| 1 | COST OF MATERIAL |
| 2 | COST OF MATERIAL |
| 3 | Supply and laying of unarmoured 1core 300sqmm XLPE power cable to be laid from transformer to Distribution Box |
| 4 | XLPE cable armoured3 ½ C X 120 sq.mm 1.1 KV Grade |
| 5 | XLPE cable armoured3 ½ C X 240 sq.mm 1.1 KV Grade |
| 6 | XLPE cable armoured3 ½ C X 35sq.mm 1.1 KV Grade |
| 7 | 4 Core XLPE Armoured cable, 1.1KV Grade 16sqmm |
| 8 | Outdoor, LV Main Switchboard for 200KVA Transformer centre made of CRCA sheet with PU painted and complete with all accsesories and HDGI mounting channels. |
| 9 | LED Lights |
| 10 | Street Light Service Pillar made out ofCRCA sheet with PU painted complete with TPN incoming and outgoing MCCBs,TP Contactors, Electonic/Digital / mechanical Timer, connectors etc. complete (Street light Pillar) |
| 11 | 3 phase and N, 415V, 200A MCCB incoming; 3-phase and N, 415,V 200 A MCCB outgoing; 12 nos. 32A. SP, MCBs; 12nos. 16A, SP, MCBs; Distribution Service Pillar suitable for outdoor installation made out ofof CRCA sheet with PU painted complete with all accessories and HDGI mounting channels. (24 way Distribution Service Pillar) |
| 12 | 3 phase, 415V,2nos of 200Amps incoming 3 TPN MCCBs and fitted with 12 Nos. 63 Amps SP, MCBs, 24nos. 32Amps SP, MCBs, 12 Nos.16 Amps SP, MCBs Distribution Service Pillar suitable for outdoor installation , made out of CRCA sheet with PU painted complete with all accesories and HDGI mounting channels (48 way Distribution Service Pillar) |
| 13 | 4-way, TP&N, 3 phase, 415V, 2 nos. of 315Amps incomings, 4 nos. of 200Amps outgoing rating type suitable for outdoor installation made out of CRCA sheet with PU painted complete with all accesories and HDGI mounting channels. (4 way Feeder Pillar) |
| 14 | Erection of 8 Mtrs Octagonal Pappeared H.D.G.I pole made out of 4 m.m. thick plate and heavy provision for cable entry, having weight not less than 97kg. 4 Nos of J type M24x 750mm long foundation bolts of grade EN 8 |
| 15 | 250 mm dia RCC Hume Pipe as per GSR 2020 (Roads) item nn 1909 |
| 16 | FRP Fencing complete with Gate as per specification for Distribution Transformer (Size 4Mx3Mx2M) with Concreting for FRP Fencing supports with plinth (0.3x0.3x0.5) Cu.m. x 12 nos. Each ratio 1:3:6 |
| 17 | FRP fencing complete with gate as per specification for Distribution transformer size 3Mx3Mx2M |
| 18 | 11KV Enamelled danger boards CEE/E-490 |
| 19 | Earthing complete with 2.5mts long, 40mm GI earthing pipe, class B, 20kgs each of salt and charcoal, excvation, re-filling etc. |
| 20 | Supply & laying of sand. |
| 21 | Disposal of surplus excavated soil/material by mechanical transportation including loading, unloading, starting leveling as directed up to a distance of 2.5 km |
| 22 | Protective covers ofsize 600mm length x 200mm width x 50mm thick for underground cables. |
| 23 | S&E of GI earthing strip of size 25x5 mm for connecting earthing pipe to other equipment |
| 24 | RCC Cable route Markers. |
| 25 | COST OF ERECTION |
| 26 | Supply and laying of unarmoured 1core 300sqmm XLPE power cable to be laid from transformer to Distribution Box |
| 27 | XLPE cable armoured3 ½ C X 120 sq.mm 1.1 KV Grade |
| 28 | XLPE cable armoured3 ½ C X 240 sq.mm 1.1 KV Grade |
| 29 | XLPE cable armoured3 ½ C X 35sq.mm 1.1 KV Grade |
| 30 | 4 Core XLPE Armoured cable, 1.1KV Grade 16sqmm |
| 31 | Outdoor, LV Main Switchboard for 200KVA Transformer centre made of CRCA sheet with PU painted and complete with all accsesories and HDGI mounting channels. |
| 32 | LED Lights |
| 33 | Street Light Service Pillar made out ofCRCA sheet with PU painted complete with TPN incoming and outgoing MCCBs,TP Contactors, Electonic/Digital / mechanical Timer, connectors etc. complete (Street light Pillar) |
| 34 | 3 phase and N, 415V, 200A MCCB incoming; 3-phase and N, 415,V 200 A MCCB outgoing; 12 nos. 32A. SP, MCBs; 12nos. 16A, SP, MCBs; Distribution Service Pillar suitable for outdoor installation made out ofof CRCA sheet with PU painted complete with all accessories and HDGI mounting channels. (24 way Distribution Service Pillar) |
| 35 | 3 phase, 415V,2nos of 200Amps incoming 3 TPN MCCBs and fitted with 12 Nos. 63 Amps SP, MCBs, 24nos. 32Amps SP, MCBs, 12 Nos.16 Amps SP, MCBs Distribution Service Pillar suitable for outdoor installation , made out of CRCA sheet with PU painted complete with all accesories and HDGI mounting channels (48 way Distribution Service Pillar) |
| 36 | 4-way, TP&N, 3 phase, 415V, 2 nos. of 315Amps incomings, 4 nos. of 200Amps outgoing rating type suitable for outdoor installation made out of CRCA sheet with PU painted complete with all accesories and HDGI mounting channels. (4 way Feeder Pillar) |
| 37 | Erection of 8 Mtrs Octagonal Pappeared H.D.G.I pole made out of 4 m.m. thick plate and heavy provision for cable entry, having weight not less than 97kg. 4 Nos of J type M24x 750mm long foundation bolts of grade EN 8 |
| 38 | 250 mm dia RCC Hume Pipe as per GSR 2020 (Roads) item nn 1909 |
| 39 | FRP Fencing complete with Gate as per specification for Distribution Transformer (Size 4Mx3Mx2M) with Concreting for FRP Fencing supports with plinth (0.3x0.3x0.5) Cu.m. x 12 nos. Each ratio 1:3:6 |
| 40 | FRP fencing complete with gate as per specification for Distribution transformer size 3Mx3Mx2M |
| 41 | 11KV Enamelled danger boards CEE/E-490 |
| 42 | Earthing complete with 2.5mts long, 40mm GI earthing pipe, class B, 20kgs each of salt and charcoal, excvation, re-filling etc. |
| 43 | Earthwork excavation in foundations trenches (not exceeding 1.5mts in width or 10mm² on plan) including opening of roads, chamber/pavements & soiling ,ramming, levelling of bottoms, making free from stones including removing out the excavated soil/material as directedwithin a lead of 40mts in laterite rock soil |
| 44 | Back Filling up of available excavated earth (excluding rock/stones) in trenches, plinth, sides, foundations etc. in layer not exceeding 0.2 mtrs. depth consolidation each deposited layer by ramming and watering |
| 45 | Protective covers ofsize 600mm length x 200mm width x 50mm thick for underground cables. |
| 46 | S&E of GI earthing strip of size 25x5 mm for connecting earthing pipe to other equipment |
| 47 | RCC Cable route Markers. |
| 48 | Removing and re-erection 200 KVA 11KV/0.4KV Distribution Transformers level II losses, Alluminium Winding, with Bimetallic Terminal Connectors, Energy Efficiency Level-II |
| 49 | Removing of M.S Distribution box with MCCB400 Amps,bus bar made out of aluminium strips 40x10mm , KIT KAT fuses for 4 feeder arrangement for 200 KVA distribution T/C. |
| 50 | Removing of RCC pole 7.5 mts long |
| 51 | Removing of RCC pole 9 mts long |
| 52 | Removing of DP Structural material |
| 53 | Removing AAC conductor \"GNAT\" |
| 54 | Removing AAC conductor \"ANT\" |
| 55 | Removing of HDGI 2 pin \"X\" arm of 75 x 40 Channel |
| 56 | Removing HDGI 4 pin \"X\" arm of 75 x 40 Channel |
| 57 | Removing of Lighting Arrestors 9KV 5KA |
| 58 | Removing of GOAB Switch 11KV 200Amp |
| 59 | Removing of H.G. Fuse unit 11KV 200Amps |
| 60 | Removing and re-erection Distribution Transformer Metering Unit |
| 61 | Removing of L.T. Shackle insulators |
| 62 | Removing of Metal parts for L.T. Shackle insulators |
| 63 | Removing of L.T. Pin Insulators |
| 64 | Removingof GI . Pin for L.T.Pin Insulators |
| 65 | Part B Civil |
| 66 | Providing and laying in position cement concrete 1:2:4(1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 40 m nominal size for foundations. (1.2*1.2*1.56) |
| 67 | Centering and shuttering including struttings, propping etc and removal of formwork . |
| 68 | 12mm cement plaster 1:4 (1 - cement: 4 - fine sand) for foundations. |
| 69 | Brick work using common burnt clay building bricks in cement mortar 1:4 (1 - cement: 4 - coarse sand) in foundation and plinth (b) with bricks of class designation 75 Kgs/sq.cm (wire cut bricks). (1.2*1.2*0.97) |