Project Description
Repair / Maintenance Of Internal Electrification, Ceiling Fan, Acs, Water Heaters Etc At Cgra Naliya And Icgs Jakhau Under Age ( I ) ( Cg ) Jakhau
BOQ
| Sl. No. | Item Description |
| 1 | Taking down carefully copper point wiring (light, fan, socket or power, bell complete fitting such as sockets, ceiling roses, pendants, batten holders, regulators and making good the disturbed surfaces of wall, floors, ceiling etc complete all as specified and directed by Engineer - in -Charge. |
| 2 | M&L for point wiring with 1.5 Sqmm, PVC insulated, unsheathed, stranded copper conductor single core FRLS cable, IS-694 marked, drawn through and including PVC casing caping complete with all PVC casing caping accessories and flexible conduit etc./ fittings ISI marked and sunk type pressed steel terminal switch box 1.6mm thick with bakelite laminated sheet top cover 3mm thick, brass screws and cup washers including 1.5 Sqmm stranded copper conductor PVC insulated green in colour as continous earth conductor connected to common earth and earth dolly with all accessories complete all as specified and directed for One light point controlled by one switch |
| 3 | All as per item No 2.00 above,but for One ceiling fan point controlled by one switch through regulator |
| 4 | All as per item No 2.00 above,but for One Exhaust fan point controlled by one switch. |
| 5 | All as per item No 2.00 above,but for One 3 pin socket out let 5 Amp on independent board |
| 6 | All as per item No 2.00 above,but for One 3 pin socket out let 5 Amp on same board |
| 7 | All as per item No 2.00 above,but for 2.5 sqmm single core cable for one 3 pin socket outlet 15 Amps on independent switch board including 2.50 Sqmm single core cable as earth continuity conductor and connected to common earth dolly. |
| 8 | S&F switch piano type, flush button single pole, one way 5 Amps, complete all as specified and directed. |
| 9 | S&F switch piano flush type 15 amps, single pole one way 240 volts complete all as specified and directed. |
| 10 | S&F socket outlet 5 Amps, 3 Pin, flush type, complete all as specified and directed. |
| 11 | S&F socket out let 2 in 1,multipurpose 3 pin 15/16 Amp flush type complete all, as specified & directed. |
| 12 | M & L for ceiling rose surface bakelite 3 terminals 63.5 x 17 mm. |
| 13 | S&F stepped type (switch type) electronic ceiling fan regulator flush type,AC, 230 volts , complete all as specified and directed. |
| 14 | S&F in repairsLED batten integratedchannel20 watt with eye soft technology& glarefree diffuser , 50 Hz , 6500K , lumen efficiency greater than 100lm/watt , energy efficient driver, wall mounted complete including connection with flexiblecable copper conductorthree coreof size 23/.2 mm upto ceiling rose/connector and making good of existing wall surface complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- COMFY VIZON, Code- LHEXRP7SN1W020 or equivalent in Bajaj / Halonix |
| 15 | S&F LED batten integratedchannel20 watt with eye soft technology& glarefree diffuser , 50 Hz , 6500K , lumen efficiency greater than 100lm/watt , energy efficient driver, wall mounted complete including connection with flexiblecable copper conductorthree coreof size 23/.2 mm upto ceiling rose/connector and making good of existing wall surface complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- COMFY VIZON, Code- LHEXRP7SN1W020 or equivalent in Bajaj / Halonix |
| 16 | S&F in repairs decorative ultra slim square profile LED light 10 watt, energy efficient , efficiency greater than 100lm/watt , 6500K,, polycarbonate extruded body, including connection with flexible cable copper conductorthree coreof size 23/.2 mm upto ceiling rose/connector and making good of existing wall surface complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- E-LITE PRIDE PLUS NEO, Code- LHEXACP7IN1W010 or equivalent in Bajaj/Halonix |
| 17 | S&F decorative ultra slim square profile LED light 10 watt, energy efficient , efficiency greater than 100lm/watt , 6500K,, polycarbonate extruded body, including connection with flexible cable copper conductorthree coreof size 23/.2 mm upto ceiling rose/connector and making good of existing wall surface complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- E-LITE PRIDE PLUS NEO, Code- LHEXACP7IN1W010 or equivalent in Bajaj/Halonix |
| 18 | S&F in repairs decorative ultra slim square profile LED light 5 watt , energy efficient , efficiency is greate than 100lm/watt , 6500K,, polycarbonate extruded body, including connection with flexiblecable copper conductorthree coreof size 23/.2 mm upto ceiling rose/connector and making good of existing wall surface complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- E-LITE PRIDE PLUS NEO, Code- LHEXBTP7IN1W005 or equivalent in Bajaj/Halonix |
| 19 | S&F decorative ultra slim square profile LED light 5 watt , energy efficient , efficiency is greate than 100lm/watt , 6500K,, polycarbonate extruded body, including connection with flexiblecable copper conductorthree coreof size 23/.2 mm upto ceiling rose/connector and making good of existing wall surface complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- E-LITE PRIDE PLUS NEO, Code- LHEXBTP7IN1W005 or equivalent in Bajaj/Halonix |
| 20 | S&F in repairs switch piano type, flush button single pole, one way 5 Amps,complete all as specified and directed. |
| 21 | S&F in repairs switch piano flush type 15 amps, single pole one way 240 volts complete all as specified and directed. |
| 22 | S&F in repairs bellpush 5 Amp complete all as specified and directed |
| 23 | S&F in repairs socket outlet 5 Amps, 5 Pin, flush type, complete all as specified and directed. |
| 24 | S&F in repairs socket out let 2 in 1, multipurpose 3 pin 5amp and 15 amp flush type complete all, as specified & directed. |
| 25 | S&F in repairs ceiling rose surface bakelite 3 terminals 63.5 x 17 mm. |
| 26 | S&F in repairs door bell ding dong type electric 230 volts AC , single phase, complete all as specified and directed. |
| 27 | S&F in repairs flush type switch socket outlet combination2 in 1, multipurpose 5 pin 5 / 15 Amps complete all as specified and directed. |
| 28 | S&F in repairs switch socket combination 2 in 1, 5 pin 5 Amp ,flush type, multipurpose all as specfied and directed |
| 29 | S&F in repairs stepped type (switch type) electronic ceiling fan regulator flush type,AC, 230 volts , complete all as specified and directed. |
| 30 | S&F in repairs lamp holder PVC / polycarbonate type with back plate complete all as specified and directed. |
| 31 | S&F in repairs Modular switch 1 way 6A, 1 module |
| 32 | S&F in repairs Modular switch 1 way 16A, 1 module |
| 33 | S&F in repairs Modular switch 2 way 6A, 1 module |
| 34 | S&F in repairs Modular bell push, 6A, 1 module |
| 35 | S&F in repairs Modular Socket 6A - 2/3 pin combined 2 module |
| 36 | S&F in repairs Modular Socket 6A/16A - 2/3 pin combined 2 module |
| 37 | S&F in repairs Fan step regulator, 120W - 2 module |
| 38 | S&F in repairs modular white cover plate with frame3 module |
| 39 | S&F in repairs modular white cover plate with frame6 module |
| 40 | S & F in repairs recess mounted decorative ultra slim square profile LED light 15 watt , energy efficient , efficiency is greate than 100lm/watt , 6500K,, polycarbonate extruded body, including connection with flexiblecable copper conductorthree coreof size 23/.2 mm upto ceiling rose/connector and making good of existing wall surface complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- TRIM PLUS , Code- LHEBGAP7IZ1W015 or equivalent in Bajaj/Halonix |
| 41 | S & F in repairs recess mounted decorative ultra slim square profile LED light 18 watt , energy efficient , efficiency is greate than 100lm/watt , 6500K,, polycarbonate extruded body, including connection with flexiblecable copper conductorthree coreof size 23/.2 mm upto ceiling rose/connector and making good of existing wall surface complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- Model- TRIM PLUS , Code- LHEBGAP7IZ1W018 or equivalent in Bajaj/Halonix |
| 42 | S & F in repairs LED ceiling light fitting driver suitable for 15 to 18 watt LED panel of exisiting make and model complete all as specified and as directed. |
| 43 | S & F in repairs building security light fitting 20 watt, robust heat sink along with IP 66, IK07 , Surge protections,230 volt 50 Hz AC , inclconnecting with three core flexible copper wire of size 23/0.0076 complete all as specified and directed by Engineer - in -Charge. Make- Havells, Model- SUPERB STREET LIGHT, Code- LHEXAYP7PN6K020 or equivalent in Bajaj/Halonix |
| 44 | S&F in replacement sub main wiring with two run of 4sqmm single core, PVC insulated, unsheathed multistranded copper FRLS cable 1100 volts conductor drawn through PVC casing caping/ Surface Rigid PVC Conduit with all accessories and 4 sqmm PVC insulated unsheathed multistranded copper conductor FRLS cable as earth continuity wire complete all as specified and directed.Note:Two runs of main cable, one run of earth wire and one run of casing / caping will be measured as one unit for payment. |
| 45 | S&F in replacement sub main wiring with two run of 6 sqmm single core, PVC insulated unsheathed multistranded copper FRLS cable 1100 volts conductor drawn through existing Surface/concealed Conduit and 6 sqmm PVC insulated unsheathed multistranded copper conductor FRLS cable as earth continuity wirecomplete all as specified and directed.Note: Two run of PVC cable with one run of PVC earth wire shall be measured and paid as one length only. |
| 46 | S & F in repairs sheet metal enclosure for double door DB made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted SP & N, 8 ways, 240 Volts, ISI marked, 200 amps bus bar stove enamelled dust and vermin proof suitable for incorporation MCBs and isolators etc complete all as specified and directed by Engineer - in -Charge.Make - Schneider / Legrand / L&T |
| 47 | S & F in repairs sheet metal enclosure for double door DB made out of CRCA mild steel sheet surface with insulated material like polyester with epoxy powder coated surface mounted SP & N 12 ways, 240 Volts, ISI marked, 200 amps bus bar stove enameled dust and vermin proof suitable for incorporation MCBs and isolators etc complete all as specified and directed by Engineer - in -Charge.Make - Schneider / Legrand / L&T |
| 48 | S&F in repairs MCCB 4 pole 63 Amps with breaking capcity 16kA ,Fixed type 415 volts AC Supply complete all as specified and directed by Engineer - in - Charge. Make - Schneider / Legrand / L&T |
| 49 | S&F in repairs the following MCBs , \"C\" curve type & 10 KA breaking capacity, at locations as directed. Make - Schneider / Legrand / L&T |
| 50 | TPN 40 Amps |
| 51 | TPN 63 Amps |
| 52 | SPN 32 Amps |
| 53 | SPN 63 Amps |
| 54 | SP 5-32 Amps |
| 55 | S & F in repairsSingle pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 amp, 240V complete as specified and directed |
| 56 | M & L for earthing complete with copper plate 60×60cm ×3.15mm thick electrodeburried directly in ground vertically to a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level connected to and including and 20×3mm copper strip as earth lead by means of bolts,nuts, check nuts and washer etc and connected to earthing test point all as shown in electrical plate No.3 of SSR Part I and as specified or indicated and testing on completion including excavation/earth work in any type of strata, PCC (1:3:6) type C1 earthing chamber, precast RCC slab 50 mm thick in reinforced cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric , cast iron frame, funnel with wire mesh, 20 mm bore medium grade GI watering pipe, 40 mm bore medium grade GI protection pipe, test point etc. including dismantling old unsv earthing complete all as specified and directed.Note : - Theunitrate quoted shalldeemed to have included for GIprotection pipe, copperearth stripup to 7.5mtr, GI waterpipe, wiremesh , funnel , excavation and earthwork, RCC pitcover complete. |
| 57 | Dismantling of complete Ceiling fan 1200/1400 mm sweep (i.e.,) down rod with its Canopies, Shackle, Capacitor holding clamp , split pins, unscrewing the body parts of Ceiling fan, taking out stater, burnt winding, ball bearing, gun metal bush etc. complete to carry out the following repairs:- (a) Removing of burnt out fan winding and rewinding of stater with suitable size of Copper enamelled wire, varnishing heating as per manufactures design and directed.(b) Re-assembling complete Ceiling fan by fixing only serviceable of old/new spare parts (i.e.,) shackle assembly , capacitor holding clamp, capacitor , gun metal bushes, ball bearing, three core flexible Copper cable, down rod and Canopies & split pins complete all as specified and directed to give designed air delivery including greasing, oiling etc all as directed. |
| 58 | All as per Item No. 52.00above but for exhaust fan of size up to 300 mm sweep. |
| 59 | All as per Item No. 52 above but for wall mounted fan of 450 mm sweep.Note: for Item No. 52 to 54:(a) Supply only spare parts found unserviceable / defective will be measured and paid separately under relevant item of BoQ. |
| 60 | Supply only against Item Ser No. 52 to 54 here-in-before the followingspare parts :- |
| 61 | (i) Capacitor for fan 2.5 mfd capacity |
| 62 | (ii) Ball bearing sealed at both ends of size6201ZZ /6202ZZ for ceiling fan . Make- NBC/SKF |
| 63 | (iii) Shackle assembly complete with rubber reel, brackets, 3 x nuts & bolts with cotter pin suitable for fixingceiling fan of any type, sweep and make complete all as specified and directed. |
| 64 | M&L for servicing of Split AC 1.5 TR / 2.0 TR complete indoor/outdoor type units by means of adding, cleaning solution (HCL) or equivalent solution with water. The cleaning of the condenser with use of nylon brushers, cleaning of filter including replacement of insulation of existing copper tubing inlet-outlet, complete all as specified and as directed. |
| 65 | Taking down thefollowing existing worn out spares of Split type Air conditioners 1.5 Ton / 2.0 Ton capacity, supply and fix in repair new spares of existing make and model all as specified and as directed:- |
| 66 | (i) Blower Motor Indoor Type |
| 67 | (ii) Fan Motor Out door Type without blades |
| 68 | (iii) Fan Blade for outdoor unit |
| 69 | (iv) Starting Capacitor 35 to 45 MFD |
| 70 | (v) Running Capacitor 50 to 60 MFD |
| 71 | (vi) Air filter for Indoor Unit |
| 72 | S&F in repairs display for Indoor unit for existing makes of AC: LG/ Voltas/ Videocon |
| 73 | S&F in repairs Remote control (Hand set only) with Battery for existing Makes of AC: LG/ Voltas/ carrier |
| 74 | S&F in repairs Universal PCB Timer electronic switch with sensor suitable for all makes of split 1.5 / 2 Ton AC complete with hand setincluding taking down unserviceable Electronic PCB from existing unit all as directed. |
| 75 | M&L for replacement taking out old unserviceable compressor of Split type AC 1.5 ton capacity and supply & fix new compressor sealed unit as per existing type in position, charging of refrigerant gas R-22 of required quantity, brazing of discharge and suction line and leak testing complete all as specified and as directed. |
| 76 | All as per item No 61.00 above but for Split Type AC 2 Ton capacity |
| 77 | M&L for Topping up / Gas charging with refrigerant gas (R-22/32) for Air conditioner window type / split type of capacity 1.5 / 2 Ton after vacuuming &leak testing including brazing suction/discharge line and testing complete all as specified and as directed. |
| 78 | M&L for servicing of package type AC 5.5 TR complete indoor/outdoor type unitsmeans of adding, cleaning solution (HCL) or equivalent solution with water. The cleaning of the condenser with use of nylon brushers, cleaning of filter including replacement of insulation of existing copper tubing inlet-outlet complete all as specified and as directed. |
| 79 | M&L for Topping up / Gas charging with refrigerant gas 407C for package typeAir conditioner of capacity 5.5 Ton after vacuuming &leak testing including brazing suction/discharge line and testing complete all as specified and as directed. |
| 80 | S&F in repairs copper tubing suction and liquid line both from Indoor to out door unit suitable for Split A/C 1.5 TR / 2 TRincluding insulation on copper tubing complete all as specified and as directed. |
| 81 | S&F in repairs condenser coil made up of copper for split AC 1.5 TR complete all as specified and as directed. |
| 82 | S&F in repairs condenser coil made up of copper for split AC 2.0 TR complete all as specified and as directed. |
| 83 | M&L for Topping up / Gas charging with refrigerant gas 134a/600a for refrigerator of capacity 230/215 Ltr after vacuuming &leak testing including brazing suction/discharge line and testing complete all as specified and as directed. |
| 84 | Taking out the unserviceable compressor from refrigerator of capacity 215/230 ltrs of any make/model,AC 230 volts single phase and supply and fixing same model /capacity sealed new compressor obtained from the factory out let/authorised dealer alongwith test certificate and with two year guarantee card, including soldering of copper pipe, replacement of copper filter single capillary, replacement offoundation rubber pads, nut and bolts and testing on full load complete all as specified and as directed by Engineer-in-Charge.Note :- Gas charging and gas shall be paid and measured separately under relevant item of this BoQ. |
| 85 | S&F in repairs Freezer chest (made out of aluminium) complete with cooling coil suitable for 215/230 Ltrs capacity refrigerator of any make/model including soldering of copper pipe, replacement ofnut and bolts complete all as specified and as directed by Engineer-in-Charge.Note :- Gas charging and gas shall be paid and measured separately under relevant item of this BoQ. |
| 86 | S&F in repairs overload protector suitable for refrigerator of any make/model and capacity upto 230/215 Ltrsincluding making necessary connections and testing complete all as specified and directed by Engineer - in- Charge. |
| 87 | S&F in repairs thermostat switch with knob, plate and screws for automatic defrosting device suitable for refrigerator of any make/model and capacity upto 230/215 Ltrs complete all as directed by Engineer - in - Charge. |
| 88 | S&F in repairs Temp control knob with defrost push button suitable for refrigerator of any make/model and capacity upto 230/215 Ltrs complete all as directed by Engineer - in - Charge. |
| 89 | S&F in repairs Pigmy lamp screw type/pin type, 15 watt, 240 volts AC supply suitable for any type of refrigerator complete all as directed by Engineer-in-charge. |
| 90 | S&F in repairs Starting Relay assembly suitable for refrigerator of any make/model and capacity upto 230/215 Ltrs complete all as directed by Engineer-in-charge. |
| 91 | Taking out the unserviceable compressor from water cooler of storage capacity 40/80 litres of any make/model,AC 230 volts single phase and supply and fixing same model /capacity sealed new compressor obtained from the factory out let/authorised dealer alongwith test certificate and with two year guarantee card, including soldering of copper pipe, replacement ofcopper tubing capillary tube, dryer filter, foundation rubber pads, nut and bolts and testing on full load complete all as specified and as directed by Engineer-in-ChargeNote :- (i) Gas charging and gas shall be paid and measured separately under relevant item of this BOQ . |
| 92 | S&F in repairs Copper Condensing coil unit of water cooler capacity 40/80 litres including erection of the coil in water cooler body and making connection by soldering/brazing/ welding etc. complete all as directed by Engineer-in-charge.Note :- (i) Gas charging and gas shall be paid and measured separately under relevant item of this BOQ . |
| 93 | S&F in repairs fan motor 1/20 HP, copper wound, single phase 240 Volts AC supply, suitablefor water cooler, including mounting ring/washer/nut bolts and making necessary connections complete all as directed by Engineer-in-charge. |
| 94 | S&F in repairs fan blade assembly made of aluminium (metallic) suitable for water cooler of any make/model and capacity complete all as directed by Engineer-in-charge. |
| 95 | S&F in repairs thermostat switch protector suitable for water cooler of any make/model and capacity including making necessary connections and testing complete all as directed by Engineer-in-charge. |
| 96 | S&F in repairs relay with over load protector suitable for water cooler of any make/model and capacity including making necessary connections and testing complete all as specified and directed by Engineer - in- Charge. |
| 97 | S&F in repairs Running capacitor 10 mfd suitable for water cooler of any make/model and capacity including making necessary connections and testing complete all as directed by Engineer-in-charge. |
| 98 | S&F in repairs PVC flexible drain hose pipe 40 mm dia, 2 metre length with adapter and clamping arrangement complete all as directed by Engineer-in-charge. |
| 99 | Taking down electric water heaters (geysers) of capacity 25 Litres storage type, disconnecting of electric and water connections, taking out inner tank from outer cover, removing the thermostat switch, geyser element and geyser assembly, cleaning the inner tank with anti scalant solution including thermostat, geyser assembly and heating element, testing the inner tank for any leakage and rectification by soldering / brazing. Re - assembling the geyser and mounting on the grouted bolts and connecting with electric and water supply system and testing complete all as specified and directed by Engineer-in-Charge. |
| 100 | S&F in repairs stainless steelinner tank for storage type water heater 25 Litres capacity to match the existing model of geysers complete all as specified and directed by Engineer-in-Charge. |
| 101 | S&F in repairs apparatus plate assembly with PVC rubber ring suitable for 25 litres capacity as per existig size and model complete all as specified and directed by Engineer-in-Charge. |
| 102 | S&F in repairs heating element push type, 1500 watt of suitable shape and size, conforming to ISI with rubber washers, with clamps complete all as specified and directed by Engineer-in-Charge. Make : Theeta / Airex / Racold |
| 103 | S&F in repairs heating element cup type/triangle with thermostate hole 2KW conforming to ISI with rubber washers, with clamps complete all as specified and directed by Engineer-in-Charge. Make : Theeta/Airex/ Racold |
| 104 | S&F in repairs brass thermostat switch ISI marked suitable for storage type geysers complete all as specified and directed by Engineer-in-Charge. Make : Airex/Bajaj/Racold |
| 105 | S&F in repairs, PVC connection wire woven 15mm size with nickel plated brass adapter, both sides threaded, length of 450 mm complete all as specified and directed by Engineer-in-Charge. |
| 106 | M&L for taking down solar water heater of capacity 200/100 LPD and servicing it by cleaning & descaling of make up tank, solar tubes using suitable anti scalent chemicaldisconnecting of electric and water connections and re assembling the solar water heater and mounting on the structure , connecting with electric and water supply system and testing complete all as specified and directed by Engineer-in-Charge. |
| 107 | S & F in repairs, heating element with inbuilt thermostat of 4000 Watt, ISI marked for solar water heater as per existing model complete all as specified and directed by Engineer-in-Charge. Make : Theeta/Airex/ Racold |
| 108 | Material and labour in repair for earthing completewith galvanizedearth plateelectrode in 60 cm x 60 cmx6 mm thick buried directly in ground verticallyat a depth not less than 2.25 meterbelowgroundlevel with top edgeof earth plateat depth not lessthan 1.5 mtrbelow ground level connecting to and including galvanised earth lead wire 4.0mmby means of GI bolts, nuts, check nuts and washerlight grade40 mm dia GI protectionpipeandconnected to equipment, GIpipe medium grade20 mmdia forwatering includingfunnel wire mesh, RCCpitcoverand PCC 1;2:4type B-1 including Rocksalt, charcoal, excavationand earth work,disposalof surplussoil shown as plateNo 3 of SSR Part - I2009 and all as specified complete.Note : - Theunitrate quoted shalldeemed to have included for GIprotection pipe, GIearth wire up to 7.5mtr, GI waterpipe, wiremesh , funnel , excavation and earthwork, RCC pitcover complete. |
AI Tender Summary
Tender Timeline
Jan 25, 2023
11:30 IST
Tender Published
Tender notice published.
CompletedFeb 13, 2023
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedFeb 14, 2023
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender