Military Engineer Services-MES has published Tender For Repair And Maintenance Of Ext Electric Lt Distribution Network And Connected Item Of Work At Md Accn Areas At Chandimandir. Submission Date for this Tender is 13-01-2023. Electrical Maintenance Tenders in chandimandir Haryana. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 06-Jan-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 13-01-2023 |
Sl. No. | Item Description |
1 | Excavation in trenches for foundations, laying / taking out of cables, erecting of poles etc, in any type of soil, not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr in width and getting out, complete all as specified and as directed. |
2 | Returning, filling in soils, in trenches including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed. |
3 | Removing excavated soils to a distance exceeding 50 metres and not exceeding 100 metre and depositing where directed at a level not exceeding 1.50 metre above the starting point. |
4 | M & L for sand cushioning for protection of cable (below, above and around the cable laid in trenchs) all as specified and as directed.Note.Punned thickness shall be measured. |
5 | Supply and laying 50mm outer dia, double walled, corrugated HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed. |
6 | Material and labour for cutting existing bituminous/cement concrete road/hard standing/pavement of size 30 cm x 30cm for passing through the cables/pipes and surrounding /filling the entire cut space with cement concrete 1:2:4 type B-I after laying of pipe/cable and finishing the top surface fair and even complete all as specified and as directed. |
7 | M&L plain cement concrete 1:2:4 type B-1 using 20 mm graded curshed stone aggregate in coping to pedestal of poles including necessay from work, fair finished surface, chamfered or rounded edges complete all as specified and directed by Engr-in-Charge. |
8 | M&L plain cement concrete 1:3:6 type C-2 using 40 mm graded curshed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly complete all as specified and directed by Engr-in-Charge. |
9 | Disconnecting and taking out old damaged/ defective LT cable from trenches or taking down from poles or taking out from pipes below or above ground level, or for rerouting of cable aluminium conductor 1100 volts grade, size6 sqmm 2 core, testing for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No26 herein after and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
10 | All as per the description of serial item-9 here-in-above but for of size 10 sqmm 2 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 27 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
11 | All as per the description of serial item-9 here-in-above but for of size 16 sqmm 4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 28 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
12 | All as per the description of serial item-9 here-in-above but for of size 25 sqmm 4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 29 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
13 | All as per the description of serial item-9 here-in-above but for of size 35 sqmm 4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 30hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
14 | All as per the description of serial item-9 here-in-above but for of size 50 sqmm 3.5/4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 31 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
15 | All as per the description of serial item-9 here-in-above but for of size 70 sqmm 3.5/4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 32 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
16 | All as per the description of serial item-9 here-in-above but for of size 95 sqmm 3.5/4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 33 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
17 | All as per the description of serial item-9 here-in-above but for of size 120 sqmm 3.5/4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 34 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
18 | All as per the description of serial item-9 here-in-above but for of size 185 sqmm 3.5/4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 35 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
19 | All as per the description of serial item-9 here-in-above but for of size 240 sqmm 3.5/4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 36 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
20 | All as per the description of serial item-9 here-in-above but for of size 300 sqmm 3.5/4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 37 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
21 | All as per the description of serial item-9 here-in-above but for of size 400 sqmm 3.5/4 coretesting for serviceability of cable cutting and segregating serviceable portion of the cable to be reused/incorporated vide serial item No 38 hereinafter and removing unserviceable cable from site of work including taking out cable cover and pipe complete all as specified and as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
22 | Dismantling of old vintage steel tubular poles alongwith insulators and disposing off from site complete all as specified and directed by Engr-in - Charge. |
23 | Taking down existing damaged/ unserviceable aluminum ACSR conductor/ GI wire of any size from HT/LT poles complete all as specified and directed by Engr-in-Charge. |
24 | Taking down unserviceable cross arm /clamps/nut bolts etc from HT/LT poles complete all as specified and directed by Engr-in-Charge. |
25 | Taking down old unserviceable Pin/disc/shackle/loop type insulators complete all as specified and directed by Engr-in-Charge. |
26 | Laying only, jointing and testing LT cable PV C insulated armoured, heavy duty 1100 volts grade with aluminium conductor of size 6.00 Sqmm 2.00 core in trenches or thorugh ducts/ pipes or fixed to poles or walls through pipes under road, jointing to OH conductor, LT panle, main swithces etc, serviceable cable as retrieved vide serial item No 9 here in above complete all as directed. |
27 | All as per the description of serial item-26 here-in-above butof size 10.00 sqmm 2 core, serviceable cable as retreived vide serial item No 10 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
28 | All as per the description of serial item-26 here-in-above butof size 16.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 11 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
29 | All as per the description of serial item-26 here-in-above butof size 25.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 12 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
30 | All as per the description of serial item-26 here-in-above butof size 35.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 13 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
31 | All as per the description of serial item-26 here-in-above butof size 50.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 14 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
32 | All as per the description of serial item-26 here-in-above butof size 70.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 15 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
33 | All as per the description of serial item-26 here-in-above butof size 95.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 16 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
34 | All as per the description of serial item-26 here-in-above butof size 120.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 17 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
35 | All as per the description of serial item-26 here-in-above butof size 185.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 18 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
36 | All as per the description of serial item-26 here-in-above butof size 240.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 19 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
37 | All as per the description of serial item-26 here-in-above butof size 300.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 20 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
38 | All as per the description of serial item-26 here-in-above butof size 400.00 sqmm 3.5/4 core, serviceable cable as retreived vide serial item No 21 herein above complete all as directed. Note : Excavation and earthwork shall be measured and paid for separately. |
39 | Supply,laying , jointing and testing LT underground electric cable XLPE insulated, PVC sheathed armoured heavy duty 1100 volts grade heavy duty multystranded aluminium conductor of size 6 Sqmm 2 core laid in trenches / ducts or passing through under road or fixed to poles or walls complete all as specifed and as directed by Engr in Charge. |
40 | All as per item No 39 above but of size 10 sqmm 2 core complete all as specified and directed by Engr-in-Charge. |
41 | All as per item No 39 above but of size16 sqmm 4 core complete all as specified and directed by Engr-in-Charge. |
42 | All as per item No 39 above but of size 25 sqmm 4 core complete all as specified and directed by Engr-in-Charge. |
43 | All as per item No 39 above but of size 35 sqmm 4 core complete all as specified and directed by Engr-in-Charge. |
44 | All as per item No 39 above but of size 50 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
45 | All as per item No 39 above but of size 70 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
46 | All as per item No 39 above but of size 95 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
47 | All as per item No 39 above but of size 120 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
48 | All as per item No 39 above but of size 185 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
49 | All as per item No 39 above but of size 240 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
50 | All as per item No 39 above but of size 300 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
51 | All as per item No 39 above but of size 400 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge. |
52 | M&L for drawing out of LT ACB 4 pole 415 volts of capacity 630/800/1000/1200 amps form the LT panel and servicing/ repair the same for proper functioning, tightening the loose hardware part and loose connection and lubricating the all mechanism, clean all contacts with fine emery paper and CRC, replacement of burnt/defective parts applying petroleum jelly on the contacts, refixing in the original position and checking for proper functioning complete all as specified and directed by Engr -in-Charge. Note - Defective parts will be measured and paid seprately under item no 53 to 57. |
53 | Supply only fixed contacts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge. |
54 | Supply only moving contacts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge. |
55 | Supply only spring charging and operating mechanism as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge. |
56 | Supply only shunt trip coil 240 volts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge. |
57 | Supply only CT as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge. |
58 | Supply and laying 100mm outer dia, double walled, corrugated HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed. |
59 | Supply and layingwell burnt bricks,sub class "B"bricks of size laid breath wise along length of cable in trenches for cable protection laid for UG cable complete all as specified and directed. |
60 | Supply and laying40 mm bore tube "light grade" galvanised iron pipe laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed by Engr-in- Charge. |
61 | Supply and laying50 mm bore tube "light grade" galvanised iron pipe laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed by Engr-in- Charge. |
62 | Supply and laying 80 mm bore tube "light grade" galvanised iron pipe laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed by Engr-in- Charge. |
63 | Supply and laying 100 mm bore tube "light grade" galvanised iron pipe laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed by Engr-in- Charge. |
64 | Supply and laying 150 mm bore tube "light grade" galvanised iron pipe laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed by Engr-in- Charge. |
65 | Labour for fixing straightening and tightening of old ACSR including all arrangement/binding using 2 mm dia/ aluminum tape and ACSR jumpers complete all as specified and directed by Engr-in-Charge. |
66 | Removing wild grass, vegetation, creeper etc aroung LT panel , climbing up towards poles and stay assembly including cleaning bottom surface of pole, stay assemble of area not less than 1m x 1m by surface dressing not exceeding 0.5 m deep in soft/loose soil complete all as specified and directed by Engr-in-Charge. |
67 | M&L for pin type insulator porcelain, viteous white/brown including one galvanised MS spindle, two GI washers and one GI nut, 100 mm height, 65 mm dia for 1100 volts grade complete all as specified. |
68 | M&L for shackle type insulator porcelain, viteous white/brown including galvanised mild steel, straps, washers insulator bolts nuts,75 mm height and 90 mm dia, size of strap 31 mm x 3 mm and dia of bolt 12 mm suitable for 1100 volts complete all as specified and directed by Engr-in-Charge. |
69 | M&L for loop type insulator, vitreous porcelain, white brown and green, large size with overall dimensions 90 mm x 140 mm clerance of hole 25.5 mm complete all as specified and directed by Engr-in-Charge. |
70 | Supply and fixin replacement fixed type MCCB four pole 400 amps 415 volt , 50 Hz breaking capacity not less than 36 KAcomplete all specified and directed by Engr-in-Charge. |
71 | Supply and fixin replacementfixed type MCCB four pole 320/350 amps 415 volts, 50 Hz breaking capacity not less than 25 KAcomplete all specified and directed by Engr-in-Charge. |
72 | Supply and fixin replacementfixed type MCCB four pole 250 amps 415 volts, 50 Hz breaking capacity not less than 25 KAcomplete all specified and directed by Engr-in-Charge. |
73 | Supply and fixin replacementfixed type MCCB four pole 200 amps 415 volts, 50 Hz breaking capacity not less than 25 KAcomplete all specified and directed by Engr-in-Charge. |
74 | Supply and fixin replacementfixed type MCCB four pole 160 amps 415 volts, 50 Hz breaking capacity not less than 25 KAcomplete all specified and directed by Engr-in-Charge. |
75 | Supply and fixin replacementfixed type MCCB four pole 120 amps 415 volts, 50 Hz breaking capacity not less than 25 KAcomplete all specified and directed by Engr-in-Charge. |
76 | Supply and fixin replacementfixed type MCCB four pole 100 amps 415 volts, 50 Hz breaking capacity not less than 25 KAcomplete all specified and directed by Engr-in-Charge. |
77 | S&F in replacement change over switch ON LOAD type, 415 volt, 50 Hz, AC 4 pole in sheet steel enclosures, capacity 250 Amps rated current manually operated confirming to IS : 13947 or lates edition with hight thermal and dynamic strength to with stand short circuit current level of 80 KA rms complete all as specified and directed by Engr-in-Charge. |
78 | S&F in replacement change over switch ON LOAD type, 415 volt, 50 Hz, AC 4 pole in sheet steel enclosures, capacity 315 Amps rated current manually operated confirming to IS : 13947 or lates edition with hight thermal and dynamic strength to with stand short circuit current level of 80 KA rms complete all as specified and directed by Engr-in-Charge. |
79 | S&F in replacement change over switch ON LOAD type, 415 volt, 50 Hz, AC 4 pole in sheet steel enclosures, capacity 400 Amps rated current manually operated confirming to IS : 13947 or lates edition with hight thermal and dynamic strength to with stand short circuit current level of 80 KA rms complete all as specified and directed by Engr-in-Charge. |
80 | S&F in replacement change over switch ON LOAD type, 415 volt, 50 Hz, AC 4 pole in sheet steel enclosures, capacity 600 Amps rated current manually operated confirming to IS : 13947 or lates edition with hight thermal and dynamic strength to with stand short circuit current level of 80 KA rms complete all as specified and directed by Engr-in-Charge. |
81 | M&L for painting of steel tubular poles 9 mtr long above ground level with two coats aluminum paint after preparation of surface including providing reflective strips of width 10 cm up to a height of 1.20 m from ground level in alternate colour green white and green complete all as specified and directed. |
82 | M&L in repairs electric panel doors fabricated from MS sheet as per existing size and shape and fixed with hinges by properly welding and checking for proper opening and closing complete including two coat of synthetic enamel paint as per existing clolour all as specified and directed. |
83 | Supply and fix aluminum bus bar of different size and capacity required as per site including PVC insulating materialsand cutting, welding, making holes etc complete all as specified and directed by Engr-in-Charge. |
84 | Supply and fix copper bus bar of different size and capacity required as per site including PVC insulating materialsand cutting, welding, making holes etc complete all as specified and directed by Engr-in-Charge. |
85 | Supply and fix in replacement of high power LED street light fitting energy saving luminaire with lens, capacity 60 W with system efficacy (lm/w) not less than 90 W lumens per watt, total system lumen not less than 5400 lumens, PF not less than 0.95, CRI not less than 70, colour temp 5000K to 6500K, surge protection not less than 5KV, high pressure die cast alumimum alloy LM6 housing IP - 65/66 class 1 protection, toughened glass cover, driver efficency >85% with constant output of current and voltage against input voltage variation 120 to 270 volt at 50 Hz (+5%), THD<10% complete all as specified and directed by Engr-in-Charge. |
86 | M&L for GI strip 32 x 6 mm for earthing complete all as specified and directed by Engr-in-Charge. |
87 | Supply, erection and fixing in position 9.00 metre long, steel tubular swaged poles complete with mild steel base plate, flat topwelded type 410, SP-31 IS:2713 marked, drilling of necessary holes including bolts, nuts and washers as required and pointed with two coats of Aluminium paint over a coat of red oxide primer on exposed, surfaces of poles and two coats of black bituminous paint throughout internally and externally upto the planting depth including providing reflective strips of width 10cm (03 Nos) at a height of 1.20 metre from ground level in alternate colour (green, white, green) alround the pole and marking pole number at appropriate height with shade and colour as approved by Engineer-in-Charge complete all as specified and as directed, with and including dismantling and taking up old existing damaged steel tubular pole and removing from site of work complete all as directed. Note : Excavation earthwork and concrete work shall be measured and paid for separately. |
88 | Aluminium conductor steel reinforced (ACSR) over head lines, on poles, straining properly on in sulators and binding with and including Aluminium tape/copper winding wire, connections, PG clamps, jumpers etc complete all as specified and as directed with and including dismantling of existing worn out/damaged ACSR conductor and earth wire, any size and removing from site of work, all as directed. |
89 | Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers welding, binding cold or hot, drilling holes for bolts, in any shape or size as indicated or directed inclusive of one coat of red oxide/Zinc chrome primer and two coats of aluminium paint and fixed erected in position on overhead poles complete all as specified and as directed including dismantling and taking down old unserviceable cross arms, bracing, claps etc from overhead poles and removing from site of work complete all as directed. |
90 | Trimming of tree branches around the LT over head conductor, poles (n. less than 3.00 metre) to clear the approach of overhead lines including removing nests wild grass creeper, unwanted vegetation etc from pole/stay including cleaning of creepers climbed on poles, cross cerms, all as directed, to the entire satisfaction of Engineer-in-Charge, including removing all rubbish to outside the MOF lard complete all as directed. NOTE :Span of 30 metre to 50 metre shall be considered / accounted for as one span for payment purposes. |
91 | M & L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level) with top edge of the plate not less than 1.5 Mtr below normal ground level, connected to galvanised earth lead strip 32x6mm by means of bolts, nuts, check nuts and washers of GI or steel all as shown in electrical plate No. 3 of SSR Part-I 2009 connected to earthing test pointall as specified or indicated and testing on completion as directed by the Engineer-in-Charge including necessary excavation & earth work in any type of soil, funnel, PCC chamber (1 : 3 : 6) type C1, CI pit cover and frame , charcol, salt includingearth lead protected by 40 mm dia medium grade GI pipe and 20mm dia medium grade GI Pipe for watering complete. Note. Earth lead strip 32 x 6 mm and GI 40 mm dia protecion pipe upto 7.5 mtr length will be deemed to include in the unit rate quoted. |
92 | Disconnecting of electric connection from LT Panels and dressing of cable including replacement of burnt out aluminum lugs with new lugs, nut bolts etc complete including necessay wiring of feeder pillar box with copper conductor cable, excavation and earth work all as directed by Engr-in-Charge. |
93 | Supply, installation testing and commissioning of out door type LT feeder piller box CPRI approved openable from front & rear double door type,dust and vermin proof, fabricated out of 3.15 mm CRCA sheet of size not less than 0.75x 0.50 x 0.50 duly painted with two coats of powder coated of approved shade over a coat of zinc chrome primer andMS channel frame of ISMC 75 at base of panel only and 04 Nos legs of not less than 50 cm long each below the base of panel made of angle iron 50 x 50 x 6mm for grouting purpose and grouted in PCC 1:2:4 type B1( using 20 mm graded stone aggregate) alongwithincoming MCCB four pole, 415 volts, 25 KA, 50 Hz, 200 amps -01 Nos including 4 Nos heat shrink insulated 200 Amps rated aluminum bus bar suitable for 4 Nos outgoing 25 sqmm to 35 sqmm 3.5/4 core XLPE armoured cable including taking down of existing rusted/unsv LT feeder pillar complete all as specified and directed by Engr-in- charge. |
94 | M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 400 sqmm and testing after jointing complete all as specified and directed. |
95 | M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 240 sqmm to 300 sqmm and testing after jointing complete all as specified and directed. |
96 | M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 185 sqmm and testing after jointing complete all as specified and directed. |
97 | M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 95 sqmm to 120 sqmm and testing after jointing complete all as specified and directed. |
98 | M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 50 sqmm to 70 sqmm and testing after jointing complete all as specified and directed. |
99 | M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 25 sqmm to 35 sqmm and testing after jointing complete all as specified and directed. |
100 | Taking down old unserviceable ACB any type andSupply, installation testing and commissioning new LT ACB of 630 Ampsfour pole mannual draw out with thermal magnetic release based, 415 Volts, 50 Hz suitable for existing location alongwith replacement ofburnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed by Engr-in-charge. |
101 | Taking down old unserviceable ACB any type andSupply, installation testing and commissioning new LT ACB of 800 Ampsfour pole mannual draw out with thermal magnetic release based, 415 Volts, 50 Hz suitable for existing location alongwith replacement ofburnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed by Engr-in-charge. |