Military Engineer Services-MES has published Tender For Improvement In Water Supply Distribution System Of South Colony And North Colony Offr Md Accn Under Ge (West) Pathankot (2Nd Call). Submission Date for this Tender is 20-02-2023. Water Pipe Line Tenders in Pathankot Punjab. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 13-Feb-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 20-02-2023 |
Sl. No. | Item Description |
1 | Excavation in trenches in soft/ loose soil for repairing/ replacement of CI & GI pipes n.exc 1.5 mtr width & n.exc. 1.5 m deep including getting out excavated earth complete all as specified and directed. |
2 | Returning, filling in trenches incl spreading and leveling, watering and well ramming in layers n.exc. 25 cm thick complete all as specified and directed. |
3 | Removal of excavated soil to a distance n.exc. 50 mtr and depositing the same where directed at a level n.exc. 1.5 mtr above starting point complete all as specified and directed. |
4 | Taking out cast iron water mains carefully (including all fittings)of size 150mm dia bore with spigot and socket ends and lead joints including burning out joints and recovering lead for relaying or depositing in MES store complete all as specified and directed by Engr- in - Charge.Note:- Excavation and earth work shall measured and paid saperately under relative items. |
5 | Relayingof CI pipe with spigot and socketed ends in trenches retrived against item no 4 above including old fittings/ new fittings, complete after cleaning internally to make rust free of size 150mm by manually or mechanical means including painting complete all as specified and directed. Note:- Lead joints shall be made new and shall be measured seprately under relative item. |
6 | M&L for Run lead joint for CI pipe 150 mm dia complete all as specified and directed |
7 | Supply, laying & testing Ductile Iron S/S pipe 150 mm dia bore shall confirm to IS-8329-2000 and 9523-2000. The pipe shall be laid in trenches, jointed and tested all as per IS 12288-1987 with specials Class “K-9” . The fittings shall withstand hydrostatic pressure without showing any leakage,sweating or defects of any kind as laid down in IS complete all as specified and directed by Engr-in-charge. (Note : 1. cutting, drilling, welding are deemed to the same rate.2. Necessary Premissions for road cutting in civil areas shall be taken by the contractor from the CompetantCivil Authorities and the rate for the same included in this item and nothing extra shall be admissible on this account) |
8 | S & F Ductile iron bend (any type radius and angle) taper any type for (straight) bend increasing /decreasing of double socket/flanged etc. Tee piece single branch, Y junction, double branch, collar and plug of upto 150 mm bore DI pipecomplete all as specified and directed. |
9 | M&L for Rubber gasket/Tyten joint for 150 mm dia pipe complete all as specified and directed by Engr-in-charge. |
10 | M&L for 15mm bore GI pipe, medium grade with all fitttings, laid in trenches, on walls, complete all as specified and directed by Engineer-in-Charge. Note :- Excavation and earth work shall be measured and paid saperately under relevant items of BOQ. |
11 | All as per Srl item No. 10.00 above but 20mm bore. |
12 | All as per Srl item No. 10.00 above but 25mm bore. |
13 | All as per Srl item No. 10.00 above but 40mm bore. |
14 | All as per Srl item No. 10.00 above but 50mm bore. |
15 | Cutting cast iron pipes of size 150mm dia and reducing to required length for insertion of new tees, branches etc complete all as speccified and directed. |
16 | M&L for Construction of brick masonry valve pit of size 1200x1200x900 mm (internal dimensions with well burnt "B" class bricks of one brick thick built in cement mortar 1.4 with 15 mm thick cement plaster in 1:4 on internal side and pointing flush over 150 mm thick PCC 1:4:8 in foundation complete with cover made of angle iron frame of size 40 x 40 x 4mm with MS sheet of 10 SWG with locking arrangement set in PCC 1:2:4 in CM 1:4 as directed and duly painted with two coats of synthetic enamel black paint over as coat of red oxide primer incl prepration of surfaces and also incl excavation, earth work, returning, filling and removal of surplus material to a distance n.exc. 50m complete all as specified and directed |
17 | Supply, Installation, Testing&Commissioning of PLC based water monitoring system having ultra sonic level sensors for level monitoring of overhead tanks duly wired in PLC panel. The panel shall be wall/floor mounted having HMI touch screen duly programmed to control one pump starter, one delivery line motorized valve with suitable size of multicore copper wires. The panel shall be suitable to be operated through SCADA & manual operation complete all as directed by Engr-in-Charge. |
18 | Notes :- (a) The contract sum shall be arrived at after deduction of amount of Schedule of Credit. (NIL). (b) PERFORMANCE SECURITY :- (Refer condition 19 of IAFW-2249) The performance security for an amount equivalent to 3% (Three percent) of the acceptedcontract sum shall be delivered by the successful bidder immediately after the date of intimation letter of acceptance and all provisions shall be applicable as per condition 19 of IAFW 2249 |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail