Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 07-01-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 14-01-2023 |
| Sl. No. | Item Description |
| 1 | Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc. complete all as specified and as directed. |
| 2 | M & L for point wiring for one light or one fan or one exhaust fan controlled by one switch complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 1.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC casing/capping of suitable size as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 1.5 sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed. |
| 3 | M & L for point wiring for one bell/ buzzer point controlled by one push button on the same board with other switches or on independent board complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 1.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC casing/capping of suitable size as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 1.5 sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed. |
| 4 | M & L for point wiring for one 3 pin/ 5 pin 5 Amps socket outlet on the same board complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 1.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC casing/capping of suitable size as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 1.5 sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed. |
| 5 | M & L for point wiring for one 3 pin/ 5 pin 5 Amps switch socket combination outlet on independent board complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 1.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC casing/capping of suitable size as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 1.5 sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed. |
| 6 | M & L for point wiring for one 3 pin/ 5 pin 15 Amps socket socket combination outlet on independent board complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 2.5 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC casing/capping of suitable size as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 1.5 sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed. |
| 7 | S & F switch, 6A, single pole, one way, 240 V, AC, 50 Hz, ordinary (IPXO), normal gap construction, unenclosed, flush type, screw type terminals, pattern no. 1, rocker type, design A complete all as specified and as directed. (Cat No. AHESXXW061 of make Havells REO or equivalent in Anchor/Legrand) |
| 8 | S & F (3 pin and 2 pin) combined socket outlets, 6A, 240 V, AC, 50 Hz with earthing contact, rewirable, pillar type terminal, normal protection, unenclosed, without Shutter, Flush type, Design B complete all as specified and as directed. |
| 9 | S & F switch socket combination with 3 pin socket outlets, 6A, 240 V, AC, 50 Hz with earthing contact, rewirable, pillar type terminal, normal protection, unenclosed, without Shutter, Flush type, Design B and switch, 6 A, single pole, one way, 240 V, AC, 50 Hz, ordinary (IPXO), normal gap construction, unenclosed, flush type, screw type terminals, pattern no. 1, rocker type, design A complete all as specified and as directed. |
| 10 | S & F switch socket combination with (3 pin and 3 pin) having two earthing pins, combined socket outlets, 6A & 16A, 240 V, AC, 50 Hz with earthing contact, rewirable, pillar type terminal, normal protection, unenclosed, without Shutter, Flush type, Design B and switch, 16 A, single pole, one way, 240 V, AC, 50 Hz, ordinary (IPXO), normal gap construction, unenclosed, flush type, screw type terminals, pattern no. 1, rocker type, design A complete all as specified and as directed. |
| 11 | S & F bell push, 6A, single pole, one way, 240 V, AC, 50 Hz, ordinary (IPXO), normal gap construction, unenclosed, flush type, screw type terminals, pattern no. 1, rocker type, design A complete all as specified and as directed. |
| 12 | S & F call bell suitable for single phase, AC, 240 volts complete all as specified and as directed. |
| 13 | S & F Bayonet plastic lamp holder, 2 A, 250 V, ordinary, backplate, non-switched, unenclosed, without T marking, B22d complete all as specified and as directed. |
| 14 | S & F step type electronic fan regulator, capacitor type, 100 watt, 240 volts, 50 Hz, single phase, flush type on the existing phenolic laminated sheet complete all as specified and as directed. |
| 15 | S & F ceiling roses, 6A, 240 V, surface type, intended to support mechanical loads by means of flexible cord, having provision for the connection of switch wiring, screw type terminal, made out of Polyamide or hornbean complete all as specified and as directed. |
| 16 | S& F surface and wall mounted LED T/L Fittig with wide angle profile high lumen with efficiency of 100 lumens batten extruded aluminium housing provided for efficient heat dissipation with polycarbonate housing & integrated electronic driverincluding LED tube light 18 watt6500K 4 feet complete all as specified and directed. Make: Havells CAT Part No LUMILINE+BS18WLED840SPCSS/ LUMILINE/BS18WLED865SPCSS |
| 17 | S& F Recess mounted SQUARE shaped 2\"x2\" size LED downlighter with durable housing with AIuminium heat sink with PC diffuser in white powder coated finish with integrated driver to give glare free light with removable driver 24 W LED 6000K complete all as specified and directed.Make Havells Cat Part NoPLANO2X2PLR24WLED840S |
| 18 | Supply and fixing Recess mounted SQUARE shaped 2\"\"x2\"\" size LED downlighter with durable housing with Aluminium heat sink with PC diffuser in white powder coated finish with integrated driver to give glare free light with removable driver 36 W LED 6000K warm white light complete all as specified and directed. (Make : Havells Cat Pat No. PLAN02X2PLR36WLED840S or Equivalent in Phillips/Wipro) |
| 19 | S & F single door MCB Distribution board of sheet metal enclosure, single pole and neutral, 4 way with 100 Amps rated bus bar, 240 volt, IP42 protection grade and fixed with PVC plug and screws and grouted in wall with M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 20 | S & F single door MCB Distribution board of sheet metal enclosure, single pole and neutral, 8 way with 200 Amps rated bus bar, 240 volt, IP42 protection grade and fixed with PVC plug and screws and grouted in wall with M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 21 | S & F single door MCB Distribution board of sheet metal enclosure, single pole and neutral, 2 way with 200 Amps rated bus bar, 240 volt, IP42 protection grade and fixed with PVC plug and screws and grouted in wall with M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 22 | S&F MCB SP 240 volts 6 to32 Amps, 10 KA breaking capacity, ’C’ Curve including connection with suitable size aluminum/copper lugs complete all as specified and directed by Engr-In-charge. (Make: - L&T Cat no-BB10320C, BB10100C, BB10060C, Schneider, ABB, Havells or equivalent) |
| 23 | S&F MCB SP 40 amps, 10KA, 240V rating, to be housed in DBs catered here in before complete all as specified and as directed. (Make : L&T Cat No. BB10060C, BB10100C, BB10200C, BB10320C, Schneider, ABB, Havells or equivalent) |
| 24 | Taking down ceiling fan/ exhaust fan, any sweep by unscrewing the U clamp, minor repair, cleaning the ceiling fan with moist cloth with detergent powder and rehanging the same after replacing the flexible copper conductor of suitable dia complete all as specified and as directed. |
| 25 | S & F suitable size fan hook made of mild steel including suitable size of clamp for mounting ceiling fan to be attached with RCC roof, truss roof etc. complete all as specified and directed. |
| 26 | Supply & fixing ceiling fans energy efficient 1200mm sweep complete including provision of PVC insulated copper multi starnded three core flexible cable for making necessary electricalconnections from ceiling rose to connector all as required at site.MAKE- USHA 1200MM ENERGIA 32 (BLDC) 5 STAR or equivalent. |
| 27 | Supply and fix sub main wiring complete with and including two Nos single core PVC insulated, unsheathed flexible conductor FR-LSH cables 4 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through and including heavy mechanical stresses class and -5 temperature class PVC casing/capping of suitable size as required at site including all accessories and fixed on walls and 2.5 sqmm one No single core copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable for earthing and connected to common earth dolly complete all as specified and directed by Engineer-in-charge. Note - Two runs of 4 sqmm cable, one run of 2.5 sqmm cable and one run of casing/capping shall be measured and paid as one unit length. Cost of cutting chase and making good shall be included in the quoted rate. |
| 28 | Supply and fix sub main wiring complete with and including two Nos single core PVC insulated, unsheathed flexible conductor FR-LSH cables 6 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through and including heavy mechanical stresses class and -5 temperature class PVC casing/capping of suitable size as required at site including all accessories and fixed on walls and 4 sqmm one No single core copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable for earthing and connected to common earth dolly complete all as specified and directed by Engineer-in-charge. Note - Two runs of 6 sqmm cable, one run of 4 sqmm cable and one run of casing/capping shall be measured and paid as one unit length. |
| 29 | Supply and fixMCB changeover63 Amps, 10 KA , C Series complete all as specified and directed. Note:- MCB Rating shall be suitable to the existing DB.Make-havelles cat Part No-DHMGODPX063 or equivalent |
| 30 | S&F metal clad socket out let with MCB three pole(3 P) 20 Amp including sheet metal enclosure complete 2nd class hard wood wooden board including complete electrical connection by proper size of copper lugs complete all as specified and directed.Havells Cat No DHDPUTN020 / DHDPUTN030 |
| 31 | S&F metal clad socket out let with MCB two pole (P+N) 20Amp including sheet metal enclosure complete 2nd class hard wood wooden boards including complete electrical connection by proper size of copper lugscomplete all as specified and as directed. MAKE : Havells cat part No. DHPPUSN020/DHDPUDP020 |
| 32 | M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 4.0 mm dia galvanised mild steel wire by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 20 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge. |
| 33 | Supplying and fixing PVC insulated cable for working voltages of 1100 V, PVC sheathed, unarmoured, 2 core, flat or circular nominal cross sectional area of main conductor 6 sqmm, stranded aluminium conductor, ISI marked as per IS 1554(Part-I): 1988 including cable glands, lugs etc. to suit the cable in service connections suspended by insulating hangers not more than 1 metre apart including 4 sqmm suspension wire complete all as specified and as directed. |
| 34 | Supplying and fixing PVC insulated cable for working voltages of 1100 V, PVC sheathed, unarmoured, 2 core, flat or circular nominal cross sectional area of main conductor 10 sqmm, stranded aluminium conductor, ISI marked as per IS 1554(Part-I): 1988 including cable glands, lugs etc. to suit the cable in service connections suspended by insulating hangers not more than 1 metre apart including 4 sqmm suspension wire and taking down complete all as specified and as directed. |
| 35 | Supplying and fixing PVC insulated cable for working voltages of 1100 V, PVC sheathed, unarmoured, 2 core, flat or circular nominal cross sectional area of main conductor 16 sqmm, stranded aluminium conductor, ISI marked as per IS 1554(Part-I): 1988 including cable glands, lugs etc. to suit the cable in service connections suspended by insulating hangers not more than 1 metre apart including 4 sqmm suspension wire complete all as specified and as directed. |
| 36 | Supply only 15W LED new adore 15W B22 cool day light ball lamp all as specified and directed. Make HavellsCatNo CLASSYLED 15 W B22CDL 3 STAR |
| 37 | Supply only 13 W LED new adore 13W B22 cool day light ball lamp all as specified and directed. Make HavellsCatNo CLASSYLED 13 W B22CDL 3 STAR |
| 38 | Supply Only Insulation tap of Red,yellow,blue ,green or black colour for day to day complain and wiring working at 240 V ac and for phase must be colour and for neutral must be black colour . |
| 39 | Supply only fan capacitor 2.5 MFD complete all as specified and directed.MAKE : Bajaj / Universal / Usha. |
| 40 | S & F exhaust fan, AC, 50 Hz, single phase, 230 V, 300 mm sweep, 4 pole, heavy duty, metal body, 4 Nos blades, Insulation Class A, ISI marked including capacitor to ensure power factor more than 0.9 including louvers complete all as specified and as directed. |
| 41 | S & F exhaust fan, AC, 50 Hz, single phase 230 V, 250 mm sweep, 4 pole, heavy duty, metal body, 4 Nos blades, Insulation Class A, ISI marked including capacitor to ensure power factor more than 0.9 including louvers complete all as specified and as directed. |
| 42 | S & F heavy mechanical stresses class and -5 temperature class PVC casing/capping of size 25 mm X 16 mm including accessories complete all as specified and as directed. |
| 43 | S & F heavy mechanical stresses class and -5 temperature class PVC casing/capping of size 32 mm X 16 mm including accessories complete all as specified and as directed. |
| 44 | Supply only FRLSH PVC insulated, single core, 1100 Volts,1.5 Sqmm complete all as specified and directed. Make- Havells . Cat No- WHFFFN…A11X5 |
| 45 | Supply only cable FRLSH PVC insulated, single core, 1100 Volts,2.5 Sqmm complete all as specified and directed. Make- Havells . Cat No- WHFFFN…A12X5 |
| 46 | Supply onlycable FRLS PVC insulated, single core, 1100 Volts,4.0 Sqmm complete all as specified and directed. Make- Havells . Cat No- WHFFFNA14X0 |
| 47 | Supply onlyFRLS PVC insulated, single core, 1100 Volts, 6.0 Sqmm complete all as specified and directed. Make- Havells . Cat No- WHFFFNA16X0 |
| 48 | Decanting of used lub oil from chamber/sump of the DG set of capacity 30 to 40 KVA and cleaning of chamber thoroughly to remove all types of deposites and supply & filling of new lub oil SAE 20 W/40 W at required level including replacement of all types of filters such as fuel filter, screen filter, oil filter etc. all as specified and directed. NOTE:-(i) Spares and engine oil shall be measured and paid separately under respective items. (ii) Periodicity/location of the DG set shall be intimated by Engr-in-Charge as and when required.(iii) Work shall be carried out at scattered locations at different sector. |
| 49 | Decanting of used lub oil from chamber/sump of the DG set of capacity 50 to 62.50 KVA and cleaning of chamber thoroughly to remove all types of deposites and supply & filling of new lub oil SAE 20 W/40 W at required level including replacement of all types of filters such as fuel filter, screen filter, oil filter etc. all as specified and directed. NOTE:-(i) Spares and engine oil shall be measured and paid separately under respective items. (ii) Periodicity/location of the DG set shall be intimated by Engr-in-Charge as and when required.(iii) Work shall be carried out at scattered locations at different sector. |
| 50 | Supply only Oil filter spares of DG set complete all as specified and directed. |
| 51 | Supply only fuel filter spares of DG set complete all as specified and directed. |
| 52 | Supply only Screen/Air filter spares of DG set complete all as specified and directed. |
| 53 | M&L for taking out FIP from DG set and calibration of fuel injection pump as per standard calibration procedure for 30 to 62.5 KVA DG set including pressure cleaning og fuel nozzals,replacement of minor spares, gaskets etc and refixing the same at its original position including transportation to and fro and testing at site on full load all as specified and directed. |
| 54 | labour for strip opening and taking out of cylinder head of 30 to 62.5KVA DG Set at site including dismantling of inlet/exhaust valves,pistons,head gasket, bearings of any description hose pipes fan belt etc all as required and setting/tunning up of DG set and replacement of faulty parts, gaskets etc,including turning/tappering of any parts at lath machine, re-assembling and testing complete all as specified and directed.Note: Spares shall be measured and paid separately. |
| 55 | Supply & fix in replacement of Cylinder liner of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 56 | Supply & fix in replacement of Piston of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 57 | Supply & fix in replacement of Piston ring set of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 58 | Supply & fix in replacement of Inlet/Exhaust valve of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 59 | Supply & fix in replacement of Valve lock of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 60 | Supply & fix in replacement of Main bearing of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 61 | Supply & fix in replacement of Liner O ring of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 62 | Supply & fix in replacement of By pass hose with clamps of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 63 | Supply & fix in replacement of Cupper washer set of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 64 | Supply & fix in replacement of Oil sump gasket of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 65 | Supply & fix in replacement of Water pump gasket of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 66 | Supply & fix in replacement of Fuel pipe suction/return of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 67 | Supply & fix in replacement of Injector over flow pipe of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 68 | Supply & fix in replacement of Valve seal of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 69 | Supply & fix in replacement of Fly wheel housing gasket of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 70 | Supply & fix in replacement of Head gasket of existing size for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 71 | M&L for taking out unsv Turbo Charger from DG set and repair/overhauling/setting of Turbo Charger including replacement of charger kit for DG set of capacity 40 to 62.5 KVA and refixing the same with DG set and testing of DG set for smooth functioning complete all as specified and directed. |
| 72 | M&L for rewinding of alternator with existing class copper super enamelled wire of existing gauge including servicing and overhauling, varnishing,drying and fixing insulating sleevs etc including transportation from site to workshop and back from workshop to site and refixing the same to its original position and testing at site on full load all as specified for DG set 40 to 62.5 KVA and as directed. |
| 73 | M&L for rewinding of commutator/armature including servicing and overhauling, varnishing in field coil etc including transportation from site to workshop and back from workshop to site and refixing the same to its original position and testing at site all as specified for DG set 40 to 50 KVA and as directed. |
| 74 | M&L for strip opening and rewinding of dynamo assy with super enamelled copper winding wire of existing gauge and insulation including insulating material and replacement of unsv parts such as carbon bush set,bush holder etc and refixing the same to its original position and testing on full load including taking out/dismantling of Dynamo assy from the DG set transporting it to workshop and back to site. Note:- Cost of any other essential spares required for repair shall be deemed included in unit rate quoted and no extra cost shall be paid for the same. |
| 75 | M&L for taking out/dismantling of water pump after disconnecting of radiator assy for complete repair and servicing of water pump replacement of kit,bearing etc for 40 to 62.5 KVA DG set including transportation from site to workshop and workshop to site and refixing the same to its original position including testing on completion. |
| 76 | M&L for taking out/dismantling of water pump after disconnecting of radiator assy for complete replacementof radiator assembly along with necessarykit,bearing etc for 40 to 50 KVA DG set including transportation from site to workshop and workshop to site and refixing the same to its original position including testing on completion.(Location: 19 WEU & Thakubari PH ) |
| 77 | Dismantling / taking down the governor assembly including all connected parts from DG set 30 KVA to 62.5 KVA and over hauling, calibration of fuel supply system,governor etc complete including renewal of wornout parts such as copper gasket, injector nozzle to maintain the desired fuel supply and provide fluctuation free output complete all as specified and directed. |
| 78 | Draining out old used water with coolent from the radiator ofGen Set of capacity 30 KVA to 62.5 KVA capacity after disconnecting the water pipe, de-scaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and renewal of coolant solution complete all as directed by EIC.(Coolant shall be measured separatelyunder appropriate items). |
| 79 | Supply, fixing, connecting, testing maintenance free battery, 12 volts, 180 Ah with lead acid terminals including initial charging of battery complete all as specified. (Make EXIDE / AMRON) including disconnection existing unserviceable battery. |
| 80 | Supply, fixing, connecting, testing maintenance free battery, 12 volts, 150 Ah with lead acid terminals including initial charging of battery complete all as specified. (Make EXIDE / AMRON) including disconnection existing unserviceable battery. |
| 81 | Dismantling and taking out unserviceable onload change over switch flush mounting type and supply & fixing new onload change over, 4 pole with front handle operated flush mounting of rating 100 Amps including making all electrical connections of incoming/outgong cables of any description/size with suitable size of lugs/thimbles,nuts,bolts & washers complete all as specified and directed. |
| 82 | Supply & fixing in replacement battery charging sets 12V with transformer, rectifyre,DC Ammeter, DC voltmeter,charging rate selector switch with OFF/TRICKLE/BOOST including rewiring of faulty control circuit,suitable length of stranded copper conductor PVC cable 2.5 sqmm 3 run from power point to battery charger and 2 run from battery charger to battery etc suitable for 12 volt battery charging unitcomplete all as directed. |
| 83 | Supply & fix in replacement dynamo 12V suitable for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 84 | Supply & replacement of rubber coupling of DG sets of capacity 40KVA complete including nuts,bolts and other connected items all as specified and directed. |
| 85 | Supply & fix in replacement carbon bush holder suitable for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 86 | Supply & fix in replacement carbon bush suitable for DG sets of capacity 30 to 62.5 KVA complete all as specified and directed. |
| 87 | M&L for preparation of surface by scrapping existing painted surface and spray painting of canopy, alternator/diesel engine body, radiator base frame etc and applying one coat of synthetic enamel paint of existing colour and one coat of heat resistant paint of approved quality to engine and exhaust pipe including writing SM/MES No of DG set capacity 30 to 62.5 KVA all as directed by Engineer-in-charge. |
| 88 | Supply and fixing, in replacement, of automatic power factor relay 12 steps with and including taking out old unsv and making all connection, testing for smooth functioning complete all as directed. Make L&T. etaSMART-14R or equivallent. |
| 89 | Supply and fixing, in replacement, of auxillary contact MXO 22E (2NO+2NC) suitable for power factor control panel of 12 steps with and including taking out old unsv and making all connection, testing for smooth functioning complete all as directed. Make L&T or equivallent. |
| 90 | Supply and fixing, in replacement, ofAutomatic Voltage Regulator (AVR) suitable for DG Set of 30 KVA to 62.5 KVA capacity of any make, with and including taking out old AVR and making all connection, testing for smooth functioning complete all as directed. |
| 91 | Supply and fixing synthetic insulating mat of size 2mx1mx25mm suitable for working pressure 3.3 KV complete all as specified and directed. |
| 92 | M&L for rewinding of excitor coil with existing size of super enamelled copper wire including necessary insulating material such as ampere tube tape,resin tape,applying F class varnishing and heating,drying up for better insulating resistance and testing after completion including commissioning complete all as specified and directed. |
| 93 | M&L renewal of burnt battery lead heavy duty with & including 2.0 metre long copper conductor wire suitable for 30 KVA to 62.5 KVA DG set consisiting with suitable size of lugs and heavy duty terminal complete all as specified and directed. |
| 94 | M&L for renewal of battery terminal heavy duty made out of brass suitable for 12 V lead acid battery. |
| 95 | Engine oil 20 W 40 suitable for DG sets of any capacity. |
| 96 | Coolant for radiator of DG sets of any capacity. |
| 97 | M&L for fan belt of any size suitable for DG sets of any capacity. |
| 98 | M & L in repairs MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 kA complete all as specified and as directed. |
| 99 | M & L for MCCB 4 Pole, 415 V, adjustable thermal & adjustable magnetic setting, 200 Amps with breaking capacity 36 kA complete all as specified and as directed. |
| 100 | Supply and wrapping Asbestos rope 8mm dia of superior quality to the silencer pipe and muffler of DG set of capacity 30 KVA to 62.5 KVA including binding with 2mm dia GI binding wire and provinding white cement/plaster of paris to the Asbestos rope for smooth finishing all as specified and directed. |
| 101 | Supply and fixing garden bollard lightmount type new generation 8 watts 6500K IP-65 protection outdoor type asthetically designed suitable for landscape/garden lights having modern look complete including making necessary electrical connection and testing on completion. Havells BAMBOOBL8WLED830SSYMTOPCM (0.6 M). |
| 102 | Supply and fixing garden focuslight for object in mono colour/multi colournew generation 12 watts 6500K IP-65 protection outdoor type asthetically designed suitable for landscape/garden lights having modern look complete including making necessary electrical connection and testing on completion. Philips 31386 12-Watt COB Garden Spike (Anthracite) |
| 103 | M & L for cement concrete in foundation, filling and mass concrete in M15(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed. |
| 104 | Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed. |
| 105 | Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and getting out in soft/ loose soil complete all as specified and as directed. |
| 106 | Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed. |
| 107 | Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed. |
| 108 | M & L for sand filling under floors or in foundations including watering and consolidation complete all as specified and as directed. |
| 109 | M & L for laying of bricks locally available sub class \"B\" bricks (old size) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed. |
| 110 | Supply and Fix 25x4mm GIstrip earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as directed including taking down of old unserviceable existingsystem. |
| 111 | M&L for porceiline insulator suitable for fixing earthing strip to the wall / floor etc all as specified and as directed |
| 112 | Supply and fix Air termination (vertical conductor), single pointed aluminium rod 12 mm dia and 300 mm long including suitable design of fixing components of gun metal as per fig 30 of IS 2309: 1989 all as specified and as directed. |
| 113 | Taking down old unsv and M&L for Test point terminal box made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hexagonal head screwed including removing the existing old unsv one |
| 114 | M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy