Road And Building Department-RBD has published Tender For Supply, Installation, Testing And Commissioning Of Medical Gas Pipe Line System For 23 Beded Icu And 12 Beded Step Down Icu At 4Th Floor At Eye Building (Dedicated Covid Hospital-I), Scbmc And H, Cuttack. Submission Date for this Tender is 13-02-2023. Medical Gas System Tenders in cuttack Odisha. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | SITC of Oxygen System Oxygen manifold 10+10 with tail pile & NRV :- 10x10 oxygen cylinder : Oxygen manifold should be suitable to with stand a pressure of 145kg/cm2 |
2 | Oxygen manifold 3+3 emergency with Regulator:- - To comply with relevant standards. -3x3x7M3 oxygen cylinder manual with good quality preset regulator |
3 | Oxygen fully Automatic control Panel:- - Oxygen cylinder : Oxygen manifold should be suitable to with stand a pressure of 145kg/cm2 |
4 | Oxygen gas Outlet point |
5 | Oxygen flow meter with Humdi Fire bottle:- - Back pressure compensated flow meter is of accurate gas flow measurement with folllowing features. - Control with in a range of 0-15 LPM (Calibration within +/- 10%) |
6 | Oxygen Adopter:- - Pressure line adopter pins etc to be supplied in adequate numbers. |
7 | SITC of Vaccum system Reciprocating Vaccum Pump :- - Cap : 10 HP, KW-7.5kw, CFM-152.6 CFM, LPM-4320 |
8 | Vaccume receiver (Cap : 1000ltr) - Vaccum receiver"s 1x1000 (Total 1000 Ltrs.) Capacity vertical Vaccum receiver |
9 | Pressure filter |
10 | Vaccume gas outlet point |
11 | Vaccume Adopter:- - Pressure line adopter pins etc to be supplied in adequate numbers. |
12 | Ward Vaccume regulator with 600ml Jar:- - Ward vacume unit shall be up light weight and compact. - The unit should consist of a regulator. |
13 | SITC of Compressed Air system Oil free Reciprocating Air Compressure - Cap:15 HP, CFM- 57.2 CFM, LPM-1620 LPM |
14 | Air Receiver (Cap- 1000 Ltrs) - The receiver assembly are be fitted with a pressure safety valve. |
15 | Air Pressure filter |
16 | Air gas outlet point |
17 | Air Adopter:- Pressure line adopter pins etc to be supplied in adequate numbers. |
18 | Desicant Air Dryer (Cap: 60CFM):- - CFM - 60 CFM, Dryer type-Regenerative Dessicant Dryer, Design Pressure-13.2 Barg, Maximum air inlet temperature-65 degree C., Maximum Pressure-25 Bar, Pressure dew point- 40 degree C. |
19 | Air Pressure regulator |
20 | SITC of Distribution Medical Grade Copper pipe, EN : 13348 - All copper pipe fittings used be made of Phosphorous de-oxidized, non arsenical copper having international standard/ ISI marked flow meter of Specified size. - The chemical composition of tubes confirm to BS6017 : 1981 and manufactured as per EN: 13348 Copper pipe 28mm x 0.9 OD |
21 | Copper pipe 42mm x 1.2 OD |
22 | Copper pipe 12mm x 0.7 OD |
23 | Copper pipe 15mm x 0.9 OD |
24 | Copper pipe 22mm x 0.9 OD |
25 | Supply & Fixing of Isolation Ball Valve - - Full bore valves for minimum pressure loss. - Non lubricated with 90 degree turn ball valve with PTFE seals.Isolation ball Valve 12mm |
26 | Isolation ball Valve 15mm |
27 | Isolation ball Valve 22mm |
28 | Isolation ball Valve 28mm |
29 | Isolation ball Valve 42mm |
30 | Supply & fixing of Isolation Ball Valve with Brass adopter andValve Box. - Powder coated signal box with lockable door. The doors are fitted with transparent breakable glass. Each Gas line had fitted with respective pressure gauges. Valve Box 3 Gas |
31 | SITC of Area Alram system:- - Indivisual Gas status LED indicator- Showing NORMAL, HIGH & LOW conditions for each service. - Audio Alarm indicator by Piez Electric buzzer. - Working pressure display via digital gauges/ Analouge type. - Aesthetic design and powder coated Alluminium construction. |