| 1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C |
| 2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/recessed steel/PVC conduit inculding dismantling as required. Group\"C\" |
| 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.3x4 sq.mm |
| 4 | 3x6 sq.mm |
| 5 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. 5/6 A switch |
| 6 | 3 pin 5/6 A socket outlet |
| 7 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 1. 8 WAY Double door |
| 8 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 9 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. A.63 A |
| 10 | Suppy and fixing following rating double pole ,240V, residual current circuit breaker having sensitivity current 30 mA in existing mcb db complete with connections,testing,commissioning etc as required . A. 25 A |
| 11 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required. (Clamped with 1 mm thick saddle) |
| 12 | Supply of XLPE InsulatedPVC Sheathed Al.conductor armoured cables for working voltages upto 1.1kv conforming to IS7098 as required.2x10sqmm |
| 13 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia includingaccessories, and providing masonry enclosure with cover platehaving locking arrangement and watering pipe etc. (but withoutcharcoal/ coke and salt) as required. |
| 14 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-fillingas required. |
| 15 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 16 | SITC of 1200 mm sweep BEE 5 star rated AC ceilling with brussless direct current motor, class of insulation:B, 3 nos. blade,30cm down road 2 nos. canopies shackle kit safety ropr,copper winding, power factor not less than .9,service value minimum 6.85,air delivery minimum 215 cmm,350 rpm,THD less than 10%,remote or electrnoic regulator unit for speed control and all remaining accessories including safety pin nuts,bolts,washertemperature rise=75 degree,insulation resistance more than 2 megha ohm,suitable for 230 v,50 hz,single phase ac supply, earthing etc complete as required fan for suitable for 230 V, 50 Hz AC supply. |
| 17 | Supply of 1.5 TR Split Type Air Conditioner (5 star rating) along with Installed Copper piping & 3 Core suitable copper wire, PVC hard drain pipe with remote suitable for 230V AC. supply complete as required.(upto 6 Mtr.) |
| 18 | Standard Installation charges for Split AC including labour and all items required for installation complete as reqd. |
| 19 | Supply & fixing of extra angle iron stand suitable for 1.5 TR Split Type Acs out door unit complete as reqd. |
| 20 | Extra for copper piping with proper insulation with PVC hard drain pipe and 3 core copper wire suitable for 1.5 TR Split type AIR Conditioner complete as reqd. |
| 21 | P&F of 4KVA Voltage Stabilizer with TDR and Triple step, High & low voltage cut off device complete as reqd. |
| 22 | SITC of LED Tube type luminaire 20 watt rating complete with Extruded Aluminum Batten prewired with high efficient LED with following specification. a) total system wattage=20watt+/-5%b) Luminous efficacy >=95 luminus/wattc). power factor >=.95 |
| 23 | Supply of 60 WattLEDfloodLight luminaire fitted with lens made of pressuredie cast aluminium housingand toughened glass cover i/c mounting bracketcomplete with following specifications.a) LED Wattage 60 ±5% b)Luminaries O/P=6000 lumens c)Luminaries efficacy = 100 lumens/wattd) Pf = 0.95e) CCT -5500K TO 6500 Kf) CRI >70g) Protection -IP66 |
| 24 | P/F hot press sheet moulded fire retardant( Temp. resustance upto 200 degree c) IP55 weather proof pole box of inner dimenson 2000x160x98mm complete with suiatable arrangement for fixing 1 no. of 6 to 32 amp singkle pole MCB( MCB/Isolator excluded) with netural link dully shorting on DIN Channel with 2 nos. of MS clamps with SS back plate of suitable size with danger monogram property printed on the cover etc as required. |
| 25 | \"S/F of Compartment alized cubical type panel board duly powder coated made out of 16 SWG.M.S sheet with insulated copper Bus bar i/c interconnection copper wiring arrangement for mounting for switch gear ,changeover switches ,MCCB i/c making the foundation brick work/angle iron frame on floor/wall with proper locking arrangement etc complete as required at site. \" |
| 26 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel making connection etc as required. 100 A, 16kA TPMCCB |
| 27 | 200 A, 35KA TPMCCB |
| 28 | Supplying and fixing metal box of 180mm x100mmx60mm deep (Nomial Size ) on surface or in recess with suitable size of phenolic laminated sheet cover in including providing and fixing 6 pin 5/6 and 15/16A socket out let and 15/16A pino type switch connections, painting etc. as required. |
| 29 | SITC of 10 inch(250mm) sweep fresh air fan heavy duty complete with shutters,blades etc as reqd. |