Tender For Repair/Replacement And Maintenance Of Lt Distribution Network And Repair/Replacement/Servicing Of Summer Appliances And Other Allied Works At Mil Stn Beas, 2 Asd And Jandiala Guru Under Ge Kapurthala, kapurthala-Punjab

Military Engineer Services-MES has published Tender For Repair/Replacement And Maintenance Of Lt Distribution Network And Repair/Replacement/Servicing Of Summer Appliances And Other Allied Works At Mil Stn Beas, 2 Asd And Jandiala Guru Under Ge Kapurthala. Submission Date for this Tender is 15-12-2022. Air Conditioner Tenders in kapurthala Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

34842121
Corrigendum : Tender For Repair/Replacement And Maintenance Of Lt Distribution Network And Repair/Replacement/Servicing Of Summer Appliances And Other Allied Works At Mil Stn Beas, 2 Asd And Jandiala Guru Under Ge Kapurthala
Open Tender
Indian
Punjab
kapurthala
15-12-2022

Tender Details

Repair / Replacement And Maintenance Of Lt Distribution Network And Repair / Replacement / Servicing Of Summer Appliances And Other Allied Works At Mil Stn Beas, 2 Asd And Jandiala Guru Under Ge Kapurthala

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Dec-2022 Corrigendum No-01 Other 08-12-2022
2 08-Dec-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 15-12-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 88000.0 /-
Tender Value
INR 44 Lakhs /-

BOQ Items

Name of Work : Repair/Replacement of External water supply line ,all type of pump sets and allied works at Mil Stn Beas, 2 ASD area and Jandiala Guru under GE Kapurthala.
Sl. No. Item Description
1Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for taking out old cable/laying of under ground cable/foundation of poles/stays including segregation of old serviceable bricks complete all as specified and directed by Engr-in-Charge.
2All as per item No. 1 above but depth exceeding 1.5 metre & not exceeding 3.00 metre, complete all as specified and directed by Engr-in-Charge.
3Returing, filling in, including spreading, leveling watering and well ramming in layers not exceeding 25 cm thick each layer, complete all as specified and directed by Engr-in-Charge.
4Removal of surplus soil to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point, complete all as specified and directed by Engr-in-Charge.
5M&L for brick protection using old size sub class "B" bricks, laid flat dry but adjoining to each other laid length wise perpendicular to the axis of cable complete all as specified and directed by Engr-in-Charge.
6Supplying, filling in trenches spreading, leveling sand cushioning 8 cm below and 15 cm above the cable for under ground cable complete all as specified and directed by Engr-in-Charge.
7Dismantling of existing old ACSR conductors, any size, from existingLT poles at area where UG cables are to be laid,by unwinding the binding wirefrom insulators including disconnecting from the existing system, keep in safe custody for reuse, complete all as specified and directed by Engr-in-Charge. Note : (a) Payment for taking down of insulators shall be made for separately. (b) Restringing of serviceable ACSR will be measured separately. (c) UG Cables to be measured separately.
8Dismantling of existing old cross arms etc made of mild steel channel, angle iron, flat iron, back plates, nuts, bolts, washers etc complete all as specified and directed by Engr-in-Charge.
9Dismantling/taking down of insulators of any type/size from LT poles complete all as specified and directed by Engr-in-Charge.
10Dismantling of existing old earth wire/guard wire service feeder or distributor span complete all as specified and directed by Engr-in-Charge.
11Supply and laying in trenches/through pipes or bare in road crossings/ paths/drains/ducts/floors/along poles/walls/ ceilings/ equipments etc. Cable Under ground, Heavy duty, armoured, XLPE insulated with stranded aluminium conductor, 1100 Volts grade of following cross sectional area complete all as specified and directed by Engr-in-Charge.
12(a) 16 Sqmm 2 core
13(b) 16 sqmm 4 Core
14(c) 25 sqmm 4 Core
15(d)35 sqmm 3.5 Core
16(e)70 sq mm 3.5 core
17(f) 95 sq mm 3.5 core
18(g)120 sq mm 3.5 core
19(h)185 sq mm 3.5 core
20Supply and layng in replacement GI pipe light grade 50 mm bore for cable porotection fixed to poles/along wall/floor/under road/preparation of GI bracket etc across the drain or nallah with clamps. Bolts, nuts & washers etc complete all as specified and directed by Engr-in-Charge including taking down the old unsv (clamps. Bolts, nuts & washers shall be measured and paid seperatly)
21All as per item No 12 abovebut of 80 mm dia
22M&L for cutting the existing hard standing/PCC/WBM road at a depth not less than 45 cm and 25 cm in width for passing of cable through GI pipe, returning filling in, complete including finishing the surfaces by providing cement concrete type B-1 (1:2:4) with 20 mm graded aggregate upto 20 cm, finishing to a uniform smooth surface complete all as specified and directed by Engr-in-Charge.
23S&F in repairs Danger notice plate for LT, 20cm x 15cm x 1.60 mm thick, mild steel sheet, vitreous, enamelled white, with letters, figures and conventional skull & bones in single red colour and fixed on LT Panel using suitable nuts, bolts and washers of required size complete all as specified and directed by Engr-in-Charge.
24Taking down old unserviceable PCC pole from site and Supply and fix Steel tubular swaged poles type 410SP-31(9.0 meter long)complete with cast iron base plate, finial taper plug, bolts, nuts and screws as complete all as specified and directed by Engr-in-Charge.
25S&F Sintex make PVC looping box comprising ofAluminiumbus bar 4 Nos(TPN) and one No 6 Amps SP MCBincluding necessary Clamps made out of MS flat iron, nuts and bolts suitable for fixing with steel tubular Poles complete all as specified and directed by Engr-in-Charge.
26M&L for wiring for Circuit from MCB box to Streetlight including supply and fixing (with suitable clamp) of pvc conduit of size 20 mm dia on pole withFRLS PVC insulated copper conductor single core cable with 2 x 1.5 sqmm + 1 x 1.5 Sqmm earth wire in surfaces/recessed as required complete all as specified and directed by Engr-in-Charge.
27S&F LED street lightfitting 35 WattIP65 Powder coated pressure die cast aluminium compact LED security light/Street light with heat resistant toughened glassincluding1.5 mtr long 32 mm bore GI pipe mounting bracket made to shape for fixing on Pole with 40 mm x 6 mm flat iron clamp 02 numbers with 16 mm dia bolts, nuts and washers complete all as specified and directed by Engr-in-Charge.
28M&L for PCC 1:4:8 type D2 (using 40 mm graded stone aggregates) as in foundation bed and around the pole as massconcrete including necessary form work and finishing the exposed surface even and smooth without using extra cement complete all as specified and directed by Engr-in-Charge.
29All as per description of serial item No 20 here-in-before but PCC (1:2:4) type B-1 using 20 mm graded stone aggregates as in coping of poles, complete all as specified and directed by Engr-in-Charge.
30S&F in replacement, shackle type porcelain vitrous white, green or brown insulators for working pressure 1100 volts grade 90 mm dia x 75 mm height including galvanised MS straps, washers, insulator bolts, washers & nuts complete all as specified and directed by Engr-in-Charge.
31S&F in replacement pin type porcelain, vitrous white, brown insulator including one galvanised MS spindle and two galvanised iron washers and one galvanised MS nut, 100 mm height 65 mm dia for 1100 volt grade complete all as specified and directed by Engr-in-Charge.
32Supply & fabricating and fixing in replacement cross arms (any type) supports bracing, stiffeners anticlimbing spikes etc made out of MS, MS channel, angle iron, flat of any size including drilling of holes, making of clamps, nut, bolts etc including painting with two coat ofaluminium paint over a coat of red oxide primer after preperation of surface to all steel and iron surfaces complete all as specified and directed by Engr-in-Charge.
33S&F in replacement of MCCB, 4 pole, 415 volt of cpacity 160 Amp, short circuit breaking capacity 35/36 KA, thermal magnatic protection type confirming to IS, including thimbles, nuts, bolts, washers etc disconnecting from LT panel and making incoming, out going connections complete all as specified and directed by Engr-in-Charge. (Cost of copper thimbles, nut & bolts shall be included in the quoted rate).
34All as per item No 25 above but capacity 200 Amps and breaking capacity 35/36 KA, complete all as specified and directed by Engr-in-Charge.
35All as per item No 25 above but capacity 250 Amps and breaking capacity 35/36 KA, complete all as specified and directed by Engr-in-Charge.
36S&F in replacement of MCCB, 4 pole, 415 volt of cpacity. Adjustable type 300 to 350Amp, short circuit breaking capacity 35/36 KA, thermal setting 70-100% confirming to IS, including thimbles, nuts, bolts, washers etc disconnecting from LT panel and making incoming, out going connections complete all as specified and directed by Engr-in-Charge. (Cost of copper thimbles, nut & bolts shall be included in the quoted rate).
37All as per item No 28 but capacity 400 Amps and breaking capacity 35/36 KA and thermal setting 5 to 10 timescomplete all as specified and directed by Engr-in-Charge.
38Note for Item No 25 to 29 : Contractor will provide MCCBs as per site requirement/design of LT Panel (as per Make,model, type of existing MCCBs) for proper housing of MCCBs in existing LT Panels)
39M&L in replacement earthing complete with GI or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically in a pit not less than 2.25 meter below ground level with top edge of earth plate at a depth not less than 1.5 meter below level covered on all sideswith alternative layers of charcol dust and common salt 15 cm thick connected to galvanised earth lead Galvanised Iron strip 32 x 6 cm by means of bolts, nuts, check nuts and washers of Galvanised Iron or steel with protection pipeearth wireprotected by galvanized steel pipe light grade 40 mm bore from top of the earth plate electrode upto test point and watering pipe 20mm bore, GI light grade with funnel and wire mesh all as shawn in electrical plate No 3 of SSR Part-1 and connected to earthing test point all as specified or indiated and testing on completion, including PCC earth pit (1:3:6) type C-2 RCCcovered with CI cover hinged with frame including excavation and earth work complete all as specified and directed by Engr-in-Charge.
40S&F in replacement cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material (Epoxy Based) and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 25 to 50 sq mm indoor/outdoor type complete all as specified and directed by Engr-in-Charge.
41All as per item No 31 above but for cable of size 70 to 95Sqmm.
42All as per item No 31 above but for cable of size 120 to 150 Sqmm.
43All as per item No 31 above but for cable of size 185 to 240 Sqmm.
44M&L for unbinding from insulators the ACSR conductor on pole and restretching the loose ACSR conductor of any size on LT poles and binding the same with 2 mm dia new alumunium binding wire complete all as specified and directed by Engr-in-Charge.
45Labour only for cutting/pruning of tree branches 1.5 mtr all around the LT overhead lines of span n.exc 40 mtr and around the pole obstruction the overhead line & removing the branches to distance n.exc 50 mtr to be the entire satisfaction of Engineer-in-charge.
46Labour only by providing a trained electrician with helper for servicing, repair/maint, replcement of unservicable components like changeover, MCCBs, Volt meter, Ammeter etc , cutting/drilling/weldingwk etc ,replacement of copper/alumn bus bar , thimbles, changing of connection copper wire lead etc complete all as specified and directed by Engr-in-Charge. (The above job also includes replacement of following component in existing LT PanelBoards including disconnecting and taking down the UNSV components at different locations complete all as specified and directed by Engr-in-Charge:- (Items used will be measured and paid separately.
47(a) Aluminium thimbles orlugs 35 sqmm
48(b) Aluminium thimbles orlugs 50 sqmm
49(c) Aluminium thimbles orlugs 70 sqmm
50(d) Aluminium thimbles orlugs 95 sqmm
51(e) Aluminium thimbles orlugs120 sqmm
52(f)Voltmeter Digital type ,0-500 Volts
53(g) Ammeter Digital type of 400 amps capacity
54(h) Selector switch for voltmeter &Ammeter Digital type
55M&L for cleaning and preparation of old painted surface of HT/LTPCC pole 9/ 11 mtr long andpainting with one coat ofmarking 30 cm high alternate black & white strips with synthetic enameled paint up to 1.5 mtr height and writing pole Nos and applying one coat of cement base paint on PCC copingcomplete all as specified and directed by Engr-in-Charge.
56M&L for preparation of old painted steel pole of 9 m long and painting with two coats of aluminium paintfrom top of the pole to 1.5 m above the bottom of the pole and painting with two coats of black bituminous paint over a coat of red oxide zinc chrome primer upto 1.5m from bottom of the pole complete all as specified and directed by Engr-in-Charge.
57Taking down existing old unsv LT panel and supply, fabricating, installation, commissioning, testing and electrically connectedCPRI approved manufacturerLT panel out door cubical type, Double door,made of 3.15 mm thick CRCA sheet steel on angle iron frame 50mm x 50mm x 6 mm of size not less than 1.5m x1.5 m x.0.60 m with removable hinged doors on both side, locking arrangement, vermin proof, painted with 2 coats of synthetic enamel paint over a coat of red oxide (internal& external surface) with heat shrinkable sleeves on Copper bus bar 400 Amp capacity - 04 Nosfor distribution, complete wiring with thimbles and other accessories using crimping tool including foundationfor fixing over PCC (1:2:4) type B-1 using 20mm graded stone aggregate foundation complete all as specified and directed by Engr-in-Charge comprising the following :- Incoming:- (i)MCCB 4 pole, 415 volts Adjustable type,400 Amps,36KA, 50 C/S with spreader link - 01 Nos. Outgoing:- (i)MCCB 4 pole, 415 volts ,100 Amps,36KA, 50 C/S with spreader link - 08 Nos. (ii) Power contactor 3P,415V AC, 32 A(Cat No 850047 of Make :Indoasian or equivalent inL&T,Legrand,Havells) - 01 No. (iii) Aanalog time switches WithBty back up ,3 P Module ,24 Hrs program. (Cat No TA 926453 of Make :Indoasian or equivalent inL&T,Legrand,Havells) - 01 No. (iv)Indicating lamps, LED type, 230VAC - 3Nos. (v)Digital Voltmeter, 3Phase -1 Nos. (vi)Digital Ammeter 3Phase - 1 Nos. (vii)CT coils - 3 Nos.
58Taking down existing old unsv LT panel and supply, fabricating, installation, commissioning, testing and electrically connectedCPRI approved manufacturerLT panel out door cubical type, Double door,made of 3.15 mm thick CRCA sheet steel on angle iron frame 50mm x 50mm x 6 mm of size not less than 1.5m x1.5 m x.0.60 m with removable hinged doors on both side, locking arrangement, vermin proof, painted with 2 coats of synthetic enamel paint over a coat of red oxide (internal& external surface) with heat shrinkable sleeves on Copper bus bar 600 Amp capacity - 04 Nosfor distribution, complete wiring with thimbles and other accessories using crimping tool including foundationfor fixing over PCC (1:2:4) type B-1 using 20mm graded stone aggregate foundation complete all as specified and directed by Engr-in-Charge comprising the following :- Incoming:- (i)MCCB 4 pole, 415 volts Adjustable type,400 Amps, 36KA, 50 C/S with spreader link - 01 Nos. Outgoing:- (i)MCCB 4 pole, 415 volts Adjustable type, 250 Amps, 36KA, 50 C/S with spreader link - 02 Nos. (ii)MCCB 4 pole, 415 volts Adjustable type,200 Amps, 36KA, 50 C/S with spreader link - 04 Nos. (iii) MCCB 4 pole, 415 volts,Adjustable type,100 Amps, 36KA, 50 C/S with spreader link - 02 Nos. (iv)Indicating lamps, LED type, 230VAC - 3 Nos. (v)Digital Voltmeter, 3 Phase - 1 Nos. (vi)Digital Ammeter, 3 Phase- 1 Nos (vii)CT coils - 3 Nos.
59Taking out damaged butt hinges and locking arrangement from out door type LT Panel door andM&L for welding new hinges and locking arrnagement on the panel door inlcuding denting/adjusting the door for proper closingandPreparing old painted outer exposed surfaces of LT Panel Board ofarea not less than 5 SqM, all exposed surfaces of steel items fixed with the Panel, without dismantling and M&L for painting with two coats of synthetic enamel paint of approved shade complete all as specified and directed by Engr-in-Charge.
60Dismantling and taking down only existing ACSR conductor of any size/type from LT electric pole with the help of suitable T&P and proper safety gears to clear the disturbed area due to wind/storm complete all as specified and directed by Engr-in-Charge.
61M&L in replacement ACSR conductor of any size including binding on existing LT poles or new poles with 2 mm dia aluminium binding wire complete including dismantling/taking down of old unsv ACSR conductor, complete all as specified and directed by Engr-in-Charge.(Squirrel/Weasel type ACSR to be used)
62S&F spacers suitable for ACSR Over head conductors, PVC, of size 4 way (For 4 wire system) including taking out the U/s items from OH lines, complete all as specified and directed by Engr-in-Charge.
63S&F spacers suitable for ACSR Over head conductors, PVC, of size 6 way (For 6 wire system) including taking out the U/s items from OH lines, complete all as specified and directed by Engr-in-Charge.
64Dismantling and taking out/ down old existing broken/ deshaped LT PCC poles 9 mtrincluding insulators from site by means of JCB/ Hydra machine/Typhor or suitable T&P with proper safety arrangements, providing proper stay wires etc to avoid damage to others poles/span of ACSR including depositing/collecting the pole a side in a proper way complete all as specified and directed by Engr-in-Charge. (Items includes dismantling of 4/2 pole structure also).
65M&L for repalcement of Stay assemblycomprising of GI stay bow 14 mm dia, 40 cm long (over all) galvanized steel stay rod 20 mm dia, 215 cm long with threaded ends GI nuts, bolts, washers, stay plate 30cmx30cmx6mm complete all as specified and directed by Engr-in-Charge.
66Supply & Replacement of stay wire standard of 7/4 mm of GI wire, complete all as specified and directed by Engr-in-Charge.
67Supply & Replacement of loop type insulators, vitreous porcelain brown or green large size with over all dimension 90 x 140 mm clearance of hole 25.5 mm, complete all as specified and directed by Engr-in-Charge.
68Taking down ceiling fansof any make,type and size by skilled electrician/mech at site given by JE E/M or Engr in Charge, removing electrical connection,dismantling blades etc, opening ofmotor, cleaning of fan body and blades using detergent, greasing and oiling of serviceable ball bearing, bushes, replacement of Capacitor 2.5/4.00 mfd in slow speed fan,reassemblingmotor and fan, testing and hanging in position, if found unserviceablethe fans shall be seggregated in two categories rewinding required or replacement of ball bearing/gun metal bush requiredthe same will be transported to workshop for repair/rewinding/maint work complete all as specified and directed by Engr-in-Charge. Note:- (i)Rewinding/ replacement of ball bearing or gun metal bushes etc will be measured & paid separately in respective item as mentioned in Schedule of work (ii)The above rates includes the replacement of Capacitor (in slow speed fan) at site.
69Taking down Exhaust fans of any make,type and size by skilled electrician/mech, removing electrical connection,dismantling blades etc, opening ofmotor, cleaning of fan body and blades using detergent, greasing and oiling of serviceable ball bearing, bushes, reassemblingmotor and fan, testing and hanging in position, if found unserviceablethe fans shall be seggregated in two categories rewinding required or replacement of ball bearing/gun metal bush requiredthe same will be transported to workshop for repair/rewinding/maint work complete all as specified and directed by Engr-in-Charge & refering the same after repair from workshop. Note:- Rewinding/ replacement of ball bearing or gun metal bushes etc will be measured paid separately in respective item as mentioned in Schedule of work.
70M&L for rewinding of ceiling fan motor 240 volt, 50 Hz, 1200/1400 mm sweep, any make, with super enameled copper winding wire of existing size, same No of turns, wound with machine, providing insulation material of E-grading, varnishing, connection with flexible copper wire of suitable size upto connector block complete all as specified and directed by Engr-in-Charge.
71S&F in replacement of ball bearing 6201/6202/6203 or any other suitable size required in defective ceiling fan of size 1200/1400mm sweep retrieved from Item No 1including testing of fans complete all as specified and directed by Engr-in-Charge.
72S&F in replacement of Gun metal bushes ofsuitable size required in defective ceiling fan of size 1200/1400mm sweep retrieved from Item No 1including testing of fans complete all as specified and directed by Engr-in-Charge.
73Supply only capacitor2.5 MFD of ceiling fan complete all as specified and directed by Engr-in-Charge.
74Supply only capacitor 4.00 MFD of ceiling fan complete all as specified and directed by Engr-in-Charge.
75M&L for rewinding of exhaust fan motor 240 volt, 50 Hz, 400 to 600 mm sweep, any make, with super enameled copper winding wire of existing size, same No of turns, wound with machine, providing insulation material ofE-grading, varnishing, connection with flexible copper wire of suitable size upto connector block complete all as specified and directed by Engr-in-Charge.
76M&L for rewinding of exhaust fan motor 240 volt, 50 Hz, 150-350 mm sweep, any make, with super enameled copper winding wire of existing size, same No of turns, wound with machine, providing insulation material of E-grading, varnishing, connection with flexible copper wire of suitable size upto connector block complete all as specified and directed by Engr-in-Charge.
77S&F in replacement of ball bearing of suitable size required in defective Exhaust fan of size 400 to 600 mm sweep retrieved from Item No 1including testing of fans complete all as specified and directed by Engr-in-Charge.
78S&F in replacement of ball bearing of suitable size required in defective Exhaust fan of size 150 to 350 mm sweep retrieved from Item No 2including testing of fans complete all as specified and directed by Engr-in-Charge.
79S&F in replacement of Gun metal bushes ofsuitable size required in defective Exhaust fan of any type any size/sweep retrieved from Item No 2including testing of fans complete all as specified and directed by Engr-in-Charge.
80S&F in replacement of Fan hanging clamp, Locking screw, Blade screw complete all as specified and directed by Engr-in-Charge.
81Supply and fixing in replacement of Down rod 15 mm dia MS tube 60 cm longcomplete all as specified and directed by Engr-in-Charge.
82Supply and fixing in replacement of Down rod 15 mm dia MS tube 90 cm long complete all as specified and directed by Engr-in-Charge.
83Taking down wall mounted fan of any make, typeand size at site by skilled electrician/mechanic , removing electrical connection, dismantling blades etc, opening ofmotor, cleaning of fan body and blades using detergent, greasing and oiling of serviceablebearing, bushes, reassemblingmotor and fan, testing and hanging in position. If found unserviceable/burnt ,rewinding required,transported to workshop for repair/rewinding/maint complete all as specified and directed by Engr-in-Charge.
84M&L for rewinding of wall mounting fan motor 240 volt, 50 Hz, any make, with super enameled copper winding wire of existing size, same No of turns, wound with machine, providing insulation material of E-grading, varnishing, connection with flexible copper wire 0.472mm dia upto connector block complete all as specified and directed by Engr-in-Charge.
85S&F in replacement at siteAir circulating wall mounted Fans 230 volts single phase, sweep size 400 mm, high performance motor for better air delivery jerk free oscillation & smooth running, Aerodynamically designed balanced heavy duty PP blades, superior low voltage performance sweep size 400 mm, power input 50 watts, Speed 1360 RPM, Air delivery 72 cmm, etc suitable for mounting on wall, complete all as specified and directed by Engr-in-Charge. (Old unsv wall fan to be deposited in MES store Yard for repair/rewinding wk).
86S&F in replacement at site electronic fan regulator 230 volts, step type,switch/socket, hum free, 120 watt complete all as specified and directed by Engr-in-Charge.
87Maintenance, servicing and testing of split type/window type AC, capacity upto1.5/2 tons, any make, by cleaning cooling coil, condenser fins, blowing of dust from machines/air filters, checking and decarbonising all electric system oiling/greasing of blower motor, checking and removing any vibration and leakage in the equipment including checking/repair to inter locking device for winter/summer to ensure cutting off of compressor/heating in case of failure of blower motor including taking down and refixing in position complete all as specified and directed by Engr-in-Charge. Note:- Cost of minor repair, replacement of petty items such as nuts, bolts, washers, screws, rubber mounting pads of compressor etc, transportation of equipment to workshop and back is deemed to be inclusive in the unit rates quoted by the contractor.
88S&F, in replacement, new compressor for window type AC 1.5/2Ton capacity including disconnecting, opening up, taking out burnt compressor by cutting/opening the pipe connections, fixing in position, reassembling, testing and commissioning including gas & oil charging after flushing the line with CO2 gas to avoid trapping the water vapour ensuring leak proof system complete all as specified and directed by Engr-in-Charge.
89S&F, in replacement, new compressor hermetic/rotary for split type AC 1.5/2Ton capacity including disconnecting, opening up, taking out burnt compressor by cutting/opening the pipe connections, fixing in position, reassembling, testing and commissioning including gas & oil charging after flushing the line with CO2 gas to avoid trapping the water vapour ensuring leak proof system complete all as specified and directed by Engr-in-Charge.
90M&L for finding out leakage with the pressure testing of the condensor/cooling unit/ compressor of window type/Split type AC of 1.5/2.00 Toncap including dismantling the same for recharging with R-22 gas or as per manufacturer"s instruction and stop leakage by brizing/soldering including charging the gas to required level and testing the AC for the entire satisfaction of EIC.
91S&F nylon type filter pad20 micron for window type AC of capacity up to 2 ton including taking out unserviceable filter pad complete all as specified and directed by Engr-in-Charge.
92S&F, in replacement, running capacitor 5 MFD 230 volts for blower motor complete all as specified and directed by Engr-in-Charge.
93S&F starting capacitor clip type of cap. 80-100 MFD,440 suitable for 1.50 Ton capacity window/Split type AC complete all as specified and directed by Engr-in-Charge.
94S&F in repairs ofrunning capacitor, 100-120 MFD suitable for 1.5 / 2.00 Ton capacity window/split type AC complete all as specified and directed by Engr-in-Charge.
95S&F in replacement, starting relay suitable for window type AC of capacity up to 2 ton complete all as specified and directed by Engr-in-Charge.
96S&F in replacement, over load protection suitable for window type AC of capacity up to 2 ton complete all as specified and directed by Engr-in-Charge.
97S&F in replacement, thermostat switch suitable for window type AC of capacity up to 2 ton complete all as specified and directed by Engr-in-Charge.
98S&F in replacement, blower motor 1/8 HP, double shaft, single phase suitable for window type AC up to 2 ton capacity including testing complete all as specified and directed by Engr-in-Charge.
99S&F in replacement, fan blade for blower motor for window type AC up to 2 ton capacity complete all as specified and directed by Engr-in-Charge.
100S&F in replacement, starting relay suitable for split type AC of capacity up to 2 ton complete all as specified and directed by Engr-in-Charge.
101S&F in replacement, thermostat switch hot & cold product no2KSP-5010 complete all as specified and directed by Engr-in-Charge.
102S&F in replacement, power circuit breaker (PCB) kit for split/window type AC complete all as specified and directed by Engr-in-Charge.
103S&F in repair drain out pipe of split type AC complete all as specified and directed by Engr-in-Charge.
104Attending general complaints and rectification of defects of any type ofAC, Refrigerator, Water Cooler, Deep Freezer, Desert Cooler, Voltage Stabilizer, water purifier etc and testing after complete all as specified and directed by Engr-in-Charge. Note :- (i) The complaint shall be notified to the contractor by Engr-in-Charge or JE E/M and recorded in the register maintained for the purpose. (ii) Cost of any minor nature of repair, replacement of petty items such as nuts, bolts, washers, screws, piece of electric cable upto 0.50 metre length etc is deemed included in the unit rate quoted by the contractor.
105S&F in replacement, fan blower motor,single phase suitable for desert cooler including testing complete all as specified and directed by Engr-in-Charge.
106M&L for taking down existing unserviceablefan motor from desert cooler andincluding replacement of wornout winding, bushes and bearing etc and testing complete, refixing and connecting complete all as specified and directed by Engr-in-Charge.
107Supply and replacement of Water lifting submersible pump suitable for desert cooleras per existing capacity, complete all as specified and directed by Engr-in-Charge.
108S&F cooler pad made of Khas-Khas suitable for desert coolers including taking out unserviceable pad complete all as specified and directed by Engr-in-Charge.
109M&L for replacement of copper conductor cable 40/0.0076 Sqmm 3 core not less than 3 mtrs long with plug top 5 Amp suitable for desert cooler, complete all as specified and directed by Engr-in-Charge.
110M&L for replacement of Fan blade of desert cooler heavy duty HDPE suitable for 4000/5000 CFT cap complete all as specified and directed by Engr-in-Charge.
111Supply, fixing & testing new compressor for water cooler of capacity 40/80 Ltr, deep freezer capacity 200 to 320 Ltr including disconnecting, opening up, taking out burnt compressor by cutting/opening the pipe connections, fixing in position, reassembling, testing and commissioning including gas & oil charging after ensuring entire system leak proof complete all as specified and directed by Engr-in-Charge.
112Supply, fixing & testing new compressor for water cooler of capacity 60/120/150 Ltr,including disconnecting, opening up, taking out burnt compressor by cutting/opening the pipe connections, fixing in position, reassembling, testing and commissioning including gas & oil charging after ensuring entire system leak proof complete all as specified and directed by Engr-in-Charge.
113S&F, in replacement blower motor 1/35 HPwith base and clamp, rubber mountings, fan blade for water coolers including taking out the old unserviceable motor complete all as specified and directed by Engr-in-Charge.
114M&L for trickle charging of gas F-12/F-22/134a or as required in water cooler/Deep freezer, any capacity, after detection of leakage with soap solution/halide torch ,making the system leak proof by brazing/ soldering the leakage point, flushing out the moisture contentstrapped in the pipe line by charging CO2 gasand maintaining the pressure forprescribed period complete all as specified and directed by Engr-in-Charge.
115S&F push type water tap, 15 mm dia, chromium plated suitable for water cooler complete all as specified and directed by Engr-in-Charge.
116S&F in replacement, thermostat switch suitable for water cooler, any capacity/make including taking down unserviceable thermostat switch complete all as specified and directed by Engr-in-Charge.
117Supply, fixing & testing new compressor for refrigerator of capacity 286/310 Ltr including disconnecting, opening up, taking out burnt compressor by cutting/opening the pipe connections, fixing in position, reassembling, testing and commissioning including gas & oil charging after ensuring entire system leak proof complete all as specified and directed by Engr-in-Charge.
118M&L for trickle charging of gas F-12/134a or as required in refrigerator of capacity 260/286/310 Ltr, after detection of leakage with soap solution/halide torch,making the system leak proof by brazing/ soldering the leakage point, flushing out the moisture contentstrapped in the pipe line by charging CO2 gas and maintaining the pressure forprescribed period complete all as specified and directed by Engr-in-Charge.
119S&F in replacement starting relay for refrigerator of different capacity/ make including taking out unserviceable relay complete all as specified and directed by Engr-in-Charge.
120S&F in replacement thermostat switch for refrigerator of different capacity/make including taking out old unserviceable thermostat switch complete all as specified and directed by Engr-in-Charge.
121S&F in replacement of voltage stabilizerfor automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 2 KVA Make- V Guard Model VG-400 or equivalent including testing complete all as specified and directed by Engr-in-Charge.
122Taking down Geyser of any capacity from existinglocationby skilled Electrician/Mechanic at site given by Engr in Charge/JE E/M , cleaning/descaling of inner tank & assembly with wire brush, sand paper and with fresh water , detecting leakages from inner tank, appartus assembly, joints of Hot & Cold pipe etc if any, including refixing the geyser in position tightening the nuts, bolts, washer, connector etc testing complete for smooth functioning or iffound unserviceablethe geysers shall be segregated in following categories (a) replacement of heating element required (b) replacement of thermostat required (c) Replacement of assembly required (b) replacement of inner tank required (e) Brazing/soldering/gas welding required in inner tank and the same will be transported to workshop for repair/maint work complete all as specified and directed by Engr-in-Charge. Note:- The item rates include the cost of minor spares, wires nuts, bolts, washer etc required at site and replacement of indicator lamp at site.
123S&F in replacement of Heating element 1500 Watt (any type,any make, any size as per sample suitable for normal/ star rated geysers of reputed make) including testing and fixing of geyser atexisting location complete all as specified and directed by Engr-in-Charge.
124Supply and replacement of Heating element 2000 Watt (any type,any make, any size as per sample suitable for normal/ star rated geysers of reputed make) including testing and fixing of geyser at existing locationcomplete all as specified and directed by Engr-in-Charge.
125S&F apparatus assembly complete with incoming /out going brass pipe complete with gasket, nuts, bolts, washers etc as required for fitting in 25 ltrcapacity geyserincluding testing and fixing of geyser atexisting location complete all as specified and directed by Engr-in-Charge.
126S&F apparatus assembly complete with incoming /out going brass pipe complete with gasket, nuts, bolts, washers etc as required for fitting in 50 ltrcapacity geyser including testing and fixing of geyser atexisting location complete all as specified and directed by Engr-in-Charge.
127S&F in replacmentthermostat for Geyser of capacity 50 Ltr/25 Ltr of any make/type/or as per sampleincluding testing and fixing of geyser atexisting locationcomplete all as specified and directed by Engr-in-Charge.
128Supply only Indicator lamp square type/round type/rectangular type as per existing at site, 220 volts, complete all as specified and directed by Engr-in-Charge.
129Taking out the worn out inner tank of Geyser of capacity 50 Ltr and supply and fixin replacement copper inner tank ISI mark with existing model, making good with the insulating glass wool including testing and fixing of geyser atexisting location complete all as specified and directed by Engr-in-Charge.
130Taking out the worn out inner tank of Geyser of capacity 25 Ltr and supply and fixin replacement copper inner tank ISI mark with existing model, making good with the insulating glass wool including testing and fixing of geyser atexisting location complete all as specified and directed by Engr-in-Charge.
131M&L for brazing/copper gas welding/solderingetcthe inner tank of any capacity and making the Geyser leak proof and testing after filling with fresh water, including testing and fixing of geyser atexisting locationcomplete all as specified and directed by Engr-in-Charge.
132M&L for shifting the Geyser of any capacity from one location to other location by grouting with fastener, nuts, bolts etc complete all as specified and directed by Engr-in-Charge.
133S&F stop cock brass of size 15 mm dia complete all as specified and directed by Engr-in-Charge.
134S&F bib cock brassof size 15 mm dia, complete all as specified and directed by Engr-in-Charge.
135Supply, laying, fixing GI pipe medium class 15 mm dia including all fittings like elbow/union etc, by cutting wall and connecting on existing 15/20mm dia GI pipe complete all as specified and directed by Engr-in-Charge.
136S&F in replacement PVC connection hot and cold water pipe 18" long, 15mm outer dia with brass jem nut and washer, both side complete all as specified and directed by Engr-in-Charge.
137S&F in replacement PVC connection hot and cold water pipe 18" long made of chromium plated brass flexible tubing, complete all as specified and directed by Engr-in-Charge.
138Scraping of old painted surfaces of Geyser & making smooth surface for painting & applying one coat of white synthetic enemelled paint over the body of Geyser 50/25 litre capacity, complete all as specified and directed by Engr-in-Charge.
139S&F Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp, 9 KA,240 volt, complete all as specified and directed by Engr-in-Charge.
140S&F in replacement switch socket combination 2 in 1, 6 pin, 5 & 15 Amp, Flush type complete all as specified and directed by Engr-in-Charge.
141S&F in replacement 3 pin top plug , 15 Amp press type with and including 1.5 mtr copper conductor lead of 40/0.0076, 3 core, complete all as specified and directed by Engr-in-Charge.
142Repair/maint/servicing/overhauling of 500 LPD Flat Plate Solar water heating System installed at 2 ASD at Beas mil stn including descaling with chemical, checking electrical connection and minor repair/ spares, electrical wires, nuts bolts, clamps etc required at site for making functional to the existing solar water heating complete all as specified and directed by Engr-in-Charge. Note:- Other spares relevant to this item will be measured and paid separately .
143S&F in replacement the following spares of the solar water heating system as to be used while servicing and repair on above items :-
144(a)U Rubber
145(b)Round Gasket
146(c)D Scale chemical
147(d)Black board paint
148(e)Acid
149(f)Glass cleaners solution
150(g)Electrical heating element
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy