| 1 | Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre depth for foundation of poles, laying of cables etc not exceeding 10 sqm on plan area and getting out in soft / loose soilcomplete all as specified and as directed. |
| 2 | Excavation in trenches not exceeding 1.5 metre wide and exceeding 1.50 metre but not exceeding 3.00 metre depth for foundation of poles, laying of cables etc not exceeding 10 sqm on plan area and getting out in soft / loose soilcomplete all as specified and as directed. |
| 3 | Returning, filling in, of soil including spreading leveling, watering and well ramming in layers not exceeding 25 cm.thick complete all as specified and as directed . |
| 4 | Removing excavated material to a distance n.exc 50.00 metre and depositing/spreading where directed at a level n. exc 1.50 metre above the starting point complete all as specified and as directed . |
| 5 | Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of under ground cableincludingspreading and punning down complete all as specified and as directed.Note:- Punned down thickness shall be measured. |
| 6 | Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified and as directed. |
| 7 | Materials and labour for PCC 1:4:8 type D2 (using 40mm graded stone as in PCC foundation complete all as specified and directedby Engr-in-Charge. |
| 8 | Materials and labour for PCC 1:2:4 type B1 using 20mm graded stone aggregate for copping the poles of any size complete all as specified and directedby Engr-in-Charge. |
| 9 | Dismantling old u/s RCC/Steel poles/struts of any size incl breaking up PCC foundation complete all as specified and directed by Engr-in-Charge. |
| 10 | Supply and fixing ofsteel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified, type 410 SP-55 (Over all length 11 metres long) conforming to IS-2713.Pole shall be painted with one coat of red oxide primer throughout internally and externally up to 1.9 mtr length from bottom andthe remaining externalportion shall be painted with two coats of aluminium paint over a coat of red oxide primer and numbering the pole with white paint alfa numeric letters on black patch complete all as specified and directed. (Note: Excavation, earth work and PCC shall be mersured and paid separatly) |
| 11 | Dismantling of exsiting Uservicable/undersize ACSR or AAC conductors (of any size), jumper from overhead line removing unservisable material from site of work complete all as specified and directed by Engr-in-Charge. |
| 12 | Materials and labour for Aluminium conductor steel reinforced (ACSR) conductor, as in HT overhead electric line and streching the same between two poles for required span with standared guage & size of ACSR and binding the conductore with pin/shackle insulator and jumper with alunimium binding wire not less than 2.00mm dia complete all as specified and directed by Engr-in-Charge. |
| 13 | Dismantling of corroded/ rusted/ defective cross-arms of MS. Channel or angle of any sections complete all as specified and directed. |
| 14 | Material and labour for cross arm bracing, support, clamps and back plate fabrication from structural steel section including nuts., bolts, washers welding bending cold or hot drilling holes in any shape or size as indicated or directed by Engr-in-Charge and incltwo coats of aluminium paint over a coat of zinc chrome primer complete all as specifiedand directed. |
| 15 | Dismantling of old unserviceable insulator, any type / size complete all as specified and directed. |
| 16 | Supply and fixingPin type insulator, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 volts grade complete all as specified and directed by Engr-in-Charge |
| 17 | Supply and fixing Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green, Single disc assembly incl nuts and bolts of working pressure 11000 volts grade complete all as specified and directed by Engr-in-Charge |
| 18 | Supply and fixing for loop type insulator porcelain, vitreous, white, brown or green large size with overall dimentions 65x90mm clearance of hole 16mm complete all as specified and directed by Engr-in-Charge |
| 19 | Dismantling of old unserviceable damaged stay assembly embedded in concrete including demolition of PCC complete all as specified and directed. |
| 20 | Supply and fixing stay assemblyusing 20 mm diameter of stay rod complete with accessories as shown in electrical plate No. 1 of SSR part -Iall as specified and directed.(Note: loop type insulator, stay strand with stay clamps, excavation and concrete shall be measured and paidseparately) |
| 21 | Materials and labour for galvanized stay strand of size 7/3.15mm incl securing with LT pole clamp and stay clamp complete all as specified and directed by Engr-in-Charge |
| 22 | M&L for cleaning, scrapping, preparingof old painted steel tubular pole 11m long and applying one coat of aluminium red oxide primer and two coat of aluminium paint to pole and accessories / fittings whatever fixed on pole including marking/writing pole No on each pole with yellow SE paintwith 5cm large bold letters on black background of suitable size at a height of 2m above GL complete all as specified and directed.Make: Asian, Nerolac, Berger, Shalimar. |
| 23 | Supply and fixing as in repair HT lightening arrestor as in repair, expulsion type with all fittings, transmmission class discharge capacity 65 kilo Amps suitable for 11 KV and conforming to IS 3070 Part III and IEC 1994 complete all as specified and directed . |
| 24 | Taking down unserviceable /damaged XLPE HT cable of any size and any type from trenches /poles/wall etc after necessary electrical disconnectin complete all as specified and directed. |
| 25 | Supplying, Laying connecting & testing XLPE insulated, PVC sheathed, armoured HT electric power UG cable (heavy duty with stranded aluminum conductor)of size 95 Sqmm, 3 core, 11000 Volts(Earthed) grade, with FRLS PVCouter sheathed, conforming to IS-7098 (Part-II) laid through duct/ pipe / in trench etc. with cable glands and including suitable size of aluminium lugs complete all as specified and as directed.Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under respective item. |
| 26 | Supplying, Laying connecting & testing XLPE insulated, PVC sheathed, armoured HT electric power UG cable (heavy duty with stranded aluminum conductor)of size 150 Sqmm, 3 core, 11000 Volts(Earthed) grade,with FRLS PVCouter sheathed, conforming to IS-7098 (Part-II) laid through duct/ pipe / in trench etc. with cable glands and including suitable size of aluminium lugs complete all as specified and as directed.Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under respective item. |
| 27 | Supply and Laying in replacement 80mm bore GI tubing light grade with all fitting for passing of cable under road, on wall or on pole with and incl clams, nuts, bolts etc incl taking down old unserviceable GI tubing of any size incl cutting, chases to wall/ floor and making good surface complete all as directed by Engr-in-charge. |
| 28 | M & L for detecting the fault of HT cable with the help of fault locator machine wherever is recquired and disconnecting of jointing kit/cutting of damaged cable of any size from existig cable in the ground complete all as specified |
| 29 | Supply and fixing end termination joint kit for HT cable, heat shrinkable, indoor type with jointing material & accessories suitable for voltage 11 kV (Earthed), 3 core95 sqmm complete all as directed by Engr-in-charge. |
| 30 | Supply and fixing end termination joint kit for HT cable, heat shrinkable, outdoor type with jointing material & accessories suitable for voltage 11 kV (Earthed), 3 core95 sqmm complete all as directed by Engr-in-charge. |
| 31 | Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for straight through joints heat shrinkable type including joint kits and labour complete for making joints suitable for 3 Core XLPE armoured alumminium cable conductor cable of size 95 Sqmm and testing complete all as directed by Engr-in-charge. |
| 32 | Supply and fixing drop out fuse single pole mounted on insulator polymer type 11000 volt grade and current rating above 25 Amps and upto 50 Amps including taking down old unserviceable drop out fuse and removing from site complete all as specified and as directed. |
| 33 | Supply and fixing as in replacement Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit thecross section of the pole complete all as specified and as directed. |
| 34 | Materials and labour in repair for replacing danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size, for HT 11000 Volts, 250 mm X 200 mm complete all as specified and as directedby Engr-in-charge. |
| 35 | Supply and fixingtriple pole mechanically operated air break isolator (GOD), vertical mounting, rotating type, mounted on insulators and steel frame with operating mechanism worked from ground level consisting of operating rod of GI pipe 25mm bore light grade of suitable length complete in all respect such as gun metal moving contacts and spring loaded gun metal fixed jaws, knife copper jumper strip etc, suitable for 11000 Volts grade, with 9 insulators of rating upto 400 Amps with Locking Arrangement Mild Steel Flat Iron Clamp 50x6mm including dismanting old unserviceable Switch Air Break of any descrip tion, complete all as specified and as directed. |
| 36 | Supply and fixingtriple pole mechanically operated air break isolator (GOD), vertical mounting, rotating type, mounted on insulators and steel frame with operating mechanism worked from ground level consisting of operating rod of GI pipe 25mm bore light grade of suitable length complete in all respect such as gun metal moving contacts and spring loaded gun metal fixed jaws, knife copper jumper strip etc, suitable for 11000 Volts grade, with 9 insulators of rating upto 200 Amps with Locking Arrangement Mild Steel Flat Iron Clamp 50x6mm including dismanting old unserviceable Switch Air Break of any descrip tion, complete all as specified and as directed. |
| 37 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced to earthing lead of 32mm x 6mm galvanised mild steel strip by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking out unserviceable earthing plate and accessoriesall as specified and as directed. (Note: Earth lead upto a length of 7.50 m from earthplate shall be deemed to be included in quoted rate.) |