| 1 | SITC of 5.0 ton capacity wired concealed type Split AC of rated cooling capacity-60000 BTU/hr. with 2 nos. twin rotary compressorwith R-410A Refrigerant, 2 nos. IDU of rated power supply- 230V-1Ph- 50 Hz., 1 no. ODU of rated power supply- 400V-3Ph- 50 Hz.Air-flow/per IDU :- 1000 CFM with necessary scaffolding arrangement incl. lifting, shifting for outdoor & indoor units of said AC machine. (Make: Hitachi/Carrier/Approved by EIC) |
| 2 | Supplying, fabrication & fixingM.S frame made with 2 Nos. angle size (40mm x 40mm x 6mm) of 1mtr. length tied by 25mm x 25mm x 6mm angle of 1100mm length for installation of indoor unit ofConcealed Split AC incl. drilling 2 nos holesin each Angle, cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc.Area of the frame as follows:-i) 1 mtr. x 1.1 mtr. |
| 3 | Supply, installation & commissioning Copper Refrigeration pipe line for liquid and suction line with supports, brackets and 13 mm thick nitryle rubberInsulation and wrapping insulation of aerotape as per direction of EIC. |
| 4 | a) Liquid Line (3/8\" dia ),0.6 mm thick with 13 mm thick nitryle rubber insulation with Al foil covered (Cu pipe make- Ryoku/Rajko /Mandev) (insulation make- Accroflex/ Supreme) |
| 5 | b) Suction line (5/8\" dia ),0.6 mm thick with 13 mm thick nitryle rubber insulation with Al foil covered (Cu pipe make- Ryoku/Rajko /Mandev) (insulation make- Accroflex/ Supreme) |
| 6 | Supply & fixing FRLS unarmoured copper Communication / Power cable for Ductable Split/ concealed Split/ Hi-wall Split AC machines as per direction of EIC (Make- Polycab/ Havells/ KEI/Finolex) |
| 7 | 4 Core 2.5 sq. mm. |
| 8 | Supply & laying PVC Drain Pipe 25mm dia with 6mm thick NitrileRubber Insulation (Make: Suprime/Oriplast) |
| 9 | Supplying, fabrication & fixing M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making Base Frame for installation of outdoor unit of 7.5, 5.0 Tr Concealed split & 11.0 Tr Ductable Split AC incl. drilling holesin each channel, cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with 2 Nos. horizontal angle of 50 mm x 50 mm x 6 mm as per direction of E.I.C. |
| 10 | Supply, cutting & fixing drop ceiling made of Gypsum & E-board(3 mm thick) incl. Al channel & complete with linkages, levers, fittings, supports, all accessoriesany other item required to make the system complete to cover the indoor units of concealed split unit incl. Painting the board as per direction of E.I.C |
| 11 | Charges for trap door with 3 mm thick ACP board (Make -Aludecor/ or others reputed make) complete with linkages, levers, fittings, support all accessories for IDU maintenance as per direction of EIC. |
| 12 | Supply & Fixing flexible Double Canvas Connection |
| 13 | SITC of aluminium continuous grill.(Make: Air Kolkata/Primier) |
| 14 | SITC of 2.0 ton capacityHi-wall split Air-conditioner machine fitted with hyper tropical Rotary compressors suitable for Refrigerant-R410A/R-32 of rated power supply 230 V-1 Ph- 50 Hz along with all accessories incl. supply & fixing required Angle Iron Structure on wall/ floor & mending works as per direction of E.I.C. along with necessary scaffolding arrangement incl. lifting, shifting for outdoor & indoor units of said AC machine. (Make- Hitachi, Model- Logicool 3100f or equivalent model of O-General/Daikin or Approved by EIC). |
| 15 | Supply & Laying of 5/8\"(for suction) & 1/4\"(for discharge) copper refrigerant pipe with 9mm thick nitrile rubber insulation, 4 core x 2.5 sq.mm. copper cable incl. fixing arrangement and wrapping insulation of aerotape complete in all respect for 2.0 TR A.C. Machine. and Supply & laying PVC Drain Pipe 25mm dia by saddling on wall incl. PVC \"T\", elbow, bend etc as per direction of E.I.C. |
| 16 | Add GST @18%Rs. |
| 17 | Add LWC @1% Rs. |