Tender For Supply Installation Testing Commissioning Of Power Supply Distribution For Cns Equipment From Ups In The Second Floor Ats Block, Chennai – P/O Installation Of Ip Radio And Establishment Of C-Smc, Chennai Airport. &Sitc Of Hf Receiver , Hf Broad, chennai-Tamil Nadu

Airports Authority Of India has published Tender For Supply Installation Testing Commissioning Of Power Supply Distribution For Cns Equipment From Ups In The Second Floor Ats Block, Chennai – P/O Installation Of Ip Radio And Establishment Of C-Smc, Chennai Airport. &Sitc Of Hf Receiver , Hf Broad. Submission Date for this Tender is 07-02-2023. Electrical Maintenance Tenders in chennai Tamil Nadu. Bidders can get complete Tender details and download the document.




Tender Notice

35680262
Corrigendum : Tender For Supply Installation Testing Commissioning Of Power Supply Distribution For Cns Equipment From Ups In The Second Floor Ats Block, Chennai – P/O Installation Of Ip Radio And Establishment Of C-Smc, Chennai Airport. &Sitc Of Hf Receiver , Hf Broad
Open Tender
Indian
Tamil Nadu
chennai
07-02-2023

Tender Details

Tender For Supply Installation Testing Commissioning Ofpower Supply Distribution For Cns Equipment From Ups In The Second Floor Ats Block, Chennai – P / O Installation Of Ip Radio And Establishment Of C-Smc, Chennai Airport. &Sitc Of Hf Receiver , Hf Broadband Antenna And Associated Accessories. Sh: Electrical Works.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 31-Jan-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 07-02-2023

Key Value

Document Fees
INR 1120 /-
EMD
INR 53300.0 /-
Tender Value
INR 26.60 Lakhs /-

BOQ Items

Name of Work: SITC of Power supply Distribution for CNS equipment from UPS in the second Floor ATS block, Chennai – P/O installation of IP radio and establishment of C-SMC, Chennai Airport. &SITC of HF receiver , HF Broadband antenna and associated accessories. SH: Electrical Works.
Sl. No. Item Description
1SH-I : Works at Equipment Room, ATS Complex.
2Supply and fixing of following (item Nos. 1.01 & 1.02) type of panels having Polycarbonate PC - GFS high flexibility modular enclosure system provision for an easy upgrading of the assembly including bus bar system at any time even after many years , made of high quality (shock proof, rust free, corrosion free, acid and chemical resistant, fire retardant, self-extinguishing, having high impact against mechanical load, made of halogen and silicon free recyclable material confirming to RoHS directive 2002/95/EC, UV resistant according to IEC 61439-1, having high grade internally embedded gasket made of Polyurethane ( PUR ). All left or right-side enclosures should have pre-moulded knockouts for side cable entry or for future extension. Each enclosure should have multi no of self-threaded holes to mount mounting plate or Din channel or any equipment. (Make: Hensel or Equivalent)
3Distribution panel details:- (Indoor & Wall Mounting) i) Incomer - 2 Nos of 100 Amp Double Pole MCCB,240V AC, 10kA, C-Curve with mechanical interlock arrangements, On/Off/Trip indications ,with rated individual digital voltmeter and digital ammeter per each incomer. ii) Outgoing - 20 Nos of (6-32) Amps Double pole,240 V AC, MCB, 10kA, C-Curve. iii) Suitable capacity copper bus bar arrangements to be made inbuilt for incomers and outgoings. iv) Provision of all necessary accessories etc., as required.
4On Load Changeover panel details:- (Indoor & Wall Mounting) i) Panel with 2 Incomers and 1 Outgoing type - 100 Amp ,240V AC,2 Pole with On/Off indications per each incomer along with necessary cable entry, exit and termination complete as required.
5Supplying and fixing of Loop-in Loop-out Boxmade of Transparent Polycarbonate with 100A copper busbar for both Phase & Neutral, Gland & connection Provision for one incomer(4C x 16sqmm) and 5 outgoing (2C x 16sqmm), earth connection and suitable for Single Phase AC supply etc complete as required.(Make: Henselor equivalent)
6Supplying and fixing of thermoplastic polycarbonate enclosure box protected with mentioned capacity of MCB and socket outlet. , suitable for fixing on surface including termination of incoming cable, necessary connections, etc. as required. i) 3 Pin 15A/5A socket outlet - 1 No, ii) 5/6A, Double Pole, 10 kA "C" curve MCB (Make: Henselor equivalent)
7Supplying and fixing of following rating miniature circuit breaker in the existing Network / Server Racks complete with Din bar, Neutral bar, connections, testing and commissioning etc. as required
810A, DP, 240/415 V, 10 kA, "C" curve
96A, DP, 240/415 V, 10 kA, "C" curve
1016A, DP, 6kA,24V DC MCB, "C" curve
111A, DP, 6kA,24V DC MCB, "C" curve
12Supplying and fixing of 63A, 4Pole, 10kA breaking capacity, "C" curveminiature circuit breaker in the existing electrical panel complete with necessary wiring connections, testing and commissioning etc. as required
13Supplying and fixing of 25 mm medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
14Supply and drawing of 2 Core X16 sq.mm FRLS PVC insulated copper conductor, single core cable in the existing cable tray / PVC conduit as required. (Connection between Battery charger and Tx/Rx racks)
15Supply of 3 Core x 10 sq.mm FRLS PVC insulated and PVC sheathed copper conductor round flexible industrial cable having 1.1 kV grade and as per IS694 complete as required.
16Supply of 2 Core x 16 sq.mm FRLS PVC insulated and PVC sheathed copper conductor round flexible industrial cable having 1.1 kV grade and as per IS694 complete as required.
17Supply of 4 Core x 16 sq.mm FRLS PVC insulated and PVC sheathed copper conductor round flexible industrial cable having 1.1 kV grade and as per IS694 complete as required.
18Supply of single core 25 sq.mm size FR PVC insulated unarmoured copper cable of 1.1 KV grade Green color for earth connection on wall surface as required.
19Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade upto 35 Sq.mm cable size in the existing RCC/ HUME/ METAL/ PVC pipe as required
20Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade upto 35 Sq.mm cable on wall surface as required.
21Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade upto 35 Sq.mm cable on existing cable tray as required.
22Providing and fixing of 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required
23Providing and fixing of 8 SWG copper wire on surface or in recess for loop earthing etc. as required
24Supply of 32A, DP, 240V AC , 10 kA, "C" curve
25Supply of 10A, DP, 240V AC , 10 kA, "C" curve
26Supply of 6A, DP, 240V AC , 10 kA, "C" curve
27Supply of 16A, DP, 6kA,24V DC MCB, "C" curve
28Supply of 1A, DP, 6kA,24V DC MCB, "C" curve
29Supply of following color 16 sq. mm FRLS PVC insulated copper conductor, single core cable
30Red
31Black
32Supply of 6 sq. mm FRLS PVC insulated copper conductor, single core cable for earth connection
33Supply of thermoplastic polycarbonate enclosure box protected with mentioned capacity of MCB and socket outlet. , suitable for fixing on surface including termination of incoming cable, necessary connections, etc. as required. i) 3 Pin 15A/5A socket outlet - 1 No, ii) 5/6A, Double Pole, 10 kA "C" curve MCB (Make: Henselor equivalent)
34Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulaterd and PVC sheathed /XLPE copper conductor cable of 1.1 KV grade as required. 4 X 16 Sq.mm
35SH-II : Works at RR Station, Operational Area.
36Supply of following size of XLPE insulated PvC sheathed copper conductor armoured power cable of 1.1KV grade confirming to IS 7098PART-1 with upto date amendments.
375C X 4 sq.mm
38Supply of following size of XLPE insulated PVC sheathed copper conductor armoured power cable of 1.1KV grade confirming to IS 7098 PART-1 with upto date amendments.
395C x 10 sq. mm
40Supplying and laying of 40 mm OD HDPE Pipe of PE 63 PN 6 along with all accessories conforming to IS 4984 direct in ground (0.75 mtr below the ground level) including excavation and refllling the trench etc., as required.
41Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size direct in ground incliding excavation, sand cudhioning , protective covering and refilling the trench etc as required.
42Upto 35 Sq.mm
43Laying and fixing of one number XLPE insulated and PVC sheathed/XLPE powercable of 1.1 KV grade of following size on wall surface as required.
44Upto 35 Sq.mm (clamped with 1mm Thick Saddle)
45Laying ofone number XLPE insulated and PVC sheathed power cable of 1.1KV grade of following size in the existing RCC/ HUME/ METAL/GI/HDPE pipe as required.
46Upto 35 Sq.mm
47Laying of one number XLPE insulated and PVC sheathed power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
48upto 35 Sq.mm
49Supply & fixing of size not less than 205mm X 255mm X 112mm of cable loop in loop out outdoor thermoplastic junction box of IP 66 with 4 way terminals and knockouts for cable entry of 5C x 4 Sq.mm cable, earth stud, supply and fixing of 6A 10KA C curve MCB, Din bar including fixing the box on concrete/steel structure etc complete as required (Make: HENSEL / LEGRAND /Equivalent)
50Supplying and making end termination with Brass compression gland and copper lugs forFollowing size of XLPE insulated and PVC sheathed Copper conductor cable of 1.1 KV grade as required.
515C X 4sq.mm
52Supplying and making end termination with brass compression gland and copper lugs for following size of XLPE insulated and PVC sheathed copper conductor cable of 1.1 KV grade as required.
535C X 10 sq. mm
54Supply & fixing of size not less than 300mm X 300mm X 182mm of cable loop in loop out outdoor thermoplastic polycarbonate junction box of IP 66 with 5 way terminals , 20A electronic timer with 3P contactor and knockouts for cable entry and exit of 5C x 10 Sq.mm cable, earth stud, supply and fixing of 32 A 10KA C curve MCB, Din bar including fixing the box on concrete/steel structure etc complete as required (Make: HENSEL / LEGRAND /Equivalent)
55Supplying and laying of "B" Class G.I pipe of80 mm dia, i/c excavation of bituminous/ concrete road/ pavement, excavation of Soil to maximum depth of 1.2 Mtrs from ground refilling the Soil and with CC of ratio 1:3:6 on top for 0.15 Mtrs after laying Pipe and plastering, making good thesame etc., as required.