Tender For Ge(N)P/T- 60 Of 22-23Rep Maint Of Existing Lt Panel Distr Sys, Lt Ug Cable Contr Connectg Items Allied Wks At Main Receiving Stns Other Ext Rep Wk At Hqsc Cesc Cepz Cwe Mayo Rd Zro, Rs Rd 06 Qg 16 Qg In The Area Of Age E/M (N) Under Ge (N, Pune-Maharashtra

Military Engineer Services-MES has published Tender For Ge(N)P/T- 60 Of 22-23Rep Maint Of Existing Lt Panel Distr Sys, Lt Ug Cable Contr Connectg Items Allied Wks At Main Receiving Stns Other Ext Rep Wk At Hqsc Cesc Cepz Cwe Mayo Rd Zro, Rs Rd 06 Qg 16 Qg In The Area Of Age E/M (N) Under Ge (N. Submission Date for this Tender is 14-12-2022. Electrical Maintenance Tenders in Pune Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

35010941
Corrigendum : Tender For Ge(N)P/T- 60 Of 22-23Rep Maint Of Existing Lt Panel Distr Sys, Lt Ug Cable Contr Connectg Items Allied Wks At Main Receiving Stns Other Ext Rep Wk At Hqsc Cesc Cepz Cwe Mayo Rd Zro, Rs Rd 06 Qg 16 Qg In The Area Of Age E/M (N) Under Ge (N
Open Tender
Indian
Maharashtra
Pune
14-12-2022

Tender Details

Repair Maintenance Of Existing Lt Panel Distr Sys, Lt Ug Cable Contr Connectg Items Allied Wks At Main Receiving Stns Other Ext Rep Wk At Hqsc Cesc Cepz Cwe Mayo Rd Zro, Rs Rd 06 Qg 16 Qg In The Area Of Age E / M ( N ) Under Ge ( N ) Pune

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Dec-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 14-12-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Name of Work:REPAIR MAINT OF EXISTING LT PANEL DISTRIBUTION SYSTEM, LT UG CABLE, CONTROLS AND CONNECTING ITEMS AND OTHER ALLIED WORKS AT MAIN RECEIVING STATIONS AND CERTAIN OTHER EXTERNAL REPAIR WORK AT, HQSC, HQ CESC, HQ CEPZ, HQ CWE, GENERAL BEWOOR ROAD, PG ROAD, KAHU ROAD, TARAPORE ROAD, MAYO ROAD, MAYO ROAD, ZRO, RS ROAD, 06 QG, 16 QG,ETC IN THE AREA OF AGE E/M SUB DIVISION UNDER GE (N) PUNE.
Sl. No. Item Description
1Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning ofLT feeder pillar panel CPRI approved double door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2.00mm for inner compartments with suitable size with aluminium bus bar (50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator,internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCCblock (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Shanti vihar Near Temple)
2Incoming
3(a) MCCB, 4 Pole, 415 Volts, 315 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 voltsIcs=100% Icu -01 No
4(c) Digital Voltmeter 0-500 volts with selector switch - 01 No
5(d) Digital Amp meter 0-200 Amp with selector switch - 01 No
6(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
7Outgoing
8(a) MCCB 3 pole, 63 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 voltsIcs=100% Icu - 06 Nos
9(b) MCB DP32 Amp, 240v, 50HZ, 10KA, "C series" - 02 Nos
10(d) Provision for space to be kept blank for fixing of MCCB - 01 No
11Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts with washer are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
12Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning ofLT feeder pillar panel CPRI approvedsingle door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2.00mm for inner compartments of suitable size with aluminium bus bar (80 x 10 mm) 800 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator,internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCCblock (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (39 Nehru Marg).
13Incoming
14(a) MCCB, 4 Pole, 415 Volts, 500 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 voltsIcs=100% Icu -01 No
15(c) Digital Voltmeter 0-500 volts with selector switch - 01 No
16(d) Digital Amp meter 0-200 Amp with selector switch - 01 No
17(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
18Outgoing
19(a) MCCB 3 pole, 125 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 voltsIcs=100% Icu - 06 Nos
20(d) Provision for space to be kept blank for fixing of MCCB - 01 No
21Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts with washer are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
22Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning ofLT feeder pillar CPRI approvedpanel single door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2.00mm for inner compartments of suitable size with aluminium bus bar (50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator,internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCCblock (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Near Bldg No T-1 Old Sapper Line).
23Incoming
24(a) MCCB, 4 Pole, 415 Volts, 320 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 voltsIcs=100% Icu -01 No
25(c) Digital Voltmeter 0-500 volts with selector switch - 01 No
26(d) Digital Amp meter 0-200 Amp with selector switch - 01 No
27(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
28Outgoing
29(a) MCCB 3 pole, 125 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 voltsIcs=100% Icu - 03 Nos
30(b) MCB TPN63 Amp, C series 415V, 50HZ - 02 Nos
31(b) MCB DP32 Amp,10KA C series 240V, 50Hz - 02 Nos
32(d) Provision for space to be kept blank for fixing of MCCB - 01 No
33Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Boltswith washer are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
34Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning ofLT feeder pillar CPRI approvedpanel single door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2.00mm for inner compartments of suitable size with aluminium bus bar (120 x 10 mm) 1200 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator,internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCCblock (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Composite officer MESS).
35Incoming
36(a) ACB, 4 Pole, 415 Volts, 800 Amp, manual drawout type, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 voltsIcs=100% Icu -01 No
37(c) Digital Voltmeter 0-500 volts with selector switch - 01 No
38(d) Digital Amp meter 0-200 Amp with selector switch - 01 No
39(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
40Outgoing
41(a) MCCB 3 pole, 200 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 voltsIcs=100% Icu - 03 Nos
42(a) MCCB 3 pole, 125 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 voltsIcs=100% Icu - 04 Nos
43(a) MCCB 3 pole, 100 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 16 KA at 415 voltsIcs=100% Icu - 04 Nos
44(d) Provision for space to be kept blank for fixing of MCCB - 01 No
45Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts with washer are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
46Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning ofLT feeder pillar CPRI approved panel single door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2.00mm for inner compartments of suitable size with aluminium bus bar (50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator,internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCCblock (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (Golf main office).
47Incoming
48(a) MCCB, 4 Pole, 415 Volts, 300 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 voltsIcs=100% Icu -01 No
49(c) Digital Voltmeter 0-500 volts with selector switch - 01 No
50(d) Digital Amp meter 0-200 Amp with selector switch - 01 No
51(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
52Outgoing
53(a) MCCB 3 pole, 100 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 voltsIcs=100% Icu - 01 Nos
54(b) MCB TPN63 Amp, 415V, 50Hz, 10KA, C series - 04 Nos
55(b) MCB DP32 Amp, 240V,50Hz, 10KA, C series - 04 Nos
56(d) Provision for space to be kept blank for fixing of MCCB - 01 No
57Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts with washer are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
58Taking down old unserviceable feeder pillar box of any type, Supply, fixing, testing and commissioning ofLT feeder pillar CPRI approved panel single door floor mounted and wall/pole mounted outdoor type, as per IP-65 grade, made out of CRCA sheet 3.00 mm thick of outer body and 2.00mm for inner compartments of suitable size with aluminium bus bar (50 x 10 mm) 500 Amps, 4 strip (3 phase & Neutral) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator,internal wiring with suitable size of copper wire, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking, shouldhave danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCCblock (1:2:4) type B-1 foundation for fixing of panel complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands, Nuts & Bolts, Washers complete with comprising of following and including: - (SCOM Sub Station).
59Incoming
60(a) MCCB, 4 Pole, 415 Volts, 500 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 50 KA at 415 voltsIcs=100% Icu -01 No
61(c) Digital Voltmeter 0-500 volts with selector switch - 01 No
62(d) Digital Amp meter 0-200 Amp with selector switch - 01 No
63(e) Indicator lamp LED type (R,Y,B) complete with bakalite fuse fitting - 01 Set
64Outgoing
65(a) MCCB 3 pole, 250 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 voltsIcs=100% Icu - 01 Nos
66(b) MCCB 3 pole, 200 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 voltsIcs=100% Icu - 03 Nos
67(c) MCCB 3 pole, 125 Amp, with RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 25 KA at 415 voltsIcs=100% Icu - 02 Nos
68(d) MCCB 3 pole, 100 Amp,RotaryHandle, adjustable Thermal Magnetic relay with breaking capacity 36 KA at 415 voltsIcs=100% Icu - 02 Nos
69(e) MCB TPN63 Amp,415V, 50Hz, C series -03 Nos
70(f) Provision for space to be kept blank for fixing of MCCB - 01 No
71Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel is included in rates quoted. All fixing material like thimble, Nuts & Bolts are included in unit rate. Earthing strip to be connected with feeder pillar box with suitable size Nuts & Bolts.
72Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 240 Sq mm3.5 core complete all as specified and as directed. Note : Provision of suitable double crimpped lugs and glands deemed to be included in quoted rates.
73-ditto- all as per item No 7 but 185 sqmm 3.5 core
74-ditto- all as per item No 7 but 120 sqmm3.5 core
75-ditto- all as per item No 7 but95 sqmm3.5 core
76-ditto- all as per item No 7 but 70 sqmm3.5 core
77-ditto- all as per item No 7 but50 sqmm3.5 core
78-ditto- all as per item No 7 but35 sqmm4 core
79-ditto- all as per item No 7 but 25 sqmm 4 core
80M&L for Boring of holes under road, pavement,hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed.
81Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 50mm bore for protection of UG cables complete all as specified and as directed.
82-Ditto-all as per Item No. 16 above but of size 80 mm bore complete all as specified and as directed.
83Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed.
84Returning filling in including spreading, leveling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
85Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
86Supply and laying 40mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propagating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
87Supply and laying 50mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propagating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
88Supply and laying 63mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
89Supply and laying 75mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
90S &FACB (air circuit breaker) draw out typeof rating 800 Amps 4 pole, 50 KA, O/L, S/C, micro processor based release and cassette mounted horizontal draw out type fully interlocked cassette door automatic safety shutters, mechanical on and off indicators, service/test/isolated position with position indicators, provision of castell lock, with O/L, S/C with 3 CT"s of standard ratings 4 blocks of 6 way sliding type LT disconnectors, error prevention plug, racking handle, safety shutters and painted with finished light grey shadeas per IS:631 and as per IS 13947-2-1993 inclusive suitable length of bus bars complete all as specified and as directed.
91M&L for Maintenance Free Grounding Solution set earthing comprising of High tensile low carbon steel rod of 3 Mts length & 17.2 mm dia with 250micron ( average ) molecularly bonded copper on the outer surface along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. Back-fill compound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. Make: JEF Technology or equivalant in True power earthings Note:- a)Test certificate from the OEM has to be produced by the contractor for the material used in earthing. b) If the test result obtain from earthing is not less than 3 Ohms then earthing has to be done again at no extra cost. c)Rates for Excavation and earthwork in any type ofsoil/strata, testing on completion, copper clad steel conductor wire 4 mm dia and 15 mm dia protection pipe upto 7.5 mtr from Electrode is deemed to be included in rate quoted.)
92S&F Earth conitnuity Copper clad steel conductor or main earthing lead fixed to wall on batten or reccess or chases or burried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing etc as required 8 mm dia after taking down the old one any type.
93Note : 1. Performance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.