| 1 | Excavation in trenches not exceeding 1.5 m wide and not exceeding1.5 m in depthfor laying cables, foundation for pole, etcand getting out inhard/dense soil complete all as specified and as directed. |
| 2 | All as peritem No.1 here in before but depth exceeding 1.5 m but not exceeding 3m. |
| 3 | Returning, filling in, including spreading, levelling, watering and well ramming of soil in layers n. exc 25cm thick complete all as specified and as directed. |
| 4 | Removing excavated soil to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point complete all as specified and as directed. |
| 5 | M&L for Stay assembly comprising of 14 mm diairon stay bow,stay strand wire of size 7/3.15 mmwith stay rod of diameter 16 mm complete with all accessories as shown in electrical plate No. 1 including dismantling of old stay assembly with foundation concrete etc and excavation workcomplete all as specified and as directed.(Note: loop type insulator and concrete work measured separately) |
| 6 | M&L forerection and fixing of steel tubular swaged pole type 410 SP - 31 (9.00 metres long) confirming to IS- 2713 Part I to III 1980 with and including cast iron base plate, finial taper plug, nuts, bolts and washers etc. fixed in PCC foundationduly painted painted with two coats of Aluminium paint over a coat of red oxide primer including preparation of surface and including dismsntling of old pole of any size and description with foundation, PCC coping etc. complete all as specified and as directed. |
| 7 | M&L for PCC 1: 2 : 4 type B-1 using 20 mm graded stone aggregate including necessary form work for coping to the new/ existingSteel Poles complete all as specified and as directed. |
| 8 | M&L for PCC 1:3:6, type C2 (using 40 mm graded stone aggregate) as in foundations, filling and mass concrete complete all as specified and as directed. |
| 9 | M&L for preparation of old painted surface of 9/11 metre long steel pole with cross arms and brackets and two applying two coats of aluminium paint and writing pole nos with synthetic enamel black japan paint at a height of 1.5 mtr above ground level complete all as specified and as directed. |
| 10 | Allas per item serial No 09here-in-before butfor double pole structure complete all as specified and as directed. |
| 11 | M&L for Cross arms, bracings, supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps, stay clamps, D clamps nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including painting with one coat ofaluminiumpaintover a coat of red oxide primer including taking down the old unserviceable cross arms, clamps etccomplete all as specified and as directed. |
| 12 | M&L for ACSR conductors (weasel type)for LT OH lines on poles including stringing, binding with aluminium wire 14 SWG or aluminium tape includingjumpers complete connecting of disconnected cable, service cable and street light connection including taking down the old unserviceable ACSR conductor of any type complete all as specified and as directed. |
| 13 | Material and labour for restringing, tightening of loose/broken ACSR conductor of any size and type, maintaining standard sag including binding the conductor with pin/shackle insulator and jumpers with aluminum binding wire not less than 2.00mm dia, PG clamp etc on HT over head lines complete all as specified and as directed. |
| 14 | M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 95 sqmm 3½ core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, including taking down old unserviceable UG cable any type complete all as specified and as directed. |
| 15 | M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 50 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, including taking down old unserviceable UG cable any type complete all as specified and as directed. |
| 16 | M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 10 sqmm 4 core laid in trenches /floor or fixed on wall /pole in including brass compression cable glands, terminal lugs etc, including taking down old unserviceable UG cable any type complete all as specified and as directed. |
| 17 | Supply and spreading clean dry river sand in cable trenches as in cable cushioning complete all as specified and as directed. (Note: Punnedthickness shall be measured and paid) |
| 18 | Supply and laying wellburntsub class‘B’ bricks locally available best quality laid dryin trenches forprotection of underground cable all as specified and directed |
| 19 | M&L for GI pipe light grade 40mm bore with all fittings laid in trenches or in floors,including taking up/ down old pipecomplete all as speciffied and as directed. |
| 20 | M&L for GI pipe light grade 80mm bore with all fittings laid in trenches or in floors,including taking up/ down old pipecomplete all as speciffied and as directed. |
| 21 | S&F in repair for cable jointing kit for LT (Earthed) grade cable for end termination outdoor heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cablesize 25-50 Sqmm 3.5/4 core complete all as specified and as directed. |
| 22 | S&F in repairs, for cable jointing kit for LT (Earthed) grade cable for end termination outdoor heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cablesize 70-150 Sqmm 3.5/4 core complete all as specified and as directed. |
| 23 | M&L for contraction of transformer platform having dimension 2mx2mx0.85m above G.L and 0.46 metre below G.L (foundation), 100 mm PCC thick lean concrete in 1:3:6 type C2 (40mm aggregate), 2mx2mx100 RCC concrete slab type B1 using 20mm graded stone aggregate, reinforcement bar 8 mm dia (TMT bar) at a distance 125mm (c/c) with ramp length not less than 2 metre, full brick wall at both end of ramp with PCC slope / path 100mm thick (1:3:6) type C2 in, fillingunder suitable soil with spreading, levellling, ramming , watering etc, including demolition of old platform complete all as specified and as directed.Note: Earth work , outer plastering & white wash are deemed to be included in the quoted rates . |
| 24 | S&F in repairs, LED polycarbonate unbreakable round doom shape milky white globe light for outdoor pole/ pillar/gate/garden -DC suitable for 45 mm dia pipeincluding LED bulb 9 watt and complete all as specified and as directed. |