Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Laying and Jointing PVC Pipe. Heading |
| 2 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system ( which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol Bacnet/ Modbus over IP complete as per specifications.Two Loop Panel |
| 3 | INTELLIGENT FIRE ALARM SYSTEM Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. |
| 4 | INTELLIGENT FIRE ALARM SYSTEM Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 5 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 6 | Supplying, installation, testing and commissioning of electric driven pressurization pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)(a) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520.(b) Suitable HP squirrel cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325.(c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.(d) Suitable cement concrete foundation duly plastered and with anti vibration pads.180 lpm at 56 m Head |
| 7 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. |
| 8 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 9 | PUBLIC ADDRESS SYSTEMSupplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required. |
| 10 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x1.5 sq. mm |
| 11 | CABLING & WIRINGSupplying & laying of 2x1.5 sq mm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required. |
| 12 | CABLING & WIRINGSupplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.speaker cable Two pair, 2- core, 1.5 sqmm |
| 13 | CABLING & WIRINGSupplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 14 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of response indicator on surface/ recessed MS Box having two LED, metallic cover complete with all connections etc as required. |
| 15 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 16 | INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 17 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recessincluding painting in case of surface conduit, or cutting the wall and making good the same incase of recessed conduit as required.25 mm |
| 18 | FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying,installation, testing & commissioning of main control and indicating panel made out of 16 SWG MS sheet to accommodate the following items duly powder coated in approved colour with louvers for ventilation, locking arrangement, audio and visual indication for fire alarm and public address system, monitoring system including connections, interconnections etc complete as required. |
| 19 | PUBLIC ADDRESS SYSTEMSupplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
| 20 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.300 mm width X 50 mm depth X 1.6 mm thickness |
| 21 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 22 | Wiring for circuit/ sub main wiring alongwith earth wirewith the following sizes of FRLS PVCinsulated copper conductor, single core cable in surface/ recessed steel conduit as required2x4 sq.mm + 1x4 sq.mm earth wire |
| 23 | CABLING & WIRINGSupplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required.speaker cable Single pair, 2-core, 1.5 sq mm |
| 24 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, conforming to IS-325.M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.Suitable cement concrete foundation duly plastered with anti vibration pads. 2850 lpm at 56 m Head |
| 25 | Providing laying, testing & commissioning ofclass heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.200 mm. dia (wall thickness = 6.3 mm) |
| 26 | Providing laying, testing & commissioning ofclass heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required.150 mm. Dia |
| 27 | Providing, laying, testing & commissioning ofclass heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :25 mm dia |
| 28 | Providing, laying, testing & commissioning ofclass heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :32 mm dia |
| 29 | Providing, laying, testing & commissioning of class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :40 mm dia |
| 30 | Providing, laying, testing & commissioning ofclass heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :50 mm dia |
| 31 | Providing, laying, testing & commissioning of class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :65 mm dia |
| 32 | Providing, laying, testing & commissioning ofclass heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm dia |
| 33 | Providing, laying, testing & commissioning of class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :100 mm dia |
| 34 | Providing, laying, testing & commissioning ofclass heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :150 mm dia |
| 35 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :80 mm dia |
| 36 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :100 mm dia |
| 37 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :150 mm dia |
| 38 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required :200 mm dia |
| 39 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :80 mm dia |
| 40 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :100mm dia |
| 41 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required :150mm dia |
| 42 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :4 way - 150 mm dia M.S. Pipe |
| 43 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.80 mm dia |
| 44 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.200 mm dia |
| 45 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Pendent Sprinkler |
| 46 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Upright Sprinkler |
| 47 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Horizontal side wall sprinkler |
| 48 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.100 mm dia |
| 49 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.150mm dia |
| 50 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required :150mm dia |
| 51 | Fabrication, supply, Installation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalized with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurization pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :INCOMING 250A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Digital Ammeter (0-250 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 300A OUTGOING ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pump 125 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 60 HP pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. Jockey Pump 63 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. DIESEL ENGINE CONTROL Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
| 52 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. |
| 53 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
| 54 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing RCC/ HUME/ METAL pipe as required.Above 95 sq. mm and upto 185 sq. mm |
| 55 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size in the existing masonry open duct as required.Above 95 sq. mm and upto 185 sq. mm |
| 56 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 57 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
| 58 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KVgrade of following size on cable tray as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
| 59 | Supplying and making end termination with brass compression gland and aluminium lugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required.3 1/2X 70 sq. mm (38mm) |
| 60 | Supplying and making end termination with brass compression gland and aluminium lugs forfollowing size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KVgrade as required.3 1/2 X 120 sq. mm (45mm) |
| 61 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 62 | Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 63 | Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 2 Nos 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. |
| 64 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 65 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 66 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 67 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 68 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.125 Amp,16 KA,TPMCCB |
| 69 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator6 way, Double door |
| 70 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way (4 + 24), Double door |
| 71 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA,curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 72 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA,curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole |
| 73 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 74 | Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. |
| 75 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. |
| 76 | Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep |
| 77 | Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required. |
| 78 | Supplying and fixing 50mm thick aluminium foil faced resin bonded fibre glass insulation (on duct) of density 24 kg/cu.m or mineral wool insulation of density 44 kg/cu m after applying two coats of cold setting adhesive (CPRX compound) sealing all joints with self adhesive aluminium tape & covering with 0.63mmx19mm GI wire mesh netting & butting all joints and laced with GI wire complete and finally covered with one layer of tar felt stuck with hot bitumen as per specifications and as required. (for outdoor applications)50 mm thick insulation |
| 79 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade offollowing size direct in ground including excavation, sand cushioning, protective covering andrefilling the trench etc as required.Upto 35 sq. mm |
| 80 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 81 | Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/ main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted.The damper shall also be closed in the event of fire signal complete as required and as per specifications.Fire damper |
| 82 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C |
| 83 | Wiring for circuit/ sub main wiring alongwith earth wirewith the following sizes of FRLS PVCinsulated copper conductor, single core cable in surface/ recessed steel conduit as required2X2.5 sq.mm+1X2.5 sq.mm earth wire |
| 84 | Wiring for circuit/ sub main wiring alongwith earth wirewith the following sizes of FRLS PVCinsulated copper conductor, single core cable in surface/ recessed steel conduit as required2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 85 | Wiring for circuit/ sub main wiring alongwith earth wirewith the following sizes of FRLS PVCinsulated copper conductor, single core cable in surface/ recessed steel conduit as required2 X 10 sq. mm + 1 X 6 sq. mm earth wire |
| 86 | Wiring for circuit/ sub main wiring alongwith earth wirewith the following sizes of FRLS PVCinsulated copper conductor, single core cable in surface/ recessed steel conduit as required4 X 6 sq. mm + 2 X 6 sq. mm earth wire |
| 87 | Wiring for circuit/ sub main wiring alongwith earth wirewith the following sizes of FRLS PVCinsulated copper conductor, single core cable in surface/ recessed steel conduit as required4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 88 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
| 89 | Providing, laying, testing & commissioning ofclass heavy dutyG.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :80 mm |
| 90 | Suppluying and Fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. |
| 91 | Supplying and Fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required. |
| 92 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular ducting as per IS 655-2006 Thickness 0.63 mm sheet |
| 93 | Supply, Installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports, etc as per approved drawings and specifications of following sheet thickness complete as required.Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.8. mm thick |
| 94 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Factory fabricated GSS sheet metal rectangular dueling as per IS 655-2006 Thickness 1.00 mm sheet |
| 95 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.factory fabricated GSS sheet metal rectangular dueling as per IS 655-2006 Thickness 1.25 mm sheet |
| 96 | Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required |
| 97 | Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes |
| 98 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*70 sqmm |
| 99 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-3.5C*120 sqmm |
| 100 | Providing and laying of HDPE PIPE OF 40mm outer dia with PN 4 rating by hand Moling/Mannual method Confirming to IS 4984 592 |
| 101 | S/I/T/C of LED Tube type luminaire 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the following:(a) Total system wattage 20 watt +/- 5%(b )Luminous efficacy lumens/watt >=95 (c)Power Factor >=0.95 |
| 102 | SITC of On-line UPS with inbuilt isolation transformer suitable for single phase AC input and single phase AC output, Floor mounted type, indicative power backup time of 60 mins through SMF batteries. 5KVA |
| 103 | supply and fixing of 4.5 KG DCP with CO2 gas cartridge fire extinguisher (conforming to IS:2171 with cylinder fully charged) |
| 104 | Providing, Installation, testing and commissioning of gun metal valves of following sizes as required 25 mm dia. |
| 105 | Providing and fixing ABC (Alumminium Phosphate) powder type fire extinguisher of 6 kgs capacity complete in all respect with ISI mark i/c fixing arrangement etc as required. |
| 106 | Supply of 18\"(450mm sweep1400 rpm exhaust fan heavy duty complete with shutter,blade etc as required |
| 107 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-4C*16 sqmm |
| 108 | Supplying and fixing of energy saving display EXIT Sign board high efficiency and long life for single side display, well ventilated powder coated having nominal size LED Lamp, battery to be installed on wall/ceiling etc, complete as required. |
| 109 | SITC Emergency light powerful light source in dark. Basically twin beam high intensity glow LED Light automatically glow in care of power failure. It requirement does not need glow both lamp here is separate switch provided for each lamp & EXIT Sign, These lights have the inbuilt feature of low battery protection at 9 volts & overcharging at 13 volts. Most suitable for hospitals etc and available in (2X10 Watt) 2 models(A) Twin beam high intensity glow LED Light. SPECIFICATIONS SLA rechargeable battery backup 1 hour backup/10 hours recharging period. For power utility protection bed switch provided. This switch is used in manned & unmanned timings power failure. FUNCTIONS AND CONTROL FUSE: Used for overloading and protection against short circuit. Use only appropriate rating (6AMP) FUSE. FUSE INDICATION:If this indication signing on it mean fuse is blown. LOW BATTERY: Defined as name it is glow in low battery condtion. LIGHT-1: Switch dedicated for light one on/off as per requirement of user. LIGHT2: This is same as switch one. It is notable point that single light increase the backup time. EXIT: Is on/off switch for exit signor display sign. BED SWITCH: This switch provide for protesting battery from futile use. MAINS: MAIN POWER IS INSERTED IN PRODUCT IS INDICATED BY THIS LED. |
| 110 | supply and installation at approved location approved make 4 nos. fire buckets of 24 guage galvanised steel, painted white inside and red outside and back on the bottom inscribed with letter FIRE in black and gold including stand fabricated out of sheet metal(16 guage) shade platform and associated civil works, painting etc as approved by fire authority. |
| 111 | SITCof Pillar box size 900 mm x 450mm x 250mm suitable for mounting incomer of 250 A MCCB/Main switch 4 Pole and energy meter 3 phase complete with eluotropic grade Aluminium bus bar of size 25mm x 19 mm mounted on galvanized M. S. body power quoted pilferage proof SMC door duly welded with S.S. withrain cover size 40mm x 40mm x 5mm x 600mm height in cutting 300 mm height below groundand covered with shode proof SMC sheet of 3 mm as required. |
| 112 | Supply and fixing of signanges on aluminium sheet 2.0mm(+-10%) fixing on wall/ceiling complete in all respect. |
| 113 | SITC of Tube Axial Lift Lobby Pressurization Fan for Ground Floor in Mild Steel construction suitable for suitable hp 50Hz F Class Induction Motor(3phase offered complete with motor mounting, Impeller balancing, Paint coating, Aluminum Impeller, Flanges Mounting arrangement, Wire Mesh, Supporting Frame etc.10,000 CFM minimum 25mm Static Pressure |
| 114 | SITC of Linear pneumatic heat Detection Tube with all necessary fittings & supports. (6mm dia x 3.0 mtr long) |
| 115 | Supply,installation,testing and commissioning of submersible dewatering pump set suitable forstorm water/sewage/raw water having rating upto 2.5 to 3.0 HP head 15mtr ,IP 68 with minimum capacity of 5 m3/Hr (82lpm) for normal/manual operation for normal conditions |
| 116 | SITC of 10 LB capacity NOVEC 1230, DLP Assembly with automatic valve, push in connector for tube, 10 LB NOVEC 1230 gas, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation. |
| 117 | Supply, Installation, Testing and Commissioning of fire rated pressurisationaxial fan in Mild Steel casing suitable for 1.5-2HP,1449 rpm,fan dia,600-700mm3-phase motorcomplete with motor mounting, impeller balancing, paint coating,mounting arrangement, Supporting frames along with starter panel complete as required for 10000 CFMincluding labour charges and civil work |
| 118 | Supply of PVC insulated and FR PVC Sheathed multicore copper conductor 1.1KV grade, conforming to grade IS 694 as required . 3*1.5 Sq.mm |
| 119 | Supply,Installation, Testing & Commissioning of Electricalpanel of cubicle construction,fabricated out of 2 mm thick CRCA sheet, compartmentalised with locakable doors, dust and vermin proof, powder coated with enclosure protection class IP 42 and suitable for operation on 3-phase, 50 Hz supply as required. (i) 16 Amp TPN MCB- 1No. (ii) MN9 Contractor 220 V- 2No. (iii) Overload Relay - 2 No. (iv) Multimeter- 1 No. (v) RYB indicator light (vi) Push Button (vii) Transformer 230V to 24 VAC- 1 No. (viii) 24 V PLA Relay - 1 No. (ix) Selector Switch Auto/Manual- 2 No. |
| 120 | \"SITC MasterControlUnit for controllingeach system, complete withpressure switches, buzzers and (D) electronichooters, including allnecessary accessories+ electrical wiring tomake each entiresystemfunctional.\" |
| 121 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding,top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing |