Tender Details

Supply Of Material At Dr. Bhimrao Amebedkar Smarak Kendra Aishbagh Lucknow , Fire Alarm & Detection System Supplying, Installation, Testing & Commissioning Sector Panel Suitable For Following Zones, Complete With Visual Indications For Short Circuit Fault, Open Circuit Fault, Fire Condition And All Other Standard Facilities As Per Is:2189 With Mimic Diagram For All Area / Zone Covered, Complete With All Connections, Interconnections As Required. ( For Sub-Station ) 4 Zone , Supplying, Installation, Testing And Commissioning Of Micro Processor Based Intelligent Addressable Main Fire Alarm Panel, Central Processing Unit With The Following Loop Modules And Capable Of Supporting Not Less Than 240 Devices ( Including Detectors ) And Minimum 120 Detectors Per Loop And Loop Length Up To 2 Km, Network Communication Card, Minimum 320 Character Graphics / Lcd Display With Touch Screen Or Other Keypad And Minimum 4000 Events History Log In The Non Volatile Memory ( Eprom ) , Power Supply Unit ( 230 ± 5% V, 50 Hz ) , 48 Hrs Back-Up With 24 Volt Sealed Maintenance Free Batteries With Automatic Charger. The Panel Shall Have Facility To Connect Printer To Printout Log And Facility To Have Seamless Integration With Analog / Digital Voice Evacuation System ( Which Is Part Of The Schedule Of Work Under Sh: Pa System ) And Shall Be Complete With All Accessories . The Panel Shall Be Compatible For Ibms System With Open Protocol Bacnet / Modbus Over Ip Complete As Per Specifications. Two Loop , Supplying, Installation, Testing & Commissioning Of Central Graphical Fire Alarm Management System To Centrally Monitor And Operate The Fire Alarm System Complete As Required. , Supplying, Installation, Testing & Commissioning Of Repeater Panel Wih 320 Character / Touch Screen Lcd Display With Inbuilt Reset, Acknowledge And Silence Switches Complete As Required. , Supplying, Installation, Testing & Commissioning Of Intelligent Analog Addressable Smoke Detector Complete With Mounting Base Complete As Required. , Supplying, Installation, Testing & Commissioning Of Response Indicator On Surface / Recessed Ms Box Having Two Led, Metallic Cover Complete With All Connections Etc As Required. , Supplying, Installation, Testing & Commissioning Of Fault Isolator Complete With Base As Required. , Supplying, Installation, Testing & Commissioning Of Intelligent Addressable Thermal Detector With Rate Of Rise Cum Fixed Tempreature Thermistor Complete With Base As Required. , Supplying, Installation, Testing & Commissioning Of Addressable Fire Control Module Complete As Required. , Supplying, Installation, Testing & Commissioning Of Addressable Phone Control Module Complete As Required. , Supplying, Installation, Testing & Commissioning Of Intelligent Addressable Duct Detector Including Suitable Photo Detector Complete With Base As Required. , Supplying, Installation, Testing & Commissioning Of Addressable Manual Call Point Complete As Required. , Supplying, Installation, Testing & Commissioning Of Addressable Horn Cum Strobe Complete As Required. , Supplying, Installation, Testing & Commissioning Of Fire Fighter Telephone Hand Set Complete As Required. , Supplying, Installation, Testing & Commissioning Of Fire Fighter Phone Jack Complete As Required. , Supplying, Installation, Testing & Commissioning Of 6 Zone, Voice Alarm Controller With Usb, Mp3 Player ( Including 6 Zone Button Paging Station ) With Seamless Integration Facility With Main Fire Alarm Panel For Voice Evacuation Complete As Required. , Supplying, Installation, Testing & Commissioning Of Ceiling / Wall Mounted Loud Speaker, 3 / 1.5 Watt In Abs Enclosure Complete As Required. , Supplying, Installation, Testing & Commissioning Of Digital Audio Amplifier 75 Watt, 25V Rms Operating At 240 Volt Ac Supply Complete As Required. , Supplying, Installation, Testing & Commissioning Of Voice Command Keypad 6 Zone, With Microphone Assembly Complete As Required. , Supplying & Laying Of 2X1.5 Sqmtm Fire Survival Armoured Cable, 600 / 1000V Rated With Annealed Copper Conductor Having Glass Mica Fire Barrier Tape Covered By An Extruded Layer Of Cross Linkable Ethylene Propylene Rubber ( Epr ) Insulation And Lszh Inner Bedding, Steel Wire Armouring & Lszh Outer Sheath Complete As Required. , Supplying And Drawing Of Cable Fire Retardant Pvc Insulated Copper Conductor Cable In The Existing Surface / Recessed Steel Conduit Of Following Pairs, Cores And Size Including Connections And Interconnections Etc. As Required. Speaker Cable Two Pair, 2-Core, 1.5 Sqmtm , Supplying And Drawing Of Cable Fire Retardant Pvc Insulated Copper Conductor Cable In The Existing Surface / Recessed Steel Conduit Of Following Pairs, Cores And Size Including Connections And Interconnections Etc. As Required. Speaker Cable Four Pair, 2-Core, 1.5 Sqmtm , Supplying And Fixing 25 Mm Dia Ms Flexible Pipe With Pvc Coating Along With All Ancillaries And Accessories Like Coupler Etc. As Required. , Supplying And Installing Following Size Of Perforated Hot Dipped Galvanised Iron Cable Tray ( Galvanisation Thickness Not Less Than 50 Microns ) With Perforation Not More Than 17.5%, Inconvenient Sections, Joined With Connectors, Suspended From The Ceiling With G.I. Suspenders Including G.I. Bolts & Nuts, Etc. As Required. 100Mm Widthx50mmdepthx1.6Mm Thickness , Supply Of Addressable Monitor Module. The Module Should Be Able To Monitor Dry Contacts. It Should Have A Led Indicator. Any Junction Box Used With The Call Point Should Have Minimum Ip 44 Rating.The Device Should Be Vds / Ul Approved , Supply Of Addressable Relay Module. The Relay Should Be Form C With No, C And Nc Contacts. The Contacts Should Work With Minimum 2.0 Amp Resistive Or 1.0 Amp Inductive Current. It Should Have A Led Indicator .Any Junction Box Used With The Module Should Have Minimum Ip 44 Rating. The Device Should Be Vds / Ul Approved , Supply, Installation, Testing And Commissioning Of Workstation Pc: Intel ( R ) Core ( Tm ) I3 10Th Gen Processor ( 8M Cache, Up To 3.90 Ghz ) ; Ram: 8Gb ( 1X8gb ) Non-Ecc Ddr5 1600Mhz ; Keyboard: 12 Function Keys; Chassis: Tower / Workstation; Dvd: 8X Slimline Dvd+ / -Rw, Data Only; Dual Graphics Card; Network Interface Card: Integrated Intel ( R ) 82579Lm Gigabit1 Ethernet Lan 10 / 100 / 1000; Ssd: 256Gb; Operating System: Windows 10Professional 64 Bit Or Latest.Approved Makes: Hp / Dell / Asus / Lenovo , Fire Fighting And Sprinklersystem Providing, Fixing, Jointing, Testing And Commissioning Of Heavy Duty ( Class C ) Ms Pipe Conforming To Is : 1239 ( Part I ) Pipes Up To 150 Trim Dia With All Necessary Fittings Like Tees, Elbows, Flanges, Reducers. Gasket, Nuts And Bolts Etc. Welded Or Screwed Joints As Required Including Fixing The Pipe With Necessary Structural Supports Including Painting Of Two Coats Of Synthetic Enamel Paint Over Two Coats Of Red Oxide Primer Including All Civil Breakages And Making Good The Same, . Make: Jindal. A ) 50Mm , 80Mm , 25Mm , Gml Double Headed Csi Marked Oblique Pattern Hydrant Landing Valves With 80Mm Dia Flanged Inlet & 63 Mm Dia Female Outlet Complete With Pvc / Rubber Cap And Gi Chain Twist Release Type Plug And All Accessories As Per Is 5290 Type A Including Fixing With Anchor Fasteners And Flanged Tapping From Wet Riser Complete As Uired. Make - Newage / Safe Gaurd / Geetech , Providing And Fixing Of Non-Percolating Flexible Rrl Hose Pipe Isi Marked ( Is:636 ) 63 Mm Diax 15 M Long Complete With Instantaneous Type 63 Mm Dia. Marked Male And Female Gm Couplings ( Is:903 ) Bound And Riveted To Hose Pipe. ( Type -1 ) Make -Newage / Safeguard / Getech , Gm Branch Pipe With Nozzle Of 20 Mm Nominal Bore Outlet As Per Is:903 Suitable To Fit With Standard Instantaneous Type 63Mm Dia Coupling Isi Marked ( 1S:903 ) Complete. Make - Newage / Safegaurd / Geetech , Wall Mounting Swinging Type First Aid Fire Hose Reel With Drum, Hanging Bracket, 30.0 Mir. Length X 20 Mm Dia High Pressure Hose Reel Tubing As Per Is: 444 With Gun Metal ( Gm ) Shut Off Nozzle Having 6.5 Mm Dia Orifice. The Hose Reel Shall Be Conforming To Is : 884-1985. Rate Shall Include 25 Mm Dia M.S. Pipe ( Heavy Class ) Connection From Riser To Hose Reel, Sockets, Nipples, Elbows And Ball Valve ( 25 Mm Dia ) . Drum Shall Be Fixed On Adjoining Wall By Means Of 120 Mm X 100 Mm Long Fasteners, Bolts And Nuts Including Painting. ( For Internal Hydrant System ) . Make - Newage / Safegaurd / Geetec , Providing & Fixing Of 1.6 Mm Thick M.S / Door Frame, Door Capable Of Accommodating Fire Hose Reel, Landing Valve, Hose Pipes, Fittings & Accessories. The Door Shall Have A Front Glass With Lock And Key Arrangement & Shall Be Painted With Post Office Red Colour ( Approval Shall Be Taken On The Basis Of Submitted Sample Before Ordering ) Cost Of Fire Extinguishers Not Included In Item Rate. ( Liasioing With Civil Contractor For Making Recessed Type Mansuary Box ( By Civil Contractor ) . Make - Localy Fabricated 900 Mm X2100mm , Supplying. Installing, Testing And Commissioning 0 To 12 Kg / Cm2 On / Off Pressure Switch In Delivery Line Of Pump Along With Control Wiring For Auto Starting And Auto Stopping Make - Danfos , Electric Driven Terrace Pump Supplying.Installing, Testing & Commissioning Of Fire Authority Approved Electrically Driven Terrace Pump Suitable For Automatic / Manual Operation Consisting Of The Following: Squirrel Cage, Tefc Induction Motor Suitable For 415 ± 10%V, 3Phase, 50 Hz A.C. Supply Of Suitable H.P. 900 Lpm @ 35 Mtr Head 2900 Rpm Make:- Kirloskar / Crompton Cireaves. , Providing And Fixing Air Vessel Made Of 200 Mm Dia , 8 Mm Thick 1200 Mm In Height With Air Release Valve On Top And Flanged Connection To Riser , Drain Arrangement With 25 Mm Dia Ball Valve With Required Accessories , Pressure Gauge Complet In All Respect Make - Fabricated , Providing, Fixing, Testing & Commissioning Of C.I. Butterfly Valve Conforming To Is : 13095 With Flanges, Nuts, Bolts And Washers Complete For Following Sizes :- [ Pn 16 Rating ( 16 Kg / Cm2 Pressure Rating ) ] . Make: - Kartar 150Mm , Providing, Fixing. Testing & Commissioning Of C.I. Dual Plate Non- Return Valve [ Pn 1.6 Rating ( 16 Kg / Cm2 Pressure Raring ) Complete With 2 Nos, Matching Flanges, Rubber Insertion, With Nuts, Bolts And Washers Etc Of Following Sizes . Make: Kartar 150Mm , Providing & Fixing Dial Type Pressure Gauge With Isolation Ball Valve Suitable For Working Pressure Of 250 Psi Cost Shall Be Of Inclusive Of Providing Any Short Pieces, Nipples, Elbows Etc As Required. Having Calibration Of 0-15 Kg / Cm2. Make -H Guru , Supplying And Laying Of Aluminium Conductor Pvc Insulated Armoured Served Sheathed Cable 1100 Volts Grade On Surface The Cable Run Shall He Fixed On Ms Clamps Etc.Of Suitable Size Or As Directed By The Engineer-Lncharge , Complete In All Respect. The Armouring Of The Cable Shall Be Properly Connected With The Earth Conductor By Clamps Etc. Following Size Make -Haveels / Rr / Polycab 16 X3.5 Core , Supplying, Installation, Testing And Commissioning Of Electrical Control Panel Of Cubicle Construction, Floor / Wall Mounted Type, Fabricated Out Of 2 Mm Thick Crca Sheet, Compartmentalised With Hinged Locakable Doors, Dust And Vermin Proof, Powder Coated Fabricated Out Of 2 Mm Thick Crca Sheet, Compartmentalised With Hinged Locakable Doors, Dust And Vermin Proof, Powder Coated Including Sutaible Contector Relay , Ct , Auto Manual Switch Complet In All Respects, For -Terrace Pump , External Fire Hydrant System Providing Laying, Testing & Commissioning Of C Class Heavy Duty Ms Pipe Conforming To Is 1239 / 3589 ( All Pipes Shall Be Is1 Marked And Of Makes Specified In The Specifications ) Lic Fittings Like Elbows, Tees Flanges, Tapers, Nuts Bolts, Gaskets Etc. In Ground Including Excavation & Providing Cement Concrete Blocks As Supports And Anti-Corrosive Treatment To Burned Pipes By Wrapping & Coating Wih Anticorrosion Tape Along With Two Coat Of Black Japan Primer For Under-Ground Pipe Including Digging And Backfilling Upto 1.0 Mu. Below From G.L.For External Work . Make -Jindal ( Under G Round ) A ) 150Mm , 80Mm , Gml Single Headed Csi Marked Oblique Pattern Hydrant Landing Valves With 80Mm Dia Flanged Inlet & 63 Mm Dia Female Outlet Complete With Pvc / Rubber Cap And Gi Chain Twist Release Type Plug And All Accessories As Per Is 5290 Type A Including Fixing With Anchor Fasteners And Flanged Tapping From Wet Riser Complete As Uired. Make -Newage / Lifeguard / Geetec , Providing And Fixing Of Non-Percolating Flexible Rrl Hose Pipe Isi Marked ( Is:636 ) 63 Mm Diax 15 M Long Complete With Instantaneous Type 63 Mm Dia. Marked Male And Female Couplings ( Is:903 ) Bound And Riveted To Hose Pipe. ( Type -A ) Make -New Age / Lifeguard / Geetech , Standard Gml Branch Pipe With Nozzle Of 20 Mm Nominal Bore Outlet As Per Is:903 Suitable To Fit With Standard Instantaneous Type 63Mm Dia Coupling Isi Marked ( 1S:903 ) Complete. Make -Life Guard / Newage / Geetec , Providing & Fixing Of 1.6 Mm Thick M.S / Fire Hose Cabinet Box 750 X600 X300 Capable Of Landing Valve, Hose Pipes, , Branch Pipe , Accessories. The Door Shall Have A Front Glass With Lock And Key Arrangement & Shall Be Painted With Post Office Red Colour ( Approval Shall Be Taken On The Basis Of Submitted Sample Before Ordering ) For Externel Yard Hydrant , Complet In All Respect Make - Fabricated , Providing And Fixing Of Fire Brigade Inlet 4 Way Connection Of Cast Iron Body With Ss Male Instantaneous Inlet Coupling Complet With Cap And Chain As Reqd For Suitable Dia Ms Pipe Connection Complet With Suitable Size Ms Box Complet In All Respect - Newage / Lifeguard / Geetech , Providing, Fixing, Testing & Commissioning Of C.I. Butterfly Valve Conforming To Is : 13095 With Flanges, Nuts, Bolts And Washers Complete For A ) Following Sizes :- [ Pn 16 Rating ( 16 Kg / Cm2 Pressure Rating ) ] . Make: -Kartar 150Mm , Make: -Kartar 80Mm , Providing, Fixing. Testing & Commissioning Of C.I. Dual Plate Non- Return Valve [ Pn 1.6 Rating ( 16 Kg / Cm2 Pressure Raring ) Complete With 2 Nos, Matching Flanges, Rubber Insertion, With Nuts, Bolts And Washers Etc Of Following Sizes . Make: Zoloto / Sant / Kartar 150Mm , Supply, And Constructing Of Masonary Valve Chamber 900X900x1000 Cm Inside 75 Class Designation Brick Work In Cement , Mortar 1:5 ( 1 Cement, 5 Find Send ) For Sluice Valve / Butter Fly Valve With Ci Surface Box 100 Mm Top Dia 180 Mm Bottom Dia, And Rcc Top Slab Complet As Per Standard , Fire Sprinkler System ( First ) Providing, Fixing, Jointing, Testing And Commissioning Of Heavy Duty ( Class C ) Ms Pipe Conforming To Is : 1239 ( Part I ) Pipes Up To 150 Trim Dia With All Necessary Fittings Like Tees, Elbows, Flanges, Reducers. Gasket, Nuts And Bolts Etc. Welded Or Screwed Joints As Required Including Fixing The Pipe With Necessary Structural Supports Including Painting Of Two Coats Of Synthetic Enamel Paint Over Two Coats Of Red Oxide Primer Including All Civil Breakages And Making Good The Same, . Make: Jindal. ( Above Ground ) 150Mm , 100Mm , 80Mm , 65Mm , 50Mm , 40Mm , 25Mm , Providing Laying, Testing & Commissioning Of C Class Heavy Duty Ms Pipe Conforming To Is 1239 / 3589 ( All Pipes Shall Be Is1 Marked And Of Makes Specified In The Specifications ) Lic Fittings Like Elbows, Tees, Flanges, Tapers, Nuts Bolts, Gaskets Etc. In Ground Including Excavation & Providing Cement Concrete Blocks As Supports And Anti-Corrosive Treatment To Burned Pipes By Wrapping & Coating Wih Anticorrosion Tape Along With Two Coat Of Black Japan Primer For Under-Ground Pipe Including Digging And Backfilling Upto 1.0 Mu. Below From G.L.For External Work As Per Is 909 Make - Jindal ( Under Ground ) 150Mm , Providing And Fixing 25 Mm Dia Flexible Stainless Steel ( Ss 304 ) Pipe For Making Final Connection Of Sprinkler Head With Sprinkler System Piping Network Including 2 Nos. 25 Mm Diameter G.I. Connector, G.E. Nipple, Reducer, Elbow And Threaded Jointing Complete As Per Detail. Make:- Newage / Tyco A ) 1000Mm , 1500Mm , Providing And Fixing And Commissioning Of Sprinkler Rosette Plate 560.00 No Supply, Installation, Testing And Commissioning Of Required Size Zonal Control Valve Inclusive Of 1 Nos Required Size Butterfly Valve, Required Size Non Return Valve, Flow Switch, Water Pressure Gauges & 25 Mm Dia. Auxiliary Drain Valve With Sight Glass With Necessary Gi C Class Piping With Threaded Fittings Of Required Sizes Complete. 150Mm , Providing, Fixing, Testing & Commissioning Of C.I. Butterfly Valve Conforming To Is : 13095 With Flanges, Nuts, Bolts And Washers Complete For Following Sizes :- [ Pn 16 Rating ( 16 Kg / Cm2 Pressure Rating ) ] . Make: Sant / Zoloto A ) 150Mm , 50Mm , Providing, Fixing, Testing And Commissioning Of 15 Mm Dia Quartzoid Bulb Type Stainless Steel Sprinkler Head Suitable To Operate At 68 Deg C ( Ul / Fm Listed / Approved ) Make - Tyco / Hd / Newage Note- Al! Sprinklers Shall Be Chrome Finish / Powder Coated Except For Conceled., The Sprinkler Shall Be Either Pendent Or Upright-Type / Side Wall And Shall Not Be Universal Style. A ) Side Wall Sprinkler 680C ( With Extended Coverage ) , B ) Pendent Sprinkler 680C ( Stadard Response ) , Upright Sprinkler 680C ( Standard Response ) , Providing And Fixing Air Vessel Made Of 200 Mm Dia , 8 Mm Thick 1200 Mm In Height With Air Release Valve On Top And Flanged Connection To Riser , Drain Arrangement With 25 Mm Dia Ball Valve With Required Accessories , Pressure Gauge Complet In All Respect Make Fabricated , Fire Pumps And Valve Electric Motor Driven Main Hydrant / Sprinkler / ( Location - Plant Room ) Supplying, Installing, Testing And Commissioning Of Fire Authority Approved Electrical Driven Fire Pump Suitable For Automatic / Manual Operation Consisting Or The Following: Horizontal Split Casing, High Pressure Single / Multistage Centrifugal Type Fire Pump Running At 2900 Rpm Complete With Gland Packing, Proper Connection To Suction And Delivery Line, And Including Bypass Arrangement For Testing Of Pumps, Having A Name Plate Indicating Suction, Delivery, Head, Discharge, Stages, Rpm And Direction Of Rotation.Pump Shall Be Capable Of Furnishing Not Less Than 150% Of Rated Capacity At A Head Not Less Than 65% Of Rated Head. The Shut Off Head Shall Not Exceed 120% Of Rated Head. Squirrel Cage, Induction Motor, Tefc Type, Efficiency Class. Eff-1, Suitable For 415 + 10%V, 3 Phase, 50 Hz, Ac Supply, Of Suitable Hp Rating For The Above Pump With Asynchronous Speed Of 2900 Rpm Conforming To Ip 55 Protection & Class F Insulation.The Motor Shall Conform To Is 12615 : 2004 And Is 325 : 1978 ( Up To Date ) With Flexible Coupling And Coupling Guard.Common Base Plate For Mounting Pump And Motor Fabricated Of Mild Steel Channel As Per Manufacturers Recommendation With Heavy Duty Anti Vibration Pads ( 6 Nos., Heavy Duty ) . Suitable Reinforced Cement Concrete Pump Foundation As Per Manufacturers Design Including Foundation Bolts, Washers As Required.Flexible Coupling And Coupling Guard For Direct Coupling Of Pump And Motor. Rate Should Include Interconnection Cables And Foundation Bolts, Grouting Of Foundation Bolts And Other Accessories Required.Main Fire Electric Driven Moter With Pump :- Suitable Hp 2900 Rpm, 2280 Lpm, 70 Mtr Head ( Horizontal Split Casing ( 02 Stage ) Or As Per Manufacturer Ecommendation. , Diesel Engine Driven Fire Pump Supplying, Installing, Testing & Commissioning Of Fire Authority Approved Diesel Engine Driven Tire Pump Suitable For Automatic / Manual Operations Consisiing Of The Following: Horizontal Split Casing, High Pressure Single Centrifugal Type Tire Pump Running At 1500 Rpm Complete With Gland Packing , Proper Connection To Suction And Elivery Line, And Including 80 Mm Bypass -Arrangement For Testing Of Pumps, Having A Name Plate Indicating Suction A Delivery Head, Discharge, Stages. Rpm And Direction Of .Rotation.Pump Shall He Capable Of Furnishing Not Less Than 150, 1 ) Of Rated Capacity At A Head Not Less Than 65% Of The Rated Head. The Shut Off Head Shall Not Exceed 120% Of Rated Head Water Cooled Eith Radiator , Diesel Engine Of Required Blip Or As Per Manufacturer Recommendation At 1500 Rpm For The Above Pump Complete With Standard Accessories & Suitable Cooling System As Described In Specifications Common Base Plate For Mounting Pump & Engine Of Required Strength Manufactured Out Of M, S. Channels As Per Manufactures Recommendation With Heavy Duly Anti Vibration Pads. ( Cushy Foot ) ( 8 Nos., Heavy Duty ) . Flexible Coupling & Coupling Guard For Direct Coupling Of Engine & Pump Suitable Reinforced Cement Concrete Pump Foundations As Per Manufacturer Design Including Foundation Bolts, Washer As Required. 1 No. 8 Hours Capacity Day Oil Storage Tank Fabricated From 3 Mm Thick M.S. Plates. Tank Shall Be Provided With Inlet, Outlet.Overflow, Air Vent, Drain Connections, Filling Connection & Magnetic Level Indicator. Tank Shall Be Mounted On A Suitable Steel Structure ( Painted With 2 Coats Of Red Oxide Paint ) . Tank Shall Be Provided With Epoxy Coat From Inside & Two Or More Coats Of Synthetic Enamel Paint Outside Over Two Coats Of Red Oxide Primer. Diesel Storage Tank Shall Be Double Skin. 24 Volts 180 Ah Lead Acid Battery ( 12 Volts-2 Nos ) With Boost / Trickle Charger For Starting The Engine Automatically Complete As Required. Make:- Kirloskar / Crompton ( Ireaves ) Fire Diesel Engine With Pumps :- Suitable Bhp 1500 Rpm, 12 Volt, 2280 Lpm, 70 Mtr Head ( Horizontal Split Casing ( 02 Stage ) Or As Per Manufacturer Recommendation. , Electric Motor Driven Jockey Pump Supplying, Installing, Testing & Commissioning Of Fire Authority Approved Electrically Driven Jockey Pump Suitable For Automatic / Manual Operation Consisting Of The Following: Horizontal / Vertical Type Fire Pump Running At 2900 R.P.M. Including Bypass Arrangement ( 25 Mm Dia Gm Stop Valve & 5M Pipe ) . Gland Arrangement Shall Be Included. Squirrel Cage Induction Motor Suitable For 415 ± 10%V, 3 Phase, 50 1.1Z„Ac Supply Of Suitable Hp Rating For The Above Pump With Asynchronous Speed O 2900 Rpm T.E.F.0 Type Having Efficiency Class Eff-1 As Per Is 12615 : 2004, Connected To Pump With Flexible Coupling And Coupling Guard. 4 Nos. Anti Vibrat Ion ( Cushy Foot ) Heavy Duty Mounting Pads. Coupling And Coupling Guard For Direct Coupling Of Motor And Pump. Make:- Kirloskar / Crompton Cireaves. 7.5 H.P. 2900 Rpm, 180 Lpm, 70 Mtr Head ( Horizontal / Vertical Multi Stage ) ( 1- Stage ) Or As Per Manufacturer Recommendation. , Design, Manufacturing And Supply Of 400A Fire Fighting Panel Fabricated Out Of 2.0Mm Thick Crca Sheet Steel, Painted With Powder Coated Paint Of Shade As Per The Direction Of Engineer In- Charge After Proper Sheet Treatment Process Of Sheet Steel. The Bus Bar Of Panel Shall Be Of Electrical Grade High Conductive Aluminum Alloy Of Appropriate Cross Section As Per Rating. The Calculation Of Continuous Rating Of Bus Bar Shall He Submitted. The Bus Bar Shall Be Supported By Non Hygroscopic Smc / Dmc Bus Bar Supports Which Shall Be Mounted On Proper Interval To Ensure The Bear The Jerks Of Short Circuit As Fault Level Require. All Indicating Lights Shall Be Led Type And All Wiring Shall Be Done From Pvc Insulated Copper Flexible Wire. The Panel Shall Be Completed In All Respect And Shall Consist Of Following, Material. Incoming- 400A Fp, 35Ka Mccb With Oil & S / C Release, Extended Rhom & With Metering Along With. Phase Indicating Lights, Ct, Cf Etc. Outgoing -75 H.P. Star / Delta Starter With Suitable Mpcb, 35Ka. 3 Nos. 80A Tp Ac Duty Contactor, Star / Delta Timer, Ammeter With Ct, Single Phase Preventer, On / Off Indicating Lights, On / Off Push Button, Auto / Manual Push Button Including All Associated Accessories ( Driven Pump 1 For Internal Hydrant, I For External Hydrant, 1 For Sprinkler System ) 2 Set 7.5 H.P. Dol Starter With Suitable Mpcb, 35Ka, 1 No. 32A Tp Ac Duty Contactor, Direct Type Ammeter With Single Phase Preventer, On / Off Indicating Lights, On / Off Push Button, Auto / Manual Push Button Including All Associated Accessories ( Electrical Driven Jockey Pump ) Sprinkler System ) Diesel Driven Pump Control Suitable For Auto / Manual Operation With Suitable Timer, Aux. Relays, 230Vac 24Vdc Battery Charger With Dc Ammeter & Voltmeter, Emergency Stop Pb, On! Off, Llop, Fiwt, Os Indicating Lights With Audio Visual Alarm, On / Off Push Button, Auto / Manual Push Button And Also Including All Associated Accessories. 1 Set , Providing, Fixing, Testing & Commissioning Of Heavy Duty Ms Pipe ( Galvanised ) Class C, Is : 3589 Marked With All Necessary Fittings Like Tees, Eibows, Flanges.Reducers, Gaskets, Nuts And Bolts Etc. Welded Or Screwed Joints As Required Including Fixing The Pipe With Necessary Structural Supports ( For Delivery / Suction Manifold Related To The Pumps ) Including Painting Of Two Coats Of Synthetic Enamel Paint Over Two Coats Of Red Oxide Zince Chromate Primer Including All Civil Breakages And Making Good The Same [ Location : Plant Room ] . Make: Jindal 250Mm , 200Mm , 150Mm , 100Mm , 80Mm , 25Mm , Providing, Fixing, Testing & Commissioning Of M.S. Class C Diesel Pump Exhaust Pipe Including All Fittings Like Bends, Tee.Clamps / Structural Steel Support Of Suitable Dia For The Engine.The Insulation Of The Exhaust Pipe Shall Be Carried Our With Rock Wool With Aladded With 22 Gauge Aluminium Sheet Complete With All Fittings & Accessories. Make: Jindal. 100Mm , Providing, Fixing, Testing & Commissioning Of Butter Fly Valve Conforming To Is : 13095 With Flanges, Nuts, Bolts And Washers Complete For Following Sizes :- [ Pn 16 Rating ( 16 Kg / Cm2 Pressure Rating ) ] . Make: - Kartar 200Mm , 150Mm , 100Mm , 80Mm , Providing, Fixing. Testing & Commissioning Of Dual Plate Non- Return Valve [ Pn 1.6 Rating ( 16 Kg / Cm2 Pressure Raring ) Complete With 2 Nos, Matching Flanges, Rubber Insertion, With Nuts, Bolts And Washers Etc Of Following Sizes . Make: Kaipatia / Kartar / Firejeet. Make - Kartar 150Mm , 80Mm , Providing, Fixing, Testing & Commissioning Of Flanged End Basket Strainer Made From Ms Body With Bottom And Top Removable Flanges With Nuts, Bolts Etc Having Filteration Area At Least 6 Times The Cross Sectional Area Of The Pipe. Make:Kartar 200Mm , Providing And Fixing Air Vessel Made Of 250 Mm Dia , 8 Mm Thick 1200 Mm In Height With Air Release Valve On Top And Flanged Connection To Riser , Drain Arrangement With 25 Mm Dia Ball Valve With Required Accessories , Pressure Gauge Complet In All Respect Make - Fabricated , Supplying. Installing, Testing And Commissioning 0 To 12 Kg / Cm2 On / Off Pressure Switch In Delivery Line Of Pump Along With Control Wiring For Auto Starting And Auto Stopping - Danfos , Providing & Fixing Dial Type ( 150 Mm Dia ) Pressure Gauge With Isolation Ball Valve Suitable For Working Pressure Of 250 Psi Cost Shall Be Of Inclusive Of Providing Any Short Pieces, Nipples, Elbows Etc As Required. Having Calibration Of 0-15 Kg / Cm2. Make -H Guru / Fiebig , 150 Mm Dia Gun Metal Fire Brigade Suction Hose Coupling Of ( Ss ) Draw Off Connection ) With 150 Mm Dia M.S. C Class Suction Pipe With 150 Mm Dia C.I. Foot Valve.Cost Shall Include A Wall Mounted Box Of M.S. Construction ( 16 Swg ) With Glass Door ( 4.0 Mm Thick ) To House The Above Mentioned Component To Be Connected To Static Water Tank. Make - Newage / Life Guard , Providing, Fixing, Testing & Commissioning Of Resilient Rubber Lined Single Arc Vibration Eliminators Suitable For Raw Water Up To 45Oc Temperature, Working Pressure 8.8 Kg / Cm2 And Test Pressure 20 Kg / Cm2 For :- Kanwal / Dunlop / Easyflex 150Mm , 80Mm , Supplying And Laying Of Aluminium Conductor Pvc Insulated Armoured Served Sheathed Cable 1100 Volts Grade On Surface The Cable Run Shall He Fixed On Ms Clamps Etc.Of Suitable Size Or As Directed By The Engineer-Lncharge , Complete In All Respect. The Armouring Of The Cable Shall Be Properly Connected With The Earth Conductor By Clamps Etc. Following Size Make -Hevells / Kei / Polycapsize 10 Sq Mm X 2 Core , Size 70 Sq Mm X 3-1 / 2 Core , Size 2X 1.5 Sq Mm For ( Control Wiring ) Copper , Signage Board Providing And Fixing Of Self Illuminated / Auto Glow Exit Signs Printed On Photo-Luminescent Sheet Containing Self Illuminated Base Chemical, Of Appropriate Size Not Less Than 400X150mm, Suspended From Ceilling Or Fixed To The Walls With Accessories As Riquired And As Directed At Site. , Hand Appliances ( Fire Extinguisher _ ) Internal / Substation Providing And Fixing Carbon-Di-Oxide Fire Extinguishers Made From Brand New Seamless Cylinder As Per Is: 7285 And Cce Approval Fitted With Discharge, Bend And Horn And Squeeze Grip / Wheel Type Valve With Initial Charge As Per Is:15683:2006 Specification, Bearing 1St Mark & Eil Approved. Make -Safe Guard / Safex 4.5 Kg Capacity , 6 Kg. Capacity , 9 Kg Capacity , Providing And Fixing Dcp Fire Extinguishers Trolley Mounted With All Accessories Internal Discharge Tube, High Pressure Discharge Hose, Discharge Nozzle, Suspension Bracket, Marked As Per Is:2878 Finished Externally With Red Enamel Paint And Fixed To Wall With Brackets Complete With Internal Charge. Make -Safe Guard / Safex Capacity50 Kg. , Providing And Fixing Abc Stored Pressure Type Mono Ammonium Phosphate Powder Magnetic Pressure Gauage Having The Faclity To Check At Site , Discharge Time 9 Sec , Controllable Discharge Mechanisum Range 4 Meters Applicable On Class Pressure Fire Extinguisher Bearing Isi Mark For Fighting Abc And Electrically Started Fire Complet In All Respect . Safe Guard / Safex 4.5 Kg. Capacity , 6 Kg. Capacity , Providing And Fixing Of Clean Agent Ceeling Mounted Type Fe Odp Fabricated Edd Cr Sheet Fitted With Brass Forged Sprinkler Assembly Incorporated With Pressure Gauge Intial 10 Kg Hfc Pressurized With Nitrogen Gas At 14 Kg / Cm2 Complet In All Respect . Make -Safe Guard / Safex , Sub Station - Transformer ( 11Kv / 0.433 Kv ) Supply, Testing & Commissioning Of Outdoor Mounted Type 11 Kv / 433 Volt Transfomer ( As Per Is : 2026, P1 To P5 ) , 3 Phase, 6.25% Impedance, Dyn 11 Vector Group, 50 Cycles, ( Onan ) Oil Immersed Naturally Cooled, Step Down, Copper Wound, Continuous Duty, Temperature Rise Above 50Oc In Oil By Thermometer 40Oc, In Winding By Resistance 45Oc And Other Standard Accessories As Required Including Followings : The Transformer Losses Should Confirm To Is : 1180 ( Level - 2 ) With Latest Amendments At The Time Of Instalation. A ) Cable Termination Box With Disconnecting Facility For 11 Kv 3C-150 Sq Mm Xlpe Cable At 11 Kv Side B ) Lv Side Box Suitable For Suitable Amp Bus Duct Termination. C ) Off Load Tap Changer +10% To -10% @ 1.25% In 16 Equal Steps With Consisting Offollowings - High Torque, Electric Motor Suitable For 415V 3 Ph. 50 Hz., Ac Supply Motor Drive And Energy Accumulator. Monitor Isolating Device With Overload Protection. Contactors For Forward & Reverse Operations Of Motor Oil Surge Relay “Raise / Lower” Control For Local Operation. “Local / Remote” Control Selector Switch. “Raise / Lower” Limit Switches. Stepping Relay. Auxiliary Transformer. D ) Bidirectional Rollers. E ) Oil Conservator With Filter Cap, Drain Plug & Oil Level Gauge F ) Earthing Terminals 2 Nos For Body Earthing. G ) 0.415 Kv Neutral Seperately Bought Out On A Bushing For Neutral Earthing. H ) Neutral Ct As Required. I ) Pressure Release Device. Double Diaphragm Explosion Vent. Ent. J ) Radiators Detachable Type With Top & Bottom Shut Off Valve. K ) First Filling Of Filtered Dehydrated Oil As Per Is : 335 Including Make Up Fill During Installation & 10% Extra L ) Silica Gel Breather With Connecting Pipe & Oil Seal. M ) Rating, Diagram & Terminal Marking Plate Of Ss. N ) Sampling Valves For Filteration, Drainage And Filling With Plugs. O ) Air Release Plugs. P ) Thermometer Pocket With Plug. Q ) Lifting Lugs. R ) Double Float Buchholz Relay With Gas Release Cock, Alarm & Shut Off Valve On Either Side With Separate Set Of Contacts For Trip And Alarm. S ) 150 Mm Winding Temperature Indicator ( Wti ) With Alarm. ( For 800 Kva & Above ) T ) 150 Mm Oil Temperature Indicator ( Oti ) With Alarm U ) Marshalling Box V ) Clamping Device W ) Jacking Pads X ) Ladder With Safety Device For Access To The Top Of Transformer Tank. The Work Shall Be Complete In All Respects Up To The Satisfaction Of Engg-In-Charge Make: Kirloskar, Transtron, Schnider, Crompton, 630 Kva , Ht Pannel Supply, Installation, Testing & Commissioning Of Indoor Type Floor Mounting, Dust & Vermin Proof, Front Operated Construction, Enclosure Class - Ip 42, Powder Coated After Proper Treatment With 9 Tank Process, 11 Kv Vcb Ht Panel -01 With 4 Nos Vcb Breakers ( 1 Incomer And 3 Out Goings ) , Totally Enclosed & Fully Interlocked, Horizontal Drawout, Horizontal Isolation Type Breaker, Having Capacities As Mentioned Below, Single Break, Trip Free Mechanism, Motorised Charged And Auto Closing Breaker Suitable For Use On 11 Kv, 3 Phase, 50 Hz A. C. Supply With Short Circuit Fault Level Of 26.3 Ka, Complete With Self Contained, Fully Interlocked, Rack In And Rack Out Mechanism, Air Insulated But Encapsulated Copper Alloy Bus Bars Of Suitable Fault Level Having Conductivity Of 97 To 99 % , Al. Earth Bar, Earth Bar, Breaker Featured With Mechanical On / Off Indicator With Hand Trip Device, Spring Release Coil, Shunt Trip Coil, Controlvoltage Of 24 Volt Dc, Tnc, Led Type Indicating Lamps For Phases And Trip Conditions And Auxiliary Switch Of 6 No + 6 Nc And Equipped With Following Switchgears And Accessories. The Panel Should Be Suitable For Connections For Up To 3 X 120 Sq.Mm Xlpe 11 Kv Cable ( Cable Entry From Bottom / Top / Side ) , End Termination With Heat Shrinkable Jointing Material Etc. As Required. ( The Cost Of End Termination Not Included In This Item ) Electrical Estimate - Substation Equipment Power Pack ( 1 Working & 1 Standby ) With 220 Volt Ac Input & 24 Volt Dc Continuousoutput Suitable For Indicating Lights & Closing / Tripping / Indication Of 4 Nos. Ht Panel Boards With 2 Nos. 12 Volts Each Maintenance Free Batteries Of Suitable Ah ( Min 4 Hrsback Up For Each Relays & Indication ) Each, Charging Unit, Capacitor Bank For Emergencydelivering For Trip System Complete With Suitable Capacity Of Ammeter & Voltmeter I / Cconnections With 2.5 Sq.Mm Frls Insulated Copper Conductor Cable Etc. Including Dc Db Consisting Of Required Mcbs For Dc Supply Distribution To Panels As Required. Makes : - 11 Kv Breaker - Abb / Siemens / Schneider / L & T ( Bus Bar :- Hindalco / Jindal ) Incoming - 1 Nos. 630 Amp. Vcb Breakers With Followings In Each Breaker - ( A ) 1 Set ( 3 Nos ) 11 Kv / V3 / 110 / V3 Volts Drawout Type Pt Class 0.5 Accuracy And 100 Va Burden With 1 No. Voltmeter ( 0-36 Kv ) , Digital Type, Selector Switch For Voltmeter And Protection Fuses / Mcb For Ht Metering. ( B ) 3 Nos. Dual Core Dual Ratio Cts Of Ratio 200 / 100 / 5 / 5A Of 15 Va Burden And Accuracy Class 0.5 For Metering And Class 5P10 For Protection. ( C ) 1 No. - ( 0-200A ) Ammeter, Digital Type With Selector Switches ( D ) Master Trip Relay ( E ) Trip Circuit Supervision Relay ( F ) Microprocessor Based Numerical Relay With Idmt Setting For O / L, E / F And S / C Protection. G ) Energy Analyser ( Digital Type ) Consisting Of I, V, Kw, Kwh, Kva, Kvah, Kvarh, Pf, Hz & Mdi With Rs 485 Port ( H ) Over And Under Voltage Relay ( I ) Timer And Tnc Switch Outgoing - 3 Nos. - 630A Vcb Breakers With Followings In Each Breaker - Note - Provide All Type Of Protection, Auxillary Relays, Release For The Transformer Protection As The Outgoing Feeders Shall Feeds The Power To Transformer. There Is A Provision In Out Going Vcb That Should Be Trip Off After Ref Relay Activated In Downstream Panel After Transformer. ( A ) 3 Nos. Dual Core Dual Ratio Cts Of Ratio 50 / 5 / 5A Of 15 Va Burden And Accuracy Class-1 For Protection. ( B ) ( 0-50A ) Ammeters, Dual Scale Digital Type & Selector Switches For Ammeters. ( C ) Microprocessor Based Numerical Relay With Idmt & Instantaneous Element For O / L, E / F And S / C Protection. ( The Relay Having Auto Doubling Feature To Prevent Nuisance Triping During Inrush Current Cycle Of Transformer ) ( D ) 12 Window Annunciation Panel With Necessary Relays, Audio And Visual Indicators And Push Buttons. ( E ) Auxilliary Relay For Buchholtz / Oti / Wti / Mog / Oltc Surge With Alarm & Trip ( F ) Tnc Switch G ) Master Trip Relay ( H ) Trip Circuit Supervision Relay ( I ) Energy Analyser ( Digital Type ) Consisting Of I, V, Kw, Kwh, Kva, Kvah, Kvarh, Pf, Hz & Mdi With Rs485 Port. Ht Panel - 04 As Described Above Metering And Class 5P10 For Protection. , Sub Head Main Lt Pannel Design, Manufacture, Supply , Installation, Inspection, Handling, Assembling, Affecting Proper Connections, Testing And Commissioning Of Main L.T. Panel ( With 275Gsm Gi / Crca ) Plc Based Load Manager, Floor Mounting, Dust & Vermin Proof, Front Operated Construction, Enclosure Class - Ip54 / 42. The Bubsbar Shall Be Of Aluminium. The Panel Should Be Double Door Design For Safety Of Operator.The Panel Has To A Bolted Design And No Welding Shall Be Allowed.The Main Parts Like Upright ( Frame ) 9 Fold Design, Busbar Support & Corner Pieces 3 Way Of Panel Should Be Supplied By Oem To System Integrator And Copy Of Inoices ( Without Price ) To Be Submit By System Integrator During Drawing Approval & Inspection For Authenticity Purpose. No Changes In The Iec Or Models / Makes Of Panels As Specified In This Particular Boq Itself Shall Not Be Allowed To Ensure High Quality Of Products For Hospital And This Boq Shall Supercedes All Previous Corrigendum / Amedmend / Sld Issued / List Of Makes For Any Make / Model / Rating During Tendering. The Main Lt Panel Shall Be As Per Iec61439 ( Tta ) . Make : System Integrator Of Abb ( Artu K ) , Schneider ( Okken ) Siemens ( Sivakon ) / L&T ( Terra ) Authorized Certificate And Agreement Copy With Oem To Be Submit While Drawing Approvals Through Contractor. Tender Based Authorization Or Any Other Certifications Shall Not Be Valid.Further, Only Oems System Integrator For Tta Panels As Per Iec61439 ( Models As Specified Above ) Shall Only Be Allowed To Manufacturer & Supply Non Tta Panels Also Like Hvac, Sub Panels, Ahu Panels, Control Panel, Fire Fighting Panel To Maintain The High Quality Vendor For Complete Lt Panels.No Other Manufacturer Shall Supply Non Tta Panels Even If It Is Specified In Make List And This Boq Shall Supercedes All Previous Corrigendum / Amedmend / Sld / List Of Makes Issued. All Acbs Shall Have Inbuilt Microprocesor Based Over Load Protection ( L ) , Short Circuit Protection ( S ) , Instantaneous Short Circuit Protection ( I ) , Earth Fault Protection ( G ) , Shunt Trip Releases. All Acb Should Have Ics=Icu=Icw=50 Ka For 1 Sec.All Acb Shall Be Supplied With All Standard Accessories I.E. Auxillary Switch With 4No + 4Nc Contacts, Cradle, Handle, Safety Shutter In Confirmity With Is:60947. All Acb Incomer Shall Be 4P, Edo, Lsig , With Display And Communication Module For Real Data Assessment Like Events, Fault And All Current Parameters All Mccb Above 250A, Shall Be Microprocessor Based With Inbuilt Ol, Sc, Ef Protections.Mccb 250A & Below Shall Be Thermal Based Ol, Sc All Mccbs Shall Be Ics = 100% Icu, With Rotary Handle, Phase Barriers, Spreader Terminals & Pad Locking Arrangement, With Per Load Requirement. All Tp Mccb Shall Be With Heavy Duty Solid Isolable Neutral Link. The Instrument Chamber Shall Be Separate And Shall Comprise Of Flush Type Ammeter, Voltmeter, Selector Switches, Cast Resin Type Cts & Pts, Etc. Separate Cts Shall Be Provided For Protective And Measuring System And For Apfcr Of Capacitor Bank With Suitable Va Each Section Of Panel Shall Have Door Opearted Light Of Sufficent Lux To Illumunate That Section & Each Section Of Capacitor, Buscoupler, All Acbs Sections Shall Have Exhaust Fans For Ventilation Purpose. Each Section Of Panel Shall Be Provided With Space Heater Alonwiththermostate And Suitable Arrangment For Automatic Operation. All Energy Analyser / Tvm Shall Have Rs 485 Modbus Rtu On Board Communication Protocolfor Scada Communication. The Fault Withstanding Capacity Of Panel & Its Control Gear Shall Be Min. 35 Ka Rms For 1 Sec The Maximum Height Of The Panel Should Not Exceed 2100 Mm Unless Specifically Approved. Ga Drawings Shall Be Got Approved From Consultants Before Fabrication.The Panel Has To Be Specifically Fabricated As Per The Space Available At Basement Level. The Existing Column Positions Will Also Be Considered.Acb Make And Model :- Abb E-Max, Schneider ( Nw ) , Siemens 3Wl ( Etu 76B ) , L & T U Power Mccb Make And Model :- Abb - T-Max, Schneider Nsx, Siemens - 3Vl, L&T - Dsine Dn2 Incomers From 2 Nos.630 Kva Transformers 2Nos Acb 1000A 4P Edo Ol, Sc, Ef With Display ( 4 Line Display ) With 20 Trip History And 60 Events And Release Should Be Compatible With Bluetooth For Extracting Data Wirelessly Andcommunication Module For Real Data Assessment Like Events, Fault And All Current Parameters Acb And Release Make / Model :- Abb E-Max ( Pr122 ) , Schneider Nw 6E, Siemens 3Wl ( Etu 76B ) ( Etu45b ) , L & T U-Power The Acb Shall Be Electrically And Mechanically Interlocked With The Bus Coupler, Dg Incomersand Other Transformer Incomers. 2 Nos. 250 Kvar Capacitor Bank With 400 Amp Tp Mccb ( 50 Ka ) For Each Transformer Incomer. 1 Nos. 32 Amp Tp Mccb ( 35 Ka ) For Oltc ( For Each Transformer Incomer ) Protection Releases / Relays, Metering & Accessories For Each Transformer Incomers Over Voltage / Under Voltage Relay / Release With Timer.Restricted Earth Fault Relay. Master Trip Relay Trip Circuit Supervison Relay. Tnc Switch. Auto Manual Selector Switch. 1 Nos. 0-500 Volt Range Digital Type Voltmeter With Selector Switch 1 Set Of 3 Cts Of Ratio 1000 / 5A, Class 1.0 Accuracy 15 Va Burden For Metering. 1 Set Of 3 Cts Of Ratio 1000 / 5A, Class 1.0 Accuracy 15 Va Burden For Apfcr 1 Set - 415 / V3 / 110 / V3 Class 1.0 Accuracy 100 Va Burden Pt Along With Primary And Secondary Fuse. 1 Set Of 4 Cts Of Ratio 1000 / 1A, Class Ps For Protection 1 No. 0-1000 Amp Range Digital Type Ammeter With Selector Switch. Energy Analyser ( Digital Type ) Consisting Of I, V, Kw, Kwh, Kva, Pf, Hz, Mdi ( Em 6400 Ofconzerve Or Equi. ) With Rs 485 Communication Port For Communication / Report Generation. ( Or Dual Meter ) Power Factor Meter Frequency Meter 3 Nos. Led Type Phase Indicating Lamps, Each Lamp Shall Be With Bakup Mcb Along With Hooter, Auxillary Relay, 2 Sets Of Push Buttons. 5 Nos. Led Type Indicating Lamp For Indicating The Status Of Feeder - On / Off / Trip / Trip Circuit Healthy / Dc Supply Healthy. Each Lamp Shall Be With Bakup Mcb. Incomers From 1 Nos 500 Kva D G Sets 1 Nos Acb 800A 4P Edo Ol, Sc, Ef With Display ( 4 Line Display ) With 20 Trip History And 60 Events And Release Should Be Compatible With Bluetooth For Extracting Data Wirelessly And Communication Module For Real Data Assessment Like Events, Fault And All Current Parameters Incomers From 1 Nos 250 Kva D G Sets 1 Nos Mccb 400A 4P Ol, Sc, Ef With Display ( 4 Line Display ) With 20 Trip History And 60 Events And Release Should Be Compatible With Bluetooth For Extracting Data Wirelessly And Communication Module For Real Data Assessment Like Events, Fault And All Current Parameters Protection Releases / Relays, Metering & Accessories For Each D G Set Incomers Over Voltage / Under Voltage Relay / Release With Timer Idmt Earth Fault Relay Master Trip Relay Trip Circuit Supervison Relay. Reverse Power Relay Main Lt Pannel As Described Above , Automatic Power Factor Correction Panel ( Capacitor Pannel ) Design, Manufacture, Supply, Installation, Inspection, Handling, Assembling, Affecting Proper Connections, Testing And Commissioning Of 16 Swg Crca Sheet Steel Fabricated Cubical Type 250 Kvar A P F C Panel- 01 / 02 / 03 Consisting Of1 / 2 / 5 / 10 / 15 / 20 / 25 / 50 / 60 Kvar Capacitor Units In Tier Formation, Housed In An Integrated Cubicle Type Automatic Switching On And Off Control Panel, Floor Mounting, Dust & Vermin Proof, Front Operated Construction, Enclosure Class - Ip 52, Powder Coated After Proper Treatment With 9 Tank Process With Top / Bottom Removable Gland Plates, As Required, Double Compression Type Cable Glands, Earth Bus, Hinged And Lockable Doors To Achieve Dust And Vermin Proof Complete With All Inter Connections Small Wiring By Min. 2.5 Sq. Mm. Copper Wires, Ckt Labels Etc. The Aluminium Bus Bar Shall Be Of Suitable Length, 500 Volts, 3 Phase 50 Hz Tpn, Electrolytic Aluminium As Per Is 8623 All Mccbs Shall Be Ics = 100% Icu, With Rotary Handle & Pad Locking Arrangement, With Adjustable O / L & S / C Trip Setting As Per Load Requirement. All Tp Mccb Shall Be With Heavy Duty Solid Isolable Neutral Link. The Breaking Capacity Specified Is Ics Value. The Instrument Chamber Shall Be Separate And Shall Comprise Of Flush Type Ammeter, Voltmeter, Selector Switches, Cts, Pts, Etc. Ac3 Duty Contactors Should Be Used For Switching Individual Capacitor Banks. The Fault Withstanding Capacity Of Panel & Its Control Gear Shall Be Min. 35 Ka Rms For 1 Sec. Each Section Of Capacitor Panel Shall Have Verticle Hood & Exhaust Fans For Ventilation Purpose. The Maximum Height Of The Panel Should Not Exceed 2100 Mm Unless Specifically Approved. Incoming Incomer Circuit Breaker Has Been Included In The Main Panel. 1 Set- 3 Cts , Ratio 250 / 5A Class 1.0 Accuracy 15 Va Burden For Metering. 1Nos- ( 0-1000A ) Digital Ammeter With Selector Switchmicro Processor Based Automatic Power Factor Control Relay ( 3 Phase ) ( Including Power Factor Meter ) In 16 Steps For Automatic Cut Off Or Add On Capacitor Units To Keep The Power Factor At 0.95 With Variation Of Loads. All Associated Auxiliary Contactors / Relays Shall Be Provided With In The Scope Of Work. Phase Indicating Lamps With Hrc Fuses, And Indicating In Each Capacitor Chamber Unit To Indicate On / Off Status Of Capacitor Unit. Bus Bars 320 Amp, 500 Volts, 3 Phase 50 Hz Tpn High Conductivity Electrolytic Aluminium Bus Bar Of Suitable Length, Smc / Dmc Supports, With Colour Coding And Insulated By Heat Shrinkable Sleeves And Clips On Shrouds For Joints. The Current Density Of Bus Bar Shall Be Minimum 1.3 Sq Mm / Amp. The Maximum Allowable Temperature For The Bus Bar To Be Restricted To 85 Deg C. The Temperature Rise Should Be Restricted To 35 Deg C Above Ambientte Mperature. Outgoings - 4 Nos. Of 100 Amps Tpn 35 Ka Mccb And 60 Amps Ac3 Duty Contactor With 30 Kvar, Mpp Resin Filled, Super Heavy Duty , 480 V Capacitor Bank, With Copper Coil 7% Detuned Filters, Auto-Manual Selector Switch, Start Stop Push Button For Manual Operation Including On / Off Indicating Lamps And Delay Timer Complete. 5 Nos. Of 63 Amps Tpn 35 Ka Mccb And 63 Amps Ac3 Duty Contactor With 20 Kvar, Mpp Resin Filled, Super Heavy Duty , 480 V Capacitor Bank, With Copper Coil 7% Detuned Filters, Auto-Manual Selector Switch, Start Stop Push Button For Manual Operation Including On / Off Indicating Lamps And Delay Timer Complete. 3 Nos. Of 40 Amps Tpn 35 Ka Mccb And 40 Amps Ac3 Duty Contactor With 10 Kvar, Mpp Resin Filled, Super Heavy Duty , 480 V Capacitor Bank, With Copper Coil 7% Detuned Filters, Auto-Manual Selector Switch, Start Stop Push Button For Manual Operation Including On / Off Indicating Lamps And Delay Timer Complete. , Section - H : D.G. Sets Supply, Testing And Commissioning Of Silent Type Diesel Generating Set At 0.8 Pf, 415 Volts, 50 Cycles Per Second, 1500 Rpm, 3 Phase, Suitable For Parallel Operation, 0.85 Load Factor, Sound Proof Acoustic And Weather Proof Enclosure, Residential Type Silencer ( As Per Cpcb Norms-2 ) Fabricated Out Of Crca Sheet Of 14 / 16 Swg Thickness With 9 Tank Pretreated Before Powder Coating With Ventillation System Complete In All Respects Comprising Of The Following. Diesel Engine Suitable For Driving Alternator Of Above Rating, Compression Ignition, 4 Stroke Cycle, Radiator Cooled, Turbo Charged, Battery Starting, 1500 Rpm, Suitable For Above Output Of Alternator At 40O C, 50% Rh & At 210 M Msl And Confirming To Bs 5514, Bs 649, Is 10000, Capable Of Taking 10% Overloading For One Hour After 12 Hrs Of Prime Continuous Loading, Complete With All The Accessories I.E. Tachometer With Hour Meter, Flexible Coupling With Guard, Crank Case Of Steel, Crank Shaft, Conncting Rods, Electronic Governing System, Dynamically Balanced Flywheel, Air Intake Manifold, Air Cleaner, Anti Vibration Pads, Starter Motor, Including All Other Accessories Required To Complete The System. Instrument Panel - Engine Mounted Instrument Panel Fitted With And Having Digital Display For Followings : Start Stop Switch With Key, Water Temperature Indication, Lubrication Oil Pressure Indication., Lubrication Oil Temperature Indication., Battery Charging Indication, Rpm Indication Over Speed Indication, Low Lube Oil Trip Indication, Engine Hours Indication, Alternator - Synchronous Alternator Of Above Capacity At 0.8 Pf, 3 Phase, 415 Volts, 50 Cycles, 4 Wire, 1500 Rpm, Suitable For Operation At 40 Deg C, 50% Rh & At 210 Meter Above Msl, Capable Of Taking 10% Overlioading For One Hour After 12 Hrs Of Prime Continuous Loading, Brushless, Self Excited, Self Regulated Through Avr, Continuous Duty Confirming To Is 4722, Bs 2613 Suitable For Tropical Conditions, Class H Insulation, Including Terminal Box Suitable For Bus Duct Termination As Required. Note : - Alternator Should Have With All Other Accessories As Per Specified In Technical Specfications. Base Frame - Both The Engine And Alternator Shall Be Mounted On Suitable Base Frame Made Of Ms Channel Which Shall Be Installed On Cement Concrete Foundation And Vibration Isolating Arrangement As Per Recommendations Of Manufacturer. Power Controller For Dg Synchronization Microprocessor Based Power Command Controller ( P.C.- 3.3 Jakson Or Equivalent ) Suitable For Auto / Manual Synchronization & Auto Load Sharing. Daily Service Fuel Tank Of 990 Liters Capacity Fabricated Out Of 2 Mm Thick Ms Sheet Complete With Inlet And Outlet Connections, Oil Indication Gauge, Drain Plug, Air Breather, Provision For Fuel Transfer System, Level Indicators And All Standard Accessories Etc. As Required. Exhaust Silencer - Exhaust Manifold With Residential Silencer. The D G Set Should Be Supplied With Required Hardware For External Plc Based Auto Synchronization, Auto Load Sharing, Auto Load Management System. Starting System - 24 Volt Dc Starting System Comprising Of Starter Motors : Voltage Regulator And Arrangement For Initial Excitation Complete With 12 / 24 Volts Suitable Nos. Lead Acid Type Batteries Of Suitable Ah. Ventillation System - Arrangement For Fresh Air Intake For Cooling Of The Engine & Alternator, Extraction, Discharging Hot Air Into The Atmosphere As Per Standard Specifications. 500 Kva , Supply Of Outdoor Unit 16 Hp Heat Pump Type - Three Phase - Sigma , 20 Hp Heat Pump Type - Three Phase - Sigma , 24 Hp Heat Pump Type - Three Phase - Sigma , Vrf Indoor Unit Supply Of Indoor Units Address Setting And Capacity As Mentioned Below. Multispeed Motor, Coil Section With Dx Coil, Outer Cabinet, Drain Pan Mechanism Insulation, Pipe Connections And Fresh Air Intake Connector As Per Hitachi Specifications Vrf Indoor Unit In The Ceiling / Ducted : 12.0 Hp , In The Ceiling / Ducted : 10.0 Hp , In The Ceiling / Ducted : 8.0 Hp , In The Ceiling : 3.0 Hp - Low Static , In The Ceiling : 2.5 Hp , In The Ceiling : 2.0 Hp , In The Ceiling : 1.5 Hp , Hi Wall 2.5 Hp , Hi Wall 1.3 Hp , 4 Way Cassette : 6.0 Hp , 4 Way Cassette : 5.0 Hp , 4 Way Cassette : 4.0 Hp , 4 Way Cassette : 3.0 Hp , Drain Pump For Conceled Split , Supply Of Multikit Joints-Indoors - Average For All Required Size Of Refnut Joints ( Above Quantities Shall Vary After Copper Pipe Designe Finalize ) , Supply Of Multikit Joints-Outdoors - Average For All Required Size Of Refnut Joints , Supply Of Cordless Remotes For Hi Wall Split , Supply Of Corded Remotes For ( All ) , Installation Of Vrf Air Conditioning System Hp Heat Pump Type ( Cooling & Heating ) Vacuumising The System Upto 500 Micron Level Which Ensures The Zero Moisture Content Level In Piping Which Results In Better Cooling Efficiency And Long Life Of System. Pressure Testing Of System With Nitrogen Gas With 1.5 Times Of Working Pressure Of R410a Refrigerant Gas To Ensure Leakproof System. To Flush The System With Food Grade Nitrogen Gas To Remove Carbon Contents , Dirt Particles To Make Sure That There Is No Chance Of Mixing Of Any Impurity With Refrigerant Gas , Lifting And Shifting & Positioning Charges Of Outdoor Unit , Chouki Type Ms Stand For Outdoor Unit , Indoor Units 1.Vrf Hi-Wall , 1 Way / 2 Way / 4 Way Cassette , In The Ceiling - 12 / 10 / 8 Hp , In The Ceiling - 1.5 / 2.0 / 2.5 / 3 / 4 / 5 Hp , Commissioning Of System Commisssion Of Vrf System Including Topping R410a Gas Per Site Requirments ( R410a Make : Dupont , Honeywell ) , Refrigerant Piping Supply Installation Testing And Commissioning Of Interconnecting Refrigerant Pipe Work With ( 19Mm / 13 Mm Thick ) Closed Cell Elastomeric Nitrile Rubber Tubular Insulation Between Each Set Of Indoor & Outdoor Units As Per Hitachi Std. & Specifications, All Piping Inside The Room Shall Be Properly Supported With Ms Hanger. , Make:- Mandev, Maxflow Or Equivalent ( Copper Pipe ) , Make:- Superlon, Accoflex, A-Flex Or Equivalent ( Insulation ) , Make:- Harris / Mexflow ( Brazing Rod ) 41.2 Mm Dia 19 Mm Thk. Insulation , 38.1 Mm Dia 19 Mm Thk. Insulation , 34.9 Mm Dia 19 Mm Thk. Insulation , 31.2 Mm Dia 19 Mm Thk. Insulation , 28.6 Mm Día 19 Mm Thk. Insulation , 25.4 Mm Día 19 Mm Thk. Insulation , 22.2 Mm Dia 19 Mm Thk. Insulation , 19.04 Mm Dia 19 Mm Thk. Insulation , 15.9 Mm Dia 19 Mm Thk. Insulation , 12.7 Mm Dia 13 Mm Thk. Insulation , 9.5 Mm Dia 13 Mm Thk. Insulation , 6.4 Mm Dia 13 Mm Thk. Insulation , Drain Piping Providing And Fixing Rigid Pvc Piping Complete With Fittings, Supports As Per Hitachi Std.& Specifications. - In Client Scope Make:- Supreme, Kissan , Astral, Or Equivalent A ) 25 Mm Dia , 32 Mm Dia , 40 Mm Dia , Drain Hose Connector - If Required , Control Cabling Supply & Fixing Of Control Cum Transmission Wiring ( Sheilded ) Of Copper Conductor Cable Alongwith Conduite For Looping Between Indoor & Outdoor Vrf System & To Main Central Remote Controller System Make:- Polycab Or Equivalent 2 C X 0.75Sq. Mm , Sheet Metal Work Fabrication, Supply, Installation, Testing & Commissioning Of Following Gauges Complete With, Supports And Turning Vanes Make:- Sail , Jindal , Or Equivalent A ) Uninsulted Gi Ducting 24 G ( 0.63 Mm ) , Uninsulted Gi Ducting 22 G ( 0.80 Mm ) , Canvas Connection - Double Layer , Thermal Insulation Work Supply, Installation & Testing Of Thermal Duct Insulation. Make:- Kflex, Accoflex, A-Flex , Supreme Or Equivalentsupply & Installation Of Thermal Insulation Over The Duct With Xlpe Sheet For The Ducts With 9 Mm Thick Sqmt One Laver Externally On The Duct. , Acoustic Lining ( Ducts ) Work Supply, Installation & Testing Of Acoustic Lining With Fiber Glass Wool. Make:- Up Twiga, Or Equivalent Supply & Installation Of Acoustic Lining Of Duct With 12.5 Mm Thick Fiber Glass Covered With Tissue Paper, Gi Screws And Washers. 25 Mm Thick With 24 Kg Density , Grilles And Diffusers Supply & Return Air Grille Supply, Installation, Testing And Balancing Of Powder Coated Extruded Aluminum Supply & Return Air Grilles / Diffuser With Approved Shop Drawings And Specifications. , Supply & Installation Of Ms Painted Supply Air Vcd Coller Dampers. , Minor Civil Work / Wall Cutting / Breaking Of Wall- , Lift Make-Otias, Schindler ( Details & Specification Attached In Tender Document )

Key Value

Document Fees
INR 11800 /-
EMD
INR 100000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work : Supply of Item at Bharat Ratna Dr. Bhimrao Ambedkar Smarak Kendra Aishbagh Lucknow.
Sl. No. Item Description
1Fire Alarm & Detection System Supplying, installation, testing & commissioning sector panel suitable for following zones, complete with visual indications for short circuit fault, open circuit fault, fire condition and all other standard facilities as per IS:2189 with mimic diagram for all area/zone covered, complete with all connections, interconnections as required. (For Sub-Station) 4 Zone
2Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. Two Loop
3Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.
4Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reSet, acknowledge and silence switches complete as required.
5Supplying, installation, testing & commissioning of intelligent analog addressable Smoke detector complete with mounting base complete as required.
6Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
7Supplying, installation, testing & commissioning of fault isolator complete with base as required.
8Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
9Supplying, installation, testing & commissioning of addressable fire control module complete as required.
10Supplying, installation, testing & commissioning of addressable phone control module complete as required.
11Supplying, installation, testing & commissioning of intelligent addressable duct detector including suitable Photo detector complete with base as required.
12Supplying, installation, testing & commissioning of addressable manual call point complete as required.
13Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
14Supplying, installation, testing & commissioning of fire fighter telephone hand Set complete as required.
15Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
16Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required.
17Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required.
18Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required.
19Supplying, installation, testing & commissioning of Voice command keypad 6 zone, with microphone assembly complete as required.
20Supplying & laying of 2x1.5 Sqmtm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.
21Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. speaker cable Two pair, 2-core, 1.5 Sqmtm
22Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. speaker cable Four pair, 2-core, 1.5 Sqmtm
23Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required.
24Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, inconvenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100mm widthx50mmdepthx1.6mm thickness
25Supply of Addressable Monitor module. The module should be able to monitor dry contacts. It should have a LED indicator. Any junction box used with the call point should have minimum IP 44 rating.The device should be Vds/UL Approved
26Supply of Addressable relay module. The relay should be form C with NO, C and NC contacts. The contacts should work with minimum 2.0 Amp resistive or 1.0 Amp inductive current. It should have a LED indicator .Any junction box used with the module should have minimum IP 44 rating. The device should be Vds/ UL Approved
27Supply, Installation, Testing and Commissioning of Workstation PC: Intel(R) Core(TM) i3 10th Gen Processor (8M Cache, up to 3.90 GHz); RAM: 8GB (1x8GB) Non-ECC DDR5 1600MHz ; Keyboard: 12 function keys; Chassis: Tower/Workstation; DVD: 8X Slimline DVD+/-RW, Data Only; Dual Graphics Card; Network interface card: Integrated Intel(R) 82579LM Gigabit1 Ethernet LAN 10/100/1000; SSD: 256GB; Operating system: Windows 10Professional 64 Bit or latest.Approved Makes: HP / DELL / ASUS / LENOVO
28FIRE FIGHTING AND SPRINKLERSYSTEM Providing, fixing, jointing, testing and commissioning of Heavy duty (class "c") MS pipe conforming to IS : 1239 (Part I) pipes up to 150 trim dia with all necessary fittings like tees, elbows, flanges, reducers. gasket, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports including painting of two coats of synthetic enamel paint over two coats of red oxide primer including all civil breakage"s and making good the same, . Make: Jindal. a) 50MM
2980MM
3025MM
31GMl double headed CSI marked oblique pattern hydrant landing valves with 80mm dia flanged inlet & 63 mm dia female outlet complete with PVC / rubber cap and GI chain twist release type plug and all accessories as per IS 5290 Type A including fixing with anchor fasteners and flanged tapping from wet riser complete as uired. MAKE - NEWAGE /SAFE GAURD /Geetech
32Providing and Fixing of Non-Percolating flexible RRL Hose Pipe ISI Marked (IS:636) 63 mm diax 15 M long complete with instantaneous type 63 mm dia. Marked Male and Female GM couplings (IS:903) bound and riveted to hose pipe. ( TYPE -1 ) MAKE -NEWAGE /SAFEGUARD /GETECH
33GM branch pipe with nozzle of 20 mm nominal bore outlet as per IS:903 suitable to fit with standard instantaneous type 63mm dia coupling ISI marked (1S:903) complete. MAKE - NEWAGE /SAFEGAURD /GEETECH
34Wall mounting swinging type first aid fire hose reel with drum, hanging bracket, 30.0 Mir. length x 20 mm dia high pressure hose reel tubing as per IS: 444 with gun metal (GM) shut off nozzle having 6.5 mm dia orifice. The hose reel shall be conforming to IS : 884-1985. Rate shall include 25 mm dia M.S. pipe (heavy class) connection from Riser to hose reel, sockets, nipples,elbows and ball valve (25 mm dia). Drum shall be fixed on adjoining wall by means of 120 mm x 100 mm long fasteners, bolts and nuts including painting. (For internal hydrant system). MAKE - NEWAGE /SAFEGAURD /GEETEC
35Providing & Fixing of 1.6 mm thick M.S / Door Frame, Door capable of accommodating fire Hose Reel, Landing Valve, Hose Pipes, fittings & accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) Cost of fire extinguishers not included in item rate. (Liasioing with civil contractor for making Recessed type mansuary box (by civil contractor). MAKE - LOCALY FABRICATED 900 MM X2100MM
36Supplying. Installing, Testing and Commissioning 0 to 12 Kg/cm2 ON/OFF Pressure Switch in delivery line of pump along with control wiring for auto starting and auto stopping MAKE - DANFOS
37ELECTRIC DRIVEN TERRACE PUMP Supplying.installing,testing & commissioning of fire authority approved electrically driven Terrace Pump suitable for automatic/manual operation consisting of the following: Squirrel Cage,TEFC induction motor suitable for 415 ± 10%V, 3phase, 50 Hz A.C. supply of suitable H.P. 900 LPM @ 35 MTR HEAD 2900 RPM Make:- Kirloskar / Crompton Cireaves.
38Providing and Fixing Air Vessel made of 200 mm dia ,8 mm thick 1200 mm in height with air release valve on top and flanged connection to riser ,drain arrangement with 25 mm dia ball valve with required accessories ,pressure gauge complet in all respect MAKE - FABRICATED
39Providing, fixing, testing & commissioning of C.I. Butterfly valve conforming to IS : 13095 with flanges, nuts, bolts and washers complete for following sizes :- [PN 16 rating (16 kg/cm2 pressure rating)]. Make: - KARTAR 150mm
40Providing, fixing. testing & commissioning of C.I. dual plate Non- Return Valve [PN 1.6 Rating (16 kg/cm2 pressure raring) complete with 2 nos, matching flanges, rubber insertion, with nuts, bolts and washers etc of following sizes . Make: KARTAR 150mm
41Providing & fixing dial type Pressure Gauge with isolation ball valve suitable for working pressure of 250 PSI cost shall be of inclusive of providing any short pieces, nipples, elbows etc as required. having calibration of 0-15 Kg/cm2. MAKE -H GURU
42Supplying and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade On surface the cable run shall he fixed on MS clamps etc.of suitable size or as directed by the Engineer-lncharge ,complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. Following size MAKE -HAVEELS/ RR /POLYCAB 16 x3.5 core
43supplying, Installation, testing and commissioning of electrical control panel of cubicle construction, floor/ wall mounted type, fabricated out of 2 mm thick CRCA sheet,compartmentalised with hinged locakable doors,dust and vermin proof,powder coated fabricated out of 2 mm thick CRCA sheet,compartmentalised with hinged locakable doors,dust and vermin proof,powder coated including sutaible contector relay ,ct ,auto manual switch complet in all respects, FOR -TERRACE PUMP
44EXTERNAL FIRE HYDRANT SYSTEM Providing Laying, Testing & Commissioning of "C" class Heavy Duty MS Pipe conforming to IS 1239/3589 (all pipes shall be IS1 marked and of makes specified in the specifications) Lic fittings like Elbows, tees flanges, tapers, nuts bolts, gaskets etc. in ground including excavation & providing cement concrete blocks as supports and anti-corrosive treatment to burned pipes by wrapping & coating wih anticorrosion tape along with two coat of black japan primer for under-ground pipe including digging and backfilling upto 1.0 mu. below from G.L.for external work . MAKE -JINDAL ( Under G round ) a) 150MM
4580MM
46GMl single headed CSI marked oblique pattern hydrant landing valves with 80mm dia flanged inlet & 63 mm dia female outlet complete with PVC / rubber cap and GI chain twist release type plug and all accessories as per IS 5290 Type A including fixing with anchor fasteners and flanged tapping from wet riser complete as uired. MAKE -NEWAGE /LIFEGUARD/GEETEC
47Providing and Fixing of Non-Percolating flexible RRL Hose Pipe ISI Marked (IS:636) 63 mm diax 15 M long complete with instantaneous type 63 mm dia. Marked Male and Female couplings (IS:903) bound and riveted to hose pipe. ( TYPE -A ) MAKE -NEW AGE /LIFEGUARD /GEETECH
48Standard GMl branch pipe with nozzle of 20 mm nominal bore outlet as per IS:903 suitable to fit with standard instantaneous type 63mm dia coupling ISI marked (1S:903) complete. MAKE -LIFE GUARD /NEWAGE /GEETEC
49Providing & Fixing of 1.6 mm thick M.S / FIRE HOSE Cabinet BOX 750 X600 X300 capable of Landing Valve, Hose Pipes, , branch pipe , accessories. The door shall have a front glass with lock and key arrangement & shall be painted with post office red colour (approval shall be taken on the basis of submitted sample before ordering) For externel yard hydrant ,complet in all respect MAKE - FABRICATED
50Providing and fixing of fire brigade inlet 4 way connection of cast iron body with SS male instantaneous inlet coupling complet with cap and chain as reqd for suitable dia MS pipe connection complet with suitable size MS box complet in all respect - NEWAGE /LIFEGUARD/GEETECH
51Providing, fixing, testing & commissioning of C.I. Butterfly valve conforming to IS : 13095 with flanges, nuts, bolts and washers complete for a) following sizes :- [PN 16 rating (16 kg/cm2 pressure rating)]. Make: -KARTAR 150mm
52Make: -KARTAR 80mm
53Providing, fixing. testing & commissioning of C.I. dual plate Non- Return Valve [PN 1.6 Rating (16 kg/cm2 pressure raring) complete with 2 nos, matching flanges, rubber insertion, with nuts, bolts and washers etc of following sizes . Make: ZOLOTO /SANt /kartar 150mm
54Supply, and constructing of masonary valve chamber 900x900x1000 cm inside 75 class designation brick work in cement ,mortar 1:5 (1 cement,5 find send ) for sluice valve / butter fly valve with CI surface box 100 mm top dia 180 mm bottom dia,and RCC Top slab complet as per standard
55Fire Sprinkler System (First) Providing, fixing, jointing, testing and commissioning of Heavy duty (class "c") MS pipe conforming to IS : 1239 (Part I) pipes up to 150 trim dia with all necessary fittings like tees, elbows, flanges, reducers. gasket, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports including painting of two coats of synthetic enamel paint over two coats of red oxide primer including all civil breakage"s and making good the same, . Make: Jindal. (Above Ground ) 150mm
56100mm
5780mm
5865mm
5950mm
6040mm
6125mm
62Providing Laying, Testing & Commissioning of "C" class Heavy Duty MS Pipe conforming to IS 1239/3589 (all pipes shall be IS1 marked and of makes specified in the specifications) Lic fittings like Elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including excavation & providing cement concrete blocks as supports and anti-corrosive treatment to burned pipes by wrapping & coating wih anticorrosion tape along with two coat of black japan primer for under-ground pipe including digging and backfilling upto 1.0 mu. below from G.L.for external work as per IS 909 MAKE - JINDAL ( UNDER GROUND ) 150MM
63Providing and Fixing 25 mm dia Flexible Stainless Steel (SS 304) Pipe for making final connection of sprinkler head with sprinkler system piping network including 2 nos. 25 mm diameter G.I. connector, G.E. Nipple, Reducer, elbow and threaded jointing complete as per detail. Make:- NEWAGE /TYCO a) 1000MM
641500MM
65Providing and Fixing and commissioning of sprinkler Rosette plate 560.00 NO Supply, Installation, testing and commissioning of required size Zonal Control Valve inclusive" of 1 nos required size Butterfly Valve, required size Non Return Valve, Flow Switch, water Pressure Gauges & 25 mm dia. Auxiliary Drain Valve with sight glass with necessary GI "C" Class piping with threaded fittings of required sizes complete. 150MM
66Providing, fixing, testing & commissioning of C.I. Butterfly valve conforming to IS : 13095 with flanges, nuts, bolts and washers complete for following sizes :- [PN 16 rating (16 kg/cm2 pressure rating)]. Make: SANT /ZOLOTO a) 150mm
6750mm
68Providing, fixing, testing and commissioning of 15 mm dia quartzoid bulb type Stainless steel sprinkler head suitable to operate at 68 deg C (UL/FM listed /approved) MAKE - TYCO /HD/newage Note- Al! sprinklers shall be chrome finish / powder coated except for conceled., The sprinkler shall be either pendent or upright-type/side wall and shall not be universal style. a) Side wall sprinkler 680C (with extended coverage)
69b) Pendent Sprinkler 680C (stadard Response)
70Upright Sprinkler 680C (standard Response)
71Providing and Fixing Air Vessel made of 200 mm dia ,8 mm thick 1200 mm in height with air release valve on top and flanged connection to riser ,drain arrangement with 25 mm dia ball valve with required accessories ,pressure gauge complet in all respect MAKE FABRICATED
72FIRE PUMPS AND VALVE Electric Motor Driven Main Hydrant/Sprinkler/ (Location - Plant Room) Supplying, installing, testing and commissioning of Fire authority approved Electrical driven fire pump suitable for automatic/ manual operation consisting or the following: Horizontal split casing, high pressure single/ multistage centrifugal type fire pump running at 2900 RPM complete with gland packing, proper connection to suction and delivery line, and including bypass arrangement for testing of pumps, having a name plate indicating suction, delivery, head, discharge, stages, RPM and direction of rotation.Pump shall be capable of furnishing not less than 150% of rated capacity at a head not less than 65% of rated head. The shut off head shall not exceed 120% of rated head. Squirrel cage, induction motor, TEFC type, efficiency class. eff-1, suitable for 415 + 10%V, 3 phase, 50 Hz, AC supply, of suitable HP rating for the above pump with asynchronous speed of 2900 RPM conforming to IP 55 protection & class "F insulation.The motor shall conform to IS 12615 : 2004 and IS 325 : 1978 (up to date) with flexible coupling and coupling guard.Common base plate for mounting pump and motor fabricated of mild steel channel as per manufacturer"s recommendation with heavy duty Anti Vibration pads (6 Nos., heavy duty). Suitable reinforced cement concrete pump foundation as per manufacturer"s design including foundation bolts, washers as required.Flexible Coupling and coupling guard for direct coupling of pump and motor. Rate should include interconnection cables and foundation bolts, grouting of Foundation bolts and other accessories required.Main Fire Electric driven Moter with Pump :- SUITABLE HP 2900 RPM, 2280 LPM, 70 Mtr HEAD (Horizontal Split Casing (02 Stage) or As per manufacturer ecommendation.
73DIESEL ENGINE DRIVEN FIRE PUMP Supplying, installing, testing & commissioning of fire authority Approved Diesel Engine driven tire pump suitable for automatic /manual operations consisiing of the following: Horizontal split casing, high pressure single centrifugal type tire pump running at 1500 RPM complete with gland packing , proper connection to suction and elivery line, and including 80 mm bypass -arrangement for testing of pumps, having a name plate indicating suction a delivery head, discharge, stages. RPM and direction of .rotation.Pump shall he capable of furnishing not less than 150,1) of rated capacity at a head not less than 65% of the rated head. The shut off head shall not exceed 120% of rated head Water cooled eith radiator ,diesel engine of required BLIP or as per manufacturer recommendation at 1500 RPM for the above pump complete with standard accessories & suitable cooling system as described in specifications Common base plate for mounting pump & engine of required strength manufactured out of M,S. channels as per manufacture"s recommendation with heavy duly Anti Vibration pads. (Cushy foot) (8 nos., heavy duty). Flexible Coupling & coupling guard for direct coupling of engine & pump Suitable reinforced cement concrete pump foundations as per manufacturer design including foundation bolts,washer as required. 1 No. 8 hours capacity day oil storage tank fabricated from 3 mm thick M.S. plates. Tank shall be provided with inlet, outlet.overflow, air vent, drain connections, filling connection & magnetic level indicator. Tank shall be mounted on a suitable steel structure (Painted with 2 coats of red oxide paint). Tank shall be provided with epoxy coat from inside & two or more coats of synthetic enamel paint outside over two coats of red oxide primer. Diesel storage tank shall be double skin. 24 volts 180 AH lead acid battery (12 volts-2 Nos) with boost/Trickle charger for starting the engine automatically complete as required. Make:- Kirloskar / Crompton (ireaves) Fire Diesel Engine with Pumps :- SUITABLE BHP 1500 RPM, 12 Volt, 2280 LPM,70 Mtr HEAD (Horizontal Split Casing (02 Stage) or As per manufacturer recommendation.
74Electric Motor Driven jockey pump Supplying,installing,testing & commissioning of fire authority approved electrically driven Jockey Pump suitable for automatic/ manual operation consisting of the following: Horizontal /vertical type fire pump running at 2900 r.p.m. including bypass arrangement (25 mm dia GM Stop valve & 5m pipe). Gland arrangement shall be included. Squirrel cage induction motor suitable for 415 ± 10%V, 3 phase, 50 1.1z„AC supply of suitable HP rating for the above pump with asynchronous speed o 2900 RPM T.E.F.0 type having efficiency class eff-1 as per IS 12615 : 2004, connected to pump with flexible coupling and coupling guard. 4 Nos. anti vibrat ion (Cushy foot) heavy duty mounting pads. Coupling and coupling guard for direct coupling of motor and pump. Make:- Kirloskar / Crompton Cireaves. 7.5 H.P. 2900 RPM, 180 LPM, 70 Mtr HEAD (Horizontal /Vertical multi stage ) (1- Stage) or As per manufacturer recommendation.
75Design, Manufacturing and Supply of 400A Fire Fighting Panel Fabricated out of 2.0mm thick CRCA sheet steel, painted with Powder coated paint of shade as per the direction of Engineer In- Charge after proper sheet treatment process of sheet steel. The Bus Bar of Panel shall be of Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating. The calculation of continuous rating of Bus Bar shall he submitted. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted on proper interval to ensure the bear the jerks of short Circuit as fault level require. All Indicating Lights shall be LED type and all wiring shall be done from PVC Insulated copper flexible wire. The Panel shall be completed in all respect and shall consist of following, material. Incoming- 400A FP, 35kA MCCB with OIL & S/C release, Extended RHOM & With Metering along with. Phase Indicating Lights, CT, CF etc. Outgoing -75 H.P. Star/Delta Starter with suitable MPCB, 35kA. 3 Nos. 80A TP AC duty Contactor, Star/Delta Timer, Ammeter with CT, Single Phase Preventer, On/ Off Indicating Lights, On/off Push Button, Auto/ Manual Push Button including all associated accessories (Driven Pump 1 for Internal Hydrant, I for External Hydrant, 1 for Sprinkler System) 2 Set 7.5 H.P. DOL Starter with suitable MPCB, 35kA, 1 No. 32A TP AC duty Contactor, Direct type Ammeter with Single Phase Preventer, On/ Off Indicating Lights, On/off Push Button, Auto/ Manual Push Button including all associated accessories (Electrical Driven Jockey Pump) Sprinkler System) Diesel driven Pump Control suitable for Auto/Manual Operation with suitable Timer, Aux. Relays, 230VAC 24VDC battery Charger with DC Ammeter & Voltmeter, Emergency Stop PB, On! Off, LLOP, FI"WT, OS Indicating Lights with Audio Visual Alarm, On/off Push Button, Auto/ Manual Push Button and also including all associated accessories. 1 Set
76Providing, fixing, testing & commissioning of heavy duty MS pipe (Galvanised) class "C", IS : 3589 marked with all necessary fittings like tees,eibows, flanges.reducers,gaskets,nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports (for delivery/suction manifold related to the pumps) including painting of two coats of synthetic enamel paint over two coats of red oxide zince chromate primer including all civil breakages and making good the same [Location : Plant room]. Make: JINDAL 250MM
77200MM
78150MM
79100MM
8080MM
8125MM
82Providing,fixing,testing & commissioning of M.S. class "C" diesel pump exhaust pipe including all fittings like bends,tee.clamps/structural steel support of suitable dia for the engine.The insulation of the exhaust pipe shall be carried our with rock wool with aladded with 22 gauge aluminium sheet complete with all fittings & accessories. Make: Jindal. 100mm
83Providing, fixing, testing & commissioning of butter fly valve conforming to IS : 13095 with flanges, nuts, bolts and washers complete for following sizes :- [PN 16 rating (16 kg/cm2 pressure rating)]. Make: - KARTAR 200mm
84150MM
85100MM
8680MM
87Providing, fixing. testing & commissioning of dual plate Non- Return Valve [PN 1.6 Rating (16 kg/cm2 pressure raring) complete with 2 nos, matching flanges, rubber insertion, with nuts, bolts and washers etc of following sizes . Make: Kaipatia/Kartar/Firejeet. MAKE - KARTAR 150MM
8880MM
89Providing, fixing, testing & commissioning of flanged end Basket Strainer made from MS body with bottom and top removable flanges with nuts, bolts etc having filteration area at least 6 times the cross sectional area of the pipe. Make:Kartar 200mm
90Providing and Fixing Air Vessel made of 250 mm dia ,8 mm thick 1200 mm in height with air release valve on top and flanged connection to riser ,drain arrangement with 25 mm dia ball valve with required accessories ,pressure gauge complet in all respect MAKE - FABRICATED
91Supplying. Installing, Testing and Commissioning 0 to 12 Kg/cm2 ON/OFF Pressure Switch in delivery line of pump along with control wiring for auto starting and auto stopping - DANFOS
92Providing & fixing dial type (150 mm dia) Pressure Gauge with isolation ball valve suitable for working pressure of 250 PSI cost shall be of inclusive of providing any short pieces, nipples, elbows etc as required. having calibration of 0-15 Kg/cm2. MAKE -H GURU /FIEBIG
93150 mm dia gun metal fire brigade suction hose coupling of (SS ) draw off connection) with 150 mm dia M.S. "C" Class suction pipe with 150 mm dia C.I. foot valve.Cost shall include a wall mounted box of M.S. construction (16 SWG) with glass door (4.0 mm thick) to house the above mentioned component to be connected to static water tank. MAKE - NEWAGE /LIFE GUARD
94Providing, fixing, testing & commissioning of resilient rubber lined single Arc Vibration Eliminators suitable for raw water up to 45oC temperature, working pressure 8.8 Kg/cm2 and test pressure 20 Kg/cm2 for :- KANWAL /DUNLOP /EASYFLEX 150mm
9580mm
96Supplying and laying of aluminium conductor PVC insulated armoured served sheathed cable 1100 volts grade On surface the cable run shall he fixed on MS clamps etc.of suitable size or as directed by the Engineer-lncharge ,complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. Following size MAKE -Hevells /kei/polycapsize 10 sq mm x 2 core
97size 70 sq mm x 3-1/2 core
98Size 2X 1.5 SQ mm for (control wiring )Copper
99SIGNAGE BOARD Providing and Fixing of Self illuminated /Auto Glow Exit Signs printed on photo-luminescent sheet containing self illuminated base chemical,of appropriate size not less than 400x150mm,suspended from ceilling or fixed to the walls with accessories as riquired and as directed at site.
100HAND APPLIANCES ( FIRE EXTINGUISHER _)INTERNAL/SUBSTATION Providing and fixing Carbon-di-oxide fire extinguishers made from brand new seamless cylinder as per IS: 7285 and CCE approval fitted with discharge, Bend and Horn and Squeeze Grip / wheel type valve with initial charge as per IS:15683:2006 specification, bearing 1St Mark & EIL approved. MAKE -SAFE GUARD /SAFEX 4.5 kg Capacity
1016 kg. Capacity
1029 KG Capacity
103Providing and Fixing DCP Fire Extinguishers Trolley Mounted with all accessories internal discharge tube, high pressure discharge hose, discharge nozzle, suspension bracket, marked as per IS:2878 Finished externally with red enamel paint and fixed to wall with brackets complete with internal charge. MAKE -SAFE GUARD /SAFEX Capacity50 Kg.
104Providing and fixing ABC Stored Pressure type Mono Ammonium phosphate powder Magnetic pressure Gauage having the faclity to check at site ,discharge time 9 sec ,controllable discharge mechanisum range 4 meters applicable on class pressure Fire Extinguisher bearing ISI Mark for Fighting ABC and electrically started fire complet in all respect . SAFE GUARD/SAFEX 4.5 kg. Capacity
1056 kg. Capacity
106Providing and fixing OF CLEAN AGENT Ceeling mounted type FE ODP Fabricated EDD CR Sheet fitted with brass forged sprinkler assembly incorporated with pressure gauge intial 10 kg HFC Pressurized with nitrogen gas at 14 kg /cm2 complet in all respect . MAKE -SAFE GUARD/SAFEX
107SUB STATION - TRANSFORMER (11KV/0.433 KV) Supply, testing & commissioning of Outdoor mounted type 11 KV / 433 Volt Transfomer (as per IS : 2026, P1 to P5), 3 phase, 6.25% impedance, Dyn 11 vector group, 50 cycles, (ONAN) oil immersed naturally cooled, step down, copper wound, continuous duty, temperature rise above 50oC in oil by thermometer 40oC, in winding by resistance 45oC and other standard accessories as required including followings : The Transformer losses should confirm to IS : 1180 (Level - 2 ) with latest amendments at the time of instalation. a) Cable Termination box with disconnecting facility for 11 KV 3C-150 sq mm XLPE cable at 11 KV side b) LV side box suitable for suitable Amp bus duct termination. c) Off Load Tap Changer +10% to -10% @ 1.25% in 16 equal steps with consisting offollowings - High torque, electric motor suitable for 415V 3 Ph. 50 Hz., AC supply Motor drive and energy accumulator. Monitor isolating device with overload protection. Contactors for Forward & Reverse operations of motor Oil Surge Relay “RAISE / LOWER” control for local operation. “LOCAL / REMOTE” control selector switch. “RAISE / LOWER” limit switches. Stepping Relay. Auxiliary Transformer. d) Bidirectional rollers. e) Oil Conservator with filter cap, drain plug & oil level gauge f) Earthing terminals 2 nos for body earthing. g) 0.415 KV neutral seperately bought out on a bushing for neutral earthing. h) Neutral CT as required. i) Pressure release device. Double diaphragm explosion vent. ent. j) Radiators Detachable type with top & bottom shut off valve. k) First filling of filtered dehydrated oil as per IS : 335 including make up fill during installation & 10% extra l) Silica gel breather with connecting pipe & oil seal. m) Rating, Diagram & Terminal marking plate of SS. n) Sampling Valves for filteration, drainage and filling with plugs. o) Air release plugs. p) Thermometer pocket with plug. q) Lifting Lugs. r) Double float Buchholz relay with gas release cock, alarm & shut off valve on either side with separate set of contacts for trip and alarm. s) 150 mm Winding temperature indicator (WTI) with alarm. (for 800 KVA & above) t) 150 mm Oil temperature indicator (OTI) with alarm u) Marshalling Box v) Clamping device w) Jacking Pads x) Ladder with safety device for access to the top of transformer tank. The work shall be complete in all respects up to the satisfaction of Engg-in-charge Make: Kirloskar, Transtron, Schnider, Crompton, 630 KVA
108HT Pannel Supply,installation, testing & commissioning of indoor type floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 42, powder coated after proper treatment with 9 tank process, 11 KV VCB HT Panel -01 with 4 nos VCB breakers (1 incomer and 3 out goings), totally enclosed & fully interlocked, horizontal drawout, horizontal isolation type breaker, having capacities as mentioned below, single break, trip free mechanism, motorised charged and auto closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A. C. supply with short circuit fault level of 26.3 KA, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated Copper alloy bus bars of suitable fault level having conductivity of 97 to 99 % , Al. earth bar, earth bar, breaker featured with mechanical ON / OFF indicator with hand trip device, spring release coil, shunt trip coil, controlvoltage of 24 Volt DC, TNC, LED type indicating lamps for phases and trip conditions and auxiliary switch of 6 NO + 6 NC and equipped with following switchgears and accessories. The panel should be suitable for connections for up to 3 x 120 sq.mm XLPE 11 KV cable (cable entry from bottom/top/side), end termination with heat shrinkable jointing material etc. as required. (The Cost of end termination not included in this item) ELECTRICAL ESTIMATE - SUBSTATION EQUIPMENT power pack ( 1 working & 1 standby) with 220 Volt AC input & 24 Volt DC continuousoutput suitable for indicating lights & closing / tripping / indication of 4 Nos. HT panel boards with 2 Nos. 12 Volts each maintenance free batteries of suitable AH (Min 4 Hrsback up for each relays & indication) each, charging unit, capacitor bank for emergencydelivering for trip system complete with suitable capacity of Ammeter & Voltmeter i/cconnections with 2.5 sq.mm FRLS insulated copper conductor cable etc. including DC DB consisting of required MCB"s for DC supply distribution to panels as required. Makes : - 11 KV Breaker - ABB / Siemens / Schneider / L & T (Bus Bar :- Hindalco / Jindal) Incoming - 1 Nos. 630 Amp. VCB breakers with followings in each breaker -(a) 1 set (3 nos) 11 KV / v3 / 110 / v3 Volts drawout type PT Class 0.5 accuracy and 100 VA burden with 1 No. Voltmeter (0-36 KV), digital type, selector switch for voltmeter and protection fuses/MCB for HT metering. (b) 3 nos. dual core dual ratio CTs of ratio 200/100/5/5A of 15 VA burden and accuracy class 0.5 for metering and class 5P10 for protection. (c) 1 No. - (0-200A) Ammeter, digital type with selector switches (d) Master trip relay (e) Trip circuit supervision relay(f) Microprocessor based numerical relay with IDMT setting for O/L, E/F and S/C protection. g) Energy analyser (digital type) consisting of I, V, KW, KWH, KVA, KVAH, KVARH, PF, HZ & MDI with RS 485 port (h) Over and Under voltage relay (i) Timer and TNC switch Outgoing - 3 Nos. - 630A VCB breakers with followings in each breaker - Note - Provide all type of Protection, Auxillary relays, release for the transformer protection as the outgoing feeders shall feeds the power to transformer. There is a provision in out going VCB that should be "trip off" after REF relay activated in downstream panel after transformer. (a) 3 nos. dual core dual ratio CTs of ratio 50/5/5A of 15 VA burden and accuracy class-1 for protection. (b) (0-50A) Ammeters, dual scale digital type & selector switches for ammeters. (c) Microprocessor based numerical relay with IDMT & instantaneous element for O/L, E/F and S/C protection. (The relay having AUTO DOUBLING feature to prevent nuisance triping during Inrush current cycle of Transformer) (d) 12 window Annunciation panel with necessary relays, audio and visual indicators and push buttons. (e) Auxilliary relay for Buchholtz / OTI / WTI / MOG / OLTC surge with alarm & trip (f) TNC switch g) Master trip relay (h) Trip circuit supervision relay (i) Energy analyser (digital type) consisting of I, V, KW, KWH, KVA, KVAH, KVARH, PF, HZ & MDI with RS485 port. HT Panel - 04 as described above metering and class 5P10 for protection.
109SUB HEAD MAIN LT Pannel Design, manufacture, supply ,installation, inspection, handling, assembling, affecting proper connections, testing and commissioning of Main L.T. Panel (with 275GSM GI/CRCA) PLC based load manager, floor mounting, dust & vermin proof, front operated construction, enclosure class - IP54/42. The bubsbar shall be of aluminium. The panel should be double door design for safety of operator.The panel has to a bolted design and no welding shall be allowed.The main parts like Upright (Frame) 9 fold design,Busbar Support & Corner pieces 3 way of panel should be supplied by OEM to system integrator and copy of inoices(without price) to be submit by System integrator during drawing approval & inspection for authenticity purpose. No changes in the IEC or models/makes of panels as specified in this particular BOQ itself shall not be allowed to ensure high quality of products for hospital and this BOQ shall supercedes all previous corrigendum/amedmend/SLD issued/List of makes for any make/model/rating during tendering. The main LT panel shall be as per IEC61439 (TTA). Make : System Integrator of ABB(ArTu k), Schneider(Okken) Siemens(Sivakon) / L&T (Terra) Authorized certificate and agreement copy with OEM to be submit while drawing approvals through contractor. Tender based authorization or any other certifications shall not be valid.Further,Only OEM"s system integrator for TTA panels as per IEC61439 (Models as specified above)shall only be allowed to manufacturer & supply Non TTA panels also like HVAC, Sub Panels, AHU Panels,Control Panel,Fire Fighting Panel to maintain the high quality vendor for complete LT Panels.No other manufacturer shall supply NON TTA panels even if it is specified in make list and this BOQ shall supercedes all previous corrigendum/ amedmend/SLD/List of makes issued. All ACB"s shall have inbuilt microprocesor based Over load protection (L), Short Circuit protection (S), Instantaneous Short Circuit protection (I), Earth Fault protection (G), Shunt Trip releases. All ACB should have Ics=Icu=Icw=50 KA for 1 sec.All ACB shall be supplied with all standard accessories i.e. auxillary switch with 4NO + 4NC contacts, cradle, handle, safety shutter in confirmity with IS:60947. All ACB Incomer shall be 4P,EDO,LSIG ,with display and communication module for real data assessment like events,fault and all current parameters All MCCB above 250A, shall be microprocessor based with inbuilt OL,SC,EF protections.MCCB 250A & below shall be thermal based OL,SC All MCCB"s shall be Ics = 100% Icu, with rotary handle, phase barriers, spreader terminals & pad locking arrangement, with per load requirement. All TP MCCB shall be with heavy duty solid isolable neutral link. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmeter, selector switches, cast resin type CT"s & PT"s, etc. Separate CT"s shall be provided for protective and measuring system and for APFCR of capacitor bank with suitable VA Each section of Panel shall have door opearted light of sufficent lux to illumunate that section & each section of capacitor, buscoupler, all ACBs sections shall have exhaust fans for ventilation purpose. Each section of panel shall be provided with space heater alonwiththermostate and suitable arrangment for automatic operation. All Energy Analyser / TVM Shall have RS 485 Modbus RTU on board Communication protocolfor SCADA communication. The fault withstanding capacity of panel & its control gear shall be min. 35 KA rms for 1 sec The maximum height of the panel should not exceed 2100 mm unless specifically approved. GA drawings shall be got approved from Consultants before fabrication.The panel has to be specifically fabricated as per the space available at basement level. The existing column positions will also be considered.ACB Make and model :- ABB E-max, Schneider (NW), Siemens 3WL (ETU 76B), L & T U POWER MCCB Make and model :- ABB - T-max, Schneider NSX, Siemens - 3VL, L&T - Dsine Dn2 INCOMERS from 2 Nos.630 KVA Transformers 2Nos ACB 1000A 4P EDO OL,SC,EF with display (4 Line display) with 20 trip history and 60 events and release should be compatible with bluetooth for extracting data wirelessly andcommunication module for real data assessment like events,fault and all current parameters ACB and Release Make / model :- ABB E-max (PR122), Schneider NW 6E, Siemens 3WL (ETU 76B) (ETU45B) , L & T U-POWER The ACB shall be electrically and mechanically interlocked with the bus coupler, DG incomersand other transformer incomers. 2 nos. 250 KVAR capacitor bank with 400 amp TP MCCB (50 KA) for each transformer incomer. 1 nos. 32 amp TP MCCB (35 KA) for OLTC (for each transformer incomer) Protection releases / relays, Metering & Accessories for each Transformer incomers Over Voltage / Under Voltage relay / release with timer.Restricted earth fault relay. Master trip relay Trip Circuit Supervison relay. TNC switch. Auto manual selector switch. 1 nos. 0-500 volt range digital type voltmeter with selector switch 1 set of 3 CT"s of ratio 1000/5A, Class 1.0 accuracy 15 VA burden for metering. 1 set of 3 CT"s of ratio 1000/5A, Class 1.0 accuracy 15 VA burden for APFCR 1 set - 415 / v3 / 110 / v3 Class 1.0 accuracy 100 VA burden PT along with primary and secondary fuse. 1 set of 4 CT"s of ratio 1000/1A, Class PS for protection 1 no. 0-1000 Amp range digital type ammeter with selector switch. Energy analyser (digital type) consisting of I, V, KW, KWH, KVA, PF, HZ, MDI (EM 6400 ofConzerve or equi.) with RS 485 communication port for communication / report generation. (or Dual meter) Power factor meter Frequency meter 3 Nos. LED type phase indicating lamps, each lamp shall be with bakup MCB along with hooter, auxillary relay, 2 sets of push buttons. 5 Nos. LED type indicating lamp for indicating the status of feeder - ON / OFF / TRIP / Trip circuit healthy / DC supply healthy. Each lamp shall be with bakup MCB. INCOMERS from 1 Nos 500 KVA D G sets 1 nos ACB 800A 4P EDO OL,SC,EF with display (4 Line display) with 20 trip history and 60 events and release should be compatible with bluetooth for extracting data wirelessly and communication module for real data assessment like events,fault and all current parameters INCOMERS from 1 Nos 250 KVA D G sets 1 nos MCCB 400A 4P OL,SC,EF with display (4 Line display) with 20 trip history and 60 events and release should be compatible with bluetooth for extracting data wirelessly and communication module for real data assessment like events,fault and all current parameters Protection releases / relays, Metering & Accessories for each D G set incomers Over Voltage / Under Voltage relay / release with timer IDMT earth fault relay Master trip relay Trip Circuit Supervison relay. Reverse power relay Main LT Pannel as described above
110AUTOMATIC POWER FACTOR CORRECTION PANEL (CAPACITOR PANNEL) Design, manufacture, supply, installation, inspection, handling, assembling, affecting proper connections, testing and commissioning of 16 SWG CRCA sheet steel fabricated cubical type 250 KVAR A P F C Panel- 01/02/03 consisting of1/ 2/ 5 / 10 / 15 / 20 / 25 / 50 / 60 KVAR capacitor units in tier formation, housed in an integrated cubicle type automatic switching ON and OFF control panel, floor mounting, dust & vermin proof, front operated construction, enclosure class - IP 52, powder coated after proper treatment with 9 tank process with top/bottom removable gland plates, as required, double compression type cable glands, earth bus, hinged and lockable doors to achieve dust and vermin proof complete with all inter connections small wiring by min. 2.5 sq. mm. copper wires, ckt labels etc. The Aluminium Bus Bar shall be of suitable length, 500 volts, 3 phase 50 Hz TPN, electrolytic aluminium as per IS 8623 All MCCB"s shall be Ics = 100% Icu, with rotary handle & pad locking arrangement, with adjustable O/L & S/C trip setting as per load requirement. All TP MCCB shall be with heavy duty solid isolable neutral link. The breaking capacity specified is Ics value. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmeter, selector switches, CT"s, PT"s, etc. AC3 duty contactors should be used for switching individual capacitor banks. The fault withstanding capacity of panel & its control gear shall be min. 35 KA rms for 1 sec. Each section of capacitor panel shall have Verticle hood & exhaust fans for ventilation purpose. The maximum height of the panel should not exceed 2100 mm unless specifically approved. INCOMING Incomer circuit breaker has been included in the main panel. 1 set- 3 CTs , ratio 250/5A Class 1.0 accuracy 15 VA burden for metering. 1Nos- (0-1000A) digital Ammeter with selector switchMicro processor based automatic power factor control relay (3 phase) (including power factor meter) in 16 steps for automatic cut off or add on capacitor units to keep the power factor at 0.95 with variation of loads. All associated auxiliary contactors / relays shall be provided with in the scope of work. Phase indicating lamps with HRC fuses, and indicating in each capacitor chamber unit to indicate On/Off status of capacitor unit. BUS BARS 320 AMP, 500 Volts, 3 phase 50 HZ TPN high conductivity electrolytic Aluminium bus bar of suitable length, SMC / DMC supports, with colour coding and insulated by heat shrinkable sleeves and clips on shrouds for joints. The current density of bus bar shall be minimum 1.3 sq mm / amp. The Maximum allowable temperature for the Bus bar to be restricted to 85 deg C. The temperature rise should be restricted to 35 deg C above ambientte mperature. OUTGOINGS - 4 nos. of 100 AMPS TPN 35 KA MCCB and 60 amps AC3 duty contactor with 30 KVAR, MPP resin filled, super heavy duty ,480 V capacitor bank, with copper coil 7% detuned filters, auto-manual selector switch, start stop push button for manual operation including on/off indicating lamps and delay timer complete. 5 nos. of 63 AMPS TPN 35 KA MCCB and 63 amps AC3 duty contactor with 20 KVAR, MPP resin filled, super heavy duty ,480 V capacitor bank, with copper coil 7% detuned filters, auto-manual selector switch, start stop push button for manual operation including on/off indicating lamps and delay timer complete. 3 nos. of 40 AMPS TPN 35 KA MCCB and 40 amps AC3 duty contactor with 10 KVAR, MPP resin filled, super heavy duty ,480 V capacitor bank, with copper coil 7% detuned filters, auto-manual selector switch, start stop push button for manual operation including on/off indicating lamps and delay timer complete.
111SECTION - H : D.G. SETS Supply, testing and Commissioning of Silent type Diesel Generating Set at 0.8 PF, 415 Volts, 50 cycles per second, 1500 rpm, 3 phase, suitable for parallel operation, 0.85 load factor, sound proof acoustic and weather proof enclosure, residential type silencer (as per CPCB norms-2) fabricated out of CRCA sheet of 14 / 16 SWG thickness with 9 tank pretreated before powder coating with ventillation system complete in all respects comprising of the following. Diesel Engine suitable for driving alternator of above rating, compression ignition, 4 stroke cycle, Radiator cooled, turbo charged, battery starting, 1500 RPM, suitable for above output of alternator at 40o C, 50% RH & at 210 M MSL and confirming to BS 5514, BS 649, IS 10000, capable of taking 10% overloading for one hour after 12 hrs of prime continuous loading, complete with all the accessories i.e. tachometer with hour meter, flexible coupling with guard, crank case of steel, crank shaft, conncting rods, electronic governing system, dynamically balanced flywheel, air intake manifold, Air cleaner, anti vibration pads, starter motor, including all other accessories required to complete the system. Instrument Panel - Engine mounted Instrument Panel fitted with and having digital display for followings : Start stop switch with key, Water temperature indication, Lubrication oil pressure indication., Lubrication oil temperature indication., Battery charging indication, RPM indication Over speed indication, Low Lube oil trip indication, Engine hours indication, Alternator - Synchronous Alternator of above capacity at 0.8 PF, 3 phase, 415 volts, 50 cycles, 4 wire, 1500 RPM, suitable for operation at 40 deg C, 50% RH & at 210 meter above MSL, capable of taking 10% overlioading for one hour after 12 hrs of prime continuous loading, brushless, self excited, self regulated through AVR, continuous duty confirming to IS 4722, BS 2613 suitable for tropical conditions, class H insulation, including terminal box suitable for bus duct termination as required. Note : - Alternator should have with all other accessories as per specified in Technical specfications. Base Frame - Both the engine and alternator shall be mounted on suitable base frame made of MS channel which shall be installed on cement concrete foundation and vibration isolating arrangement as per recommendations of manufacturer. Power Controller For DG synchronization Microprocessor based Power command controller (P.C.- 3.3 Jakson or equivalent) suitable for auto / manual synchronization & auto load sharing. Daily service Fuel tank of 990 liters capacity fabricated out of 2 mm thick MS sheet complete with inlet and outlet connections, oil indication gauge, drain plug, air breather, provision for fuel transfer system, level indicators and all standard accessories etc. as required. Exhaust Silencer - Exhaust manifold with residential silencer. The D G set should be supplied with required hardware for external PLC based auto synchronization, auto load sharing, auto load management system. Starting system - 24 Volt DC starting system comprising of starter motors : voltage regulator and arrangement for initial excitation complete with 12/24 Volts suitable nos. lead acid type batteries of suitable AH. Ventillation System - Arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air into the atmosphere as per standard specifications. 500 KVA
112Supply of Outdoor Unit 16 HP Heat Pump Type - Three Phase - SIGMA
11320 HP Heat Pump Type - Three Phase - SIGMA
11424 HP Heat Pump Type - Three Phase - SIGMA
115VRF INDOOR UNIT Supply of Indoor units address setting and capacity as mentioned below. multispeed motor, coil section with DX coil, outer cabinet, drain pan mechanism insulation, pipe connections and fresh air intake connector as per Hitachi specifications VRF INDOOR UNIT IN THE CEILING / Ducted : 12.0 HP
116IN THE CEILING / Ducted : 10.0 HP
117IN THE CEILING / Ducted : 8.0 HP
118IN THE CEILING : 3.0 HP - LOW STATIC
119IN THE CEILING : 2.5 HP
120IN THE CEILING : 2.0 HP
121IN THE CEILING : 1.5 HP
122HI WALL 2.5 HP
123HI WALL 1.3 HP
1244 WAY CASSETTE : 6.0 HP
1254 WAY CASSETTE : 5.0 HP
1264 WAY CASSETTE : 4.0 HP
1274 WAY CASSETTE : 3.0 HP
128Drain pump for Conceled Split
129Supply of Multikit Joints-Indoors - Average for all required size of Refnut Joints ( Above Quantities shall vary after Copper Pipe Designe Finalize )
130Supply of Multikit Joints-Outdoors - Average for all required size of Refnut Joints
131Supply of Cordless remotes for HI WALL SPLIT
132Supply of Corded remotes for ( ALL)
133INSTALLATION OF VRF AIR CONDITIONING SYSTEM HP Heat Pump Type (Cooling & Heating ) Vacuumising the system upto 500 micron level which ensures the zero moisture content level in piping which results in better cooling efficiency and long life of system. Pressure testing of System with Nitrogen Gas with 1.5 Times of working pressure of R410A Refrigerant Gas to ensure leakproof system. To flush the system with food grade nitrogen gas to remove carbon contents , dirt particles to make sure that there is no chance of mixing of any impurity with refrigerant gas
134Lifting and shifting & Positioning charges of outdoor unit
135CHOUKI TYPE MS stand for outdoor unit
136INDOOR UNITS 1.VRF HI-WALL
1371 WAY / 2 WAY / 4 WAY CASSETTE
138IN THE CEILING - 12 / 10 / 8 HP
139IN THE CEILING - 1.5/ 2.0 / 2.5 / 3 / 4 / 5 HP
140COMMISSIONING OF SYSTEM Commisssion of VRF System including topping R410A gas per site requirments (R410A Make : Dupont , Honeywell)
141REFRIGERANT PIPING Supply installation testing and commissioning of Interconnecting refrigerant pipe work with (19mm/13 mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per HITACHI STD. & specifications, all piping inside the room shall be properly supported with MS hanger.
142Make:- Mandev, Maxflow or equivalent (Copper Pipe)
143Make:- Superlon, Accoflex, A-Flex or equivalent (Insulation)
144Make:- Harris / mexflow (Brazing Rod) 41.2 mm dia 19 mm thk. Insulation
14538.1 mm dia 19 mm thk. Insulation
14634.9 mm dia 19 mm thk. Insulation
14731.2 mm dia 19 mm thk. Insulation
14828.6 mm día 19 mm thk. Insulation
14925.4 mm día 19 mm thk. Insulation
15022.2 mm dia 19 mm thk. Insulation
15119.04 mm dia 19 mm thk. Insulation
15215.9 mm dia 19 mm thk. Insulation
15312.7 mm dia 13 mm thk. Insulation
1549.5 mm dia 13 mm thk. Insulation
1556.4 mm dia 13 mm thk. Insulation
156DRAIN PIPING Providing and fixing rigid PVC piping complete with fittings, supports as per HITACHI STD.& specifications. - In Client Scope Make:- Supreme, Kissan ,Astral, or equivalent a)25 mm dia
15732 mm dia
15840 mm dia
159Drain Hose Connector - if required
160CONTROL CABLING supply & fixing of control cum transmission wiring (Sheilded) of Copper conductor cable alongwith conduite for looping between indoor & outdoor VRF system & to main Central remote controller system Make:- Polycab or equivalent 2 C X 0.75Sq. mm
161SHEET METAL WORK Fabrication, supply, installation, testing & commissioning of following gauges complete with, supports and turning vanes Make:- Sail , Jindal , or equivalent a) Uninsulted GI Ducting 24 G (0.63 mm)
162Uninsulted GI Ducting 22 G (0.80 mm)
163Canvas connection - Double Layer
164THERMAL INSULATION WORK Supply, installation & testing of Thermal duct Insulation. Make:- Kflex, Accoflex, A-Flex , Supreme or equivalentSupply & Installation of thermal insulation over the duct with XLPE sheet for the ducts with 9 mm thick Sqmt one laver externally on the duct.
165ACOUSTIC LINING (DUCTS) WORK Supply, installation & testing of acoustic lining with fiber glass wool. Make:- UP Twiga, or equivalent Supply & Installation of acoustic lining of duct with 12.5 mm thick fiber glass covered with tissue paper, GI screws and washers. 25 mm thick with 24 kg density
166GRILLES AND DIFFUSERS SUPPLY & RETURN AIR GRILLE Supply, installation, testing and balancing of powder coated Extruded Aluminum supply & return air Grilles / Diffuser with approved shop drawings and specifications.
167Supply & Installation of MS Painted Supply Air VCD Coller dampers.
168Minor Civil Work/ Wall cutting / Breaking of wall-
169Lift Make-Otias, Schindler (Details & Specification Attached in Tender Document)