| 1 | Sub Head -I( Conduit laying )Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. 20 mm (DSR 2022 Item no.1.20.1) |
| 2 | 25 mm (DSR 2022 Item no.1.20.2) |
| 3 | Sub Head -II ( Wiring )Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C (DSR 2022 - Item no.1.10.3) |
| 4 | Sub Head -II ( Wiring ) S/D of following sizes of FRLS PVC insulated copper conductor ISI marked single core cable in the existing surface/recessed steel/PVC conduit as reqd. 3 X 1.5 sq mm (DSR 2022 Item no.1.17.3) |
| 5 | 4 X 1.5 sq mm (DSR 2022 Item no.1.17.4) |
| 6 | 5 X 1.5 sq mm (DSR 2022 Item no.1.17.5) |
| 7 | 6 X 1.5 sq mm (DSR 2022 Item no.1.17.6) |
| 8 | 7 X 1.5 sq mm (DSR 2022 Item no.1.17.7) |
| 9 | 8 X 1.5 sq mm (DSR 2022 Item no.1.17.8) |
| 10 | 9 x 1.5 sq mm (DSR 2022 Item no.1.17.9) |
| 11 | 3 X 2.5 sq mm (DSR 2022 Item no. 1.17.12) |
| 12 | 6 X 2.5 sq mm (DSR 2022 Item no.1.17.15) |
| 13 | 3 X 4 sq mm (DSR 2022 Item no.1.17.21) |
| 14 | Sub Head -III(Switchgear and earthing) Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. 75 mm X 75 mm X 60 mm deep (DSR 2022 - Item no.1.22.1) |
| 15 | 150 mm X 75 mm X 60 mm deep (DSR 2022 - Item no.1.22.3) |
| 16 | Sub Head -III(Switchgear and earthing)Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. 5/6 A switch (DSR 2022 - Item no.1.23.1) |
| 17 | Sub Head -III(Switchgear and earthing)Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.6 Module (200mmX75mm) (DSR 2022 - Item no.1.27.4) |
| 18 | 12 Module (200mmX150mm) (DSR 2022 - Item no.1.27.6) |
| 19 | Sub Head -III(Switchgear and earthing) Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 A switch (DSR 2022 - Item no.1.24.1) |
| 20 | 15/16 A switch (DSR 2022 - Item no.1.24.3) |
| 21 | 3 pin 5/6 A socket outlet (DSR 2022 - Item no.1.24.4) |
| 22 | 6 pin 15/16 A socket outlet (DSR 2022 - Item no.1.24.5) |
| 23 | Sub Head -III(Switchgear and earthing)Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.(DSR 2022 - Item no.1.33) |
| 24 | Sub Head -III(Switchgear and earthing) Supplying and fixing of horizontal type three pole and nuetral sheet steel MCB distribution board, 415Volts, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, inter connections, powder painted including earthing etc., as required (but without MCB/RCCB/Isolator )4 way (4 + 12), Double door (DSR 2022 Item 2.4.1) |
| 25 | Sub Head -III(Switchgear and earthing) Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door (DSR 2022 Item 2.3.2) |
| 26 | Sub Head -III(Switchgear and earthing) Supplying and fixing 5 amps to 32 amps rating, 240/415 volts,\"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DBomplete with connections, testing and commissioning etc. as required. Single pole (DSR 2022 Item no.2.10.1) |
| 27 | Single pole and neutral (DSR 2022 Item no.2.10.2) |
| 28 | Triple pole and neutral (DSR 2022 Item no.2.10.5) |
| 29 | Sub Head -III(Switchgear and earthing)Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30mA in the existing MCB DB complete with connections, testing and commisssioning etc. as required.25 ADSR 2022 item no 2.14.1 |
| 30 | Sub Head -III(Switchgear and earthing)Dismantling the existing switch cover/plate alongwith damaged tumbler type switches and damaged existing metal box as required. |
| 31 | Sub Head -III(Switchgear and earthing)Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps \"C\" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.(DSR 2022 - Item no.2.18) |
| 32 | Sub Head -III(Switchgear and earthing)Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required..(DSR 2022 Item no.5.4) |
| 33 | Sub Head -III(Switchgear and earthing)Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from FRLS om earth electrode including connection with G.I. thimble excavation and re-filling as required. (DSR 2022 Item no.5.12) |
| 34 | Sub Head -III(Switchgear and earthing) Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. (DSR 2022 Item no.5.16) |
| 35 | Sub Head -III(Switchgear and earthing)Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.(DSR 2022 Item no.5.6) |
| 36 | Sub Head -III(Switchgear and earthing) Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.(DSR 2022 Item no.5.10) |
| 37 | Sub Head -III(Switchgear and earthing) Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. (DSR 2022 Item no.5.14) |
| 38 | Sub Head -IV ( Fittings )Supplying, installation, testing andcommissioningof 1x 20W Retrofit type Photon Ultra bright LED polycarbonate tubelight along withIndustrial Box type Luminaire batten suitable for singleT8 LED Tube on wall/truss for fixing LED tube including connection, testing as required. |
| 39 | Sub Head -IV ( Fittings )Supplying, installation, testing andcommissioningof 2x 20W Retrofit type Photon Ultra bright LED polycarbonate tubelight along withIndustrial Box type Luminaire batten suitable for TwinT8 LED Tube on wall/truss for fixing LED tube including connection, testing as required. |
| 40 | Sub Head -IV ( Fittings ) Supplying, installation, testing andcommissioningof 20W LED tube alongwith Industrial Batten of Environmental friendly, long life, corrosion resistant, impact proof, surface mounting IP65 luminaire with PC housing & opal finish cover suitable for LED tubes and fixing on wall/truss by using necessary clamps and also dismantling the existing fitting. |
| 41 | Sub Head -IV ( Fittings ) Supplying, installation, Testing and commissioning of 45 watt LED 5700K type LED streetlight made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection with impact resisitance of IK07 and fixing on truss /wall/ pole with suitable clamps and nut bolts including giving connection testing etc., at site of work as required. |
| 42 | Sub Head -IV ( Fittings ) Supplying, Installation, Testing & Commissioning ofIntegral 120W LED flood light with driver inside a PDC housing with IP66 protection and suitable fixing accessories accessorieson wall/ GI Pipe/tower/truss of the godown , making connections from the existing point / loop in loop out box to fittingswith copper conductor round flexible cable etc. as required. |
| 43 | Sub Head -IV ( Fittings )Supplying, installation, Testing and commissioningof70 watt LED Well Glass fitting of Environmental friendly, IP protection energy saving long life corrosion resistant, vertical/horizontal surface mounting pressure die-cast aluminium well glass luminaires with high power LED as light source and fixing on truss /wall/ pole with suitable clamps and nut bolts including giving connection testing etc., at site of work as required. |
| 44 | Sub Head -IV ( Fittings )Supplying, installation, Testing and commissioning of 35 watt LED 5700K Post top lantern type Coral(Opal) - IP65 with high power LEDs as light source and fixing on pole with suitable clamps and nut bolts including giving connection testing etc., at site of work as required. |
| 45 | Sub Head -IV ( Fittings )Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019),THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. DSR 2022 item no. 19.1 |
| 46 | Sub Head V - Underground Cabling WorksSupply of PVC insulated and PVC sheathed XPLE power cable of 1.1 KV grade armoured UG aluminium conductor cable conforming to IS 7098 part 1 with up-to-date amendment of the following size as required. 3 x 16 sq.mm |
| 47 | 4 x 16 sq.mm |
| 48 | 2 × 16 sq.mm |
| 49 | Sub Head V - Underground Cabling Works Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) (DSR 2022 -Item no.7.7.1) |
| 50 | Sub Head V - Underground Cabling Works Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq mm DSR 2022 Item no 7.1.1 |
| 51 | Sub Head V - Underground Cabling Works Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq mm DSR 2022 Item no 7.2.1 |
| 52 | Sub Head V - Underground Cabling Works Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.up to 35 sq.mm. Up to 35 Sq mm (DSR 2022 -Item no.7.5.1) |
| 53 | Sub Head V - Underground Cabling WorksProviding, laying and fixing following dia G. I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and refilling etc as required. 100 mm dia (DSR item no 14.13.3) |
| 54 | Sub Head V - Underground Cabling WorksSupplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 meter length along the pole for protection of under ground cable as required (DSR 2022 -Item no.12.37) |
| 55 | Sub Head V - Underground Cabling WorksSupplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 x 16 sq mm (DSR 2022 item no 9.1.3) (22 mm) |
| 56 | 3 x 16 sq mm (DSR 2022 item no 9.1.8) (25 mm) |
| 57 | 4 X 16 sq. mm (28mm) (DSR 2022 -Item no.9.1.33) (28 mm) |
| 58 | Sub Head V - Underground Cabling Works Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. DSR 2022 Item no 7.10 |
| 59 | Sub Head V - Underground Cabling WorksSupplying and fixing street light loop in loop out weather proof PVC boxof size 8\"x6\"x4\"with 1 No. 6A SP MCB, 2/4 way strip connector i/c testing as reqd. |
| 60 | Sub Head V - Underground Cabling Works Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish Paint etc. as required. DSR 2022 item no 12.34 |
| 61 | Sub Head V - Underground Cabling WorksSupply and fixing 5.0 mtrs of 40 mm GI pipe (medium grade) with necessary clamping at both the ends of the pipe as required. |
| 62 | Sub Head VI - MV PanelS/F of 100 Amp Kit Kat fuse complete set for main panel in switch room. |
| 63 | Sub Head VI - MV PanelS/I/T/C of floor mounted cubical panel board fabricated 14 SWG CRCA sheet of approx. size 1.5mtr X 1.5mtr X 0.40mtr deep with provision of vertical adopter box on both sides & cubical boxes for fixing MCCB of various ratiing , the vertical bus bar of 4 strip Al. 600 mm long , 200 Amp. interconnections with copper conductor cable with suitable size of thimbles,lungs etc. & powder coated as required I/c P/f following mounting & placing the panel on a stand 60 cm above the ground fabricated with channel iron (100 X 40 mm) /angle iron (50x50x6 mm) i/c sheet covering with 16 SWG sheet etc. as required including the following items :- MCCB 4 pole 200 AmpBreaking cap. 35 KA (For Main) - 1No.MCCB T.P. 100 Amp, 16 KA - 1 No.MCCB T.P. 63 Amp16 KA - 3 No.Voltmetrer & selectors switches, Ammeter,CT\"S & PT\"S (with HRC fuse )- 1 SetIndicatorsmake with toggle switches- 3 Set |
| 64 | Sub Head VII - Miscellaneous worksRemoving the existing aluminium wire from conduit, main board, sub-main boards, switch boards, tube light fittings etc., and shifting the same to stores etc., as required.( for shed no 1,2 ) |
| 65 | Sub Head VII - Miscellaneous works Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. DSR 2022 Item no. 2.21 |
| 66 | Sub HeadVIII - Credit Items Less credit for dismantaled old damaged metal scrap including transportation and disposal of the same from the site. |
| 67 | Sub HeadVIII - Credit Items Less credit for dismantled old damaged PVC insulated Al wire including transportation and disposal of the same from the site. |
| 68 | Sub HeadVIII - Credit ItemsLess credit for dismantaled old damagedSingle pole MCB 6 to 32 Amp. |
| 69 | Sub HeadVIII - Credit Items Less credit for dismantaled old damagedSingle SPN 6 to 40 Amp. |
| 70 | Sub HeadVIII - Credit ItemsLess credit for dismantaled old damaged 5/6Amp piano/round type switch. |
| 71 | Sub HeadVIII - Credit ItemsLess creditfor dismantaled old damaged70/150W street light HPSV fitting. |
| 72 | Sub HeadVIII - Credit ItemsLess creditfor dismantaled old damaged70 w low bayHPSV/MH fitting. |
| 73 | Sub HeadVIII - Credit Items Less creditfor dismantaled old damaged40W Flourescent fitting. |
| 74 | Sub HeadVIII - Credit ItemsLess creditfor dismantaled old damagedcable termination M.S box and scrap. |