Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 30-11-2022 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 07-12-2022 |
| Sl. No. | Item Description |
| 1 | M&L for taking down unserviceable geyser of 25 Ltr capacity from existing position by disconnecting Elect/ water connectioions, from any position, locations and replacing the following unserviceable parts as mentioned below: - |
| 2 | (i) S&F in repairs thermostat suitable for 25 ltr storage type Vertical water heater ISI mark as per existing one complete all as specified and directed. |
| 3 | (ii) S&F in repairs LED indication lamp suitable for Geysers in round/ rectangular shape complete all as specified and directed. |
| 4 | (iii) S&F in repairs Geyser assembly suitable to fix thermostat, heating elements as of the existng size suitable for 25 ltr capacity geyser including suitable washers, clamps with bolts & nuts suitable for 06/09 hole complete all as specified and directed. |
| 5 | (iv) S&F in repairs fusible plug suitable for 25 ltr capacity Geysers as per existing complete all as specified and directed. |
| 6 | (v) Taking down unserviceable bottom/ top cover plates (2 half) and S&F with new bottom/ top cover plates with machine coloumns of Geyser 25 ltr capacity complete all as specified and directed. |
| 7 | (vi) S&F in repairs steel water tank suitable for 25 ltr capacity water heater vertical type as per existing model and size complete all as specified and directed. |
| 8 | (vii) S&F safety plug suitable for 25 ltr capacity vertical type water heater as per existing model/ make complete all as specified and directed. |
| 9 | (viii) S&F in replacement of M S heavy duty fabricated frame suitable for holding water tank of 25 ltr capacity geyser, as per sample and existng shape and size including suitable hole for mounting the Geyser complete all as specified and directed.Note: Sample can be taken for the geyser by the contractor from concerned JE E/M before quoting the rate. |
| 10 | (ix) S&F in replacement heating element 2 KW triangle type suitable for 25 ltr capacity vertical type water heater ISI mark. Make: Theeta complete all as per existing one and as directed. |
| 11 | (x) S&F glass wool heat insulation superior quality suitable for geyser ofCapacity 25/35/50 ltr |
| 12 | (xi) S&F outer cover in replacement suitable for 25 ltr capacity vertical water heater as per existing model heavy duty complete all as specified and directed. |
| 13 | (xii) M&L for spray painting to water heater of capacity 25 ltr capacity by spray machine with two coats of synthetic enamel paint after filling cavities with filler and cleaning dust etc complete all as specified and directed. |
| 14 | (xiii) Supply only nuts, bolts, washers suitable of existing size and model suitable for fixing of Geyser assembly with geyser tank complete. |
| 15 | (xiv) S&F PVC connection mesh type for HOT/ cold water supply 2\" long heavy duty ISI mark as per sample complete all as specified and directed. |
| 16 | M&L for point wiring complete with stranded copper conductor 4 Sqmm size (Nominal area) PVC insulated unsheathed FRLScable 1100 volts grade confirming to IS: 694 drawn in and including medium grade concealed PVC conduit confirming toISI marked not less than 25mm dia with concealed sunk-in pressed steel terminal boxes of required size not less than 1.2 mm thick factory made and painted with stove enamelled black paint top cover 2.80 mm thick plastic laminated sheet of required colour fixed with brass screwes and cup washers including single core stranded copper conductor 4 Sqmm PVC insulated unsheathed cable as earth wire to common earth and connected to earth dolly drawn in same concealed conduit complete all as specified for one 6 pin socket outlet two in one 16/6 Amps on an independent board. (for geysers point)Note : 1) For item No 2 & 3 Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. No Extra payment will be done on this account2) The work is of day to day repair nature. Contractor has to engage a supervisor to collect the complaint slips from the department on day to day basis and complete the job in 2 days. |
| 17 | All as per item No 2 above but with cable 2.5 Sqmm and earth continuity conductor of 2.5 Sqmm stranded copper unsheathed complete all as specified and as directed. |
| 18 | Supply and fix switch in repairs socket combination 5 Amps/16 Amps, 5 in 1, flush type complete all as specified and as directed. |
| 19 | Supply and fix in replacement MCB, DB , SPN 8 way suitable for single phase 240 volts with 100 Amps rated bus bar, double door type suitable for mounting incoming and outgoing MCB\"s single/double polecomplete all as specified and as directed. |
| 20 | Supply and fixing in replacement of MCB signle pole 6-32 Amps 230 volts \"C\" series complete all as specified and as directed. |
| 21 | Supply and fixing in replacement of MCB single pole and neutral 40 /63 Amps 230 volts \"C\" series complete all as specified and as directed. |
| 22 | S&F MCB SP 32 Amps 230 Volts \"B\" series complete all as specified and as directed. |
| 23 | Supply & fix in replacement of SPN enclosure with two pin and earth plug and socket complete with one SP MCB 20 Amps complete all as specified and directed by Engineer-in-Charge. Make:- Model No 607841 of Make Legrand or equivalent in Siemens/Hagger/L&T. |
| 24 | Supply and fix in repairsswitch piano, flush type single pole, one way, 5 Amps, 240 volts complete all as specified and as directed. |
| 25 | Supply and fix in repairs switch piano, flush type single pole, two way, 5 Amps, 240 volts complete all as specified and as directed. |
| 26 | Supply and fix in repairs bell pushflush type single pole, one way, 5 Amps, 240 volts complete all as specified and as directed. |
| 27 | Supply and fixing in repairs socket outlet 2 in 1, 3 pin 5 Amps complete all as specified and as directed. |
| 28 | Supply and fix in repairs ceiling roses, 3 phase, PVC/Polycarbonate, isolated body complete all as specified and as directed. |
| 29 | Supply and fix in repairs stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc as required complete all as specified and as directed. |
| 30 | Supply and fix in replacement of 20 watt (4ft long) decorative box type fitting with blue coloured end caps for LED tube etc complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cablefrom ceiling rose to terminal block and testing complete all as specified and as directed. |
| 31 | Supply and fix in replacement of 12 watt 2 ft decorative box type fitting with coloured end caps for LED tube etc complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cablefrom ceiling rose to terminal block and testing complete all as specified and as directed. |
| 32 | Supply and fix lamp holder, PVC/Polycarbonate type with back plate suitable for batten fitting including with one number 12 watt LED lamp complete all as specified and directed. |
| 33 | Supply & fixcapacitor of 2.5 mfd complete all as specified and as directed. |
| 34 | All as per item No 18 above but 3.15mfd complete all as specified and as directed. |
| 35 | All as per item No 19 above but 4.0 mfd complete all as specified and as directed. |
| 36 | Supply & fixcapacitor of 0.85/1.00 mfd complete all as specified and as directed. |
| 37 | Supply & fix in replacement of plug and socket for metal clad box complete all as specified and directed by Engineer-in-Charge. Make:- Legrand or equivalent in Siemens/Hagger/L&T. |
| 38 | S&F submain wiring withunsheathed multi-stranded FRLS Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 6 Sqmm single core HR Grade and one run of 6 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB complete all as specified and as directed.Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.Note 1: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. |
| 39 | S&F submain wiring withunsheathed multi-stranded FRLS Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 4 Sqmm single core HR Grade and one run of 1.5 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB complete all as specified and as directed.Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.Note 1: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. |
| 40 | Supply and fix PVC insulation tape 18mm width and 25 m Length complete all as specified and as directed. |
| 41 | S&F cable copper flexible 3 Core cicular type 2.5 sqmm heavy duty complete all as specified and as directed. |
| 42 | S&F cable copper flexible 3 Core cicular type 4 sqmm heavy duty complete all as specified and as directed. |
| 43 | S&F water heater vertical type Ivory in colour Cat part No. G51/3025, rated power 2 KW complete all as specified and as directed. |
| 44 | Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5m in depth and getting out in soft/loose soil complete all as specified and as directed. |
| 45 | Returning filling in including spreading, leveling, watering and well ramming in layersexc 25 cm thick complete all as specified and as directed. |
| 46 | Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed. |
| 47 | Supply and filling river sand in trenches including spreading for cushioning of LT UG cable complete all as specified and as dirceted.Note : Punned down thickness shall be measured and paid . |
| 48 | M&L for sub class ‘B’ bricks old sizelaid flat dry in trenches over cable, across the direction of cable complete all as specified & as directed . |
| 49 | Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 185 Sq mm. complete all as specified and as directed.Note : Provision of suitable double crimpped lugs and glands shall deemed to be included in quoted rates. |
| 50 | All as per item No 35 described here in before but 3.5 core 120 sqmm |
| 51 | All as per item No 35 described here in before but 3.5 core 95 sqmm |
| 52 | All as per item No 35 described here in before but 3.5 core 70 sqmm |
| 53 | All as per item No 35 described here in before but 3.5 core 50 sqmm |
| 54 | All as per item No 35 described here in before but 4 core 25 sqmm |
| 55 | All as per item No 35 described here in before but 4 core 16 sqmm |
| 56 | Material and Labour for disconnection of LT Electric supply by taking proper shut down and removing old unserviceable LT Fidder Pillar retrieved from existing location vide Ser item No 72 of DCS complete all as spd and as directed by Engr-in-Charge. |
| 57 | S&FACB (air circuit breaker) draw out typeof rating 800 Amps 4 pole, 50 KA, O/L, S/C, micro processor based release and cassette mounted horizontal draw out type fully interlocked cassette door automatic safety shutters, mechanical on and off indicators, service/test/isolated position with position indicators, provision of castell lock, with O/L, S/C with 3 CT\"s of standard ratings 4 blocks of 6 way sliding type LT disconnectors, error prevention plug, racking handle, safety shutters and painted with finished light grey shadeas per IS:631 and as per IS 13947-2-1993 inclusive suitable length of bus bars complete allspecified and as directed. |
| 58 | All as per item No 43 described here in before but 630 Amps |
| 59 | S&F MCCB 400 A ,4 pole ,36 KA with adjustable thermal & fixed magnetic settingwith bus bar spreader links forconnecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning complete all as directed as per existing model/make. |
| 60 | M & L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including using galvanised iron strip 32×6mm as earthing strip by means ofbolts, nuts, check nuts and washers of galvanized iron or steel, earth plate surrounded by packed layer of char coal dust and common salt, 15cm thick all around bottom and top and watering pipe 20mm bore of GI light grade with funnel, wire meshand 40 mm dia GI protection pipe medium grade all as shown in electrical plate No 3 of SSR Part-I and connected to earthing test point, main switch board and testing on completion including excavation, earth work concrete pit with 80mm thick RCC cover in RCC 1:2:4 type B-1 duly reinforced with MS bars 8mm dia @ 150C/C both ways and pit chamber in PCC 1:2:4 type B-1 with 2 Nos suitable lifting handles of 12mm MS bar complete all as specified and as directed. |
| 61 | Supply and lay in trenches GI strip 25 mm x 4 mm galvanised iron strip for earth continuityearthing all as specified and as directed |
| 62 | M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as spcified and as directed. |
| 63 | Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 40mm bore for protection of UG cables complete all as specified and as directed. |
| 64 | All as per item No 49 described here in before but 80 mm |
| 65 | M&L for defect rectification high tension or LT cable laid in trenches by locating fault with the help of electronic fault locating machine comprising of surge generator pulse, ECHO fault locator with high frequency distance calculator etc. including and additionalexcavation in normal alluvial strata required forexposing the cable fault ; removal of deteriorated portion of cable treating of cable and keeping the same ready for jointing work for cable of size up to 185 Sq mm three core/ FOUR CORE. The fault locating equipments shall be brought to site within the hours of instruction from Engr-in-Charge as directed |
| 66 | S&F in repairs/removing the UG cable for rectification of faults after fault detection excavating the area and Crimping with suitable ferrules/lugs or any other misc itemsproviding suitable insulation tape and relaying complete after rectification of faults complete all as specified and as directed. Note: (i) Excavated area shall be made good to original finish and no extra payment shall be done on this account. The items like Lugs, Ferrules, nuts, bolts if any shall deemed to be included in the rates quoted and no extra payment shall be done on this account.(ii) Item No 51 & 52 shall be attended immediately on intimtion by phone or SMSfailing which an amount of Rs 1000/- per day after 2 days shall be recovered as penality. |
| 67 | Supply and Fix in replacement of security Light for use on top of the watch tower cabin with motorised system: 400 W HPSV high intensity, long range, weather & dust proof motor operated Security Search light with highly polished stainless steel reflector-cum-body, suitable heat sinks, toughened front glass, retaining ring, M.S. Cradle and passivated bolts. The search light would be supplied with 230 V ,400 Watt HPSV Lamps with control gear in cast alumiminum housing, The search light fitting would be suitable for installing on the roof of the watch tower cabin. The search light would be swiveling type & have both vertical & horizontal operational controls with the help of remote control unit with suitable control cables complete all as specified and as directed.Make: Kalin or equivalent model of Group-1 out of makes specified in list of makes. |
| 68 | Dismantling and taking down existing LED light fittings with safty from pole bracket and refix the same on newly installed pole complete all as specified and as directed. |
| 69 | Dismantling concrete poles any size complete and setting aside complete all as specified and as directed.Note: \"Hydra Crane Charges deemed to be included in the quoted rate\". |
| 70 | Supply, fixing and erection steel tubular swaged pole type 410SP-31(9 Mtr long) Swan neck complete with CI base plate,taper plug,bolts,nuts,and screws etc duly paintedinternally and externally with metal oxide anti corrosive paint before errection and painting with two coats aluminium paintafter erection complete all as cofirming to IS 2713 (part-1 to 111) and complete all as specified and as directed.Note : Necessary earth work and concrete shall bemeasured and paid separately |
| 71 | M&L for Foundation for Tubular swaged pole type including excavation , getting out, pole foundation with PCC (1:4:8) type D 2 (using with 40 mm graded crushed stone aggregate). Coping of pole with PCC (9:3:6) type C ( using with 20 mm graded stone agregate)and removing surplus soil to a distance n.exc 50 m and making good surface complete all as specified and as directed |
| 72 | Supply andjointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size120 to 185 sqmm 3.5 corecomplete all as specified and as directed |
| 73 | Supply andjointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 70 to 95 Sqmm 3.5 corecomplete all as specified and as directed |
| 74 | Supply andjointing in replacement of heat shrinkable straight through joint suitable for LT 1100 volts XLPE cable of size 25 to 50 Sqmm 3.5 corecomplete all as specified and as directed |
| 75 | Taking down old UNSV fidder pillar and Supply, fixing, testing and commissioning in replacement of feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of MS sheet 3.15 mm thick of size 540x525x200mm with aluminium bus bar 250 Amps, 4 strip (3 phase) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking with 150 Amps 25 KA MCCB four pole for incomer cable, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCCblock (1:2:4) complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands etc and providing fixing arrangements including earthing lead fixing arrangement, complete all as directed.Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel shall included in rates quoted. |
| 76 | S&F vertical type load line distribution board, double door, 4 way AC, 3 phase 415 volts, TPN bus bar 200 Amps rating and earth bus and din rail including 01 No. MCCB 3/4 pole 415 volts, 50 Hz, 100Amps 16 KA breaking capacity as incomer complete all as specified and as directed |
| 77 | S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 63 Amps with breaking capacity 16 KA and connecting testing with MCCB complete all as specified and as directed. |
| 78 | S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 100 Amps with breaking capacity 16 KA and connecting testing with MCCB complete all as specified and as directed. |
| 79 | M&L submain wiring withunsheathed multi-stranded FR Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 6 Sqmm single core HR Grade and one run of 4 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB complete all as specified and as directed.Note :- (i) Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete.Note (ii): Rates shall deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. |
| 80 | Supply & fix in replacement of SPN enclosure with two pin and earth plug and socket complete with one SPN MCB 32 Amps complete all as specified and as directedMake Legrand or equivalent in Siemens/Hagger. |
| 81 | M&L for painting of steel tubular pole including cable protection pipe and all iron parts of 9 mtr long pole complete with 2 coats of aluminium paint after cleaning all rust and dust and preparing surface with wire brush and including strips of white and red colour of synthetic enamel paint up to the height of 1.5 mtr from the bottom of the pole complete all as specified and as directed. |
| 82 | S&F MCCB 250 A ,3 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links forconnecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning complete all as specified and as directed. |
| 83 | S&F MCCB 200 A ,3 pole ,25 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links forconnecting both incoming and outgoing cables with suitable connections with suitable size ofglands etc complete including testing & commissioning all as specified and as directed |
| 84 | Supply and fixing weather proof street light junction box of size 300 x 200 x 105mmincluding MCB SP 6 Amps and connecting terminals 4 way and fixing with street light poles using necessary MS clamps, nuts, bolts washers, lugs for incoming and out going cables, gland for cable etc of suitable size complete all as specified and as directed. Make : Hensel/Sintex/Universal Switch Gear control Note : The rates quoted shall inclusive of provision and fixing of suitable lugs and glands for cable connection. |
| 85 | Material and labour for PVC flat twin core 2.5 sq mm aluminium wire 1100 volt grade laid in 20 mm dia medium grade rigid PVC conduit (and fixing brackets on PCC pole) from Loop-in-loop out junction box to light fitting terminal complete all as specified and as directed.Note :- PVC conduit shall be clamped properly with suitable clamps and no extra payment shall be done on this account. |
| 86 | Supply, installing, testing and commissioning factory made and tested LT Panel Feeder Pillar Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. Shall be dust and vermin proof, protection class (IP-42) and made of 3.00 mm thick CRCA SHEET & suitable frame work/ support made out of 40 x 40 x 5 mm Aluminium, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. The scope of work also comprising of the following:- Make:- Havells/ Schneider / ABB/ L&T/Universal Switch Gear Control/ Tricolite. |
| 87 | BUS BAR CHAMBER :- (a) 600 Amp 3 Strips & Neutral Strip 300 Amp, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings.INSTRUMENT CHAMBER :- (i) Digital Multi Function Meter with LED display for measurement of Voltage, current, frequency, Power Factor, 96 X 96 mm, 3 Phase - 01 Set.(ii) C.T\"s 400/5 A CL 1.0 Tape Wound- 01 Set. (Set of three)(iii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three).(iv) Protection MCB 6 A SP C Series- 1 Set. (Set of three). Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.INCOMING SUPPLY :-(i) MCCB 400 Amps 50 KA , 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., OUTGOING SUPPLY :- (i) MCCB 315 Amps 36 KA , 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., (i) MCCB 160 Amps 25 KA , 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., (iii)Provision for Space = 1 No. Make of MCCB:- L&T/ Siemens/ Legrand/ABB. |
| 88 | The panel manufacturer should have following Govt. Approved Certificates: 1. CPRI Certification Degree of Protection IP-542. CPRI Short Circuit withstand strenght should be 50kArms for 1.0 Sec with intial peak of 105kA3. CPRI Certification Rated current for short circuit not less than 4000 A with rated insulation voltage 660V4. ISO 9001 CERTIFIED |
| 89 | S&F street light liminaree high power LED of 72 watt rating with unique lens to ensure to uniform distribution complete all as spcd as directed Cat Part No LSTP-72-CDL Make of CG or its equvalent Havells/Hallonix Note :- Rent for hydra is included in rates quoted by the contractor. All fixing material inculdied in the unit rate. |
| 90 | Supply & fixing aluminium thimble heavy duty ISI mark suitable for 25 sqmm 3.5 cable complete all as specified and as directed. |
| 91 | All as item 74 above but 35 x 3.5 sqmm cable |
| 92 | All as item 74 above but 50 x 3.5 sqmm cable |
| 93 | All as item 74 above but 70 x 3.5 sqmm cable |
| 94 | All as item 74 above but 95 x 3.5 sqmm cable |
| 95 | All as item 74 above but 120 x 3.5 sqmm cable |
| 96 | All as item 74 above but 150 x 3.5 sqmm cable |
| 97 | All as item 74 above but 185 x 3.5 sqmm cable |
| 98 | All as item 74 above but 240 x 3.5 sqmm cable |
| 99 | All as item 74 above but 300 x 3.5 sqmm cable |
| 100 | Dismantling and taking down LED Street lights, High Mast lights, Dome/ Gate lights fitting and bollards of any type or size for repair and replacement of worn out accessories and fixing on bracket on pole/wall after repair complete all as specified and as directed. (worn out accessories or components to be measured and paid separately as supply only). |
| 101 | Supply and Fixing LED street light luminaire High power LED of 45 watt rating with unique peanut lens to ensure uniform distributioncomplete complete all as specified and as directed. and as directed . Cat Part No. LSTP-45-CDLmake of CG or its equivalent in Havells/HalonixNote:- Rent for hydra is included in rates quoted by the contractor. All fixing material is included in the unit rate. |
| 102 | Removing out of carbon particle/sulphate from 9/11 mtr street light pole junction box/light fitting/OH conductor incuding cleaning and refixing properly to make light functional complete all as specified and as directed.Note:- Rent for hydra is included in rates quoted by the contractor. |
| 103 | S&F Energy saving environment friendly High mast Light with innovative di cast aluminium IP 66 Flood light fitting with 150W LED as light source complete all as specified and as directedMake: Havells/Phillips/Wipro/CromptonNote: All fixing material is included in the unit rate. |
| 104 | S&F Energy saving environment friendly High mast Light with innovative di cast aluminium IP 66 Flood light fitting with 120W LED as light source complete all as specified and as directedMake: Havells/Phillips/Wipro/CromptonNote: All fixing material is included in the unit rate. |
| 105 | S&F Energy saving environment friendly High mast Light with innovative di cast aluminium IP 66 Flood light fitting with 100W LED as light source complete all as specified and as directedMake: Havells/Phillips/Wipro/CromptonNote: All fixing material is included in the unit rate. |
| 106 | Supply and fixed in repair, integral post top ideal to lit up luminaires energy saving40 watt LED lamp, with symmetrical light distribution system di-cast aluminium luminairie with high power LED as light source including LEDlamp complete all as specified and as directed.Make : Cat pt no LPTO-40-CDL-M of Crompton or equivalent in Havells/Bajaj/polycab.Note: All fixing material is included in the unit rate. |
| 107 | Repair/Maintenance of high mast light 15 Metre height, oiling of motor of wench, repairing/renewal of burnt out cables, CG box, luminaire and made it functional all as specified and as directed.Note : (i) Components & parts to be replaced will be measured and paid separately.(ii) Worn out components will be measured and paid separately under relevant items of schedule. |
| 108 | Supply only spare parts/ luminairies for high mast light are as under :- |
| 109 | (a)Copper conductor cable 10 sqmm x 4 core, 650 V/1100 V, un-armoured all as specified and as directed. |
| 110 | (b)M&L in replacement of control panel for High Mast Light comprising of Timer, contactor, starter, up & down push button in sheet steel enclosure of 3.0mm thick CRCA sheet and fixed on PCC plateform all as specified and as dirceted.Make : National/Universal/SMS Panels/EAP Panels |
| 111 | (c)M&L for rewinding of winch motor of high mast lightwith super enamelled copper conductor and insulating material all as specified and as directed. |
| 112 | Supply and fix automatic timer switch 3 phase with switches ON/OFF the street lights base on lux level of natural light current rating 40 Amps, 220 Volts, 50 Hz. The sensor based timer should also have over voltage and low voltage trip with auto reset facility the sensor alongwith suitable power contactor, MCB and support terminals should be enclosed in pole/wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade special moulding compounds confirming to IP 54. The contactor MCB and circuit wiring shall have enough capacity to take load of 12 KW equally distributed over 3 phase complete all as specified and as directed.Make : Healer/Universal Swtich Gear/Kakatiya |
| 113 | S&F in replacement of Intergrated Solar Street light 24 watt LED with Li-ion battery 11.1 V, 17Ah with inbuilt BMS,MPPT complete all as specified and as directed. |
| 114 | S&F Solar panel in replacement for Intergrated Solar Street light 24 watt LED with Li-ion battery complete all as specified and as directed. |
| 115 | M&L for rewinding of winch motor of high mast lightwith super enamelled copper conductor and insulating material all as specified and as directed. |
| 116 | S&F DC wire for connection to street light panel to fitting to make light functional all as specified and as directed. |
| 117 | Supply and Fixing LED street light luminaire High power LED of 70 watt rating with unique peanut lens to ensure uniform distributioncomplete all as specified and as directed . Cat Part No. LSTP-72-CDLmake of CG or its equivalent in Havells/HalonixNote:- Rent for hydra is included in rates quoted by the contractor. All fixing material is included in the unit rate. |