Tender For Provision Of Variable Frequency Drives (Vfds) At Water Supply And Ac Plant Installation At Mil Stn Dappar Under Ge (P) Dappar, dappar-Punjab

Military Engineer Services-MES has published Tender For Provision Of Variable Frequency Drives (Vfds) At Water Supply And Ac Plant Installation At Mil Stn Dappar Under Ge (P) Dappar. Submission Date for this Tender is 02-01-2023. Industrial Drive Tenders in dappar Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

35173188
Corrigendum : Tender For Provision Of Variable Frequency Drives (Vfds) At Water Supply And Ac Plant Installation At Mil Stn Dappar Under Ge (P) Dappar
Open Tender
Indian
Punjab
dappar
02-01-2023

Tender Details

Tender For Provision Of Variable Frequency Drives (Vfds) At Water Supply And Ac Plant Installation At Mil Stn Dappar Under Ge (P) Dappar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 28-Dec-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 02-01-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 60500.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Provn of variable frequency drives (VFDs) at water supply and AC plant installation at Mil Stn Dappar under GE (P) Dappar
Sl. No. Item Description
1Supplying, installing, testing and commissioning of LT panel for incorporating VFD of size as mentioned herewith alongwith conncted items, factory fabricated, all as per CPRI approved norms, floor/wall mounted, indoor double door type made out of CRCA MS sheet duly powder coated after seven tank chemical treatment with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar, incoming and outgoing connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. Panel should be mounted/grouted on the existing PCC floor/wall using appropriate size (as approved by Engr-in-Charge) MS equal angle; all the sides of the base frame should be duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. The panel should have following accessories fitted in :-
2INCOMER:
3MCCB 100 Amps, 415 V, 3 pole, 50 KA, 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : CM98944OOKO including spreader terminals - set of 03 and extended rotary handle - 01No. all as per OEM specifications or equivalent in Siemens/ABB/Schenider - 01 No.
4METERING :
5RED INDICATION LAMP LED TYPE 220 V AC - 01 No.
6YELLOW INDICATION LAMP LED TYPE 220 V AC - 01 No.
7BLUE INDICATION LAMP LED TYPE 220 V AC - 01 No.
8Multifunction Meter, LED Display, Class accuracy Cl1.0 with RS-485 all as per Schneider Make EM6400NG+ series Model - METSEEM6400NGRSCL1 - 01 No.
9CTs 100/5 A for Multifunction Meter - 03 Nos.
10VARIABLE FREQUENCY DRIVE (VFD):
11VFD 45KW, 380-440 V, 3 phase AC, Heavy Duty all as per Siemens Make, SINAMICS G120XA Series, Cat Part No. 6SL3220-2YD38-0UB0 or in ABB Make Cat Part No. - ACS560-01-088A-4 or equivalent in Schnieder Make - 01 No.
12Suitable size SINE WAVE FILTER for VFD OUTPUT so that Drive shall have total harmonic distortion not exceeding 5% as per IEEE-519 standard - 01 No. (Make must be of as recommended by VFD OEM)
13Module for wireless commissioning, diagnostics and servicing using wireless connection of mobile devices such as tablets, smartphones or laptops all as per Siemens Make, Smart Access Model, Cat Part No. 6SL3255-0AA00-5AA0 - 01 No. or in ABB Make ACx-AP-x Assistant control panels or equivalent in Schnieder Make.
14CONTROL TRANSFORMER 415/240VAC, 500VA - 01 No.
156A, 2P, MCB, "C" Curve - 02 Nos.
16EMERGENCY STOP PUSH BUTTON WITH MUSHROOM HEAD "RED" COLOUR - 01 No.
17MANUAL START PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, GREEN COLOUR - 01 No.
18MANUAL STOP PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, RED COLOUR - 01 No.
19FAULT RESET PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, BLUE COLOUR - 01 No.
20TWO POSITION SELECTOR SWITCH FOR LOCAL/REMOTE SELECTION WITH SYMMETRIC HEAD, BLACK COLOUR - 01 No.
21VFD RUN INDICATION LAMP, LED TYPE, 240V AC - 01 No.
22CONTROL TERMINAL BLOCKS - Lumpsum (as per requirement)
23RELAY WITH BASE, 14 PIN, 240VAC - 01 No.
24ACCESSORIES:
253 W LED LAMP 230 V AC WITH HOLDER - 01 No.
26DOOR LIMIT SWITCH, 6A TO BE CONNECTED WITH LED LAMP - 01 No.
276A, 240V, 3 PIN POWER & SOCKET SWITCH - 01 No.
28PANEL MOUNTING HIGH SPEED FAN, 6", 230V AC WITH FILTER & AIR VENT HOODS Rexnord Make - 02 Nos.
29FILTER FOR HEAT DISSIPATION, Rexnord Make - 02 Nos.
30WIRING & ACCESSORIES :
31Wires, Thimbles Ferrules, PVC DUCT, Cable ties & other wiring accessories as required - 01 LS
32All as per Item No. 1 above but consisting of following -
33INCOMER:
34MCCB 100 Amps, 415 V, 3 pole, 50 KA, 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : CM98944OOKO including spreader terminals - set of 03 and extended rotary handle - 01No. all as per OEM specifications or equivalent in Siemens/ABB/Schenider - 01 No.
35METERING :
36RED INDICATION LAMP LED TYPE 220 V AC - 01 No.
37YELLOW INDICATION LAMP LED TYPE 220 V AC - 01 No.
38BLUE INDICATION LAMP LED TYPE 220 V AC - 01 No.
39Multifunction Meter, LED Display, Class accuracy Cl1.0 with RS-485 all as per Schneider Make EM6400NG+ series Model - METSEEM6400NGRSCL1 - 01 No.
40CTs 100/5A for Multifunction Meter - 03 Nos.
41VARIABLE FREQUENCY DRIVE (VFD):
42VFD 15KW, 380-440 V, 3 phase AC, Heavy Duty all as per Siemens Make, SINAMICS G120XA Series, Cat Part No. 6SL3220-2YD26-0UB0 or in ABB Make Cat Part No. - ACS560-01-039A-4 or in Schnieder Make - 01 no.
43Suitable size SINE WAVE FILTER for VFD OUTPUT so that Drive shall have total harmonic distortion not exceeding 5% as per IEEE-519 standard - 01 No. (Make must be of as recommended by VFD OEM)
44Module for wireless commissioning, diagnostics and servicing using wireless connection of mobile devices such as tablets, smartphones or laptops all as per Siemens Make, Smart Access Model, Cat Part No. 6SL3255-0AA00-5AA0 - 01 No. or in ABB Make ACx-AP-x Assistant control panels or equivalent in Schnieder.
45CONTROL TRANSFORMER 415/240VAC, 500VA - 01 No.
466A, 2P, MCB, "C" Curve - 02 Nos.
47EMERGENCY STOP PUSH BUTTON WITH MUSHROOM HEAD "RED" COLOUR - 01 No.
48MANUAL START PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, GREEN COLOUR - 01 No.
49MANUAL STOP PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, RED COLOUR - 01 No.
50FAULT RESET PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, BLUE COLOUR - 01 No.
51TWO POSITION SELECTOR SWITCH FOR LOCAL/REMOTE SELECTION WITH SYMMETRIC HEAD, BLACK COLOUR - 01 No.
52VFD RUN INDICATION LAMP, LED TYPE, 240V AC - 01 No.
53CONTROL TERMINAL BLOCKS - Lumpsum (as per requirement)
54RELAY WITH BASE, 14 PIN, 240VAC - 01 No.
55ACCESSORIES:
563 W LED LAMP 230 V AC WITH HOLDER - 01 No.
57DOOR LIMIT SWITCH, 6A TO BE CONNECTED WITH LED LAMP - 01 No.
586A, 240V, 3 PIN POWER & SOCKET SWITCH - 01 No.
59PANEL MOUNTING HIGH SPEED FAN, 6", 230V AC WITH FILTER & AIR VENT HOODS Rexnord Make - 02 Nos.
60FILTER FOR HEAT DISSIPATION, Rexnord Make - 02 Nos.
61WIRING & ACCESSORIES :
62Wires, Thimbles Ferrules, PVC DUCT, Cable ties & other wiring accessories as required - 01 LS
63All as per Item No. 1 above but consisting of following -
64INCOMER:
65MCCB 400 Amps, 415 V, 3 pole, 50 KA, 50 Hz with Ics =100% Icu & thermal magnetic adjustable type all as per L&T Make : Cat pat No : CM94516OOROOG including spreader terminals - set of 03 and extended rotary handle - 01No. all as per OEM specifications or equivalent in Siemens/ABB/Schenider - 01 No.
66METERING :
67RED INDICATION LAMP LED TYPE 220 V AC - 01 No.
68YELLOW INDICATION LAMP LED TYPE 220 V AC - 01 No.
69BLUE INDICATION LAMP LED TYPE 220 V AC - 01 No.
70Multifunction Meter, LED Display, Class accuracy Cl1.0 with RS-485 all as per Schneider Make EM6400NG+ series Model - METSEEM6400NGRSCL1 - 01 No.
71CTs 400/5A 15VA for Multifunction Meter - 03 Nos.
72VARIABLE FREQUENCY DRIVE (VFD):
73VFD 5.5KW, 380-440 V, 3 phase AC, Heavy Duty all as per Siemens Make, Cat Part No. 6SL3210-1KE21-7UB1 or in ABB Make Cat Part No. - ACS560-01-039A-4 or in Schnieder Make - 09 Nos.
74Suitable size SINE WAVE FILTER for VFD OUTPUT so that Drive shall have total harmonic distortion not exceeding 5% as per IEEE-519 standard - 01 No. (Make must be of as recommended by VFD OEM)
75Basic Operator Panel - 09 Nos, Make - Siemens, Cat No. 6SL3255-0AA00-4CA1 or equivalent in ABB/Schenider.
76CONTROL TRANSFORMER 415/240VAC, 500VA - 09 Nos.
776A, 2P, MCB, "C" Curve - 18 Nos.
78EMERGENCY STOP PUSH BUTTON WITH MUSHROOM HEAD "RED" COLOUR - 09 Nos.
79MANUAL START PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, GREEN COLOUR - 09 Nos.
80MANUAL STOP PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, RED COLOUR - 09 Nos.
81FAULT RESET PUSH BUTTON WITH CONTACT BLOCK FLUSH TYPE, BLUE COLOUR - 09 Nos.
82TWO POSITION SELECTOR SWITCH FOR LOCAL/REMOTE SELECTION WITH SYMMETRIC HEAD, BLACK COLOUR - 09 Nos.
83VFD RUN INDICATION LAMP, LED TYPE, 240V AC - 09 Nos.
84CONTROL TERMINAL BLOCKS - Lumpsum (as per requirement)
85RELAY WITH BASE, 14 PIN, 240VAC - 09 Nos.
86ACCESSORIES:
873 W LED LAMP 230 V AC WITH HOLDER - 01 No.
88DOOR LIMIT SWITCH, 6A TO BE CONNECTED WITH LED LAMP - 01 No.
896A, 240V, 3 PIN POWER & SOCKET SWITCH - 01 No.
90PANEL MOUNTING HIGH SPEED FAN, 6", 230V AC WITH FILTER & AIR VENT HOODS Rexnord Make - 02 Nos.
91FILTER FOR HEAT DISSIPATION, Rexnord Make - 02 Nos.
92WIRING & ACCESSORIES :
93Wires, Thimbles Ferrules, PVC DUCT, Cable ties & other wiring accessories as required - 01 LS
94Supply, laying, jointing, connecting, testing & commissioning UG cable XLPE insulated, screened, PVC bedded, galvanised steel strip armoured electric power cable (heavy duty 1100 volts grade with standard aluminium conductor of cross sectional area 35 sqmm x 3.5 core all as specified and directed by Engr-in-Charge. NOTE - (a). The quoted rate is deemed to be inclusive of arranging respective shutdown, disconnection of cables, commissioning of feeder after the completion of job and inclusive of any minor spares and jobs required for the completion of the job. (b). The cost of saddling or clamping of cable to wall is deemed to be included in the quoted rate.