Tender For Provision Of Certain Misc Civil And Electrical Works At Aiims Bibinagar
Tender Value
36 Lakhs
Estimated cost
Bid Submission
08 Dec 2022
0 days left
EMD
72400
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
bibinagar → Telangana
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Provision Of Certain Misc Civil And Electrical Works At Aiims Bibinagar
BOQ
| Sl. No. | Item Description |
| 1 | Providing and fixing false ceiling at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595mm of approved texture, design and patterns as per CPWD specification 2019, 12.5 mm thick tapered edge gypsum moisture resistant board to be laid in true horizontal level suspended on inter-locking metal T-Grid of hot dipped galvanized iron section of 0.33mm thick (galvanized @ 120 grams per sqm including both sides)comprising of main-T runners of size 24x38 mm of length 3000 mm, cross - T of size 24x32 mm of length 1200 mm and secondary intermediate cross-T of size 24x32 mm of length 600mm to form grid module of size 600 x 600 mm, suspended from ceiling using galvanized mild steel items (galvanizing @ 80 grams per sqm) i.e. 12x50 mm long dash fasteners, 6 mm dia fully threaded hanger rod up to 1000 mm length and L- shape level adjuster of size 76x25x25x1.6 mm fixed with grid and Z cleat of size 25x37x25x1.6mm thick with precut hole on both 25mm flange to pierce into 12x50mm or even bigger size dash fastener if require, fixed with Galvanized iron perimeter wall angle or size 24x24x0.40 mm of length 3000 mm to be fixed on periphery wall / partition with the help of plastic rawl plugs at 450mm center to center and 40 mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing and as per directions of the Engineer-in- Charge. (Make: USG, Gyprock, Diamond, Saint gobain) |
| 2 | Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications, drawings and direction of Engineer-in-charge complete. |
| 3 | Extra for providing frosted glass panes 4 mm thick instead of ordinary float glass panes 4 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured). |
| 4 | Providing and fixing Anodizedaluminum (Anodized transparent or dyed to required shade according to IS:1868, minimum anodic coating of grade AC-15) work forfixed portion doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleatangle, Aluminium snap beading for glazing / paneling, C.P.brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.: |
| 5 | Anodized aluminum (Anodized transparent or dyed to required shade according to IS: 1868, minimum anodic coating of grade AC-15) For shutters of doors, windows & ventilators including providing and fixing hinges /pivots and making provision for fixing of fitting wherever required including the cost of EPDM rubber/neoprene gasket required. |
| 6 | Providing and fixing 12mm thick pre-laminatedparticleboardflat pressed three layer or graded wood particle boardwith decorative lamination on the both sides confirmingto IS:12823 Grade l , type ll in paneling fixed in aluminum doors, windows, shutters and partition frames with C.P brass/stainless steel screws etc., complete as per architectural drawings and directions of Engineer-in-charge. |
| 7 | Providingandfixingglazing of float glass panesof 5.5mm thickness in aluminum door, window, ventilator shuttersandpartitionsetc,with EPDM rubber/neoprene gasket etc. completeasperthearchitectural drawings and the directions of Engineer-in charge.(Cost of aluminum snap beading shall be paid in basic item)t |
| 8 | Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body/plate with double spring mechanism and door weight up to 125 kg for doors including cost of cutting floors embedding in floors as required and making good the same matching to the existing floor finishing and stainless steel cover plate with minimum thickness of 1.25mm with brass pivot and single piece. M.S sheet outer box with slide plates etc. complete as per the direction of Engineer-in charge.. |
| 9 | Providing and fixing Anodized (AC15)aluminum round shape handle of outer dia 100 mm with stainless steel screws etc. Complete as per direction of Engineer in-charge |
| 10 | Providing and fixing bright finished 100 mm mortise lock with 6 levers without pair of handles of approved quality for aluminum door, with necessary screws etc complete as per direction of Engineer in- charge. |
| 11 | Providing andFixingaluminum tower bolts, size of 200 mm X 10 mm ISI marked anodized (anodic coating not less than grade AC 10 as per IS 1868) transparent or dyed to required colour or shade with necessary screws etc. complete: |
| 12 | Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete. |
| 13 | Providing and fixing 5 mm thick M.S. chequered plate sheet of 4 feet width (For ramp) including applying a priming coat of approved steel primer, enamel paint required coates and colour as directed by Engineer-in-charge. |
| 14 | Providing and fixing 32 mm outer dia 2 mm of M.S.Pipe. for side Railing works including applying a priming coat of approved steel primer, enamel paint required coates and colour as directed by Engineer-in-charge. |
| 15 | Providing and fixing of 25 mm outer dia 2 mm Thickness of M.S.Pipe . For side Railing works including applying a priming coat of approved steel primer, enamel paint required coates and colour as directed by Engineer-in-charge. |
| 16 | Providing and fixing Angle iron 50x50x5mm for fixing the support frame with steeps including applying a priming coat of approved steel primer, enamel paint required coates and colour as directed by Engineer-in-charge. |
| 17 | Providing and fixing of hand Rail including Excavation, PCC and foundation as directed by Engineer-in-charge. |
| 18 | Removal of existing bulbs as number of bulbs available on rooms and Supply and Fixing of 36 WATT False ceilingLED as directed by Engineer-in-charge. |
| 19 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc as required. |
| 20 | Wiring for light Group C point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. |
| 21 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. Heading |
| 22 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (Make: Havells, Finolex, KEI, RR Kables) |
| 23 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire (Make: Havells, Finolex, KEI, RR Kables) |
| 24 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire (Make: Havells,Finolex, KEI, RR Kables) |
| 25 | Supplying and fixing suitable size PVC/GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. |
| 26 | Supplying and fixing suitable size PVC/GI box with modular plate and cover in FRLS ont on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. |
| 27 | Supplying and fixing 6 way (4 + 18), Double door, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. |
| 28 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of 1 Single pole in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 29 | Supplying and fixing 63 A rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Make:Legrand,Schneider Electric,havells) |
| 30 | Anchor fasteners hook 8 mm Dia |
| 31 | Iron metal Lock chain 6 mm Dia |
| 32 | Hydraulic Door Closers (Make:Godrej, Hafele, Dorset) |
| 33 | Removing of existing smoke detectors from ceilingand refixing the same detector to false ceiing |
| 34 | Fixing of SS Sprinkler Flexible Drops 1 inch dia1 mtr length |
| 35 | Supply installation testing and commissioning 2 Ton, Inverter type 5 Star Rating of BEE Air Cooled Split Type Air Conditioners complete with indoor unit (IDU), Outdoor unit (ODU), surface / concealed coper Refrigerant piping with insulation (EP Foam pipe section) . (IDU to ODU) copper power cable (at least 3CX 2.5 Sqmm, PVC Insulation, FRLS copper wire). (IDU to ODU), R-22/R-410 Refrigerant , PVC drain pipe (dia 15mm) Remote,ODU stand, suitable for 400/230V +10% of 50 Hz, 1/3 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with scroll/ reciprocating/ rotary compressor. (Make:Voltas,Blue Star,Llyod,Hitachi,Carrier) |
| 36 | Supply installation testing and commissioning of 60 min backup of 10 KVA UPSSystem andbatteries with following Specifications-HeadingSystem Configuration: 10KVA/8KW online inbuilt isolation transformer UPS system with min 60 minute battery backup.(Make:Eaton/Vertiv/Emerson/Fuji Electric Only)2 years WarrantyTechnology: True On line Double conversion, using IGBT for both Rectifier and inverter section.Rectifier Technology: The rectifier/Charger shall be a only high frequency PWM designed using Insulated Gate Bi-polar Transistors(IGBTs).Modes of Operations: Double Conversion True On-Line.Emergency: In the event of an output bus failure or an extreme overload condition, the load shall be transferred, seamlessly and without interruption to a fully rated static switch.Rectifier InputInput Voltage: 230 VAC 1 Phase,Input Voltage Facility: 415+20%V AC,3-Phase 4 wireInput Voltage Range in at 50% load : 110V to 300VInput Frequency: 50 Hz +/-6%Input frequency Range: 47Hz to 52.5 HzInput current Harmonics: <3% at 100 load andInput Power Factor: 0.85 to UnityBYPASSStatic Bypass switch: A Build in static transfer switch shall be provided as integral part of the UPSInput Voltage: 230VAC, 1 PhaseRated Frequency: 50 HOUTPUTRated Power: 10 Kva /8000 WattWave form: Sinusoidal/Pure sinewaveOut voltage: 220/230/240 VAC +/- 1% in single phase.Out voltage Regulation: +/-1%, for 100% Static Load, /-5% dynamic 100% load changeFrequency: 50HzFrequency sync range: 47 to 52.5 HzFrequency regulations: +/-0.1HzStatic Stability: +/-1 HzCrest factor: 03:01Transfer time in normal mode: 0Overall efficiency: >85% 100% Load on Mains and battery.Over Load: 101%-109%: 10 min111%-130%: 1 minBATTERIES(Make: Amaron / Exide / Luminous Only) 2 Years WarrantyTYPE: Maintains free sealed lead acidBattery Blocks: 12V SMFDesired Backup time: Min 60 minutes, or Above (Battery Brand, Number & AH should be mention clearly otherwise bid not acceptable)Battery Charger: Build-in solid state float-cum-boost charger with automatic boost/ trickle charge modes with current limiting features. Min 8 Amp charger is must for charging the batteries. |
| 37 | Supply installation testing and commissioning of 60 min backup of 20 KVA UPSSystem andbatteries with following Specifications-HeadingSystem Configuration: 20KVA/16KW online inbuilt isolation transformer UPS system with min 60 minute battery backup.(Make: Eaton/ Vertiv/Emerson/Fuji Electric Only)2 years WarrantyTechnology: True On line Double conversion, using IGBT for both Rectifier and inverter section.Rectifier Technology: The rectifier/Charger shall be a only high frequency PWM designed using Insulated Gate Bi-polar Transistors(IGBTs).Modes of Operations: Double Conversion True On-Line.Emergency: In the event of an output bus failure or an extreme overload condition, the load shall be transferred, seamlessly and without interruption to a fully rated static switch.Rectifier InputInput Voltage: 230 VAC 1 Phase,Input Voltage Facility: 415+20%V AC,3-Phase 4 wireInput Voltage Range in at 50% load : 110V to 300VInput Frequency: 50 Hz +/-6%Input frequency Range: 47Hz to 52.5 HzInput current Harmonics: <3% at 100 load andInput Power Factor: 0.85 to UnityBYPASSStatic Bypass switch: A Build in static transfer switch shall be provided as integral part of the UPSInput Voltage: 230VAC, 1 PhaseRated Frequency: 50 HzOUTPUTRated Power: 20 KVaA/8000 WattWave form: Sinusoidal/Pure sinewaveOut voltage: 415+20%V AC,3-Phase 4 wireOut voltage Regulation: +/-1%, for 100% Static Load, /-5% dynamic 100% load changeFrequency: 50HzFrequency sync range: 47 to 52.5 HzFrequency regulations: +/-0.1HzStatic Stability: +/-1 HzCrest factor: 03:01Transfer time in normal mode: 0Overall efficiency: >85% 100% Load on Mains and battery.Over Load: 101%-109%: 10 min111%-130%: 1 minBATTERIES(Make: Amaron / Exide / Luminous Only) 2 Years WarrantyTYPE: Maintains free sealed lead acidBattery Blocks: 12V SMF Desired Backup time: 60 minutes or above (Battery Brand, Number & AH should be mention clearly otherwise bid not acceptable)Battery Charger: Build-in solid state float-cum-boost charger with automatic boost/ trickle charge modes with current limiting features. Min 8 Amp charger is must for charging the batteries. |
| 38 | Supply & fixing of floor mounted Surgical Scrub Station (Stainless steel grade 304 1.2mm thick) Working size of 2.2 x.5x.1.3 m (L x W X H) with 3 no. of Bay instrument, 3 taps of approved make, foot operated System. Cutting, welding, buffing, polishing and making holes for plumbing fittings and fastener etc. Including all necessary pipe fittings complete works as specified by engineer-in-charge. (Surgical Scrub Station to be Procured from firms which have expertise and Certified in Medical equipments with good track record approved by engineer-in-charge) |
| 39 | Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directed by Engineer-in-charge. |
| 40 | MEDICAL GAS PIPE LINE (Total Medical Gas Pipe line System works have to be executed by firms which have expertise and certified in medical Gaspipe line system with good Track Record and approved by engineer-in-charge-Heading |
| 41 | Supply installation testing and commissioningMedical Gas Copper PipelineMedical Gas Copper Pipeline 15mm OD 0.90mm thick copper pipearrangement to hang on the wall of socket type connectioninstallation of seamless cleaned and greased non arsenical phosphrous gascopper pipe line with saddles complete withbrazing work including all copper fitting(tee, elbow, reducer, coupling). The copperpipelines should be tested suitable for steam452.00 452.00 452.00BD-921 Bof working pressure of 17.34Kg. / cm2 (17bar) andconfirm to Bs 864 Standard withspecially made for brazed socket typeconnection. The medical gas copper pipeline should be tested as per standard and commissioning after painting as perinternation Code No. IS2379/1963 TableV. The pipelines installed at the variouswings and floors etc., complete as directedby the Departmental Officers as per IS code12827 / 1989 & ISO 7396 / 1987Specification |
| 42 | Supply installation testing and commissioning Medical Gas Arrangements : Medical Gas Copper Pipeline 12mm OD0.90mm thick copper pipe arrangement to hang on the wall of socket type connection installation of seamless cleaned and greased non arsenical phosphorusgas copper pipe line with saddles complete with brazing work including all copper fitting (tee, elbow, reducer, coupling). The copper pipelines should be tested suitable for steam of working pressure of 17.34Kg. / cm2 (17bar) and confirm to Bs 864 Standard with specially made for brazed socket type RM 311.00 311.00 311.00 connection. The medical gas copper pipeline should be tested as per standard and commissioning after painting as per international Code No. IS 2379/1963 Table V. The pipelines installed at the various wings and floors etc., complete as directed by the Departmental Officers as per IS code 12827 / 1989 & ISO 7396 / 1987Specification |
| 43 | Supply installation testing and commissioning Med flow outlets:> Terminal UNITs (Gas Outlets) with probes/Adaptors for O2 -4, N2O-2, Compressed Air-2 &Vacuum-2 > Push to insert and press-to-release mechanism for probes.> All outlets should have respective labels (i.e.O2 / N2O / CO2 / Air/Vacuum/etc.) displayed accordingly.> Self-sealing valve on disengaging the probe (Quick disconnect).> Color-coded gas specific front plate. |
| 44 | Supply installation testing and commissioning Horizontal Bed head Panel double Railing Aluminum Panel (4 feet each)The design should be approved by the respective institute before installation and it is responsibility of the bidder after getting order they have to discuss with respective institute and finalized the Bed Head Panel (Vertical/Horizontal) as per Site condition. Horizontal BHP should be of maximum 1200mm for up to 5 outlets configuration. Efficient, Safe & Robust design in extruded aluminium section. Smooth curved surfaces, and choice of base colour and fascia plates. UNIT should have integrated rail system to mount accessories.Each bed-head unit shall be supplied with electrical and electrical outlets pre-fitted, wired and certified. (Wired up to the distribution box provided with leakage protection & proper earthling arrangements). The sockets should have color coding / identification marks for UPS supply.Switches/Sockets and data points.All are inclusive as directed by Engineer-in-charge |
AI Tender Summary
Tender Timeline
Nov 29, 2022
11:30 IST
Tender Published
Tender notice published.
CompletedDec 08, 2022
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedDec 09, 2022
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender