| 1 | Supplying and fixing 415V, 250A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make- L&T , Havells/ approved make. ) |
| 2 | Supplying and fixing sheet steel (16SWG) cable end box on TPN SFU enclosure with nuts bolts etc incl. powder coated painting.(Make- L&T / Havells/ approved make. ) |
| 3 | Supply and delivery of 1.1 KV grade 3.5 core 240 sq. mm. PVC XLPE Aluminium armoured cablefrom Service meter to LT panel (Make- Havells / Gloster or approved make). |
| 4 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : (i) 3.5 Core 240 sq. mm. XLPE AL. Ar. Cable. |
| 5 | Finishing of the XLPE/PVC insulated armoured cable ends by soldering with cable sockets and insulated tapes etc., including supplying sockets, soldering materials, tapes etc. and making connection to switch, BDB and BBC etc. (i) 3.5 Core 240 sq. mm. XLPE AL. Ar. Cable. |
| 6 | Laying of one No. cable above 185 sqmm in underground trench 460mm wide x 760mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per Mtr. including filling the space between the bricks and cable and also the trenchwith shifted soil, leveling up and restoring surface duly rammed. |
| 7 | Supply, Erection, testing & commissioning of LT panel including the following items. i) Incommer MCCB FP 250A - 01 no, ii) DGIncommer MCCB FP 100A - 01 no, iii) 4 Pole MCB typeChange over 4 pole 100 A- 01 no , iv) 415V 400A 4bar Aluminium busbar - 1 set, (v) 415V 150A 4bar Aluminium busbar - 1 set, (vi)415V 63A 4 Pole MCCB- 13 Nos., (vii)415V 32A Triple Pole MCB- 04 Nos., (viii)415V 32A Dobule Pole MCB- 04 Nos., (ix) 0-500V Volt meter with selector switch - 2 Sets., (x)0-500A Ammeter with selector switch - 2 Sets., (xi) Indication lamp - 06 no, (xii) Internal wiring -01 lot, (xiii) MS enclosure having 2 mm thick CRCA sheet and duly paintedas directed by EIC.. |
| 8 | Supplying and fixing 415V, 63A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make- L&T / Havells/ approved make. ) |
| 9 | Supplying and fixing sheet steel (16SWG) cable end box on 63A TPN SFU enclosure with nuts bolts etc incl. powder coated painting.(Make- L&T / Havells/ approved make. ) |
| 10 | Supply of 1.1KV grade 4 Core 25 SQ. mm. PVC Armoured XLPE Aluminium cable as per GS. (Make- Havells / Gloster or approved make). |
| 11 | Supply of 1.1KV grade 4 Core 10 SQ. mm. PVC Armoured XLPE Aluminium cable as per GS. (Make- Havells / Gloster or approved make). |
| 12 | Supply of 1.1KV grade 2 Core 10 SQ. mm. PVC Armoured XLPE Aluminium cable as per GS. (Make- Havells / Gloster or approved make). |
| 13 | Laying of cable upto 3/4 core 25 sqmm on wall/ surfaceincl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting. |
| 14 | Laying of cable as below, on existing Cable Tray and binding with suitable size GI wire. Above 150 sq.mm. |
| 15 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : (i) 4 Core 25 sq. mm. XLPE AL. Ar. Cable. |
| 16 | 4 Core 10 sq. mm. XLPE AL. Ar. Cable. |
| 17 | 2 Core 10 sq. mm. XLPE AL. Ar. Cable. |
| 18 | Finishing of the XLPE/PVC insulated armoured cable ends by soldering with cable sockets and insulated tapes etc., including supplying sockets, soldering materials, tapes etc. and making connection to switch, BDB and BBC etc. 4 Core 25 sq. mm. XLPE AL. Ar. Cable. |
| 19 | 4 Core 10 sq. mm. XLPE AL. Ar. Cable. |
| 20 | 2 Core 10 sq. mm. XLPE AL. Ar. Cable. |
| 21 | Supply and fixing of 63A TPN MCB and 3 nos. Phase indicating lamp including S&F. suitable SS enclosure with necessary interconnection as to GS. (As floor incommer). |
| 22 | Design, drawing , layout andcalculations of complete electrical distribution system |
| 23 | Supplying and fixing double door Horizontal 4 way TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment . (Make- Legrand / PWD approved make). |
| 24 | Supplying and fixing of 2+8 way double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make- Legrand / PWD approved make). |
| 25 | Supplying and fixing 240/415 V MCB Isolator / SP MCB on din rail of existing DBs and necessary connection as follow (Make- Legrand / PWD approved make). 63A 4 Pole MCB Isolator |
| 26 | 40A DP MCB Isolator . |
| 27 | 6 - 32A SPMCB. |
| 28 | Supplying and Drawing 1.1 KV single core stranded \"FR\" PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as requiredas follow :- 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC |
| 29 | 2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC |
| 30 | 3 x 22/0.3 (1.5 sqmm) |
| 31 | Supplying and fixing 20 mm PVC Rigid Conduit \"FR\" [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works |
| 32 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:By ISI-Medium GI pipe |
| 33 | Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6)of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe incl. Extra for treatment of soil by using salt & charcoal or coke for plate electrode |
| 34 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 35 | Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, 6mm dia MS suspender, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support. 300x50x1.25mm (18SWG) |
| 36 | Checking, testing and load balancing arrangement incl. changing or replacing necessary existing conneions as required. |
| 37 | Dismentaling existing Floor service cable including all old HT/LT electrical Panels and Switches as required and as direction of EIC. |
| 38 | Straigh through Jointing of cable of different size by compound jointing kit including S&F ferrul, tapes and jointing materials (Brand approved by EIC)3½ / 4 core 25-35 sqmm cable |
| 39 | Supply and fixing of 19mm Green Wooden Ply (water proof) necessary nuts bolts arrangement as required. |
| 40 | Supply & fixing of 110mm(4 kgf/cm2) dia ISI Medium PVC Pipe. |
| 41 | Add GST @ 18% on item no. 1 to 32 |
| 42 | Add Cess @ 1% on item no. 1 to 32 |