Tender For Provision Of Stand By Dg Set For Central Ac Plant At 183 Mh At Leimakhong Mil Stn, leimakhong-Manipur

Military Engineer Services-MES has published Tender For Provision Of Stand By Dg Set For Central Ac Plant At 183 Mh At Leimakhong Mil Stn. Submission Date for this Tender is 17-01-2023. Diesel Generators Tenders in leimakhong Manipur. Bidders can get complete Tender details and download the document.




Tender Notice

35394448
Corrigendum : Tender For Provision Of Stand By Dg Set For Central Ac Plant At 183 Mh At Leimakhong Mil Stn
Open Tender
Indian
Manipur
leimakhong
17-01-2023

Tender Details

Tender For Provision Of Stand By Dg Set For Central Ac Plant At 183 Mh At Leimakhong Mil Stn

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 05-Jan-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 12-01-2023
2 12-Jan-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-01-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 87100.0 /-
Tender Value
INR 43.51 Lakhs /-

BOQ Items

Name of the Work: PROVN OF STAND BY DG SET FOR CENTRAL AC PLANT AT 183 MH AT LEIMAKHONG MIL STN.
Sl. No. Item Description
1Supply, Install, testing and commissioningof DG set600 KVA, Acoustic type 12 cylinder diesel engine developing 723 HP @ 1500 RPM, water / liquid cooled engine with radiator, cooling fan, fan belt, turbo charger with after cooler etc. The diesel engine shall be directly coupled to AC generator capable of developing 600 KVA / 480 KW suitable for continious operationrated at 1500 RPM. The engine shall be electric start, compression ignition, 4 stroke , design to run continiously at 1500 RPM conforming to IS 10002, ISO-3046, BS-5514, standard with an overload capacity of 10% for one hour in every 12 hrs of operation. The Diesel Engine shall comply with present CPCB norms. The diesel Engine set shall be as per IS 10002 and alternator shall be as per IS-4722/BS EN 60034-1/IEC 34-1 with electronic speed governor including necessary anti vibration pad as per the recommendation of the manufacturer with the following specification complete all as specified and directed.
2(A) The diesel engine comprising of following: - (i) Self starter motor able to work in 24 V DC supply. (ii)Fuel injection pump with Electronic Governor. (iii) Dry type air cleaner. (iv) Exhaust pipe with thoroughly insulated silencer. (v)First fill of lubricating oil upto the required level. (vi) Lubricating oil filter (Replaceable element type) (vii) Fuel filter (primary and secondary) (viii) Battery charging alternator. (ix) Emergency stop button
3B) GEN-SET CONTROLLER Following indication / LCD display shall be available in the Digitial GEN Set controller:- (i) Lubricating oil pressure and temperature guage (ii) Battery voltage, minimum battery voltage (iii) Engine RPM (iv) Fuel level in the dry tank (v) Engine running hours indication. (vi) Line current (vii) Phase Voltage (viii) Frequency (ix)Unit generated reading (x) Power factor (xi) Earth leakage current (xii) Low lubricating oil pressure. (xiii) Low radiator water level (xiv) Low fuel level (xv) Engine temperature
4The following electrical and mechanical safety system to be available alongwith display:- (i) Under / over voltage (ii) Under / over frequency (iii) Phase failure (iv) Phase sequence reverse (v) Over current (vi) Over load in KW (vii) High earth current (viii) Engine under / over speed (ix)Low / high lubricating oil pressure (x) Low / high engine coolant temperature (xi) Low fuel level (xii) Low coolant level. (xiii) Low radiator water level (xiv) Battery charging alternator fail (xv) Engine Start / Stop fail
5(C) ALTERNATOR Alternator, suitable to deliver rated output at 1500 RPM, 380-440V0.8 PF (lag), 50 Hz three phase in SPDP enclosure, , self excited & self regulated with brushless technology. The alternator conforms to IS: 4722 and IEC 34-1 & will suitable for tropical condition. Full load efficiency of the alternator offered should be above 90%, class of insulation shall be "H".
6(D) BASE FRAME Suitable to couple the 600 KVA / 480KW Engine & Alternator made from steel sheet metal. (E) FUEL TANK Capacity of the fuel tank should not be less than 12 Hrs continious run with inlet & outlet arrangement, air vent & drain plug arrangement. (F) BATTERY 2x12 V 180 AH M/F batteries with connecting leads and terminals.
7(G) TECHNICAL SPECIFICATION FOR ACOUSTIC ENCLOSURE (i) The enclosure shall be modular in construction. (ii) Base frame shall be made of sheet metal. (iii) Locking system shall be provided on all doors. (iv) Doors shall be gasketed with high quality EDPN gasket. (v) All sheet metal parts / components shall be hot dipped and gone through seven tanks process. (vi) Sheet metal components shall be painted with pure polyester powder coated. (vii) Base frame shall be epoxy coated.
8(H) ACOUSTIC INSULATION (i) Sound proofing of the enclosure done with quality foam conforming to IS:8183. (ii) Acoustic foam shall be FRFS (iii) Specially designed Residential silencer shall be provided. (iv) Hooks for lifting / shifting.
9(J) VENTILATION AND AIR CIRCULATION (i) Exhaust pipe is thoroughly insulated by covering it with glass wool and further gladded in enclosure. (ii) Suitable slots / ventilators need tobe provided in canopy for natural air circulation. (K) ELECTRICAL (i) Neutral body earthing pointsat the sides of enclosure are isolated through Dough Moulded compound. (ii) A light points with switch need to be provided inside the canopy.
10NOTES :- 1. Design / Drawing / BOM of the DG set showing the dimension is to be obtained from the OEM / Authorized supplier and to be got approved from GE before placing final order to the manufacturer. 2. The cost of servicing / minor repairs / replacement such as topping up of coolant, engine oil / lubricating oil as well as lubricating oil filter including periodical checking of the complete DG sets for the defect liability period and as when required is deemed to be included in the quoted rate. 3. Anything missed out in the technical specification but technically required for efficient working of DG set is deemed to be included in the quoted rate. 4. The quoted rate is deemed to be inclusive of first fill of engine oil and final successful acceptance test. 5. The quoted rate is deemed to be inclusive of all testing arrangement / equipement, resistive load or water load with measuring instruments including POL which shall be made available by the contractor. 6. The foundation drawing for installation of the DG set to be obtained from the manufacturer and the same is to be approved by Accepting Officer before starting the foundation work. The cost of the foundation shall also deemed to be included in the quoted rate.
11Excavating in trenches, n exec 1.5 mwide and n exec 1.5 m depth, for foundation/ laying of UG cables,etc or for shafts ,wells, cesspits, manholes, pier holes etc n exec 10 sq m on plain and n exec 1.5 m in depth and getting out soft or loose soil.all as specified and as directed by engr-in-charge.
12Returning, filling in, including spreading,leveling, watering and well ramming in layers not exc 25 cm in soft/loosesoil completeall as specified and directed.
13Removing excavated material not exc 50 mtr and deposited where directed at a level not exc 1.5 mtr above the starting point completeall as specified and directed.
14Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cableincludingspreading and punning down to desired thickness complete all as specified and as directed.(Note: Punned thickness shall be measured for payment purpose)
15Supplying and laying reinforced precast concrete cable cover, class LV, type 1 with flat, size 250mm x 150mm x 40mm complete all as specified and as directed.
16Supply and laying under ground XLPE insulated PVC sheathed (Heavy duty) armoured 1100 volts grade aluminium conductor cable of size 300 Sqmm 3.5 Core laid in trenches or fixed to wall / pole /ceiling as per IS 7098 (partI) including connection cable glands, aluminium lugs etc complete all as specified and as directed. Note : Earth work, brick protection and sand cushioning and GI Pipe will be measured and paid separately under respective items.
17M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.