Tender For Repair/ Replacement/ Maintenance External Lt Distribution, Equipment And Allied Works At Mil Stn Kapurthala Under Ge Kapurthala, kapurthala-Punjab

Military Engineer Services-MES has published Tender For Repair/ Replacement/ Maintenance External Lt Distribution, Equipment And Allied Works At Mil Stn Kapurthala Under Ge Kapurthala. Submission Date for this Tender is 16-02-2023. Cushioning Supplies Tenders in kapurthala Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

35825412
Corrigendum : Tender For Repair/ Replacement/ Maintenance External Lt Distribution, Equipment And Allied Works At Mil Stn Kapurthala Under Ge Kapurthala
Open Tender
Indian
Punjab
kapurthala
16-02-2023

Tender Details

Tender For Repair / Replacement / Maintenance External Lt Distribution, Equipment And Allied Works At Mil Stn Kapurthala Under Ge Kapurthala - Taking Down Existing Lt Panel By Disconnecting All Incoming And Outgoing Cables, Earthing Connection, Dismantling Pcc And Making Good The Disturbed Surface Complete All As Specified And Directed By Engr-In-Charge. 2 Supply Fabricating Erecting Lt Panel Outdoortype Cpri Approved Double Door Totally Enclosed Weather And Vermin Proof Suitably Ventilated 415 Volts50 Cycles, Ac Supply Factory Made Fully Compart Mentalized Made Out Of 3.14 Mm Thick Crca Sheet For Laod Bearing And 2.00 Mm Thick For Nonload Bearing Protection Of Enclose Ip 54 As Per Is 2147 Of 1962 With Pretreatment And Powder Coated Of Approved Colour Including Suitable Size Of Abgle Iron / Flat Iron Frame Work / Support Required Civil Works, Excavation & Earth Work, Pcc Foundation Etc, Installation, Testing & Commissioningwith Including The Following :- ( A ) Aluminium Bus Bar Of Capacity 600 Amps For Three Phase Andneutral.-04 NoS ( B ) Combined Voltmeter & Ammeter 0 To 500 Amps Digital Type With Built In Selector Switch Cts Of Suitable Ratio ( Set Of Three ) Incoming : ( I ) Mccb 4P 400 Amps, 36 Ka 415 Volts - 01 NoS Outgoing : ( I ) Mccb 4 Pole 250 Amps 36 Ka 415 Volts - 01 NoS ( Ii ) Mccb 4 Pole 200 Amps 36 Ka, 415 Volts - 01 NoS ( Iii ) Mccb 4 Pole 125 Amps 16 Ka, 415 Volts - 02 NoS 3 Supply Fabricating Erecting Lt Panel Outdoortype Cpri Approved Double Door Totally Enclosed Weather And Vermin Proof Suitably Ventilated 415 Volts50 Cycles, Ac Supply Factory Made Fully Compart Mentalized Made Out Of 3.00 Mm Thick Crca Sheet For Laod Bearing And 2.00 Mm Thick For Nonload Bearing Protection Of Enclose Ip 54 As Per Is 2147 Of 1962 With Pretreatment And Powder Coated Of Approved Colour Including Suitable Size Of Abgle Iron / Flat Iron Frame Work / Support Required Civil Works, Excavation & Earth Work, Pcc Foundation Etc, Installation, Testing & Commissioningwith Including The Following :- ( A ) Aluminium Bus Bar Of Capacity 400 Amps For Three Phase And Neutral. -04 NoS ( B ) Combined Voltmeter & Ammeter 0 To 500 Amps Digital Type With Built In Selector Switch Cts Of Suitable Ratio ( Set Of Three ) Incoming : ( I ) Mccb 4P 250 Amps, 36 Ka 415 Volts ( Thermal Magnatic And Microprocessor Release- 01 No Outgoing : ( I ) Mccb Fp 200 Amps 36 Ka, 415 Volts ( Adjustable Thermal And Magnatic Type70% To 100% ) - 01 No ( Ii ) Mccb Fp 125 Amps 16 Ka 415 Volts ( Adjustable Thermal And Magnatic Type70% To 100% ) - 02 N ( Iii ) Mcb Tpn, 63 Amps, 16 Ka 415 Volts.- 02 NoS ( Ii ) Digital Type Digital Timer Switch Suitable For 3 Phase, 415 Volts Ac Supply For Street Light Feeder Programmable 1 Min, With Backup For 6 Years, 28 Memory Locations, Current Capacity 10 Amps Weekly Program With 1 Changeover ( 1Co ) Total 28 Programs Model No Din, Type Eco Weekly With 1 Co Cat Part No Tda44196. 4 Supply Fabricating Erecting Lt Panel Outdoortype Cpri Approved Double Door Totally Enclosed Weather And Vermin Proof Suitably Ventilated 415 Volts50 Cycles, Ac Supply Factory Made Fully Compart Mentalized Made Out Of 3.14 Mm Thick Crca Sheet For Laod Bearing And 2.00 Mm Thick For Nonload Bearing Protection Of Enclose Ip 54 As Per Is 2147 Of 1962 With Pretreatment And Powder Coated Of Approved Colour Including Suitable Size Of Abgle Iron / Flat Iron Frame Work / Support Required Civil Works, Excavation & Earth Work, Pcc Foundation Etc, Installation, Testing & Commissioningwith Including The Following :- ( A ) Aluminium Bus Bar Of Capacity 250 Amps For Three Phase And Neutral.-04 NoS ( B ) Combined Voltmeter & Ammeter 0 To 500 Amps Digital Type With Built In Selector Switch Cts Of Suitable Ratio ( Set Of Three ) Incoming : ( I ) Mccb Tpn 160 Amps, 36 Ka 415 Volts - 01 NoS Outgoing : ( I ) Mccb 4 Pole 100 Amps 25 Ka 415 Volts - 03 No ( Ii ) Mccb 4 Pole 63 Amps 25 Ka, 415 Volts - 02 NoS 5 M & L For Earthing Complete With Galvanized Iron Or Steel Or Steel Earth Plate Electrode Of Size 60Cmx60cmx6.3Mm Thick Buried Directly In Ground, Vertically To A Depth Not Less Than 2.25 Mtr Below Normal Ground Level With Top Edge Of Earth Plate At Depth Of Not Less Than 1.5 Mtr Below Ground Level Surrounded From All Sides With Alternate Layers Of Charcoal And Common Salt And Connected To Gi Strip Of Size 32X6 Mm By Means Of Gi Bolts, Nuts Washers & Check Nuts Electrode Connected To Main Switch Board Or Main Control Board Or On Poles Or On Transformer And Gi Pipe Light Grade 20 Mm Bore For Watering Including Providing Funnel And Wire Mesh Gi Frame And 10 Cm Thick Suitably Reinforced Rcc Pit Cover Pcc Chamber Pit With Pcc 1:3:6 Type C2 Using 40Mm Graded Stone Aggregates Complete Including Excavation And Earth Work, Disposal Of Surplus Soil To A Distance Not Exceeding 50 Mtr All As Specified And Shown In Plate No 5 Of Srr-1991 Part-1 Complete All As Specified And Directed By Engr-In-Charge. 6 M&L Preparation To Steel Surface Of Existing Lt Panels, Lt Feeder Pillars Boxes Of Any Size And Description Internally And Externally After Scraping And Scratching The Old Paint With Emery Paper Etc, And Painting With Two Coat Of Gray Painting With Spray Gun And Writing Feeder Names And Numbers With Suitable Capital Letters In English With White Paint On And A Black Paint Strip Of Size 20 Cm X 25 Cm Complete All As Specified And Directed By Engr-In-Charge. 7 Material And Labour For Repair To Lt Panels Feeder Pillar Box By Dismantling Old Rusted And Perished Doors Shutter And Bus Bar Covers Etc And Providing New Doors Shutters, Bus Bar Cover Etc By Cutting, Welding, Fabricating And Madeto Existing Shape With 3.15 Mmplain Black Sheet And Angle Iron Of Required Size Including Providing Hinges And Locking Arrangement All As Directed Includingmaterial And Labour For Two Coat Ofpaintingwith Synthetic Enameled Grey Paint Over A Coat Of Red Oxide Primer Complete All As Specified And Directed By Engr-In-Charge. 8 Supply And Fixing In Replacement Mccb, 4 Pole, 3 Phase, 415 Volts, 400 Amps, Repturing Capacity 35 Ka With Overload And Thermal Tripping Features Complete All As Specified And Directed By Engr-In-Charge. Make; Havell’S / Abb / Standard 9 All As Per Item No 8 Here-In-Before But 200 Amps Repuring Capacity 25 Ka Complete All As Specified And Directed By Engr-In-Charge. 10 All As Per Item No 8 Here-In-Before But 250 Amps Repuring Capacity 25 Ka Complete All As Specified And Directed By Engr-In-Charge. 11 All As Per Item No 8 Here-In-Before But Tpn 160 Amps Repuring Capacity 16 Ka Complete All As Specified And Directed By Engr-In-Charge. 12 Supply And Fixing Aluminum Thimbles Crimping Type Of Size 16 To 25 Sq Mm Complete All As Specified And Directed By Engr-In-Charge. 13 Supply And Fixing Aluminum Thimbles Crimping Type Of Size 50 To 120 Sq Mm Complete All As Specified And Directed By Engr-In-Charge. 14 Supply And Fixing Aluminum Thimbles Crimping Type Of Size 150Sq Mm To 240 Sq Mm Complete All As Specified And Directed By Engr-In-Charge. 15 Taking Out Old Defective Underground Cable Fromtrenches / Floors / Road / Wall / Pipe / Pole Lt Cable Of Any Size / Description Including Segregating The Serviceable Cable By Cutting Down Defective Portion After Testing By Meggar And Relaying Complete All As Specified And Directed By Engr-In-Charge. ( Note : Excavation And Earth Work Will Be Measured Separately Under Respective Item ) 16 Supply, Laying, Jointing And Testing Xlpe Pvc Insulated & Pvc Sheathed Lt Cable, 1100 Volts Grade ( Heavy Duty ) With Stranded Aluminium Conductor, Cross Sectional Area 10 Sqmm 2 Core Fixed Along The Poles Or Passing Through Pipes Or Laid Under Floors Or Through Walls Complete All As Specified And Directed By Engr-In-Charge.Note ( I ) Earthwork, Sand Cushioning, Brick Protection And Gi Pipe To Be Measured And Paid For Separately Under Respective Items. 17 All As Per Description Of Serial Item No.16 Here In Before But Cross Sectional Area 16 Sqmm 2 Core Complete All As Specified And Directed By Engr-In-Charge. 18 All As Per Description Of Serial Item No.16 Here In Before But Cross Sectional Area 16 Sqmm 4 Core Complete All As Specified And Directed By Engr-In-Charge. 19 All As Per Description Of Serial Item No.16 Here In Before But Cross Sectional Area 25 Sqmm 3½ Core Complete All As Specified And Directed By Engr-In-Charge. 20 All As Per Description Of Serial Item No.16 Here In Before But Cross Sectional Area 35 Sqmm 3½ Core Complete All As Specified And Directed By Engr-In-Charge. 21 All As Per Description Of Serial Item No.16 Here In Before But Cross Sectional Area 50 Sqmm 3½ Core Complete All As Specified And Directed By Engr-In-Charge. 22 All As Per Description Of Serial Item No. 16 Here In Before But Cross Sectional Area 70 Sqmm 3½ Core Complete All As Specified And Directed By Engr-In-Charge. 23 All As Per Description Of Serial Item No. 16Here In Before But Cross Sectional Area 95 Sqmm 3½ Core Complete All As Specified And Directed By Engr-In-Charge. 24 All As Per Description Of Serial Item No. 16Here In Before But Cross Sectional Area 150 Sqmm 3½ Core Complete All As Specified And Directed By Engr-In-Charge. 25 Excavation In Trenches In Soft / Loose Soil Not Exceeding 1.50 Mtr Wide And Not Exceeding 1.50 Mtr In Depth For Laying Of Cables And Gettingout Including Trimming Of Sides Complete All As Specified And Directed By Engr-In-Charge. 26 Returing, Filling In, Including Spreading, Leveling Watering And Well Ramming Inlayers Not Exceeding 25 Cms Thick Each Layer Complete All As Specified And Directed By Engr-In-Charge. 27 Removal Of Surplus Soil To A Distance Not Exceeding 50 Mtr And Depositing Where Directed At A Level Not Exceeding 1.5 Mtr Above The Starting Point Complete All As Specified And Directed By Engr-In-Charge. 28 Material And Labour For Sand Cushioning With A Layer Of Sand 8Cm Thick Before Laying Of Cable And 15 Cm Thick After Laying Of Cable In Trenches Complete All As Specified And Directed By Engr-In-Charge. 29 Supply & Laying Old Size Sub Class B Bricks Laid Flat In Trenches Over The Cable With The Length Of Brickperpendicular To The Directionof Cable Length, Adjacent / Abutting Each Othercomplete All As Specified And Directed By Engr-In-Charge. ( For Lt Cable ) 30 All As Per Srl Item No 29 Here-In-Before But Usingold Bricks Obtained By Taking Out Cable Complete All As Specified And Directed By Engr-In-Charge. 31 M&L For Straight Through Joint ( Epoxy ) For Lt 1100 Volts Grade, Aluminum Conductor Including Jointing Kits, Aluminium Ferrules And Labour Complete For Making Joints And Testingsize 185 To 240 Sqmm, 3.5 Core Complete All As Specified And Directed By Engr-In-Charge. 32 Cable Size 120 To 150 Sqmm, 3.5 Core Complete All As Specified And Directed By Engr-In-Charge. 33 Cable Size 70 To 95 Sqmm, 3.5 Core Complete All As Specified And Directed By Engr-In-Charge. 34 Cable Size 25 To 50 Sqmm, 3.5 Core Complete All As Specified And Directed By Engr-In-Charge. 35 Cable Size 10 To 16 Sqmm, 4.0 / 2.0 Core Complete All As Specified And Directed By Engr-In-Charge. 36 Supply And Fixing In Replacement For Gi Protection Pipe 50Mm Dia Light Grade For Cable Protection Incl All Fittings Laid In Trenches Or Fixed On Pole Complete All As Specified And Directed By Engr-In-Charge. 37 Supply And Fixing In Replacement For Gi Protection Pipe 80Mm Dia Light Grade For Cable Protection Incl All Fittings Laid In Trenches Or Fixed On Pole Complete All As Specified And Directed By Engr-In-Charge. 38 Cutting The Tree Branches Which Touches The Lt Oh Lines And 2.5 M Away From Centre Line Of Lt Oh Line Span Not Exceeding 60Mts Distance Between Poles By Using Necessory T&P Items And Depositing The Tree Branches / Leaves At 30M Distance Away From The Site Complete All As Specified And Directed By Engr-In-Charge. Note:- Any Number Of Tree Branches Cut In One Span Will Be Measured As One Length For Payment Pupose 39 Dismantling Cross-Arms Of M.S. Channel Or Angle Sections Etc. Complete And Setting At Side For Re-Use With In 50M Complete All As Specified And Directed By Engr-In-Charge. 40 Material And Labour For Mild Steel Cross Arms, Bracing, Supports, Clamps And Back Plates Fabricated From Structural Steel Section Including Nuts, Bolts Washers, Welding, Bending Cold Or Hot , Drilling Holes For Bolts In Any Shape / Size As Directed Including Painting With Two Coats Of Approved Colour Over A Coat Red Oxide Primer Complete All As Specified And Directed By Engr-In-Charge. 41 M&L For Pcc 1:3:6 Type C2 Using 40Mm Graded Stone Aggregate For Fdn Of Poles, Stay Etc Complete All As Specified And Directed By Engr-In-Charge. 42 M&L For Pcc 1:3:6 Type C1 Using 20Mm Graded For Padestal Coping Incl Necessary Formwork Finished Fair Using Extra Cement Complete All As Specified And Directed By Engr-In-Charge. 43 Dismantling Stay Assembly Complete All As Specified And Directed By Engr-In-Charge. ( Demolition Of Concrete, Etc. And Excavation Measured Separately ) 44 Material And Labour For Stay Assembly With Accessories In Replacement As Shown In Electrical Plate No.1 Complete With Diameter Of Rod 20 Mm.Note:- Loop Type Insulator, Stay Clamps, Excavation And Concretewill Be Measured And Paid Separately Complete All As Specified And Directed By Engr-In-Charge. 45 M&L Galvanised Stay Strand Size 7 / 4 Mm Complete All As Specified And Directed By Engr-In-Charge. 46 Dismantling & Taking Down Existing Acsr Conductor Of Any Sizeby Opening The Binding Wire From Ht / Lt Electric Poles Complete All As Specified And Directed By Engr-In-Charge. 47 Supply, Stringing And Fixing On Existing Poles, Acsr Conductor Of Any Type / Size Including Fixing To Insulators With Binding Wire Complete All As Specified And Directed By Engr-In-Charge. Make: Allind, Icc, Bharat Conductor, Vk Conductors, Nicco. 48 Taking Down Insulators Of Any Size & Type. 49 Supply And Fix Pin Type, Porcelain, Vitreous, White Brown Or Green Insulator Including One Galvnised Mild Steel Spindle, Two Nos Galvanised Iron Washer And One Galvnised Iron Nut, 100Mm Height, 65Mm Dia For 1100V Grade Complete All As Specified And Directed By Engr-In-Charge. 50 Supply And Fixshackle, Porcelain, Vitreous, White Brown Or Green Insulator Including Galvnised Mild Steel Straps, Washers, Insulator, Bolts, Washers And Nuts For Size 100Mm Height And 115Mm Dia For Working Pressure 1100 Volts Complete All As Specified And Directed By Engr-In-Charge. 51 Supply And Install In Replacement Of Steel Tubular Swaged Poles Type 410 Sp-31 ( 9 Mtr Long ) Complete With Ci Base Plate And Finial Taper Plug, Bolts, Nuts And Screws Complete All As Specified And Directed By Engr-In-Charge. Note :-Excavation, Earth & Pcc Workonly Will Be Measuredseparetely All Other Accessories And Work Deemed To Be Included In Quoted Rates.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 09-Feb-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 16-02-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 80000.0 /-
Tender Value
INR 40 Lakhs /-

BOQ Items

Name of Work : Repair/replacment /maintenance externalLT distribution, equipment and allied works at Mil Stn Kapurthala under GE Kapurthala
Sl. No. Item Description
1Taking down existing LT panel by disconnecting all incoming and outgoing cables, earthing connection, dismantling PCC and making good the disturbed surface complete all as specified and directed by Engr-in-Charge.
2Supply fabricating erecting LT panel outdoortype CPRI approved double door totally enclosed weather and vermin proof suitably ventilated 415 Volts50 cycles, AC supply factory made fully compart mentalized made out of 3.14 mm thick CRCA sheet for laod bearing and 2.00 mm thick for nonload bearing protection of enclose IP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour including suitable size of abgle iron/flat iron frame work/ support required civil works, excavation & earth work, PCC foundation etc, installation, testing & commissioningwith including the following :-(a) Aluminium bus bar of capacity 600 Amps for three phase andNeutral.-04 No"s (b)Combined Voltmeter & Ammeter 0 to 500 Amps digital type with built in selector switch CTS of suitable ratio (Set of Three) Incoming : (i) MCCB 4P 400 Amps, 36 KA 415 Volts - 01 No"s Outgoing : (i) MCCB 4 pole 250 Amps 36 KA 415 Volts - 01 No"s (ii) MCCB 4 pole 200 Amps 36 KA, 415 Volts - 01 No"s (iii) MCCB 4 pole 125 Amps 16 KA, 415 Volts - 02 No"s
3Supply fabricating erecting LT panel outdoortype CPRI approved double door totally enclosed weather and vermin proof suitably ventilated 415 Volts50 cycles, AC supply factory made fully compart mentalized made out of 3.00 mm thick CRCA sheet for laod bearing and 2.00 mm thick for nonload bearing protection of enclose IP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour including suitable size of abgle iron/flat iron frame work/ support required civil works, excavation & earth work, PCC foundation etc, installation, testing & commissioningwith including the following :-(a) Aluminium bus bar of capacity 400 Amps for Three phase and Neutral. -04 No"s (b) Combined Voltmeter & Ammeter 0 to 500 Amps digital type with built in selector switch CTS of suitable ratio (Set of Three) Incoming : (i) MCCB 4P 250 Amps, 36 KA 415 Volts (Thermal Magnatic and microprocessor release- 01 No Outgoing : (i)MCCB FP 200 Amps 36 KA, 415 Volts (adjustable thermal and magnatic type70% to 100%)- 01 No (ii) MCCB FP 125 Amps 16 KA 415 Volts(adjustable thermal and magnatic type70% to 100%)- 02 N (iii) MCB TPN, 63 Amps, 16 KA 415 Volts.- 02 No"s (ii) Digital type Digital Timer switch suitable for 3 phase, 415 volts AC supply for street light feeder programmable 1 min, with backup for 6 years, 28 memory locations, current capacity 10 Amps weekly program with 1 changeover (1co) total 28 programs Model No DIN, Type ECO weekly with 1 CO cat part No TDA44196.
4Supply fabricating erecting LT panel outdoortype CPRI approved double door totally enclosed weather and vermin proof suitably ventilated 415 Volts50 cycles, AC supply factory made fully compart mentalized made out of 3.14 mm thick CRCA sheet for laod bearing and 2.00 mm thick for nonload bearing protection of enclose IP 54 as per IS 2147 of 1962 with pretreatment and powder coated of approved colour including suitable size of abgle iron/flat iron frame work/ support required civil works, excavation & earth work, PCC foundation etc, installation, testing & commissioningwith including the following :-(a) Aluminium bus bar of capacity 250 Amps for three phase and Neutral.-04 No"s (b)Combined Voltmeter & Ammeter 0 to 500 Amps digital type with built in selector switch CTS of suitable ratio (Set of Three) Incoming : (i) MCCB TPN 160 Amps, 36 KA 415 Volts - 01 No"s Outgoing : (i) MCCB 4 pole 100 Amps 25 KA 415 Volts - 03 No" (ii)MCCB 4 pole 63 Amps 25 KA, 415 Volts - 02 No"s
5M & L for earthing complete with galvanized iron or steel or steel earth plate electrode of size 60cmx60cmx6.3mm thick buried directly in ground, vertically to a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth of not less than 1.5 mtr below ground level surrounded from all sides with alternate layers of charcoal and common salt and connected to GI Strip of size 32x6 mm by means of GI bolts, nuts washers & check nuts electrode connected to main switch board or main control board or on poles or on transformer and GI pipe light grade 20 mm bore for watering including providing funnel and wire mesh GI frame and 10 cm thick suitably reinforced RCC pit cover PCC chamber pit with PCC 1:3:6 type C2 using 40mm graded stone aggregates complete including excavation and earth work, disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown in plate No 5 of SRR-1991 Part-1 complete all as specified and directed by Engr-in-Charge.
6M&L Preparation to steel surface of existing LT panels, LT feeder pillars boxes of any size and description internally and externally after scraping and scratching the old paint with emery paper etc, and painting with two coat of gray painting with spray gun and writing feeder names and numbers with suitable capital letters in English with white paint on and a black paint strip of size 20 cm x 25 cm complete all as specified and directed by Engr-in-Charge.
7Material and labour for repair to LT panels feeder pillar box by dismantling old rusted and perished doors shutter and bus bar covers etc and providing new doors shutters, bus bar cover etc by cutting, welding, fabricating and madeto existing shape with 3.15 mmplain black sheet and angle iron of required size including providing hinges and locking arrangement all as directed includingmaterial and labour for two coat ofpaintingwith synthetic enameled Grey paint over a coat of red oxide primer complete all as specified and directed by Engr-in-Charge.
8Supply and fixing in replacement MCCB, 4 pole, 3 phase, 415 volts, 400 Amps, repturing capacity 35 KA with overload and thermal tripping features complete all as specified and directed by Engr-in-Charge. Make; Havell’s/ABB/Standard
9All as per item No 8 here-in-before but 200 Amps repuring capacity 25 KA complete all as specified and directed by Engr-in-Charge.
10All as per item No 8 here-in-before but 250 Amps repuring capacity 25 KA complete all as specified and directed by Engr-in-Charge.
11All as per item No 8 here-in-before but TPN 160 Amps repuring capacity 16 KA complete all as specified and directed by Engr-in-Charge.
12Supply and fixing aluminum thimbles crimping type of size 16 to 25 Sq mm complete all as specified and directed by Engr-in-Charge.
13Supply and fixing aluminum thimbles crimping type of size 50 to 120 Sq mm complete all as specified and directed by Engr-in-Charge.
14Supply and fixing aluminum thimbles crimping type of size 150Sq mm to 240 Sq mm complete all as specified and directed by Engr-in-Charge.
15Taking out old defective underground cable fromtrenches/ floors/road/wall /pipe/ pole LT cable of any size/ description including segregating the serviceable cable by cutting down defective portion after testing by meggar and relaying complete all as specified and directed by Engr-in-Charge.(Note : Excavation and earth work will be measured separately under respective item)
16Supply, Laying, jointing and testing XLPE PVC insulated & PVC sheathed LT cable, 1100 volts grade (heavy duty )with stranded aluminium conductor, cross sectional area 10 Sqmm 2 core fixed along the poles or passing through pipes or laid under floors or through walls complete all as specified and directed by Engr-in-Charge. Note (i) Earthwork, sand cushioning, brick protection and GI pipe to be measured and paid for separately under respective items.
17All as per description of serial item no.16 here in before but cross sectional area 16 Sqmm 2 core complete all as specified and directed by Engr-in-Charge.
18All as per description of serial item no.16 here in before but cross sectional area 16 Sqmm 4 core complete all as specified and directed by Engr-in-Charge.
19All as per description of serial item no.16 here in before but cross sectional area 25 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
20All as per description of serial item no.16 here in before but cross sectional area 35 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
21All as per description of serial item no.16 here in before but cross sectional area 50 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
22All as per description of serial item no. 16 here in before but cross sectional area 70 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
23All as per description of serial item no. 16here in before but cross sectional area 95 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
24All as per description of serial item no. 16here in before but cross sectional area 150 Sqmm 3½ core complete all as specified and directed by Engr-in-Charge.
25Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for laying of cables and gettingout including trimming of sides complete all as specified and directed by Engr-in-Charge.
26Returing, filling in, including spreading, leveling watering and well ramming inlayers not exceeding 25 cms thick each layer complete all as specified and directed by Engr-in-Charge.
27Removal of surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge.
28Material and labour for sand cushioning with a layer of sand 8cm thick before laying of cable and 15 cm thick after laying of cable in trenches complete all as specified and directed by Engr-in-Charge.
29Supply & laying old size sub class "B" bricks laid flat in trenches over the cable with the length of brickperpendicular to the directionof cable length, adjacent/abutting each othercomplete all as specified and directed by Engr-in-Charge. (for LT Cable )
30All as per srl item No 29 here-in-before but usingold bricks obtained by taking out cable complete all as specified and directed by Engr-in-Charge.
31M&L for straight through joint (epoxy) for LT 1100 Volts grade, aluminum conductor including jointing kits, aluminium ferrules and labour complete for making joints and testingsize 185 to 240 Sqmm, 3.5 core complete all as specified and directed by Engr-in-Charge.
32Cable size 120 to 150 Sqmm, 3.5 core complete all as specified and directed by Engr-in-Charge.
33Cable size 70 to 95 Sqmm, 3.5 core complete all as specified and directed by Engr-in-Charge.
34Cable size 25 to 50 Sqmm, 3.5 core complete all as specified and directed by Engr-in-Charge.
35Cable size 10 to 16 Sqmm, 4.0/2.0 core complete all as specified and directed by Engr-in-Charge.
36Supply and fixing in replacement for GI protection pipe 50mm dia light grade for cable protection incl all fittings laid in trenches or fixed on pole complete all as specified and directed by Engr-in-Charge.
37Supply and fixing in replacement for GI protection pipe 80mm dia light grade for cable protection incl all fittings laid in trenches or fixed on pole complete all as specified and directed by Engr-in-Charge.
38Cutting the tree branches which touches the LT OH lines and 2.5 m away from centre line of LT OH line span not exceeding 60mts distance between poles by using necessory T&P items and depositing the tree branches/leaves at 30m distance away from the site complete all as specified and directed by Engr-in-Charge. Note:- Any number of tree branches cut in one span will be measured as one length for payment pupose
39Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting at side for re-use with in 50m complete all as specified and directed by Engr-in-Charge.
40Material and labour for mild steel cross arms,bracing,supports,clamps and back plates fabricated from structural steel section including nuts,bolts washers,welding,bending cold or hot , drilling holes for bolts in any shape/size as directed including painting with two coats of approved colour over a coat red oxide primer complete all as specified and directed by Engr-in-Charge.
41M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate for fdn of poles, stay etc complete all as specified and directed by Engr-in-Charge.
42M&L for PCC 1:3:6 type C1 using 20mm graded for padestal coping incl necessary formwork finished fair using extra cement complete all as specified and directed by Engr-in-Charge.
43Dismantling stay assembly complete all as specified and directed by Engr-in-Charge. (demolition of concrete, etc. and excavation measured separately)
44Material and labour for stay assembly with accessories in replacement as shown in electrical plate No.1 complete with diameter of rod 20 mm.Note:- loop type insulator, stay clamps, excavation and concretewill be measured and paid separately complete all as specified and directed by Engr-in-Charge.
45M&L galvanised stay strand size 7/4 mm complete all as specified and directed by Engr-in-Charge.
46Dismantling & taking down existing ACSR conductor of any sizeby opening the binding wire from HT/LT electric poles complete all as specified and directed by Engr-in-Charge.
47Supply, stringing and fixing on existing poles, ACSR conductor of any type/ size including fixing to insulators with binding wire complete all as specified and directed by Engr-in-Charge. Make: Allind, ICC, Bharat Conductor,VK conductors,NICCO.
48Taking down insulators of any size & type.
49Supply and fix pin type, porcelain,vitreous,white brown or green insulator including one galvnised mild steel spindle, two nos galvanised iron washer and one galvnised iron nut, 100mm height,65mm dia for 1100v grade complete all as specified and directed by Engr-in-Charge.
50Supply and fixshackle, porcelain,vitreous,white brown or green insulator including galvnised mild steel straps, washers,insulator, bolts, washers and nuts for size 100mm height and 115mm dia for working pressure 1100 Volts complete all as specified and directed by Engr-in-Charge.
51Supply and install in replacement of steel tubular swaged poles type 410 SP-31 (9 mtr long) complete with CI base plate and finial taper plug,bolts, nuts and screws complete all as specified and directed by Engr-in-Charge. Note :-Excavation, earth & PCC workonly will be measuredseparetely all other accessories and work deemed to be included in quoted rates.