| 1 | Supplying of PVC/XLPE armoured cable with aluminium conductor 1.1 KV Gradeconfirming to IS 7098 (part I)1988 with upto date amendments of the following size at the site of work. |
| 2 | 2 X 10 Sq.mm |
| 3 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. |
| 4 | upto 35 Sq.mm (Clamped with 1 mm thick saddle) |
| 5 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 6 | 2 X 10 sq. mm (19mm) |
| 7 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. |
| 8 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 9 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 10 | Group C |
| 11 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required |
| 12 | 3 x 4 sq. mm |
| 13 | 6 x 2.5 sq. mm |
| 14 | 3 x 2.5 sq. mm |
| 15 | 3 x 1.5 sq. mm |
| 16 | 6 x 1.5 sq. mm |
| 17 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. |
| 18 | 20 mm |
| 19 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. |
| 20 | 5/6 amps switch |
| 21 | 3 pin 5/6 A socket outlet |
| 22 | Supplying and fixing of 20 cm X 16 cm X 3 mm phenolic laminated sheet cover on the existing metal box etc., asrequired. |
| 23 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. |
| 24 | 12 Module (200mmX150mm) |
| 25 | 8 Module (125mmX125mm) |
| 26 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 27 | 5/6 A switch |
| 28 | 3 pin 5/6 A socket outlet |
| 29 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 30 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 31 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted includingearthing etc. as required. (But without MCB/RCCB/Isolator) |
| 32 | 6 way , Double door |
| 33 | 8 way , Double door |
| 34 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 35 | Single pole |
| 36 | Single pole and neutral |
| 37 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 38 | Earthing with 60mm outer dia ,2 mtr length GI earthing electrode, completely filled with conductive crystalline compound ,fitted with minimum of 40x6x2000mm GI strip including 50 kgs of eco friendly maintenance free earthing compound to enhance soil conductivity and providing masonry enclosure with cover plate having locking arrangement etc at the site of work as specified by the engineer incharge. |
| 39 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required |
| 40 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. |
| 41 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 42 | Supplying, installation, Testing and commissioning of70W LED Street light fitting made up of pressure die cast alluminium housing and fixing on wall/truss/pole with suitable clamps and nut bolts including giving connection etc., at site of work as required.(NABL certified as per ISO/IEC specification) (RatingIP66,Luminare efficacy>120Lm/W,CRI>80). |
| 43 | Supplying, installation, testing andcommissioningof 20W LED T8 tubelight with PC body with efficacy min of 100 lumens/W along with Highly robust industrial box type luminaire suitable for single T8 LED tube and fixing on wall/truss by using necessary clamps and also dismantling the existing fitting. (NABL certified as per ISO/IEC specification) |
| 44 | Supplying, installation, testing andcommissioningof 20W LED T8 tubelight with PC body with efficacy min of 100 lumens/W in the existing box type fittings including providing suitable internal wiring, side holders, clamps, nuts and bolts etc at the site of work as required.(NABL certified as per ISO/IEC specification) |
| 45 | Supplying and fixing of single phase, 230V,50Hz, 300mm dia sweep, 4 blade Exhaust fan with bird screen for protection against birds & foreign material and fixing on the wall surface including giving connections etc. at site of work as required.(NABL certified as per ISO/IEC specification) |
| 46 | Supplying, installation, testing andcommissioningof 1200mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current(BLDC) motor, class of insulation: B, 3 no.s blades, 30 cm long down rod, 2 no.s canopies, shackle kit, safety rope, copper winding, power factor not less than 0.9, Service value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit forspeed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max), insulation resistance more than 2 mega ohm, suitable for 230v, 50Hz, single phase AC supply, earthing etc. complete as required. |
| 47 | Supplying and laying of 1.1 KV grade Aerial Bundled Cable (three phase conductors of 35 sq.mm and insulated reduced neutral conductor around bare steel messenger) including giving connection etc at site of workas required. |
| 48 | Supplying and fixing of 5 KVAR Box type Heavy Duty Capacitor on existing surface/Panel including giving connection etc at site of work as required.(Make:L&T) |
| 49 | Providing M.V. danger notice plate of 200 mm X 150mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required. |
| 50 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required |
| 51 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 52 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 53 | Supply of 2m x 1m x 6mm thick corrugated rubber mat as required conforming to relevant ISI specification (suitable for electrical application) |
| 54 | Dismantling of existing conduit along with aluminium wire, main board, sub-main boards, switch boards and shifting to depot stores etc., as required. |
| 55 | CREDIT ITEMS |
| 56 | Dismantled Aluminium insulated wire |
| 57 | Dismantled Box type 1x40W/Street light fitting |