Tender For Electrical And Mechanical Works To Be Carried At Wss Nowgam Gund Payeen Stage 1St And 2Nd Under Jjm
Tender Value
1.05 Crore
Estimated cost
Bid Submission
14 Jan 2023
0 days left
EMD
Ref. Documents
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
nowgam → Jammu And Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Electrical And Mechanical Works To Be Carried At Wss Nowgam Gund Payeen Stage 1St And 2Nd Under Jjm Electrical And Mechanical Works
BOQ
| Sl. No. | Item Description |
| 1 | Providing, fitting, installation, testing and commissioning of VT pumping unit (Raw Water Stage 1st) of following specifications: A. PUMP1. Discharge = 30000 GPH 2. Type = Self water lubricated, VT pump, open line shaft.3. Liquid to be handled = Raw Water 4. RPM = 14605. Head = 65 Meters6. Efficiency = Not less than 75%B. Prime Mover 1. Type = Vertical hollow shaft, AC induction2. Power Supply = 03 Phase, 41 5V± 10% AC3. Frequency = 50Hz±3%4. RPM = 1450 Synchronous5. Efficiency = Not less than 85%6. HP = Corresponding to Head and discharge but not less than 60HP.Rest of Specification/Details are as per clause 6 of Annexure \"C\" of SBD for stage 1st |
| 2 | Providing, fitting, installation, testing and commissioning of VT pumping unit of following specifications: A. PUMP1. Discharge = 12000 GPH 2. Type = Self water lubricated, VT pump, open line shaft.3. Liquid to be handled = Clear Water4. RPM = 14605. Head = 40 Meters6. Efficiency = Not less than 75%B. Prime Mover 1. Type = Vertical hollow shaft, AC induction2. Power Supply = 03 Phase, 41 5V± 10% AC3. Frequency = 50Hz±3%4. RPM = 1450 Synchronous5. Efficiency = Not less than 85%6. HP = Corresponding to Head and discharge but not less than 15HP.Rest of Specification/Details are as per clause 6 of Annexure \"C\" of SBD for stage 2nd OHT 1st |
| 3 | Providing, fitting, installation, testing and commissioning of VT pumping unit of following specifications: A. PUMP1. Discharge = 15000 GPH 2. Type = Self water lubricated, VT pump, open line shaft.3. Liquid to be handled = Clear Water4. RPM = 14605. Head = 40 Meters6. Efficiency = Not less than 75%B. Prime Mover 1. Type = Vertical hollow shaft, AC induction2. Power Supply = 03 Phase, 41 5V± 10% AC3. Frequency = 50Hz±3%4. RPM = 1450 Synchronous5. Efficiency = Not less than 85%6. HP = Corresponding to Head and discharge but not less than 20HP.Rest of Specification/Details are as per clause 6 of Annexure \"C\" of SBD for stage 2nd for OHT 2nd |
| 4 | Providing, fitting, installation, testing and commissioning of VT pumping unit of following specifications: A. PUMP1. Discharge = 7000 GPH 2. Type = Self water lubricated, VT pump, open line shaft.3. Liquid to be handled = Clear Water4. RPM = 14605. Head = 50 Meters6. Efficiency = Not less than 75%B. Prime Mover 1. Type = Vertical hollow shaft, AC induction2. Power Supply = 03 Phase, 41 5V± 10% AC3. Frequency = 50Hz±3%4. RPM = 1450 Synchronous5. Efficiency = Not less than 85%6. HP = Corresponding to Head and discharge but not less than 12.5HP.Rest of Specification/Details are as per clause 6 of Annexure \"C\" of SBD for stage 2nd for OHT 3rd proposed |
| 5 | Providing/supplying and fitting ofG.I flanged Rising Main at site. The Pipe shall be hot dip Galvanized, class-C confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) for Y junctionSize: 150mmClass:C (Heavy)Rest of Specification as per clause 8 of Annexure \"C\" of SBD for stage 1st |
| 6 | Providing and fitting of, Ductile Iron double flanged, non-rising spindle soft seatedglandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units .Size: DN150PN:1.6/16 Rest of Specification/Details areas per clause 12 of Annexure \"C\" of SBD for stage 1st |
| 7 | Providing and fitting ofDuctile Iron double flanged, Slanted seatswing check valve( NRV) as per IS 5312. Size: 150mmPN: 1.6/16Rest of Specification/Details areas per clause 13 of Annexure \"C\" of SBD for stage 1st |
| 8 | Providing/supplying and fitting ofG.I flanged Rising Main at site. The Pipe shall be hot dip Galvanized, class-C confirming to IS 1239. The job includes providing and fitting of M.S Flanges conforming to BIS 6392/1997 Table 17 (Rating PN16) for Y junctionSize: 100mmClass:C (Heavy)Rest of Specification as per clause 8 of Annexure \"C\" of SBD for stage 2nd |
| 9 | Providing and fitting of, Ductile Iron double flanged, non-rising spindle soft seatedglandless gate/ sluice valves as per IS14846 for regulating the water supply outside the pumping units .Size: DN100PN:1.6/16 Rest of Specification/Details areas per clause 12 of Annexure \"C\" of SBD for stage2nd |
| 10 | Providing and fitting ofDuctile Iron double flanged, Slanted seatswing check valve( NRV) as per IS 5312. Size: 100mmPN: 1.6/16Rest of Specification/Details areas per clause 13 of Annexure \"C\" of SBD for stage 2nd |
| 11 | Providing, fitting, testing and commissioning of Manually operated copper wound, 3-phase, AC power supply multi step voltage stabilizer.Rating::50KVAStage-2nd Manufacturers test certificate to be apended and rest of specification as per clause 44 of Annexure \"C\" of SBD for stage 2nd |
| 12 | Providing, fitting, testing and commissioning of Manually operated copper wound, 3-phase, AC power supply multi step voltage stabilizer.Rating::100KVA Stage-1stManufacturers test certificate to be apended and rest of specification as per clause 45 of Annexure \"C\" of SBD. |
| 13 | Stage 1st: Creation of pole mounted , outdoor type Electric Sub Stationby way ofS/I/T/C of 11/0.433 KVA , 3 Phase Distribution Transformer with Bimetallic Terminal connectors Energy level -2 Aluminum woundSpecifications conforming to IS : 1180 (Part 1) 2014 with latest amendments Type of cooling:ONAN.Rating: 200 KVA HT Transformer, 3 phase (Level 2).Manufacturers certificate be apended and rest of specification as per cluase 26 of Annexure \"C\" of SBD for stage 1st |
| 14 | Stage 2nd: Creation of pole mounted , outdoor type Electric Sub Stationby way ofS/I/T/C of 11/0.433 KVA , 3 Phase Distribution Transformer with Bimetallic Terminal connectors Energy level -2 Aluminum woundSpecifications conforming to IS : 1180 (Part 1) 2014 with latest amendments Type of cooling:ONAN.Rating: 200 KVA HT Transformer, 3 phase (Level 2).Manufacturers certificate be apended and rest of specification as per cluase 26 of Annexure \"C\" of SBD for stage 2nd |
| 15 | Supply, installation, erection of 9 mtrs long H.T pope of specifications ST410 (SP-33). The job further includes drilling of holes for installation of various accessories .wherever required the job further includes G.I wire earthing of pole as per REC standard.as per Clause 32 of Annexure \"C\" of SBD for stage 1st & 2nd |
| 16 | Cement Bottoming 1:2:4 mix as per REC standards 0.5 cum/pole |
| 17 | Providing and fitting G.I Channel /Angle/ Flat /Riser of sizes including clamps as per Clause 27 of Annexure \"C\" of SBD for stage 1st & 2nd |
| 18 | Supply, Installation, Testing and commissioning of Polymeric Gang operated Air break switch, outdoor type, triple pole, suitable for vertical installation, single break provided with locking arrangement at both ON and OFF positionconsisting of HT post double insulator, copper or copper alloy high pressure heavy contact assembly, rod with bearings , operating handle and 2 length of 32mm dia. GI pipe conforming to IS 1818 1961, 06 No. of insulators, rated voltage 11KV 200A complete as per IS specs. as per Clause 28 of Annexure \"C\" of SBD for stage 1st & 2nd |
| 19 | Supply, Installation, Testing and commissioning of 11KV polymer fuses Set Horn Gap 3-phase 200 A suitable for vertical installation. as per Clause 29 of Annexure \"C\" of SBD for stage 1st & 2nd |
| 20 | Supply, Installation, Testing and commissioning of Gapless Surge arrestor station class, 10KA, 9KV, LA With polymer housing, Station Type as per Clause 30 of Annexure \"C\" of SBD for stage 1st & 2nd |
| 21 | Supply and fitting of 11 KV polymeric composite pin insulator 12 KV, 5KN, Lighting impulse 75KV Positive, and 80 KV Negative , creepage distance 320 mm as per Clause 31 of Annexure \"C\" of SBD for stage 1st & 2nd |
| 22 | Providing of bamboo ladders 18 feet long along with 15 feet long Link rods and HT Glove pair (01 No each) as per Clause 61 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 23 | Painting of poles Red oxide as per Clause 37 of Annexure \"C\" of SBD for stage 1st & 2nd |
| 24 | Painting of poles Aluminum paint as per Clause 38 of Annexure \"C\" of SBD for stage 1st & 2nd |
| 25 | P/I of earthing station for electric substation, LT panel and stabilizer comprising of company fabricated earthing electrode as per IS: 3043 as per Clause 48 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 26 | P/L of ACSR conductor of size 0.05 as per the relevant IS standard as per clause 78 of Annexure \"C\" of SBD for stage 1st |
| 27 | Providing and fitting of 3”x5/8” Galvanized nuts and bolts |
| 28 | Providing and fitting of LT Distribution box for H.T transformer with MCCB For incomer and SFU for outgoing circuits as per clause 42 of Annexure \"C\" of SBD |
| 29 | Distribution Cables:Providing, Installation, testing of multi-stranded copper conductor PVC insulated single core unsheathed 70mm sq. Copper cable for internal distribution wiring for stage 1st |
| 30 | Distribution Cables:Providing, Installation, testing of multi-stranded copper conductor PVC insulated single core unsheathed 35mm sq. Copper cable for internal distribution wiring for stage 2nd as per clause 67 of Annexure \"C\" of SBD |
| 31 | Fabrication Providing and fitting of modular control panel for stage 2nd . THE technical details/ Ratings of various components of Modular Control Panel are given Below a. Main Circuit Breaker (Incommer MCCB) of rting = 160-200AmpWith S.C. Breaking Capacity of50kAb. Changeover Switch of rating = 100Amp c. Motor Breakup ProtectionMCCB of rating = 100-125 Amp With S.C. Breaking Capacity of36kAd. FASD Submersible startersuitable for 30 HP Load with Relay range of 30-50 Ampe. Auxillary MCCB for Heating/Lighting = 63 AmpWith S.C. Breaking Capacity of25kAf. Capcitor bank of 15KVAr cpacity Rest of Deatils/Technical specification are as per clause 43 (e) ofAnnexure \"C\" of SBD for stage2nd |
| 32 | Fabrication Providing and fitting of modular control panel for Stahe-1st . THE technical details/ Ratings of various components of Modular Control Panel are given Below a. Main Circuit Breaker (Incommer MCCB) of rting = 250AmpWith S.C. Breaking Capacity of50kAb. Changeover Switch of rating = 200Amp c. Motor Breakup ProtectionMCCB of rating = 160-200 Amp With S.C. Breaking Capacity of36kAd. FASD Submersible startersuitable for 75 HP Load with Relay range of 66-110 Ampe. Auxillary MCCB for Heating/Lighting = 63 AmpWith S.C. Breaking Capacity of25kAf. Capcitor bank of 15KVAr cpacity Rest of Deatils/Technical specification are as per clause 43 (h) ofAnnexure \"C\" of SBD |
| 33 | Providing and Fitting of 120 sqmm single core LT 1.1 KV for stagestage ist and 2nd, XLPE Armoured Aluminium Cable conforming to IS: 7089 part 1st as service line from the HT transformer/DG set to control panel including necessary thimbling, crimping, taping etc.NOTE:- The cable terminal ends for connection to switchgear at various requisite points shall be Al. Thimbles of appropriate size and connected by hydraulic crimp tool only for stage 1st and 2nd |
| 34 | Steel work in built up tubular (round, square or rectangular hollow tubes, ISMC,ISMB,ISA etc.) trusses, construction of liner etc. including cutting , hoisting , fixing in position and applying a priming coat of approved steel primer , including welding and bolted with special shaped washers etc. complete Stage 1st & 2ndThe drawings and Dimensions for Gantry/Transformer Bed/Pumping Equipment Base will be provided by Site In Charge at the time of execution of job |
| 35 | Providing, installation and testing of manual type triple spur gear chainpulley block at stage 1st and 2nd along with monorail geared travelling trolley having followingfeaturesMake = Reputed make Capacity = 3 ton (P) No. Of load chain falls = 2 or above Min. Height of lift = 6 M Rest of Deatils/Technical specification are as per clause 24 ofAnnexure \"C\" of SBD for stage 1st and 2nd |
| 36 | Illumination of Premises: Stage 1st and 2ndProviding and erection of 9 Mtr long Hot Dip Galvanized octagonal pole (single Section) with bottom 150mm, top 75mm wide, thickness 3mm with 70 Microns Zinc coating having inside arrangement for providing of power connection along with following items.1) 3 Way Terminal Connector 20 Amp.2) 3 No MCB 8 Amp.Rest of Deatils/Technical specification are as per clause 50 ofAnnexure \"C\" of SBD for stage 1st and 2nd |
| 37 | Providing, installation, testing and commissioning of area lighting 120 Watt LED (Street Light Type) on top of octagonal pole Having following specs:Input: 90-240 V 50 HzPower Factor: >0.9Rest of Deatils/Technical specification are as per clause 51 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 38 | Providing and installation of Junction Box with DP 32Amp MCB to serve as amin switch for LED lighting for stage 1st and 2nd Rest of Deatils/Technical specification are as per clause 52 of Annexure \"C\" of SBD |
| 39 | Providing, Installation and testing of 2KVA fully automatic voltage stabilizer for stage 1st and 2nd Rest of Deatils/Technical specification are as per clause 53 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 40 | Supply, installation, Testing & commissioning of 1000VA Full Sine wave power inverter with 12V, 180AH Tubular inverter Battery for stage 1st and 2nd Rest of Deatils/Technical specification are as per clause 54 of Annexure \"C\" of SBD |
| 41 | Providing, laying & fixing with adhesive/bonding material of insulation rubber mats on the floor of the pump house, covering area around electro-mechanical machinery for safeguarding the life & limb of the workmen . Rest of Deatils/Technical specification are as per clause 55 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 42 | TOOL KIT For Maintenance: -stage 1st and 2ndThe Tool Kit for maintenance as per detailed specification in cluase 56 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 43 | Providing of good quality conveinence and utility items as per details in Caluse57 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 44 | Fabricationof6’ x 6’ angle iron bedfor operators. Rest of Deatils/Technical specification are as per clause 58 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 45 | Providing and fitting of 19 mm thick multilayered ply sheet of size 6 x 3 feet , 2 nos. Rest of Deatils/Technical specification are as per clause 59 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 46 | Providing of solar/ electrical lantern chargeable on both solar & electrical 220v supply for stage 1st and 2nd |
| 47 | Providing of 1 KW heat convector for operators for winter season for stage 1st and 2nd |
| 48 | Providing and fitting of 01 No. LED (scroll type) sign board fabricated out of stainless steel and metalRest of Deatils/Technical specification are as per clause 64 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 49 | Providing & fitting oflighting points for( machine room , operators room,) as per site requirement in 1.5 mm² multistranded single core 1100 volts, pvc insulatedcopper conductor through pvcconduit pipe by way, switches, socket modules , regulators ,indicators, 08/10 watt LED lamps Surface light Make. .Included is cost on account of modular switch boards with the wooden frames as per site requirements for stage 1st and 2nd |
| 50 | Providing fitting of heating points in 2.5mm² multistranded single core 1100 volts, pvc insulated copper conductor through pvc conduit by way of p / f of 15 Amp switches, 6 pin socketon modularfittingas per site requirements. Heating points are to be connected from main control panel. All accessories required is to be provided by the firmfor stage 1st and 2nd |
| 51 | Providing and fitting of 01 No. angle iron/sheet metal board duly painted showing various specifications of the mechanical and electrical equipments installed at site.Rest of Deatils/Technical specification are as per clause 65 of Annexure \"C\" of SBD for stage 1st and 2nd |
| 52 | Providing and fitting of 3-Core flatsubmersible copper cable conforming to IS: 694 (Part 1st) – 1964 & IS: 694 (Part 2nd) - 1964Size = 25 Sq mm for stage 1st and 2nd as per details in Clause 47 ofAnnexure \"C\" of SBD |
| 53 | Fabrication, providing and fitting of split type MS clamps10 mm thick, 2 ft long and 3 inch wide for lowering and holding of pumping unit fitted. The job includes the cost of required size of nuts and bolts. Size: 100mm Rest of Specification/Details areas per clause 16 of Annexure \"C\" of SBD for stage 1st and 2nd |
AI Tender Summary
Tender Timeline
Dec 24, 2022
11:30 IST
Tender Published
Tender notice published.
CompletedJan 14, 2023
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedJan 16, 2023
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender