabrication. Angles/ flats/ slottedanglesetc shallnot beusedfor thefabricationof panelassembly. The measurmentswillbetakentheareaof thecompletesheetsusedforpanelboardincluding partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 44 | 2.1.1Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N |
| 45 | ODSupply & installation of dust and vermin proof, 3 Phase Syntax Meter Board( 3 Phase Syntax Meter Board( GS-MB-3750) [350x481x210] and to fix KSEB meters, fuse units, CT etc as required including fixing it on wall, making good the damages colour washing etc. as required. |
| 46 | 90.16.1.3Supply and drawing bare earthing conductorsof the following sizesalong with wiring/ cables and giving connection as required 3.15 mm copper conductor ( 10 SWG) |
| 47 | 90.16.1.2Supply and drawing bare earthing conductorsof the following sizesalong with wiring/ cables and giving connection as required 2.65 mm copper conductor (12 SWG) |
| 48 | 90.16.1.1Supply and drawing bare earthing conductorsof the following sizesalong with wiring/ cables and giving connection as required 2.00 mm copper conductor ( 14 SWG) |
| 49 | 90.16.5.2Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required. 2.65 mm (12 SWG) |
| 50 | 90.16.5.3Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required. 3.15 mm (10 SWG) |
| 51 | 90.16.5.1Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required. 2.00 mm (14 SWG) |
| 52 | ODSupply and providing 25x6mm brass nut and bolt etc. as required. |
| 53 | ODSupply and providing 12x3mm brass nut and bolt etc. as required. |
| 54 | ODCharges for preperation of KSEB test Report for submitting to the concerned KSEB section office |
AI Tender Summary
Tender Timeline
Jan 31, 2023
11:30 IST
Tender Published
Tender notice published.
CompletedFeb 10, 2023
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedFeb 13, 2023
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender